product launch shrmi - toshiba · 2013. 2. 20. · if you operate those air conditioning pattern,...
TRANSCRIPT
-
Product Product ‐‐
LaunchLaunch SHRMiSHRMi
-
What’s SHRM‐i
SMMS‐i (High Efficiency & Reliability)
Simultaneous Operation by heat recovery
““SHRMSHRM‐‐ii””
meets various customersmeets various customers’’
needs!needs!
+
=
-
Refrigerant flow, cooling
Flow selector unit
Liquid pipe
Discharge gas pipe
Suction gas pipe
Indoor unit
Pulse motor valve
Heat exchanger
Fan
-
Refrigerant flow, heating
Flow selector unit
Liquid pipe
Discharge gas pipe
Suction gas pipe
Indoor unit
Pulse motor valve
Heat exchanger
Fan
-
Rotary comp. vs. Scroll comp.
Part load efficiency : Rotary has more advantage than Scroll !
Compression process
-
Rotary comp. vs. Scroll comp.
Energy loss
Required
pressure
Operating
pressure >
-
Rotary comp. vs. Scroll comp.
High efficiency operation
Required
pressure
Operating
pressure =
-
Flex‐Variable Refrigerant Flow control scheme
are get balanced out !
-
Double refrigerant control
Flex‐Variable Refrigerant Flow controls two refrigerant flow simultaneously !
Flex‐Variable
Refrigerant Flow control
regulates aperture of
the pulse motor valve
and controls the cooling
distribution control and
the heating distribution
control.
-
Fast‐calculating vector controlled inverter
All‐inverter control realizes finer control over
operation to match the load on the system.
-
Heat discharge of condenser
depends on indoor cooling
Consumption minimize control
Heat absorption of evaporator
depends on indoor heating
Minimum outdoor fan rotation
Consumption minimize control
60rpm
+=
-
Super efficient operation, straight cooling
-
Super efficient operation, straight cooling
In cooling operation, all absorbed heat is thrown away ambient air !
-
Surplus exhaust
heat or surplus
absorbed heat
Super efficient operation, simultaneous cooling / heating
-
If you operate those air conditioning pattern, you
can enjoy the super efficient operation !
Super efficient operation, simultaneous cooling / heating
*The actual operation may differ slightly from the above chart.
(Exhaust heat 10 = 8 + 2) (Absorbed heat 10 = 5 + 5)=
-
Auto change over operation image (cooling and heating)
If you set the temperature of an air conditioner at 24.0 deg., the
indoor temperature fluctuation is just +/‐
1.5 deg.!
-
HPModel name
(MMY-)
Cooling capacity
(kW)
Heating capacity
(kW)
Max. No. of indoor units
8 MAP0804FT8-E 22.4 25.0 13
10 MAP1004FT8-E 28.0 31.5 16
12 MAP1204FT8-E 33.5 37.5 20
14 MAP1404FT8-E 40.0 45.0 23
16 AP1614FT8-E 45.0 50.0 27
18 AP1814FT8-E 50.4 56.5 30
20 AP2014FT8-E 56.0 63.0 33
22 AP2214FT8-E 61.5 69.0 37
24 AP2414FT8-E 68.0 76.5 40
26 AP2614FT8-E 73.0 81.5 43
28 AP2814FT8-E 78.5 88.0 47
HPModel name
(MMY-)
Cooling capacity
(kW)
Heating capacity
(kW)
Max. No. of indoor units
30 AP3014FT8-E 85.0 95.0 48
32 AP3214FT8-E 90.0 100.0 48
34 AP3414FT8-E 96.0 108.0 48
36 AP3614FT8-E 101.0 113.0 48
38 AP3814FT8-E 106.5 119.5 48
40 AP4014FT8-E 112.0 127.0 48
42 AP4214FT8-E 118.0 132.0 48MMY‐MAP/AP***4FT8‐E 380‐415V 50Hz Europe model
Line‐up, outdoor units
Total 18 line‐up
: Added model
-
8 to 10HP 12 to 14HP 16 to 20HP 22 to 24HP 26 to 28HP
0.77㎡ 0.94㎡ 1.56㎡ 1.73㎡ 1.90㎡
Line up, appearance
30HP 32 to 34HP 36 to 38HP 40 to 42HP
2.35㎡ 2.52㎡ 2.69㎡ 2.86㎡
* Bottom figures show foot print
Current 12HP*
0.77㎡
*Current 12HP model (small chassis) will be continued to sell, it
is only for stand alone unit.
-
Equivalent HP New 8, 10HP (current 12HP) New 12, 14HP
Appearance
External dimensions
Height 1,830mmWidth 990mm 1,210mmDepth 780mm
Weight 272kg 349kg
Fan unitMotor output 1,000WFan diameter φ740mm
Connecting port diameter
Suction gas side φ22.2mm* φ28.6mmDischarge gas side φ19.1mm
Liquid side φ12.7mm 12HP:φ12.7mm 14HP:φ15.9mmBalance pipe φ9.5mm
Anchor bolt pitch
Width 700mm 920mmDepth 755mm
Depth including attached legs 790mm
Specifications
*Current 12HP : suction gas side is φ28.6mm.
-
Heating range expanded from ‐15 deg. to ‐20 deg. !
* Cooling range is from ‐10 degree to 43 degree as with SHRM.
Specifications, outdoor operation range
-
4-way air discharge cassette type
Compact 4-way cassette type
2-way air discharge cassette type
1-way air discharge cassette type Concealed duct type
Cooling capacity (HP)
2.2kW (0.8HP) MMU-AP0074MH-E MMU-AP0072WH MMU-AP0074YH-E MMD-AP0074BH-E
2.8kW (1.0HP) MMU-AP0092H MMU-AP0094MH-E MMU-AP0092WH MMU-AP0094YH-E MMD-AP0094BH-E
3.6kW (1.25HP) MMU-AP0122H MMU-AP0124MH-E MMU-AP0122WH MMU-AP0124YH-E MMD-AP0124BH-E
4.5kW (1.7HP) MMU-AP0152H MMU-AP0154MH-E MMU-AP0152WH MMU-AP0154SH-E MMD-AP0154BH-E
5.6kW (2.0HP) MMU-AP0182H MMU-AP0184MH-E MMU-AP0182WH MMU-AP0184SH-E MMD-AP0184BH-E
7.1kW (2.5HP) MMU-AP0242H MMU-AP0242WH MMU-AP0244SH-E MMD-AP0244BH-E
8.0kW (3.0HP) MMU-AP0272H MMU-AP0272WH MMD-AP0274BH-E
9.0kW (3.2HP) MMU-AP0302H MMU-AP0302WH MMD-AP0304BH-E
11.2kW (4.0HP) MMU-AP0362H MMU-AP0362WH MMD-AP0364BH-E
14.0kW (5.0HP) MMU-AP0482H MMU-AP0482WH MMD-AP0484BH-E
16.0kW (6.0HP) MMU-AP0562H MMU-AP0562WH MMD-AP0564BH-E
22.4kW (8.0HP)
28.0kW (10.0HP)
Line up, indoor units 15 types, total 97 models
-
Concealed duct high static pressure type Slim duct type Ceiling type High wall type 2 series* High wall type 3 series
Cooling capacity (HP)
2.2kW (0.8HP) MMD-AP0074SPH-E MMK-AP0074MH-E MMK-AP0073H
2.8kW (1.0HP) MMD-AP0094SPH-E MMK-AP0094MH-E MMK-AP0093H
3.6kW (1.25HP) MMD-AP0124SPH-E MMK-AP0124MH-E MMK-AP0123H
4.5kW (1.7HP) MMD-AP0154SPH-E MMC-AP0154H-E MMK-AP0153H
5.6kW (2.0HP) MMD-AP0184H-E MMD-AP0184SPH-E MMC-AP0184H-E MMK-AP0183H
7.1kW (2.5HP) MMD-AP0244H-E MMC-AP0244H-E MMK-AP0243H
8.0kW (3.0HP) MMD-AP0274H-E MMC-AP0274H-E
9.0kW (3.2HP)
11.2kW (4.0HP) MMD-AP0364H-E MMC-AP0364H-E
14.0kW (5.0HP) MMD-AP0484H-E MMC-AP0484H-E
16.0kW (6.0HP)
22.4kW (8.0HP) MMD-AP0724H-E
28.0kW (10.0HP) MMD-AP0964H-E
Line up, indoor units 15 types, total 97 models
-
Floor standing concealed type
Floor standing cabinet type Console type Floor standing type
Air to air heat exchanger with DX-coil type
Cooling capacity (HP)
2.2kW (0.8HP) MML-AP0074BH-E MML-AP0074H-E MML-AP0074NH-E
2.8kW (1.0HP) MML-AP0094BH-E MML-AP0094H-E MML-AP0094NH-E MMD-VN(K)502HEXE
3.6kW (1.25HP) MML-AP0124BH-E MML-AP0124H-E MML-AP0124NH-E
4.5kW (1.7HP) MML-AP0154BH-E MML-AP0154H-E MML-AP0154NH-E MMF-AP0154H-E MMD-VN(K)800HEXE
5.6kW (2.0HP) MML-AP0184BH-E MML-AP0184H-E MML-AP0184NH-E MMF-AP0184H-E MMD-VN(K)1002HEXE/2
7.1kW (2.5HP) MML-AP0244BH-E MML-AP0244H-E MMF-AP0244H-E
8.0kW (3.0HP) MMF-AP0274H-E
9.0kW (3.2HP)
11.2kW (4.0HP) MMF-AP0364H-E
14.0kW (5.0HP) MMF-AP0484H-E
16.0kW (6.0HP) MMF-AP0564H-E
22.4kW (8.0HP)
28.0kW (10.0HP)
Line up, indoor units 15 types, total 97 models
-
Connectable indoor unit
RBC‐AMT32E RBC‐AMT32E
NRC‐01HE
Connect the air to air heat exchanger with
DX‐coil to SHRM‐i
-
Specifications, branching joints for outdoor unit
Suction gas pipeDischarge gas pipe /
Liquid pipeBalance pipe
RBM-BT14FE / RBM-BT24FE
The suction gas pipe
of branching joint switched from
previous T‐shape to Y‐shape.
RBM-BT14FE Less than 73kW (26HP)
RBM-BT24FE 73kW (26HP) or more
-
Specifications, branching joints for outdoor unit
Be sure to use the Y‐shape joint for suction gas pipe
!
Header unit
-
Specifications, flow selector unit
RBM-Y1122FE RBM-Y1802FE RBM-Y2802FE
Appearance
Connectable indoor unit
capacityBelow 11.2kW 11.2kW to below 18.0kW
18.0kW to 28.0kW or less
Connectable indoor units* 5 8 8
*Only group operation is possible with 1 (or 2) remote controller.
-
SHRM‐i is able to keep on operation except an indoor unit with the broken FS unit !
Specifications, in case of accident of flow selector unit
-
Flow selector unit piping length
15m
Piping flexibility
Possible to install the FS unit away !
15m as maximum length by using the connection cable kit (RBC‐
CBK15FE, sold separately).
-
Piping flexibility
11F
10F
9F
8F
7F
6F
5F
4F
3F
2F
1F
Height between CDU‐FCU
50m
Height between FCU‐FCU
40m
-
Piping flexibility
Farthest pipe from 1st
branch
65m
Farthest equivalent length
195m
-
HP Model name (MMY-) EER COP
8 MAP0804FT8-E 4.33 4.40
10 MAP1004FT8-E 3.85 4.20
12 MAP1204FT8-E 4.00 4.14
14 MAP1404FT8-E 3.54 3.54
16 AP1604FT8-E 4.35 4.40
18 AP1814FT8-E 4.05 4.29
20 AP2014FT8-E 3.85 4.20
22 AP2214FT8-E 3.93 4.17
24 AP2414FT8-E 3.66 3.79
HP Model name (MMY-) EER COP
26 AP2614FT8-E 3.71 3.75
28 AP2814FT8-E 3.47 3.46
30 AP3014FT8-E 3.89 4.22
32 AP3214FT8-E 3.92 4.16
34 AP3414FT8-E 3.71 3.90
36 AP3614FT8-E 3.75 3.86
38 AP3814FT8-E 3.56 3.63
40 AP4014FT8-E 3.62 3.69
42 AP4214FT8-E 3.48 3.46
High efficient EER & COP (100% load)
-
High efficient EER & COP (50% part load)
50% part load EER50% part load EER 50% part load COP50% part load COP8 6.02 5.6310 5.81 5.6712 6.05 5.6114 5.46 5.50
6.50
5.50
4.50
8HP 50% EER 12HP 50% COP
SHRM SHRM‐i SHRM SHRM‐i
5.776.02
5.06
5.61
SHRM‐i
-
High efficient EER & COP (100%, 50% part load)
SHRM‐i
-
Heat recovery operation is more efficient than individual operation of cooling
and heating!
High efficient EER & COP, COP of heat recovery operation (image)
-
Applications
(Complex bldg.)
No FS unit FS unit FS unit
Kitchen Restaurant Office
Cooling only
-
Applications (Office bldg. 1)
FS unit No FS unit
Meeting room Office Server room
FS unit
Cooling only
-
Applications (Office bldg. 2)
FS unit FS unit FS unit
Office Office Office
South North
The building where a room temperature difference is big !The building where a room temperature difference is big !The building where a room temperature difference is big !
STOP
-
Applications (Hotel)
FS unit FS unit FS unit
Room 1 Room 2 Room 3Hotel with much individual operation ne
eds !Hotel with much individual operation needs !Hotel with much individual operation needs !
STOP
-
Application Name Model Appearance
Wired
Lite-Vision plus remote controller
RBC-AMS51E-ESRBC-AMS51E-EN
Standard remote controller RBC-AMT32E
Remote controller with weekly timer RBC-AMS41E
Simple wired remote controller RBC-AS21E2
Remote sensor TCB-TC21LE2
Connectable wired remote controllers
-
Application Name Model Appearance
Wireless
For 4-way air discharge cassette
RBC-AX32U(W)-ERBC-AX32U(WS)-E
For 2-way air discharge cassette RBC-AX32UW(W)-E
For Ceiling, 1-way air discharge cassette RBC-AX32CE2
For all indoor unitsStand alone receiverTCB-AX32E2
Connectable wireless remote controllers
-
Connectable central controllers
Application Name Model Appearance
Central
ON-OFF controller TCB-CC163TLE2
Central remote controller TCB-SC642TLE2
Schedule timer TCB-EXS21TLE
-
Connectable BMS controllers
Application Name Model Appearance
BMS
Touch-screen controller
BMS-TP0641ACE/PWEBMS-TP5121ACE/PWE
Smart manager BMS-SM1280HTLE
Smart manager with data analyzer BMS-SM1280ETLE
-
Application Function Model Appearance
Open network
BACnet
Intelligent Server
BMS-LSV6E
BACnet Server Software
BMS-STBN08E
Relay Interface
BMS-IFLSV4E
LonWORKSLN Interface
TCB-IFLN642TLE
ModbusModbus Interface
TCB-IFMB640TLE
Connectable open network
○R
○R
○R
: ANSI/ASHRAE 135‐1995, A data
Communication Protocol for Building Automation
and Control Networks.
: Registered trademark Echelon
corporation
is a registered trademark of Schneider
-
Application Name Model Appearance
Outdoor unit
Power peak-cut control TCB-PCDM4E
Operation / Error output displayCompressor operation output controlOperation rate display control
TCB-PCIN4E
Snowfall fan controlExternal master ON/OFF controlNight operation (sound reduction) control
TCB-PCMO4E
Indoor unit Remote location ON/OFF control box TCB-IFCB-4E2
Connectable optional PC boards
-
Your building appreciates in value by SHRM‐i!
Slide Number 1Slide Number 2Slide Number 3Slide Number 4Slide Number 5Slide Number 6Slide Number 7Slide Number 8Slide Number 9Slide Number 10Slide Number 11Slide Number 12Slide Number 13Slide Number 14Slide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19Slide Number 20Slide Number 21Slide Number 22Slide Number 23Slide Number 24SHRMi-2.pdfSlide Number 1Slide Number 2Slide Number 3Slide Number 4Slide Number 5Slide Number 6Slide Number 7Slide Number 8Slide Number 9Slide Number 10Slide Number 11Slide Number 12Slide Number 13Slide Number 14Slide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19Slide Number 20Slide Number 21Slide Number 22