product guide & information - brkbrk.co.uk/wp-content/uploads/2015/10/brk-product...3 brk...
TRANSCRIPT
1
Professional Fire & Carbon Monoxide Solutions
PRODUCT GUIDE& INFORMATION
2
Nearly 50 years’ experience of designing, manufacturing and supplying home safety products, makes BRK an industry leader.We believe it is our responsibility to provide superior performing products at cost effective prices; with ranges designed for professionals, by professionals.
3
BRK Introduction 2
Contents 3
700MRL Series Range Pages 4 - 5
700MBX Series Range Pages 6 - 7
Product Range 8 - 16
760MRL/MBX Mains Powered Smoke Alarm 8 - 9
770MRL/MBX Mains Powered Mains Smoke Alarm 10 - 11
790MRL/MBX Mains Powered Mains Heat Alarm 12 - 13
DS700RF Wireless Interlink Base RF Base 14
CO850MRLi/MBXi Mains Powered Carbon Monoxide Alarm 15
CO850MRLi/MBXi Mains Powered Carbon Monoxide Alarm Product Specification 16
General Guidance 17 - 23
Siting of Smoke Alarms 18
Siting of Heat Alarms 19
Siting of Carbon Monoxide Alarms 20
System Grades & Categories Explained 21
Minimum Grade & Category of Detection 22
Notes 23
ContentsBRK Product Guide
4
MRL BACK-UPLong life rechargeable lithium battery removes the need to replace the batteries
• Thermally enhanced optical sensor for fast detection of all fire types• Supplied with PUSH-FIT base• Hardwire interconnect with up to 12 units
• Dual ionisation sensing chamber• Supplied with PUSH-FIT base• Hardwire interconnect with up to 12 units
• Advanced Class A2 thermistor• Supplied with PUSH-FIT base• Hardwire interconnect with up to 12 units
THERMALLY ENHANCED OPTICAL760MRL
IONISATION SMOKE770MRL
HEAT790MRL
700MRL SeriesMains powered alarms with rechargeable Lithium battery back-up
EN14604:2005Licence No: 14LHK0078
03590359-CPR-00253EN14604: 2005
DoP: 14/11
BSEN14604:2005Licence No: KM597992
00860086-CPR-597993
EN14604: 2005DoP 13/05
BS5446-2:20035Licence No: 14LHK0079
See page 8-9
See page 10-11
See page 12-13
5
• RF base provides a wireless interlink between mains powered smoke and heat alarms in the 700 series
• Quick to install and quick to link• Interlink up to 50 smoke and heat alarms
• Advanced electrochemical sensor• Mains powered with battery back-up• Hardwire interconnect with up to 12 CO alarms
WIRELESS INTERLINK BASEDS700RF
CARBON MONOXIDECO850MRLi
BSEN50291-1:2010Licence No: KM554921
See page 14
See page 15
6
MBX BACK-UP9V alkaline battery is ideal where cost saving is a priority
700MBX SeriesMains powered alarms with Alkaline battery back-up
• Thermally enhanced optical sensor for fast detection of all fire types• Supplied with PUSH-FIT base• Hardwire interconnect with up to 12 units
• Dual ionisation sensing chamber• Supplied with PUSH-FIT base• Hardwire interconnect with up to 12 units
• Advanced Class A2 thermistor• Supplied with PUSH-FIT base• Hardwire interconnect with up to 12 units
THERMALLY ENHANCED OPTICAL760MBX
IONISATION SMOKE770MBX
HEAT790MBX
EN14604:2005Licence No: 14LHK0078
03590359-CPR-00253EN14604: 2005
DoP: 14/11
BSEN14604:2005Licence No: KM597992
00860086-CPR-597993
EN14604: 2005DoP 13/05
BS5446-2:20035Licence No: 14LHK0079
See page 8-9
See page 10-11
See page 12-13
7
• Advanced electrochemical sensor• Mains powered with battery back-up• Hardwire interconnect with up to 12 CO alarms
WIRELESS INTERLINK BASEDS700RF
CARBON MONOXIDECO850MBXi
BSEN50291-1:2010Licence No: KM554921
• RF base provides a wireless interlink between mains powered smoke and heat alarms in the 700 series
• Quick to install and quick to link• Interlink up to 50 smoke and heat alarms
See page 14
See page 15
8
Technical Specification
Dimensions
140mm (diameter) x 53mm (depth) 140mm (diameter) x 53mm (depth)
Product Code 760 MRL 760 MBX
Supply voltage 230V AC, 50Hz 230V AC, 50Hz
Battery back-up Rechargeable lithium battery 9V alkaline battery
Technology Thermally enhanced optical Thermally enhanced optical
Alarm sound level 85dB(A) at 3m (minimum) 85dB(A) at 3m (minimum)
Installation positions Ceiling / Wall Ceiling / Wall
Operating temperature +5°C to +38°C +5°C to +38°C
Operating humidity 10% to 85% relative 10% to 85% relative
Storage temperature +5°C to +38°C +5°C to +38°C
Storage humidity 10% to 85% relative 10% to 85% relative
Plastic material ABS, UL94 VO fire retardant ABS, UL94 VO fire retardant
Warranty 5 years 5 years
Master pack quantity 10 10
Weight 340g 377g
Certified to BS EN 14604: 2005 BS EN 14604: 2005
Independently tested to N/A N/A
Maximum number of connected units 12 hardwired units 12 hardwired units
Operating Frequency N/A N/A
Range N/A N/A
Grade D - Mains Powered with battery back-up
Sensor type Thermally enhanced optical
Battery back-up type MRL - Rechargeable lithium / MBX - 9V alkaline
760MRL & 760MBX Mains Powered Smoke Alarm
Key Features
140mm 53mm 140mm 53mm
• Thermally enhanced optical sensing technology for fast detection of all fire types.
• 230V mains powered.• Battery back-up:
• MRL - 10 year sealed for life rechargeable lithium battery.• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 smoke/heat alarms.• Compatible with DS700RF wireless interlink base.• Supplied with PUSH-FIT base.• Central test and silence button.
EN14604:2005Licence No: 14LHK0078
03590359-CPR-00253EN14604: 2005
DoP: 14/11
9
• The smoke alarm shall carry the BSI Kitemark to indicate type testing to BS EN14604: 2005 and will meet the requirements of Grade D as defined in BS 5839 Pt.6: 2013. The alarm shall carry the CE mark to indicate conformance to all of the applicable EC directives including Low Voltage and Electromagnetic Compatibility Directives.
• The alarm shall utilise thermally enhanced optical technology which incorporates an optical sensing chamber and thermal enhancement components which make adjustments to the sensitivity settings of the alarm dependent upon background temperature. Providing a quicker response time to both slow smouldering, and fast flaming fires.
• MRL – The alarm shall operate on a 230V mains power supply and have a built-in, sealed for life, rechargeable lithium battery back-up to power the alarm in the event of a mains failure.
• MBX - The alarm shall operate on a 230V mains power supply and shall be supplied with 9V PP3 alkaline battery back-up to power the alarm in the event of a mains failure.
• The alarm is supplied with a PUSH-FIT mounting base for ease of installation. The alarm shall automatically connect to the mains as it locks onto the mounting base without the need to use a separate wired connector.
• The alarm shall disconnect from the mains supply as it’s removed from the mounting base with the use of a tool.
• The alarm shall have the ability to hardwire or interconnect with up to 12 other smoke or heat alarms of a similar type on a single network.
• The alarm shall have wireless interconnect capability with the DS700RF wireless interlink base, allowing up to 50 alarms of a similar type to be wirelessly interlinked on a single network.
• The alarm shall have a green LED mains indicator to confirm mains power supply is on.
• The alarm shall have a separate red LED that will flash approximately every 45 seconds to confirm circuitry integrity.
• The alarm shall have an integral test / silence button in order to test circuitry, sensor and sounder and activate all interconnected alarms in the system.
• The alarm shall have a silence feature which allows the alarm to be silenced for up to 10 minutes in the event of a known false alarm. A red LED shall flash every 10 seconds to indicate that the alarm is in ‘silence’ mode and will automatically reset after approximately 10 minutes.
• The alarm shall have a low battery warning signal, which will ‘chirp’ approximately every 45 seconds. This will continue until the alarm which has the low battery condition is removed.
• The alarm shall be supplied with a dust cover that can be fitted to protect it from contamination during installation.
• The alarm has a built in sounder giving a minimum sound output of 85dB(A) at 3m.
• The alarm shall be supplied with installation / user instructions.
• The alarm and base shall have the following combined dimensions: 140mm dia. x 53mm depth.
• MRL - The alarm and base shall have the following combined weight: 304g.
• MBX - The alarm and base shall have the following combined weight: 332g.
• The alarm shall have a 5 year warranty.
Product Specification
Key TechnologyTwo sensors provide heat readings, to enable early warning of fire
MRL - Rechargeable lithium battery back-upMBX - 9V alkaline battery back-up
Test and alarm silence button
Thermally enhanced optical sensing chamber
PUSH-FIT base
10
Technical Specification
Dimensions
140mm (diameter) x 53mm (depth) 140mm (diameter) x 53mm (depth)
Product Code 770 MRL 770 MBX
Supply voltage 230V AC, 50Hz 230V AC, 50Hz
Battery back-up Rechargeable lithium battery 9V alkaline battery
Technology Ionisation Ionisation
Alarm sound level 85dB(A) at 3m (minimum) 85dB(A) at 3m (minimum)
Installation positions Ceiling / Wall Ceiling / Wall
Operating temperature +5°C to +38°C +5°C to +38°C
Operating humidity 10% to 85% relative 10% to 85% relative
Storage temperature +5°C to +38°C +5°C to +38°C
Storage humidity 10% to 85% relative 10% to 85% relative
Plastic material ABS, UL94 VO fire retardant ABS, UL94 VO fire retardant
Warranty 5 years 5 years
Master pack quantity 10 10
Weight 262g 316g
Certified to BS EN 14604: 2005 BS EN 14604: 2005
Independently tested to N/A N/A
Maximum number of connected units 12 hardwired units 12 hardwired units
Operating Frequency N/A N/A
Range N/A N/A
Grade D - Mains powered with battery back-up
Sensor type Ionisation
Battery back-up type MRL - Rechargeable lithium / MBX - 9V alkaline
770MRL & 770MBX Mains Powered Smoke Alarm
140mm 53mm140mm 53mm
• Ionisation sensing technology.• 230V mains powered.• Battery back-up:
• MRL - 10 year sealed for life rechargeable lithium battery.• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 smoke/heat alarms.• Compatible with DS700RF wireless interlink base.• Supplied with PUSH-FIT base.• Central test and silence button.
BSEN14604:2005Licence No: KM597992
00860086-CPR-597993
EN14604: 2005DoP 13/05
Key Features
11
• The smoke alarm shall carry the BSI Kitemark to indicate type testing to BS EN14604: 2005 and will meet the requirements of Grade D as defined in BS 5839 Pt.6: 2013. The alarm shall carry the CE mark to indicate conformance to all of the applicable EC directives including Low Voltage and Electromagnetic Compatibility Directives.
• The alarm shall have a dual ionisation chamber sensor, with corrosion resistant electrodes and an insect resistant cover.
• MRL - The alarm shall operate on a 230V mains power supply and shall be supplied with a built-in, sealed for life, rechargeable lithium battery back-up to power the alarm in the event of a mains failure.
• MBX - The alarm shall operate on a 230V mains power supply and shall be supplied with 9V PP3 alkaline battery back-up to power the alarm in the event of a mains failure.
• The alarm is supplied with a PUSH-FIT mounting base for ease of installation.
• The alarm shall automatically connect to the mains as it lock onto the mounting base without the need to use a separate wired connector. The alarm shall disconnect from the mains supply as it’s removed from the mounting base with the use of a tool.
• The alarm shall have the ability to hardwire or interconnect with up to 12 other smoke and heat alarms of a similar type on a single network.
• The alarm shall have wireless interconnect capability with the DS700RF wireless interlink base, increasing the number of connected alarms to a maximum of 50.
• The alarm shall have a green LED mains indicator to confirm mains power supply is on.
• The alarm shall have a separate red LED that will flash approximately every 45 seconds to confirm circuitry integrity.
• The alarm shall have an integral test / silence button in order to test circuitry, sensor and sounder and activate all interconnected alarms in the system.
• The alarm shall have a silence feature which allows the alarm to be silenced for up to 10 minutes in the event of a known false alarm. A red LED shall flash every 10 seconds to indicate that the alarm is in ‘silence’ mode and will automatically reset after approximately 10 minutes.
• The alarm shall have a low battery warning signal, which will ‘chirp’ approximately every 45 seconds. This will continue until the alarm which has the low battery condition is removed.
• The alarm shall be supplied with a dust cover fitted to protect it from contamination during installation.
• The alarm has a built in sounder giving a minimum sound output of 85dB(A) at 3m.
• The alarm shall be supplied with installation / user instructions.
• The alarm and base shall have the following combined dimensions: 140mm dia. x 53mm depth.
• MRL – The alarm and base shall have the following combined weight: 262g.
• MBX - The alarm and base shall have the following combined weight: 316g.
Dual ionisation chamberMRL - Rechargeable lithium battery back-upMBX - 9V alkaline battery back-up
Test and alarm silence button
PUSH-FIT base
Product Specification
Key Technology
1212
Technical Specification
Dimensions
140mm (diameter) x 68mm (depth) 140mm (diameter) x 68mm (depth)
Product Code 790 MRL 790 MBX
Supply voltage 230V AC, 50Hz 230V AC, 50Hz
Battery back-up Rechargeable lithium battery 9V alkaline battery
Technology Advanced Thermistor Advanced Thermistor
Alarm sound level 85dB(A) at 3m (minimum) 85dB(A) at 3m (minimum)
Installation positions Ceiling Ceiling
Alarms at temperature range +54°C to +70°C +54°C to +70°C
Operating temperature +5°C to +38°C +5°C to +38°C
Operating humidity 10% to 85% relative 10% to 85% relative
Storage temperature +5°C to +38°C +5°C to +38°C
Storage humidity 10% to 85% relative 10% to 85% relative
Plastic material ABS, UL94 VO fire retardant ABS, UL94 VO fire retardant
Warranty 5 years 5 years
Master pack quantity 10 10
Weight 340g 377g
Certified to BS 5446-2: 2003 BS 5446-2: 2003
Independently tested to N/A N/A
Maximum number of connected units 12 hardwired units 12 hardwired units
Operating Frequency N/A N/A
Range N/A N/A
Grade D - Mains powered with battery back-up
Sensor type Thermistor
Battery back-up type MRL - Rechargeable lithium / MBX - 9V alkaline
140mm 68mm 140mm 68mm
• Advanced Class A2 thermistor sensing technology.• 230V mains powered.• Battery back-up:
• MRL - 10 year sealed for life rechargeable lithium battery.• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 smoke/heat alarms.• Compatible with DS700RF wireless interlink base.• Supplied with PUSH-FIT base.• Central test and silence button.
BS5446-2:20035Licence No: 14LHK0079
790MRL & 790MBX Mains Powered Heat Alarm
Key Features
1313
• The heat alarm shall carry the BSI Kitemark to indicate type testing to BS 5446-2: 2003. It will meet the requirements of Grade D as defined in BS 5839 Pt.6: 2013 for a Class A2 device. The alarm shall carry the CE mark to indicate conformance to all of the applicable EC directives including; Low Voltage and Electromagnetic Compatibility Directives.
• The alarm shall be a fixed point heat alarm, with a temperature range of 54°C to 70°C.
• MRL – The alarm shall operate on a 230V mains power supply and have a built-in, sealed for life, rechargeable lithium battery back-up to power the alarm in the event of a mains failure.
• MBX – The alarm shall operate on a 230V mains power supply and shall be supplied with 9V PP3 alkaline battery back-up to power the alarm in the event of a mains failure.
• The alarm is supplied with a PUSH-FIT mounting base for ease of installation.
• The alarm shall automatically connect to the mains as it locks onto the mounting base without the need to use a separate wired connector. The alarm shall disconnect from the mains supply as it’s removed from the mounting base with the use of a tool.
• The alarm shall have the ability to hardwire or interconnect with up to 12 other smoke and heat alarms of a similar type on a single network.
• The alarm shall have wireless interconnect capability with the DS700RF wireless interlink base, allowing up to 50 alarms of a similar type to be wirelessly interlinked on a single network.
• The alarm shall have a green LED mains indicator to confirm mains power supply is on.
• The alarm shall have a separate red LED that will flash approximately every 45 seconds to confirm circuitry integrity.
• The alarm shall have an integral test / silence button in order to test circuitry, sensor and sounder and activate all interconnected alarms in the system.
• The alarm shall have a silence feature which allows the alarm to be silenced for up to 10 minutes in the event of a known false alarm. A red LED shall flash every 10 seconds to indicate that the alarm is in ‘silence’ mode and will automatically reset after approximately 10 minutes.
• The alarm shall have a low battery warning signal, which will ‘chirp’ approximately every 45 seconds. This will continue until the alarm which has the low battery condition is removed.
• The alarm shall be supplied with a dust cover that can be fitted to protect it from contamination during installation.
• The alarm has a built in sounder giving a minimum sound output of 85dB(A) at 3m.
• The alarm shall be supplied with installation / user instructions.
• The alarm and base shall have the following combined dimensions: 140mm dia. x 68mm depth.
• MRL – The alarm and base shall have the following combined weight: 286g.
• MBX – The alarm and base shall have the following combined weight: 304g.
• The alarm shall have a 5 year warranty.
High performance thermistor
Central test button and robust sensor shield
PUSH-FIT base
MRL - Rechargeable lithium battery back-up
MBX - 9V alkaline battery back-up
Product Specification
Key Technology
1414
Technical Specification
Dimensions 140mm (diameter) x 30mm (depth)
Supply voltage 3V DC
Battery back-up 10 year sealed for life lithium battery
Technology Wireless technology
Alarm sound level N/A
Installation positions Ceiling / Wall
Operating temperature +5°C to +38°C
Operating humidity 10% to 85% RH non-condensing
Storage temperature -20°C to 60°C
Storage humidity 10% to 85% RH non condensing
Plastic material ABS, UL94 VO fire retardant
Warranty 5 years
Master pack quantity 10
Weight 145g
Certified to N/A
Independently tested to ETSI EN 300 220-2 V2.3.2 (2010-02), EN300489-1 &-3, EN50130-4, EN60065
Maximum number of connected units 50 wireless units
Operating Frequency 868 MHz
Range 35m (over 200m in clear air)
DS700RFWireless Interlink Base
• 10 year sealed for life lithium battery.• PUSH-FIT base.• Automatic ID coding.• Wirelessly interlink up to 50 smoke and heat alarms of a
similar type.• Base has both side and rear entry knock outs• Visual LED and audible fault warnings.• 5 year guarantee.
140mm 30mm
Key Features
1515
Technical Specification
Dimensions134mm (height) x 69mm (width)x 60mm (depth)
134mm (height) x 69mm (width)x 60mm (depth)
Product code CO850 MRLi CO850 MBXi
Supply voltage 230V AC, 50Hz 230V AC, 50Hz
Battery back-up Rechargeable lithium battery 9V alkaline battery
Technology Electrochemical Electrochemical
Alarm sound level 85dB(A) at 1m (minimum) 85dB(A) at 1m (minimum)
Installation positions Wall Wall
Operating temperature -10°C to +40°C -10°C to +40°C
Operating humidity 30% to 90% RH non-condensing 30% to 90% RH non-condensing
Storage temperature 0°C to +40°C 0°C to +40°C
Storage humidity 30% to 90% RH non-condensing 30% to 90% RH non-condensing
Plastic material ABS, UL94 VO fire retardant ABS, UL94 VO fire retardant
Warranty 5 years 5 years
Master pack quantity 10 10
Weight 226g 226g
Certified to BS EN 50291-1:2010 BS EN 50291-1:2010
Independently tested to N/A N/A
Maximum number of connected units 12 hardwired units 12 hardwired units
Operating Frequency N/A N/A
Range N/A N/A
Sensor type Electrochemical
Battery back-up type MRLi - Rechargeable lithium / MBXi - 9V alkaline
CO850 (MRLi/ MBXi)Mains Powered CO Alarm
• Advanced electrochemical sensor - calibrated and tested in CO gas.
• 230V mains powered.• Battery back-up:
• MRL - 10 year sealed for life rechargeable lithium battery.• MBX- 9V alkaline battery.
• Hardwire interconnect with up to 12 units of a similar type.• Power, alarm and fault indicators.• Instant test / reset feature.
BSEN50291-1:2010Licence No: KM554921
Key Features
69mm
134m
m
60mm 69mm
134m
m
60mm
16
• The carbon monoxide alarm shall carry the BSI Kitemark to indicate type testing to BS EN50291-1: 2010. The alarm shall carry the CE mark to indicate conformance to all of the applicable EC directives including Low Voltage and Electromagnetic Compatibility Directives.
• The alarm shall have an advanced electrochemical sensor. Each sensor shall be calibrated and tested in CO gas to ensure accuracy.
• The alarm shall operate on a 230V mains power supply with a battery back-up.
• CO850MRLi- The alarm shall operate on a 230V mains power supply and have a built-in, sealed for life, rechargeable lithium battery back-up to power the alarm in the event of a mains failure.
• CO850MBXi- The alarm shall operate on a 230V mains power supply and shall be supplied with 9V PP3 alkaline battery back-up to power the alarm in the event of a mains failure.
• The alarm shall have the ability to hardwire interconnect with up to 12 CO alarms of a similar type on a single network.
• The alarm shall have a green LED mains indicator to confirm mains power supply is on.
• In the event of a mains failure the green LED will flash approximately once every 60 seconds, to indicate that the back-up battery is in use.
• The alarm shall have a low battery warning signal, which will ‘chirp’ approximately once every 60 seconds. A yellow LED shall also flash approximately once every 60 seconds.
• The alarm shall have a fault warning, which will emit 2 short ‘chirps’ approximately once every 60 seconds. A yellow LED shall also light up and remain lit.
• The alarm shall have an end of life warning, which will emit 3 short ‘chirps’ approximately once every 60 seconds.
• The alarm shall have an integral test / reset button in order to test circuitry, sensor and sounder and activate all interconnected alarms in the system.
• The alarm has a built in sounder giving a minimum sound output of 85dB(A) at 1m.
• The alarm shall be supplied with installation / user instructions.
• The alarm and base shall have the following combined dimensions: 134mm height x 69 width x 71mm depth.
• The alarm and base shall have the following combined weight: 262g.
• The alarm shall have a 5 year warranty.
CO AlarmProduct Specification
CO850 (MRLi/MBXi)
17
General Guidance
18
Siting of Smoke Alarms*
600mm
• Site at no more than 600mm vertically below apex.
300mm150mm
• Site at least twice the depth of the beam away e.g. 150mm beam depth: site the alarm at least 300mm away from the beam.
* For full guidance on what type of alarm to install and where consult BS 5839 Pt.6: 2013
Flat ceiling
Flat ceilings with beams
Pitched roof
300mm 300mm
• Site at least 300mm from walls.
• Site at least 300mm from any light fittings.
• Site as centrally as possible.
300mm 300mm
>10%
ceiling
heig
ht• If depth of beam is greater than 10% of
the ceiling height, the beam should be treated as a wall (alarms need to be on either side of the beam).
Wall mounted
• The top of the detection element is between 150mm and 300mm below the ceiling.
• Site at least 300mm from a perpendicular wall.
150-300mm300mm
19
300mm150mm• Site at least twice the depth of the
beam away e.g. 150mm beam depth: site the alarm at least 300mm away from the beam.
* For full guidance on what type of alarm to install and where consult BS 5839 Pt.6: 2013
Siting of Heat Alarms*
Flat ceiling
Flat ceilings with beams
600mm
• Site at no more than 600mm vertically below apex.
Pitched roof
300mm 300mm
• Site at least 300mm from walls.
• Site at least 300mm from any light fittings.
• Site as centrally as possible.
300mm 300mm
>10%
ceiling
heig
ht
• If depth of beam is greater than 10% of the ceiling height, the beam should be treated as a wall (alarms need to be on either side of the beam).
20
Wall mounted
• Site at the breathing height of the occupants (bed height).
• Site at the breathing height of the occupants (seated height).
Siting of CO Alarms*
300mm 300mm
• Site at least 300mm from walls.
• Site at least 300mm from any light fittings.
Ceiling mounted
Wall mounted in a bedroom
• Site close to the ceiling but at least 150mm down.
• Site at least 300mm from a perpendicular wall.
• Site between 1 to 3 metres from the fuel burning appliance.
• Site between 1 to 3 metres from the fuel burning appliance.
• If the room has a partition, site the alarm on the side of the appliance.
1-3m
1-3m150mm
300mm
* The guidance is taken from BS 50292-2013, for further advice please refer to the standard.
When installing a CO alarm in a room where there is no appliance fitted
When installing a CO alarm in a room where there is an appliance fitted
21
BS 5839 Pt. 6: System Grades & Categories
System Grades
Categories
GRADE
A
GRADE
C
GRADE
B
GRADE
D
GRADE
E
GRADE
F
A fire detection and fire alarm system which incorporates control and indicating equipment installed to BS 5839: Part 1.
A fire detection and fire alarm system comprising of fire detectors other than smoke alarms and heat alarms, fire alarm sounders and control and indicating equipment.
A system of fire detection and alarm sounders (which may be combined in the form of smoke alarms) connected to a common mains power supply with back-up and indicating equipment.
Mains powered alarms with an integral stand-by power supply(battery back up).
Mains powered alarms with no stand-by power supply.
Battery powered alarms.
Alarms in all circulation spaces that form part of escape routes and all areas where a fire might start, but not bathrooms, shower rooms or toilets.
In all circulation spaces that form part of escape routes and rooms or areas that present a high fire risk.
Alarms in all circulation spaces that form part of escape routes.
LD1MAXIMUM
PROTECTION
LD2ADDITIONAL PROTECTION
LD3MINIMUM
PROTECTION
22
Minimum Grade and Category of Detection*BS 5839 Pt.6:2013
Class of premises
New or materially altered premises conforming to guidance that supports national building regulations
Existing premises conforming to current guidance that supports national building regulations
Existing premises where structural fire precautions are of a lower standard than those recommended in current guidance that supports national building regulations
Grade Category Grade Category Grade Category
Single-family dwellings and shared houses with no floor greater than 200m2 in area
Owner-occupied bungalow, flat or other single-storey unit D LD2 F LD3 D LD2
Rented bungalow, flat or other single-storey unit D LD2 D LD3 D LD2
Owner-occupied maisonette, or owner-occupied two-story house D LD2 F LD3 D LD2
Rented maisonette or rented two-storey house D LD2 D LD3 D LD2
Three-storey house D LD2 D LD3 D LD2
Four (or more) storey house A LD2 D LD2 A LD2
Single-family dwellings and shared houses with one or more floors greater than 200m2 in area
Bungalow, flat or other single-storey unit D LD2 D LD3 D LD2
Maisonette or two-storey house A LD2 A LD2 A LD2
Three (or more) storey house Grade A, Category LD2, with detectors sited in accordance with the recommendations of BS 5839-1 for Category L2 system
Houses in multiple occupation
HMOs of one or two-storeys with no floor greater than 200m2 in area
D LD2 D LD3 D LD2
Other HMOs: Individual dwelling units, within the HMO, comprising two or more rooms
D LD2 D LD3 D LD2
Communal areas of the HMO Grade A, Category LD2, with detectors sited in accordance with the recommendations of BS 5839-1 for Category L2 system
Sheltered housing
Individual dwelling unitsCommunal area D LD2 D LD3 D LD2
Housing provided NHS supported living in the community
All premises Grade A, Category LD1, with detectors sited in accordance with the recommendations of BS 5839-1 for Category L1 system
Fire detection and fire alarm system for protection of life in typical premises
*The above guidance is taken from BS 5839 Pt.6: 2013, for further advice please refer to the standard. However other relevant standards and guidance exist, for example the Local Authority Co-ordinators of Regulatory Services (LACoRS).
23
Notes
24
HEAD OFFICE Sprue Safety Products Ltd.
Vanguard Centre, Sir William Lyons Road, Coventry, CV4 7EZ UK.
TRADE SALES Sprue Safety Products Ltd.
Unit 6, Carter Court, Davy Way, Waterwells Business Park, Quedgeley, Gloucester, GL2 2DE UK.
MAIN SWITCHBOARD
024 7771 7700
CUSTOMER SERVICE / TECHNICAL ENQUIRIES
0800 141 2561
brk.co.uk GN3
770/
R2