Project Documentation Page 1 of 18 05/2020
Project Documentation Gebäude-Dokumentation
1 Abstract / Zusammenfassung
Childcare centre in Torrens Australia
1.1 Data of building / Gebäudedaten
Year of construction/ Baujahr
2018 Space heating / Heizwärmebedarf
15 kWh/(m²a) U-value external wall/
U-Wert Außenwand 0.263 W/(m²K)
U-value basement ceiling/ U-Wert Kellerdecke
0.469 W/(m²K) Primary Energy Renewable (PER) / Erneuerbare Primärenergie (PER) 29 kWh/(m²a)
U-value roof/ U-Wert Dach
0.177 W/(m²K) Generation of renewable energy / Erzeugung erneuerb. Energie
143 kWh/(m²a)
U-value window/ U-Wert Fenster
0.91 W/(m²K) Non-renewable Primary Energy (PE) / Nicht erneuerbare Primärenergie (PE)
64 kWh/(m²a)
Project Documentation Page 2 of 18 05/2020
Heat recovery/ Wärmerückgewinnung
77 % Pressure test n50 / Drucktest n50
0.6 h-1
Special features/ Besonderheiten Solar PV array, heat pump domestic hot water, rainwater utilisation
Project Documentation Page 3 of 18 05/2020
1.2 Project Description
Torrens Early Learning - Passive House
Torrens Early Learning is a long-day-care facility which provides early education and care for 89 children aged from 6 weeks to 6 years, and has a staffing element of around 20 carers/teachers /administration staff.
The facility consists of 2 separate buildings, (both 2 storey) linked by a large external deck and playgrounds and front entrance.
The first building has administration, commercial kitchen, dining rooms and a baby’s nursery space – this building was a re-adaption of the existing building’s footprint. The re-adaption reused the slab and services, retained brick fences, and boundaries, and rebuilt and re-developed the space. The building was built to the Passive House standard, but did not meet the final airtight criteria.
The second building is a certified Passive-House building – certified as Premium. The building was developed for solar performance – to face north, allow a roofline for maximum solar panels, to allow natural light into all learning spaces, and mobility access for children to all spaces and playgrounds. Careful attention was paid to windows and the distribution of light into classrooms, and importantly solar heat gain in winter, and the rejection of such heat in summer. The building consists of 6 large classrooms, and 3 bathrooms.
Project Documentation Page 4 of 18 05/2020
1.3 Responsible project participants / Verantwortliche Projektbeteiligte
Architect/ Entwurfsverfasser
Christie Hartfiel Architectural Design / Can PLAY / VRD Design
Implementation planning/ Ausführungsplanung
Christie Hartfiel Architectural Design / Can PLAY / VRD Design
Building systems/ Haustechnik
Rudds Consulting Engineers
Structural engineering/ Baustatik
Tim Gibney & Associates
Building physics/ Bauphysik
H3Space
Passive House project planning/ Passivhaus-Projektierung
H3Space
Construction management/ Bauleitung
Can PLAY
Certifying body/ Zertifizierungsstelle
Detail Green
Certification ID/ Zertifizierungs ID
Project-ID (www.passivehouse-database.org)
Projekt-ID (www.passivehouse-database .org) 6326
Author of project documentation / Verfasser der Gebäude-Dokumentation
Harley Truong H3Space
Date, Signature/ Datum, Unterschrift
8 May 2020
Project Documentation Page 5 of 18 05/2020
2 Views
North west elevation
North elevation
Project Documentation Page 6 of 18 05/2020
East elevation
South elevation
Project Documentation Page 7 of 18 05/2020
Playground
Classroom
Project Documentation Page 8 of 18 05/2020
3 Section drawings
Cross section
The thermal envelope consists of prefabricated Carbonlite panels for walls and roof all sitting on an insulated concrete slab. The mid floor is made from Cross Laminated Timber (CLT)
Detailed cross section
GROUND FLOOR
643050
BASEMENT
640000
UPPER CEILING
648580
1
A32
2030
5025
50
85 m²RESOURCE
87 m²
PRESCHOOLX 22
TIMBER PANEL ROOF TO ENGINEER'S DETAILS,COLORBOND 'MONUMENT' STANDING SEAMCLADDING
TIMBER PANEL FLOORTO ENGINEER'SDETAILS, FYRCHEKCLADDING TOUNDERSIDE AS PERFIRE ENGINEER'SDETAILS
DOUBLE BRICKWALLS AND CONCRETESLAB FLOOR TOENGINEER'S DETAILS,INSULATEDINTERNALLY.
400500
JOINERY TO YOLK DETAIL
JOINERY TO YOLK DETAIL
600270
ROLLER SHUTTER 5
9
1
2
SHEET TITLE:
CLIENT:
LOCATION:
PROJECT: SHEET No:
AREAS:
SCALE: JOB No:
DATE:
&1�016�5%#.'�1((�2.#0��94+66'0&+/'05+105�9+..�6#-'�24'%'&'0%'�
#..�6+/$'4�(4#/+0)�#0&�%105647%6+10�/756%1/2.;�9+6*�#5����������6*'�0#6+10#.�6+/$'4�(4#/+0)�%1&'�
#..�4�%�(116+0)5�#0&�%10%4'6'�5.#$5�#4'57$,'%6'&�61�#�51+.�%.#55+(+%#6+10�#0&/756�%1/2.;�9+6*�#5�����������4'5+&'06+#.�5.#$5��(116+0)�%1&'��
.+06'.5�61�64755�/#07(#%674'45�%*#46�&'5+)0�9+0&�.1#&+0)����O�U6'44#+0�%#6')14;���
#..�$7+.&+0)�914-�/756�$'�+0�#%%14�%'9+6*�6*'�0#6+10#.�%105647%6+10�%1&'�%1/2.;�9+6*�#..�4'8'.#06�#5�%1&'5�#0&#�%6��5722.'/'06�#5�4'37+4'&��
#0;�&+5%4'2#0%+'5�/756�$'�&+5%755'&9+6*�6*'�&4#(65/#0
ABN 53 008 609 925 PH: (02) 6101 5917 MOB: 0414 488 420
DESIGN
10
VERSICLAD 'MONOLITH' ROOFING & STEEL PERGOLA
2360
2412
SECTION XX
ORIGINAL DESIGN BY:
AMENDMENTS: 16-02-181. REMOVE STAIRS FROM DECKS2. EXTEND DECK3. INTERNAL LAYOUT CHANGED4. CHANGEROOM LAYOUT ALTERED TO ADD SHOWER5. TIMBER GATES CHANGED TO ROLLER SHUTTER6. EXTERNAL DOOR OF WASTE ENCLOSURE REMOVED7. BRICKS & COLOURBOND CHANGED TO ALUCOIL8. COLOUR OF MODWOOD CLADDING CHANGED TO GREY9. BALUSTRADES CHANGED TO BLACK FRAMED GLASS10. NEW VERSICLAD & SAIL ROOF OVER DECK11. NEW TERRACES & DECK TO PLAYSPACE12. COLOURBOND CLADDING CHANGED TO BRICKWORK13. NO SUB-FLOOR DOOR14. NEW SHADE SAILS15. ALTERED FENCE
2016
1206
-TO
RR
ENS-
ADD
ITIO
N-S
ECTI
ON
ATBA
SEM
ENT
ATFY
RC
HEC
K
boun
dary
sout
hw
all
EQ6434_SPEC
EQ6434_SPEC
EQ6434_SPEC
EQ6434_SPEC
FYRCHECK 16MM
CSR Gyprock Fire Mastic
lvl raftersOSB 18mm
Alu roller shutters
900
under fascia (by others)
cladding + top hat by others
13
13
2x 13mm fyrcheck - noggins(in between rafters)
2x 13mm fyrchek
CSR Gyprock Fire Mastic
40
overlap13
13
1616
160mm LVL
Brick lintel
2005016
1214055
45 14012
13
13
900
Project Documentation Page 9 of 18 05/2020
4 Floorplan
The ground floor has four classrooms and two bathrooms. The lower ground has a similar layout with two classrooms and single bathroom. Access to each of the classrooms is through an external entry door. There are no internal stairwells.
Ground floor
Lower ground floor
63 m²
TODDLERSX 16
87 m²
PRESCHOOLX 22
ABCDEFGHIJKLM
270
11430
30275
3200 600 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400 2400
62 m²
INFANTSX 16
643050
900270600
9960
600270
3000
N
81 m²
EARLYLEARNERS
4930
5030
11700
54
600
100
4930
850355850475800800800
12 m²WC 2
12 m²WC 1
850
600
600
600
P
O
WASHER
WASHER
WASHER
WASHER
1
3 3
2
SHEET TITLE:
CLIENT:
LOCATION:
PROJECT: SHEET No:
AREAS:
SCALE: JOB No:
DATE:
ABN 53 008 609 925 PH: (02) 6101 5917 MOB: 0414 488 420
DESIGN
Q
ORIGINAL DESIGN BY:
�����������+0&+%#6+8'�.1%#6+105�1(#..�$7+.&+0)�914-�/756�%1/2.;�9+6*�6*'�
��������9*'4'�5*190��*#4&�9+4'&�61�#5�����
0�%�%�#0&�#..�4'.'8#06�#5�%1&'5�
&+/'05+105�9+..�6#-'�24'%'&'0%'&1�016�5%#.'�1((�2.#0��94+66'0
/#+06#+0�%#8+6;�%105647%6+10�
�����������4'(4+)'4#614��16*'4�#22.+#0%'5�(4
��������5/1-'�#.#4/5�/756�%1/2.;�9+6*������������������1(�6*'�0�%�%��#5������+056#..'&�AMENDMENTS: 16-02-18
1. REMOVE STAIRS FROM DECKS2. EXTEND DECK3. INTERNAL LAYOUT CHANGED4. CHANGEROOM LAYOUT ALTERED TO ADD SHOWER
5. TIMBER GATES CHANGED TO ROLLER SHUTTER6. EXTERNAL DOOR OF WASTE ENCLOSURE REMOVED7. BRICK SKIN CHANGED TO ALUCOIL8. COLOUR OF MODWOOD CLADDING CHANGED TO GREY9. BALUSTRADES CHANGED TO BLACK FRAMED GLASS
10. NEW VERSICLAD & SAIL ROOF OVER DECK11. NEW TERRACES & DECK TO PLAYSPACE12. COLOURBOND CLADDING CHANGED TO BRICKWORK13. NO SUB-FLOOR DOOR14. NEW SHADE SAILS15. ALTERED FENCE
11
641
250
639500
639
750
6400
00
6405
00
640
750
6410
00
6412
50
641
500
639750
6400
00
640250
640500
640750
6410
00
641
250
ABCDEFGHIJKLM
85 m²RESOURCE
79 m²STORAGE
240024002400240024002400240024002400240024002400600
270
1056
060
027
090
0
16430460
XX
N
1170
0
600
600
4930
800
447
900
1400
34 m²PLANT
ROLLER SHUTTER
ADD WINDOWS
ADD WINDOW
ADD WC
4930
5630
UNDERCROFT WITHSUSPENDED TIMBER FLOORABOVE. STEEL PIERS TOENGINEER'S DETAIL 17
00
640000
640000
640000
641800
641800
PAINTED BLOCKRETAININGWALL
10 m²WC 3
TIMBER SCREEN
11501001150
2701860270
600
Q
P
O
WASHER
1
3
2
5
SHEET TITLE:
CLIENT:
LOCATION:
PROJECT:
SCALE:
AREAS:
SHEET No:
JOB No:
DATE:
ABN 53 008 609 925 PH: (02) 6101 5917 MOB: 0414 488 420
DESIGN
0�%�%�#0&�#..�4'.'8#06�#5�%1&'5�
&+/'05+105�9+..�6#-'�24'%'&'0%'&1�016�5%#.'�1((�2.#0��94+66'0
/#+06#+0�%#8+6;�%105647%6+10������������+0&+%#6+8'�.1%#6+105�1(
#..�$7+.&+0)�914-�/756�%1/2.;�9+6*�6*'������������4'(4+)'4#614��16*'4�#22.+#0%'5�(4
��������9*'4'�5*190��*#4&�9+4'&�61�#5�����
��������5/1-'�#.#4/5�/756�%1/2.;�9+6*������������������1(�6*'�0�%�%��#5������+056#..'&�
5*4
4
ORIGINAL DESIGN BY:
11
AMENDMENTS: 16-02-181. REMOVE STAIRS FROM DECKS2. EXTEND DECK3. INTERNAL LAYOUT CHANGED4. CHANGEROOM LAYOUT ALTERED TO ADD SHOWER
5. TIMBER GATES CHANGED TO ROLLER SHUTTER6. EXTERNAL DOOR OF WASTE ENCLOSURE REMOVED7. BRICK SKIN CHANGED TO ALUCOIL8. COLOUR OF MODWOOD CLADDING CHANGED TO GREY9. BALUSTRADES CHANGED TO BLACK FRAMED GLASS
10. NEW VERSICLAD & SAIL ROOF OVER DECK11. NEW TERRACES & DECK TO PLAYSPACE12. COLOURBOND CLADDING CHANGED TO BRICKWORK13. NO SUB-FLOOR DOOR14. NEW SHADE SAILS15. ALTERED FENCE
Project Documentation Page 10 of 18 05/2020
5 Construction details
5.1 Floor slab/basement ceiling
Part of the building has a concrete slab floor that is insulated above with 50mm Phenolic foam (Lambda 0.020 W/mK). The other part of the building has a timber suspended floor insulated with 240mm of fiberglass insulation (Lambda 0.043 W/mK).
Project Documentation Page 11 of 18 05/2020
5.2 Exterior walls
The walls are timber framed and insulated with 140mm of fiberglass batts (Lambda 0.035 W/mK).
Project Documentation Page 12 of 18 05/2020
5.3 Roof
The roof is made from timber rafters and insulated with 240mm of fiberglass batts (Lambda 0.043 W/mK). Above, it is lined with OSB, a weathertight membrane and then counter battens, battens and metal roofing.
Project Documentation Page 13 of 18 05/2020
5.4 Windows
The Windows and doors are Neuffer brand timber – aluminium framed, made of Eucalyptus and have an average Uf value of 1.03 W/m2K. The glazing is triple glazed Argon filled with low E coatings and laminated glass where there is the possibility of human impact. The average Ug is 0.60 W/m2K and g value 0.54. Barrier free thresholds were used in the bathrooms for wheelchair access.
EQ6434_SPEC
EQ6434_SPEC
VB 401VB 401
1100
1000
400
21/22/23 09/10 35 25
2012
1208
-Alte
ratio
n-G
roun
dflo
or-V
ertic
alse
ctio
n
Idealu78
NET
nachaußen
öffnend
Project Documentation Page 14 of 18 05/2020
6 Airtightness
Pro Clima Intello airtight membranes were used on the walls and ceilings for airtightness. These were taped to the windows, doors, and junctions with matching airtight tapes. Penetrations were sealed with grommets.
The building achieved an airtightness test result of 0.6 ACHn50. Main leakage areas were around penetrations for data cabling.
Project Documentation Page 15 of 18 05/2020
7 Ventilation systems
Three SystemAir heat recovery ventilation machines are used to service the building. The heat recovery efficiency is 77% and electrical efficiency is 0.22 Wh/m3. Fresh air is delivered to the classrooms and extracted in the bathrooms. Air is delivered via rigid metal ducting that is insulated in some areas with fiberglass batts.
Project Documentation Page 16 of 18 05/2020
8 Heating and cooling systems
Each classroom has an average area of 83m2 and is heated and cooled with its own reverse cycle air sourced heat pump with a capacity of 5 kW.
Project Documentation Page 17 of 18 05/2020
9 PHPP results
The project is the first of its kind to achieve the Passive House Premium certification in Australia owing to its very low energy usage and very large 30kW solar PV array.
Passive House VerificationPhoto or Drawing Building:
Street:Postcode/City: 2607
Province/Country:Building type:
Climate data set: AU0003a-Canberra
Climate zone: 4: Warm-temperate Altitude of location: 640 m
Home owner / Client:
Street:Postcode/City:
Province/Country:
Architecture: Mechanical engineer:
Street: Street:Postcode/City: Postcode/City: 2609
Province/Country: Province/Country:
Energy consultancy: Certification:
Street: Street:Postcode/City: 2606 Postcode/City: 3747
Province/Country: Province/Country:
Year of construction: 2017 Interior temperature winter [°C]: 20.0 Interior temp. summer [°C]: 25.0
No. of dwelling units: 1 Internal heat gains (IHG) heating case [W/m2]: 2.8 IHG cooling case [W/m²]: 2.8
No. of occupants: 50.0 Specific capacity [Wh/K per m² TFA]: 60 Mechanical cooling: x
Specific building characteristics with reference to the treated floor area
Treated floor area m² 485.8 Criteria Fullfilled?2
Space heating Heating demand kWh/(m²a) 15.4 ≤ 15 -
Heating load W/m² 12 ≤ - 10
Space cooling Cooling & dehum. demand kWh/(m²a) 1 ≤ 15 15
Cooling load W/m² 4 ≤ - 11
Frequency of overheating (> 25 °C) % - ≤ - -Frequency of excessively high humidity (> 12 g/kg) % 0 ≤ 10 yes
Airtightness Pressurization test result n50 1/h 0.6 ≤ 0.6 yes
PE demand kWh/(m²a) 54 ≤ - -
PER demand kWh/(m²a) 24 ≤ 30 24
kWh/(m²a) 143 ≥ 120 111
2 Empty field: Data missing; '-': No requirement
Non-renewable Primary Energy (PE)
Primary Energy Renewable (PER) yesGeneration of renewable
energy (in relation to pro-jected building footprint area)
AU-Australia
AU-AustraliaCanberra
Rudds Consulting Engineers
5 Bodalla Place Fyshwick
Detail Green
18 Fletcher Road
Beechworth
Victoria
10B Anderson Street Chifley
Canberra
Australian Capital Territory
Torrens Childcare - New building
1 Torrens Place Torrens
Canberra
Australian Capital Territory
Majura Park Childcare Pty Ltd
AU-AustraliaChildcare centre
Christie Hartfiel Architectural Design
Australian Capital Territory
Harley Truong H3space
AU-Australia
yes
yes
Alternative criteria
AU-Australia
AU-Australia
Australian Capital Territory
Project Documentation Page 18 of 18 05/2020
10 Build cost
The construction cost was 2050 Euro/m2 of Treated Floor Area and that included the outdoor play area, shading devices and landscaping.
11 Experience
Some observations after the owner occupied the site for over 12 months:
“Working at Torrens is so comfortable, we rarely need to use artificial heating or cooling, and the constant temperature and quietness of the building (no external noise, no mechanical noise) makes for a relaxing work environment. The building feels fresh and the air is clean – even during poor weather – like the January smoky bushfire events when Canberra had the worst air quality in the world. “
“My other buildings cost me 9,000 Euro a year in electricity – whilst Torrens is only 21 Euro – and that is mostly from the administration fees for being connected to the electricity grid.”