prikaz mjera zaŠtite od poŽara - unist.hr mjera zastite o… · kojim se laĐan antonini, mag....
TRANSCRIPT
N & N PROJEKT d.o.o. Split, Gundulićeva 26
Ž
PRIKAZ MJERA ZAŠTITE OD POŽARA
SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
INVESTITOR:
SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
NARUČITELJ:
ADAPTACIJA – PROJEKT UNUTARNJEG UREĐENJA POSTOJEĆE POSLOVNE ZGRADE BRODOMERKUR SPLIT
GRAĐEVINA:
kat. čest. 7840/28 k.o. SPLIT, Poljička cesta 35, Split
LOKACIJA:
OZNAKA:
T.D. 43 P/17
FAZA:
GLAVNI PROJEKT- adaptacija
MAPA:
Z.O.P.
:
PRILOG
A - 10/17 - GP
Lađan Antonini, mag. Ing. aedif. PRIKAZ IZRADIO:
Neno Delaš, mag. Ing. aedif. DIREKTOR:
Mirta Sučić, mag. ing. arch. GLAVNI PROJEKTANT:
Split, listopad 2017. g
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 2
PRIKAZ MJERA ZAŠTITE OD POŽARA
SADRŽAJ
1. OPĆI DIO
1.1. Podaci o naručitelju
1.2. Podaci o građevini (investitor, građevina, lokacija, vrsta zahvata)
1.3. Podaci o osobama koje su izradile prikaz mjera zaštite od požara
1.4. Rješenje o imenovanju osoba za izradu prikaza mjera zaštite od požara
1.5. Ovlaštenje
1.6. Popis mapa
2. STRUČNI DIO
Uvod
2.1. Lokacija, sadržaj, namjena
2.2. Opis postojećeg stanja mjera zaštite od požara
2.3. Primijenjeni propisi i tehnički uvjeti
2.4. Zaposjednutost prostora
2.5. Otpornost na požar i reakcija na požar konstrukcije i elemenata
2.6. Sprječavanje širenja požara i / ili dima unutar građevine
2.7. Sprječavanje širenja požara na susjedne građevine
2.8. Evakuacijski putevi
2.9. Vatrogasni pristup
2.10. Požarno opterećenje
2.11. Uređaji i oprema za dojavu i gašenje požara
2.12. Odvod dima i topline
2.13. Dizala
2.14. Elektroinstalacije
2.15. Strojarske instalacije
3. GRAFIČKI PRILOZI
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 3
PRIKAZ MJERA ZAŠTITE OD POŽARA
1. OPĆI DIO
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 4
PRIKAZ MJERA ZAŠTITE OD POŽARA
1.1. Podaci o naručitelju 1.2. Podaci o građevini
1.3. Podaci o osobi koja je izradila prikaz mjera zaštite od požara
Lađan Antonini, mag.ing.aedif., Upisni broj: 187
UP/I-1413/13,8.3.2013.,8.3.2018.
OVLAŠTENA
OSOBA:
SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
NARUČITELJ:
SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
INVESTITOR:
ADAPTACIJA – PROJEKT UNUTARNJEG UREĐENJA POSTOJEĆE POSLOVNE ZGRADE BRODOMERKUR SPLIT
GRAĐEVINA:
kat. čest. 7840/28 k.o. SPLIT, Poljička cesta 35, Split
LOKACIJA:
GLAVNI PROJEKT VRSTA
ZAHVATA:
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 5
PRIKAZ MJERA ZAŠTITE OD POŽARA
1.4. Rješenje o imenovanju osoba za izradu prikaza mjera zaštite od požara
Temeljem članka 28. Zakona o zaštiti od požara (NN 92/10) izdaje se:
RJEŠENJE
kojim se LAĐAN ANTONINI, mag. Ing. aedif. imenuje za projektanta PRIKAZA MJERA ZAŠTITE OD POŽARA za:
Neno Delaš, mag. Ing. aedif.
DIREKTOR:
Split, listopad 2016. g
SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
INVESTITOR:
ADAPTACIJA – PROJEKT UNUTARNJEG UREĐENJA POSTOJEĆE POSLOVNE ZGRADE BRODOMERKUR SPLIT
GRAĐEVINA:
kat. čest. 7840/28 k.o. SPLIT, Poljička cesta 35, Split
LOKACIJA:
GLAVNI PROJEKT- adaptacija VRSTA
ZAHVATA:
T.D. 43 P/17
OZNAKA:
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 6
PRIKAZ MJERA ZAŠTITE OD POŽARA
1.5. Ovlaštenje
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 7
PRIKAZ MJERA ZAŠTITE OD POŽARA
1.6. Popis mapa
MAPA 1 GLAVNI PROJEKT – ARHITEKTONSKI PROJEKT TD 10/17-GP
MIDPOINT STUDIO d.o.o. Split, Ive Tijardovića 24, OIB 56079920397
Glavni projektant: MIRTA SUČIĆ, mag.ing.arch., A 4187
MAPA 2 GLAVNI PROJEKT – GRAĐEVINSKI PROJEKT – Projekt čelične konstrukcije TD 36/17
Ured ovl. inženjera građevinarstva ŠEPAROVIĆ ANTE, Odeska 7, 21000 Split
Glavni projektant: ANTE ŠEPAROVIĆ, dipl.ing.građ, G 10
MAPA 3 GLAVNI PROJEKT – ELEKTRO INSTALACIJE JAKE I SLABE STRUJE TD 188/17
VOLT-ING d.o.o. Split, Jadranska 7, OIB 27550971925
Glavni projektant: MLADEN ŽANIĆ, dipl.ing.el., br.up. 394
MAPA 4 GLAVNI PROJEKT – PROJEKT HIDROTEHNIČKE INSTALACIJE TD-07-VK/17
FRIGOMOTORS d.o.o. Dugopolje, Dugopoljska 35, OIB 09191580513
Glavni projektant: IVAN DOMAGOJ SUČIĆ, mag.ing.mech., br.up. 1865
MAPA 5 GLAVNI PROJEKT – PROJEKT TERMOTEHNIČKIH INSTALACIJA TD-06-STR/17
FRIGOMOTORS d.o.o. Dugopolje, Dugopoljska 35, OIB 09191580513
Glavni projektant: IVAN DOMAGOJ SUČIĆ, mag.ing.mech., br.up. 1865
MAPA 6 GLAVNI PROJEKT VATRODOJAVE E-270/17-VD
VOLT-ING d.o.o. Split, Jadranska 7, OIB 27550971925
Glavni projektant: MLADEN ŽANIĆ, dipl.ing.el., br.up. 394
PRILOG PRIKAZ MJERA ZAŠTITE OD POŽARA T.D. 43 P/17
N&N PROJEKT d.o.o. Split, Gundulićeva 26, Split
Glavni projektant: LAĐAN ANTONINI, dipl.ing.aedif., Osoba ovlaštena za izradu elaborata zaštite od požara, br.ovl. 187
2. STRUČNI DIO
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 8
PRIKAZ MJERA ZAŠTITE OD POŽARA
Uvod
Predmetni je zahvat, primjena mjera zaštite od požara za adaptaciju- unutarnje uređenje postojeće poslovne zgrade BRODOMERKUR SPLIT (dalje građevina), a obzirom na nove potrebe Filozofskog fakulteta u Splitu i stručnih službi Rektorata Sveučilišta u Splitu.
Za predmetnu građevinu postoji tehnička dokumentacija koju su izradili projektna organizacija
I.L. LAVČEVIĆ-Split-OOUR iz Splita (idejni autor/glavni projektant Danko Colnago,
dipl.ing.arh), i suradnici Projektno-tehnološki biro RO ''Monter'' Zagreb, OOUR Projektni biro –
jedinica Split , ''ING BIRO'' Split, RO ''TERMOFRIZ'' Split i ishođene su:
1. Građevinska dozvola Broj: 08/UP-I-6835/88-KS-NL. od 25. svibnja 1989. godine
2. Dopuna građevinske dozvole
Klasa: UP-I-361-03/90-01/36, Ur.broj: 2181-08-05-03/90-02/KS/NL od 17. travnja 1990. godine
3. Dopuna građevinske dozvole
Klasa: UP-I-361-03-90-01/66, Ur.broj: 2181-08-05-03-90-02-KS/DB od 5. lipnja 1990. godine
4. Dozvola za upotrebu Klasa: UP-I-361-05/90-01/14/KS/MM, Ur.broj: 2181-08-05-03/9 od 3.
travnja 1991. godine
Cilj je ovog prikaza mjera zaštite od požara, unaprijediti postojeće mjere zaštite od požara prema novom uređenju prostora građevine za potrebe Filozofskog fakulteta i Rektorata Splitskog sveučilišta, a poseban akcent će se dati na evakuaciju, budući da se povećao broj osoba u odnosu na broj za koji je građevina projektirana i unaprjeđivanje postojećih mjera zaštite od požara (podjela na požarne odjeljke, izvedba novog sustava za dojavu požara, protupanik rasvjete, sustava za odvod dima i topline sa atrija i stubišta).
Ovim će se prikazom, na odgovarajući način prilagoditi mjere zaštite od požara sa regulativom koja definira mjere za predmetno područje- Američki propis NFPA 101, poglavlje 15 (Educational occupancies), koji se u nedostatku hrvatskih propisa sukladno čl. 19 Zakona o zaštiti od požara (NN 92/10) primjenjuje kao priznato pravilo tehničke prakse, pri tome uvažavajući regulativu koja se koristila za projektiranje u vrijeme izgradnje građevine, sukladno Elaboratu zaštite od požara, izradio ING- BIRO Split, T.D. -185/88.
Važno je napomenuti, da se predmetnim zahvatom ne utječe gabarite (visinu i površinu) postojeće građevine.
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 9
PRIKAZ MJERA ZAŠTITE OD POŽARA
2.1. Lokacija, sadržaj, površina, namjena
Lokacija
Postojeća građevina, nalazi se na lokaciji Poljička cesta 5, Split (k.č.z. 7840/28 – č.z. 1332/28 k.o. Split).
Kolni i pješački pristup građevini, zadržava se postojeći, ali su za isključivo potrebe u nuždi- evakuacije, dodani izlazi, što će se posebno obraditi u točki 2.8.
Sadržaj
Katnost građevine je podruma, prizemlja 1, prizemlja 2 ,1. i 2. kat (Po+Pr1+Pr2+2K), netto korisne površine cca. 8.080 m2, a u uvodu je rečeno, kako se katnost ni gabariti predmetnim zahvatom ne mijenja.
U podrumu građevine nalazi se strojarnica i prostorija ex. centralnih baterija (za telefonsku centralu), sada spremišta.
Najveći dio površine građevine pripada uredskim prostorima. Pored toga su prisutni prostori vertikalnih i horizontalnih komunikacija, zajednički prostori komunikacije, sistem sala AOP-a, kuhinja, čajne kuhinje, skladišta, sanitarni čvorovi i gospodarski prostor.
U zapadnom dijelu građevine nalazi se centralni atrij koji se visinski proteže kroz tri etaže, a na krovu su izvedeni svjetlarnici koji propuštaju svjetlo i time omogućuju prirodnu rasvjetu tog prostora.
U prizemlju 1, na istočnom ukopanom dijelu, izvedena su dva dvonamjenska skloništa. Jedno se koristilo kao restoran, a drugo kao polivalentna dvorana za održavanje sastanaka.
Prema zahtjevima novog korisnika i prema Projektnom zadatku građevina je podijeljena na 3 prostorno-funkcionalne cjeline. Uredski prostori na zapadnom dijelu etaža Priz 1 i Priz 2 će se prilagoditi potrebama rada Filozofskog fakulteta – dio ureda će se spojiti u prostorije za grupni rad sa studentima te će se na sjevernom dijelu etaže Priz 2 organizirati rad knjižnice. Ostatak ureda smještenih na etažama 1. i 2. kata i dalje ostaju uredski prostori u funkciji zaposlenika Filozofskog fakulteta i Rektorata Splitskog sveučilišta.
Površina
Neto površina građevine je cca. 8.080 m2:
R.b. Etaža Površina (cca. m2)
1. Podrum 225
2. Prizemlje 1 2.710
3. Prizemlje 2 1.990
4. 1. kat 2.015
5 2. kat 1.140
Ukupno 8.080
Namjena
Namjena građevine se zadržava- poslovna- uredski prostori sa prilagođenim prostorima za grupni rad prema potrebama rada Filozofskog fakulteta i Rektorata Splitskog sveučilišta.
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 10
PRIKAZ MJERA ZAŠTITE OD POŽARA
2.2. Opis postojećeg stanja mjera zaštite od požara
Postojeća građevina, podijeljena je na požarne odjeljke prema izvornom Elaboratu zaštite od požara, izrado ING- BIRO Split:
1. PS1 -Administrativno upravne prostorije (podrum, prizemlje 1. i 2. kat)
2. PS2- Arhiva
3. PS3- Spremište
4. PS4- Spremište
5. PS5- Ekonomat
6. PS6- ONO- DSZ
7. PS7- Toplinska podstanica
8. PS8- Trafostanica
9. PS9- Restoran (sklonište)
10. PS10- Mjesna zajednica (sklonište)
11. PS11- Automatska obrada podataka (sistem sala)
12. PS11A- ERC (ekonomski računski centar)
13. PS11B- Agregat
Obilaskom građevine, uočeno je da cjelovitost između požarnih odjeljaka ne zadovoljava, odnosno: postoje naknadni prodori instalacija koji nisu brtvljeni; zaklopke na kanalima su neispravne i nisu spojene na sustav za dojavu požara; klizna vrata na granicama sektora nisu automatska.
Od stabilnih instalacija za dojavu i gašenje požara, u građevini su izvedeni: sustav za dojavu požara i unutarnja hidrantska mreža.
Sustav za dojavu požara zastarjele je tehnologije, sa klasičnom centralom postavljenom na recepciji. Automatski detektori i ručni javljači postavljeni su po prostorima građevine, ali nedostatno (dosta prostora nema postavljenih detektora), odnosno sustav nije u skladu sa današnjim standardom. Stoga je potrebno izvesti kompletno novi sustav, što će se navesti u jednoj od slijedećih točaka.
Hidrantska mreža izvedena je uglavnom zadovoljavajuće, sa dovoljnim brojem hidranata koji osiguravaju pokrivenost prostora građevine. Podaci o tlaku i količini nisu bili dostupni.
U građevini je izvedena protupanična rasvjeta, sa autonomnim baterijama, a opće stanje je loše. Postojeće svjetiljke su raznolike, na pojedinim mjestima neispravno postavljenje i opremljene nestandardnim piktogramima.
Vatrogasni aparati, postavljeni po prostorima građevine, ali nisu usklađeni prema važećem Pravilniku.
Važno je navesti, da je u prostoriji server (sistem sali) bio izveden i uklonjen stabilni sustav za gašenje tipa „Halon“, koji je uklonjen.
Evakuacija iz prostora građevine projektirana je na 450 osoba, a adaptacijom prostora građevine, odnosno formiranje prostorija za grupni rad (okrupnjavanjem postojećih ureda) te povećanjem broja osoba (na cca. 900), neće zadovoljiti postojeći izlazi pa će se izvršiti prilagodba dodatnih izlaza, što će se navesti u točki 2.8. Podne obloge (tapeti), koji su postavljeni na pojedinim putevima rekacije ne zadovoljavaju uvjete teško gorivih, stoga je iste potrebno ukloniti.
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 11
PRIKAZ MJERA ZAŠTITE OD POŽARA
Vatrogasni pristupi građevini vozilom, omogućeni su samo sa južne strane, dok je sa sjeverne moguća intervencija isključivo tehničko- taktičkim nastupom. Od nadležne vatrogasne postrojbe JVP „Split“, zatraženo je mišljenje o učinkovitoj intervenciji, za što je izdano pozitivno mišljenje.
2.3. Primijenjeni propisi i tehnički uvjeti - Zakon o zaštiti od požara (NN 92/10)
- Zakon o gradnji (NN 153/13, 20/17)
- Zakon o prostornom uređenju (NN 153/13, 65/17)
- Zakon o vatrogastvu (NN 139/04 – pročišćeni tekst, 174/04, 38/09 i 80/10)
- Zakon o zapaljivim tekućinama i plinovima (NN 108/95, 56/10)
- Zakon o normizaciji (NN 80/13)
- Zakon o tehničkim zahtjevima za proizvode i ocjenjivanju sukladnosti (NN 80/13,40/14)
- Zakon o građevnim proizvodima (NN 76/13, 30/14)
- Pravilnik o otpornosti na požar i drugim zahtjevima koje građevine moraju zadovoljiti u slučaju požara (NN 29/13, 87/15)
- Pravilnik o uvjetima za vatrogasne pristupe (NN 35/94, 142/03)
- Pravilnik o zapaljivim tekućinama (NN 54/99)
- Pravilnik o sustavima za dojavu požara (NN 56/99)
- Pravilnik o hidrantskoj mreži za gašenje požara (NN 8/06)
- Pravilnik o vatrogasnim aparatima (NN 101/11, 74/13)
- Pravilnik o provjeri ispravnosti stabilnih sustava zaštite od požara (NN 44/12)
- Pravilnik o temeljnim zahtjevima za zaštitu od požara elektroenergetskih postrojenja i uređaja (NN 146/05)
- Pravilnik o osiguranju pristupačnosti građevina osobama s invaliditetom i smanjene pokretljivosti (NN 78/13)
- Pravilnik o sadržaju elaborata zaštite od požara (NN 51/12)
- Pravilnik o ovlaštenjima za izradu elaborata zaštite od požara (NN 141/11)
- Pravilnik o razvrstavanju građevina u skupine po zahtjevanosti mjera zaštite od požara (NN 56/12, 61/12)
- Pravilnik o razvrstavanju građevina, građevinskih dijelova i prostora u kategorije ugroženosti od požara (NN 62/94, 32/97)
- Pravilnik o mjerama zaštite od požara kod građenja (NN 141/11)
- Tehnički propis za niskonaponske električne instalacije (NN 5/10),
- Tehnički propis za sustave zaštite od djelovanja munje na građevinama (NN 87/08, 33/10),
- Tehnički propis o građevnim proizvodima (NN 33/10, 87/10, 146/10, 81/11, 130/12, 81/13),
- Pravilnik o tehničkim normativima za ventilacijske i klimatizacijske sustave (NN 55/96, SL
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 12
PRIKAZ MJERA ZAŠTITE OD POŽARA
38/89)
- Austrijske smjernice TRVB 100-126 Austrijske Tehničke smjernice za preventivnu zaštitu od požara (Požarno tehničke karakteristike za različite namjene, skladištenja, robu)
- Austrijske smjernice TRVB 125 Austrijske Tehničke smjernice za postavljanje i rad sustava za odvođenje dima i topline nastalih u požaru u prostorijama sa velikom tlocrtnom površinom
- Pravilnik o tehničkim normativima za ventilacijske i klimatizacijske sustave (NN 55/96, SL 38/89)
- Smjernice za projektiranje i izgradnju automatskih vatrodojavnih uređaja HRN DIN VDE 0833, 1, i 2. dio
- NFPA 101 (National Fire Protection Association Code for Safety to Life from Fire in Buildings and Structures)
- HRN - STANDARDI KOJI SE PRIMJENJUJU U RH TEMELJEM PRAVILNIKU O OTPORNOSTI NA POŽAR I DRUGIM ZAHTJEVIMA KOJE GRAĐEVINE MORAJU ZADOVOLJITI U SLUČAJU POŽARA (NN 29/13, 87/15)- PRILOG 6 .
2.4. Zaposjednutost prostora Prema novoj prilagodbi/adaptaciji prostora, odnosno prema broju zaposlenika i studenata, procijenjeno je da se u građevini može zateći cca. do cca. 900 osoba.
Broj osoba određen je prema kapacitetu sjedećih mjesta i faktoru zaposjednutosti prema namjeni (prilogu 4., tablica 1, Pravilniku o otpornosti na požar i drugim zahtjevima koje građevine moraju zadovoljiti u slučaju požara (NN 29/13, 87/15)
Prizemlje 1- 305 osoba, prema kapacitetu sjedećih mjesta
Prizemlje 2- 280 osoba, prema kapacitetu sjedećih mjesta; 40 osoba (rektorat), prema faktoru zaposjednutosti od 9,3m2/osobi
1 kat- 140 osoba (fakultet); 40 osoba (rektorat), prema faktoru zaposjednutosti od 9,3m2/osobi
2 kat- 85 osoba (rektorat), prema faktoru zaposjednutosti od 9,3m2/osobi
Uzevši u obzir prethodno, procijenjeno je da se u građevini može zateći makismalno cca. 900 osoba (pun kapacitet).
2.5. Otpornost na požar i reakcija na požar nosive konstrukcije i elemenata
Otpornost nosive konstrukcije postojeće građevine prema izvornom elaboratu zaštite od požara je 60 minuta, koja će se zadržati, a budući da će se izvesti novi požarni odjeljci, isti će zadovoljiti vatrootpornost postojeće građevine.
Negorivost ili klase gorivosti uporabljenih materijala dokazati će se prema normi po HRN EN 13501-1 i HRN EN 1363-1, 1363-2, 1363-3, 1364, 1365, 1366, 1634 ili HRN DIN 4102.
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 13
PRIKAZ MJERA ZAŠTITE OD POŽARA
2.6. Sprječavanje širenja požara i / ili dima unutar građevine
Požarni odjeljci
Požarnim odjeljcima smatramo prostorije ili skupine prostorija koje su u požarnom smislu odvojene od ostalih prostora, odnosno tretiraju se zasebno, tako da će u slučaju požara širenje plamena i dima u okolne odjeljke biti spriječeno u vremenu odabranog stupnja otpornosti na požar.
Podjela na požarne odjeljke izvršena je obzirom na novu prilagodbu prostorija zbog puteva evakuacije, uvažavajući postojeće požarne odjeljke.
Prodori instalacija na granicama požarnih odjeljaka
Za sve prodore kroz zidove i stropove (instalacije, cjevovodi i sl.) na granici požarnih odjeljaka potrebno je predvidjeti nove elemente (zamjena dotrajalih i ne funkcionalnih) za sprječavanje širenja požara (zaklopke, obujmice itd.) i zaptivanje protupožarnim materijalima (pjenila itd.), tako da se zadovolji zahtijevana otpornost na požar (vatrootpornost konstrukcije- 60minuta), atestirano prema normi HRN EN 1366 ili HRN DIN 4102.
Horizontalni i vertikalni prijenos požara između požarnih odjeljaka
Potrebno je zadovoljiti sigurnosne uvjeti za širenje požara (horizontalno i vertikalno) na način da će se poštovati horizontalne (200 cm) i vertikalne udaljenosti (120 cm) otvora između požarnih odjeljaka, sukladno čl. 11. i 14. Pravilniku o otpornosti na požar i drugim zahtjevima koje građevine moraju zadovoljiti u slučaju požara (NN 29/13, 87/15).
Cjelokupna građevina, a posebno građevinski elementi kao što i moraju biti izvedeni iz certificiranog materijala i sklopova i moraju udovoljavati svim propisanim tehničkim zahtjevima.
R.b. Požarni odjeljak Lokacija Površina (cca. m2)
1. PO1- Prostorije za grupni rad Pr1, Pr2, i 1. kat 5.150
2. PO2- Stubište sa ulaznim hall-om Pr1, Pr2,1. i 2 kat 295
3. PO3- Zavojito stubište Po, Pr1, Pr2,1.,2. i K 5
4. PO4- Evakuacijski hodnik Pr1 55
5. PO5- Spremišta Pr1 35
6. PO6- Spremišta Pr1 40
7. PO7- Spremište Pr1 330
8. PO8- Prostorija servera Pr1 140
9. PO9- Evakuacijski hodnik Pr1 80
10. PO10- Spremište Pr1 410
11. PO11- Evakuacijsko stubište Pr1, Pr2,1. i 2. kat 120
12. PO12- Poslovni prostor za najam Pr2 360
13. PO13- Uredski prostori 1. i 2 kat 1.480
14. PO14- Teretno dizalo (malo) Pr1, Pr2 1,2
15. PO15- Strojarnica Po 225
16. PO16- Dizalo Po, Pr1, Pr2,1. i 2. kat 7
17. POe1- Energetska vertikala Pr1, Pr2 i 1.kat 6
18. POe2- Energetska vertikala Pr1, Pr2,1. i 2. kat 5
19. POe3- Energetska vertikala Pr2,1. i 2. kat 2
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 14
PRIKAZ MJERA ZAŠTITE OD POŽARA
2.7. Sprječavanje širenja požara na susjedne građevine
Planiranim zahvatom, ne utječe se na udaljenost od najbliže susjedne građevine. Najbliža građevina, udaljena je sa istočne strane od predmetne na cca. 4m, što je odobreno kroz postupak gradnje, odnosno uporabnu dozvolu.
2.8. Evakuacijski putevi
Određivanje izlaznih puteva kao i dimenzioniranje istih iz građevine, usklađeno je sa NFPA 101, poglavlje 15 i poglavlje 7, u dijelovima koji se odnose na evakuaciju.
Broj izlaznih evakuacijskih puteva
Sukladno NFPA 101, točka 7.4.1.2 u građevini je potrebno predvidjeti najmanje tri neovisna izlaza (od 500 - 1000 osoba) odnosno puta za spašavanje koji vode u različitim smjerovima do vanjskog prostora, ili sigurnog mjesta u građevni i koji ne završavaju u istom požarnom i/ili dimnom odjeljku, što je planiranim stanjem (otvaranje dodatnih izlaza) i zadovoljeno:
- centralni izlaz jug- Pr1
- centralni izlaz sjever- Pr2
- vanjsko stubište zapad – Pr1, Pr2 i 1.kat
- istok evakuacijski hodnik- Pr2
- glavni ulaz/izlaz- Pr2
Važno je napomenuti, da se na nijednoj etaži neće naći više od 500 osoba, a sa svake etaže postoje dva neovisna izlaza što je zadovoljava uvjete zahtijevane propisom.
Širine evakuacijskih puteva
Određuju se prema NFPA 101, tablica 7.3.3.1:
Ravni dijelovi puta evakuacije i rampe 0,5 cm/osobi
Stubišta 0,76 cm/osobi
Širine izlaza:
- Prizemlje 1- 1x100cm (izlaz zapad); 1 x 125 cm (centralni izlaz jug); 1 x 110cm (jug); 4 x 80cm (evakuacijsko stubište- PO2); 2 x 80 cm (evakuacijsko istočno stubište- PO11)
- Prizemlje 2- 1x100cm (vanjsko stubište zapad); 2 x 100 cm (centralni izlaz sjever); 4 x 80cm (glavni ulaz/izlaz istok- PO2);1 x 120cm (istok evakuacijski hodnik- PO11)
- 1 kat- 1x100cm (vanjsko stubište zapad); 2 x 80cm (evakuacijsko centralno stubište- PO2); 2 x 80 cm (evakuacijsko istočno stubište- PO11)
- 2 Kat- 2 x 80cm (evakuacijsko centralno stubište- PO2); 2 x 80 cm (evakuacijsko istočno stubište- PO11)
Širine stubišta:
- Vanjsko- zapadno- 120cm svijetlo, što odgovara propusnosti od 158 osoba
- Centralno- evakuacijsko- 160cm svijetlo, što odgovara propusnosti od 210 osoba
- Istočno- evakuacijsko- 160cm svijetlo, što odgovara propusnosti od 210 osoba
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 15
PRIKAZ MJERA ZAŠTITE OD POŽARA
U građevni se pridržavalo slijedećeg:
- Širina vrata gdje boravi više od 50 osoba min svjetlo 91 cm (101 sa panik okovom) sa otvaranjem u smjeru izlaza, sa ugradnjom panik okova sukladno normi HRN EN 1125.
- Širina vrata gdje boravi manje od 50 osoba min svjetlo 81 cm (bez panik okova)
- Jedino vrata kabineta/ureda se mogu otvarati prema unutra
- Minimalna širina koridora za prizemlje 1 i 2 mora biti 183 cm (NFPA 101, točka 15.2.3.2), što je za obrazovne ustanove i zadovoljeno, osim na prizemlju 2, gdje se zadržava postojeće širina od 140 cm (sa svake strane), koja zadovoljava kapacitet osoba koji se može naći u fakultetskom dijelu (cca. 280 osoba), a kao dodatna mjera, izveden je most, kojim se skratio put te formirao izlaz koji vodi direktno na vanjski otvoreni prostor
- Minimalna širina koridora za uredske prostore/kabinete (Prizemlje 2- poslovni prostor za najam, 1. i 2. kat), mora biti minimalno 112 cm (NFPA 101 točka 39.2.3.2.), što je i zadovoljeno
Napomena:
Pojedina zaokretna vrata (navedeno na nacrtu), spojiti će se na sustav za dojavu požara, pri čemu će se u slučaju aktiviranja istog zatvarati (zbog cjelovitosti požarnog odjeljka).
Predviđeno je da se na putovima za izlaženje neće nalaziti električne instalacije (GRO), predmeti koji pomažu širenju požara (primjerice goriva ambalaža i sl.) te stvari koje bi mogle ometati izlaz osobama (primjerice aparati različitih namjena, pričuvni dijelovi, uskladištena roba i sl.) u slučaju evakuacije, a izlazi će biti ravni, protuklizne izvedbe i bez prepreka.
Završno oblaganje građevinskih elemenata navedeno je u točki 2.5.
Dužine evakuacijskih puteva
Dužine evakuacijskih puteva definirane su u skladu sa NFPA točka 7.6, tablica A.7.6. i 15.2.6 za obrazovne ustanove (Educational occupancies)
Najveća dužina evakuacijskog puta
Najveća dužina evakuacijskog puta ne smije prelaziti 46 metara (Educational occupancies) za prostore bez ugrađenog sustava za gašenje požara- sprinkler sustav
Najveća dužina zajedničkog dijela evakuacijskog puta
Najveća dužina zajedničkog dijela evakuacijskog puta ne smije prelaziti 23 metara za prostore bez ugrađenog sustava za gašenje požara- sprinkler sustav
Dužine slijepih krakova
Dužine slijepih krakova ne smiju prelaziti 6,1 metara za prostore bez ugrađenog sustava za gašenje požara- sprinkler sustav
Na evakuacijskim i izlaznim putevima (evakuacijska vrata itd.) predvidjeti sigurnosnu protupaničnu rasvjetu primjenom odredbi hrvatskih normi HRN EN 1838, HRN EN 50171 i HRN EN 50172.
Osim toga, na evakuacijskim putovima predvidjeti će se oznake za smjer evakuacije, sukladno HRN ISO 6309, a po etažama pojednostavljene planove evakuacije i spašavanja, odnosno po sobama.
Iz svega navedenog, može se zaključiti da osigurane mjere omogućavaju sigurnu i pravovremenu evakuaciju svih zatečenih osoba u građevini.
Evakuacija osoba sa smanjenom pokretljivosti
Što se tiče osoba sa invaliditetom i smanjenom pokretljivošću, osigurati će se elementi
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 16
PRIKAZ MJERA ZAŠTITE OD POŽARA
pristupačnosti za direktan izlazak na vanjski otvoreni prostor (dizala nisu planirana za evakuaciju).
Napomena:
Poseban akcent potrebno je staviti na uvježbanom i redovitom izvođenju vježbe evakuacije i spašavanja prema posebnom dokumentu- Plan evakuacije i spašavanja, kojeg je potrebno korisnik imati.
2.9. Vatrogasni pristupi
Predmetnim se zahvatom ne utječe na vatrogasne pristupe, tako da je pristup građevini vozilom, omogućen sa jedne duže strane građevine, dok je sa sjeverne moguća pješačka intervencija.
Budući da većinu pročelja građevine čine fiksni stakleni elementi, sukladno čl. 43 Pravilnika o otpornosti na požar i drugim zahtjevima koje građevine moraju zadovoljiti u slučaju požara (NN 29/13, 87/15), vatrogascima će se radi sigurne akcije spašavanja i gašenja osigurati elementi pročelja od sigurnosnog stakla (jedan element pročelja), tako da maksimalna udaljenost između dva otvora/elementa ne prelazi 25 metara sa parapetom ne manjim od 90 i višim od 120cm, koja se mogu lako razbiti jednostavnim alatima. Uz te elemente, na vidljivom mjestu i u neposrednoj blizini biti mora se postaviti čekić za razbijanje sigurnosnog stakla uz kojeg mora biti natpis: ''PROZOR ZA SPAŠAVANJE - RAZBITI STAKLO U SLUČAJU OPASNOSTI'' tiskanim slovima zelene boje RAL 6005 Font Arial, veličina fonta određuje se projektom ovisno o veličini prostora. Osim toga, elementi pročelja moraju biti označeni s vanjske strane slijedećim znakom minimalnih dimenzija 20,00 x 20,00 cm, boje RAL 3000 sa natpisom „RAZBITI U SLUČAJU OPASNOSTI“, što je u skladu sa prethodno citiranim pravilnikom.
Važno je napomenuti, da je od nadležne vatrogasne postrojbe- JVP „Split“, zatraženo mišljenje o učinkovitoj intervenciji za što je izdano pozitivno mišljenje.
2.10. Požarno opterećenje
Požarno opterećenje je količina toplinske energije koja se može razviti u nekom prostoru, a nastaje sagorijevanjem sadržaja građevine (pokretno opterećenje) i dijelova konstrukcije i elemenata građevine (stalno opterećenje), a razlikuje se ukupno požarno opterećenje (MJ) i specifično požarno opterećenje (MJ/m2)
Ukupno specifično požarno opterećenje (Q) čini suma stalnog (qi) i pokretnog (qm) požarnog opterećenja.
Q = qi + qm ( MJ/ m2)
Prema austrijskim smjernicama za preventivnu zaštitu od požara TRVBA 100 i TRVBA 126 sukladno namjeni, konstrukciji građevine i ugrađenog materijala očitavamo stalno i pokretno požarno opterećenje.
Stalno požarno opterećenje građevine, s obzirom na konstrukciju i ugrađeni materijal, prema TRVBA 100 iz tablice 6.2/04, je qi =0 MJ/m2.
Pokretno požarno opterećenje očitava se iz TRVBA 100, tablice 2- 300 MJ/m2 (prostorije za grupni rad), 700 MJ/m2 (uredski prostori), 500 MJ/m2 (pomoćne prostorije, spremišta), elektro prostori (300 MJ/m2), restoran sa kuhinjom (300 MJ/m2).
Ukupno specifično požarno opterećenje građevine predstavlja nisko požarno opterećenje (<1000 MJ/ m2).
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 17
PRIKAZ MJERA ZAŠTITE OD POŽARA
2.11. Uređaji i oprema za dojavu i gašenje požara
2.11.1. Mobilna oprema za gašenje požara
Vrsta, broj i tip vatrogasnih aparata odrediti će se u skladu sa Pravilnikom o vatrogasnim aparatima (NN 101/11, 74/13), na način da će se u požarnim odjeljcima rasporediti vatrogasni aparati u ovisnosti o požarnoj opasnosti i površini požarnog odjeljka, što će se navesti u slijedećoj tablici.
Požarni odjeljak Površina
požarnog
odjeljka
(cca.)
Požarna
opasnost
Broj
JG
Broj
vatrogasnih
aparata
(kom.)
Tipski
požar
PO1- Prostorije za grupni rad 5.150
Srednja
108
120
120
10* 12JG- Pr1 (6 kg, prah)
11* 12JG- Pr2 (6 kg, prah)
11* 12JG-1.k (6 kg, prah)
43A,233B,C
43A,233B,C
43A,233B,C
PO2- Stubište sa ulaznim hall-om 295 Srednja 30
3* 12JG- Pr2 (6 kg, prah)
43A,233B,C
PO4- Evakuacijski hodnik 55 Srednja 18
3* 12 JG (6 kg, prah) 43A,233B,C
PO7- Spremište 330 Srednja 36
3* 12 JG (6 kg, prah) 43A,233B,C
PO8- Prostorija servera 140
Srednja 24
2* 12 JG (6 kg, prah)
1* 6 JG (5 kg, CO-2)
43A,233B,C
113B
PO9- Evakuacijski hodnik 80 Srednja 18
2* 12 JG (6 kg, prah) 43A,233B,C
PO10- Spremište 410 Srednja 36
3* 12 JG (6 kg, prah) 43A,233B,C
PO11- Evakuacijsko stubište 120
Srednja 24
1* 12JG- Pr2 (6 kg, prah) 1* 12JG- 1.k (6 kg, prah) 1* 12JG-2.k (6 kg, prah)
43A,233B,C
43A,233B,C
43A,233B,C
PO12- Poslovni prostor za najam 360 Srednja 36
3* 12 JG (6 kg, prah) 43A,233B,C
PO13- Uredski prostori 1.480
Srednja
36
84
3* 12JG- 1.k (6 kg, prah) 7* 12JG- 2.k (6 kg, prah)
43A,233B,C
43A,233B,C
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 18
PRIKAZ MJERA ZAŠTITE OD POŽARA
PO15- Strojarnica 225 Srednja 30
3* 12 JG (6 kg, prah) 43A,233B,C
UKUPNO 67 * 12 JG (6 kg, prah)
1* 6 JG (5 kg, CO-2)
43A,233B,C
113B
Aparati za gašenje požara postaviti će se na lako uočljiva i trajno pristupačna mjesta, tako da ručka za nošenje aparata ne smije biti na visini većoj od 1,50 m mjereno od poda, prema članku 14. stavak 2. Pravilnika o vatrogasnim aparatima (NN 101/11 i 74/13).
2.11.2. Stabilni sustavi za dojavu i gašenje požara
Stabilni sustav za gašenje požara- hidrantska mreža
Hidrantska mreža je postojeća i istu je potrebno prilagoditi obzirom na novu adaptaciju prostora.
Unutarnja hidrantska mreža mora zadovoljiti najveće požarno opterećenje- 70 MJ/m2 (uredski prostori/kabineti), na najnepovoljnijem mjestu (najviša etaža- 2. kat), što bi značilo da je potrebno osigurati minimalno 60 l/min pri izlaznom tlaku ne manjem od 0,25 MPa Unutarnje hidrante potrebno je rasporediti na način da štite svaku točku prostora građevine (15 ili 20m cijev + 5m mlaz), osim prostora za koje nije potrebno štićenje.
Sustav za dojavu požara
U uvodu je navedeno, da je u građevini izveden sustava za dojavu požara koji je zastario i ne udovoljava propisima pa će se stoga izvesti kompletno novi sustav za dojavu požara, što je i u skladu sa NFPA 101 točka 15.3.4.1.1.
Sustav za dojavu požara potrebno je projektirati sukladno Pravilniku o sustavima za dojavu požara (NN 56/99), a dijelovi sustava moraju udovoljavati odredbama normi niza HRN EN 54, HRN DIN VDE 0833 (dio 1. i 2.)
Za sve prostore (osim onih izuzeti prema čl. 26 Pravilnika o sustavima za dojavu požara (NN 56/99) potrebno je predvidjeti tzv. „gornju“ mrežu automatskih javljača, a u ovisnosti o izvedbi stropa (spušteni strop), potrebno je izvesti i „donju mrežu“ javljača te spuštanje paralelnog indikatora na razinu spuštenog stropa (sa „gornje zone“).
Budući da neće biti 24- satno dežurstvo, centralu sustava za dojavu požara potrebno je predvidjeti u posebnom požarnom ormariću (izvedba EI60), sa telefonskim dojavnikom odnosno automatskim prosljeđivanjem signala prema mjestu stalnog dežurstva.
Put od prilaznog mjesta vatrogasne tehnike do centrale za dojavu požara bit će označen putokazima D1 i D2 prema normi HRN DIN 4066.
Napajanje energijom sustava za dojavu požara predvidjeti sa dva međusobno neovisna izvora (el. mreža i vlastite baterije) sukladno odredbama norme HRN EN 54-4.
Kabelski razvod predvidjeti minimalne vatrootpornosti od 30 minuta.
Sastavni dio dokumentacije sustava za dojavu požara čine: plan sustava za dojavu požara, plan uzbunjivanja, knjiga održavanja i upute za rukovanje i održavanje pri čemu se poseban akcent stavlja se na plan uzbunjivanja, koji mora biti razrađen i u kojemu je utvrđen način postupanja. U planu uzbunjivanja potrebno je razraditi postupke uzbunjivanje (izvan i za vrijeme radnog vremena građevine), odnosno treba sadržavati: upozoravanje osoba u slučaju opasnosti i pravodobna evakuacija, uključivanje u gašenje požara dežurnog osoblja, odnosno osoblja koje ima posebne dužnosti glede zaštite
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 19
PRIKAZ MJERA ZAŠTITE OD POŽARA
od požara (prema Općem aktu korisnika ili Planu zaštite od požara); uzbunjivanje najbliže dobrovoljne vatrogasne postrojbe (JVP „Split“).
Prilikom prorade alarma predvidjeti slijedeće automatske radnje centrale sustava za dojavu požara:
- Isključuju se sustavi ventilacije i klimatizacije
- Zatvaranje protupožarnih zaklopki na granicama požarnih odjeljaka
- Zatvaranje zaokretnih dvokrilnih vrata (6)- PO2 (na grafici)
- Otvaranje prozora (2) za dovod zraka (atrij)
- Otvaranje prozora (svako stubište jedan prozor) za odvod dima i topline u evakuacijskim stubištima- PO2 i PO11
- Vrši se uzbunjivanje zaposlenika i studenata na način da se automatski aktiviraju alarmne sirene vatrodojave.
- Dizalo se prebacuje na požarni režim rada (spuštanje na evakuacijsku stanicu, otvaranje vrata da eventualno zatečene osobe izađu vani i daljnji rad dizala je blokiran)
Napomena:
Predvidjeti da se izvršne funkcije sustava za dojavu požara izvrši u onoj zoni/požarnom odjeljku u kojoj je alarm, budući se radi o građevini za većim faktorom zaposjednutosti, kako se ne bi stvorila panika.
Stabilni sustav za gašenje požara- sprinkler sustav
Obzirom da se radi o postojećoj građevini, sukladno NFPA 101, prema točki 15.3.5.1 (učenici borave na etažama u razini izlaska) i 15.3.5.2 (etaža koja se nalazi ispod zemlje- strojarnica u podrum je požarno odvojena od ostalog dijela građevine 60 minuta) u građevini nije potrebno predvidjeti stabilni sustav za gašenje- sprinkler sustav.
2.12. Odvod dima i topline
Odvod dima i topline sa atrija
Obzirom na specifičnost građevine (niska visina stropa), atrijski prostor nije moguće podijeliti na dimne odjeljke (postaviti dimne zavjese). U atrijskom prostoru, planiran je odvod dima i topline prirodnim putem prema TRVB S 125 preko pravilno raspoređenih kupola, za što će se iskoristiti postojeći svjetlarnici.
Površina otvora za dotok zraka koja će se osigurati preko otklopnih prozora (2) i izlaznih vrata (3), koja će osigurati dovoljnu površinu (manja u odnosu za odvod dima). Važno je napomenuti, da je izlazna vrata potrebno opremiti uređajem za fiksiranje u stalno otvorenom položaju.
Otvori za odvod dima i topline
Iz tablice 11.1 TRVB S 125 80
A= 2.100 m2- površina atrija
H = 11 m – računska visina
H= 8,3 m- visina bezdimne zone
Pretpostavljena površina požarna površina sukladno Tablici 11.1 je 10m2 (skupina 1), iz čega proizlazi da je potrebno predvidjeti 15,8 m2 efektivne površine za odvod dima i topline sa prostora atrija preko kupola.
U ovisnosti o geometriji kupole, od proizvođača će se dobiti informacija o efektivnoj površini ili
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 20
PRIKAZ MJERA ZAŠTITE OD POŽARA
se može proračunati iz tablice 11.2, preko faktora za kupole-Cv= 0,35 koji pomnožen sa površinom kupole, daje efektivnu površinu za odvod dima i topline.
Odvod dima i topline u evakuacijskim stubištima i na vrhu spiralnog stubišta
Na vrhu evakuacijskih stubišta (najviša etaža)- PO2 i PO11 i spiralnog stubišta- PO3, potrebno je predvidjeti otvor/prozor za odvod dima i topline minimalne efektivne površine 1m2, preko sustava za odvod dima i topline koji je potrebno povezati sa sustavom za dojavu požara ili preko žaluzine minimalne površine 1m2 (prirodno provjetravanje- stalno otvoreno).
Da bi se osigurao prirodni uzgon odvođenja dima iz stubišta nužno je osigurati dovod vanjskog zraka preko vrata (glavna ulazna vrata- PO2 i izlaz u nuždi- PO11), koja moraju biti opremljena uređajem za fiksiranje u stalno otvorenom položaju.
Provjetravanje u oknima dizala
Na vrhu okna svakog osobnog dizala predvidjeti otvor za prirodno provjetravanje (žaluzina na vrhu okna) čija efektivna površina neće biti manja od 1,5% tlocrtne površine okna.
2.13. Dizala
U građevini su predviđena dva (2) osobna dizala i jedno (1) teretno dizalo. Teretno dizalo je formirano kao posebni požarni odjeljak, a jedno osobno dizalo (PO16) potrebno predvidjeti kao posebni požarni odjeljak, jer povezuje više različitih požarnih odjeljaka. Stoga je potrebno predvidjeti, da vrata na svakoj stanici zadovolje zahtjev EW60.
Važno je navesti da su osobna dizala isključivo u funkciji elementa pristupačnosti, odnosno ista nisu u funkciji evakuacije te je stoga pored svakog potrebno je postaviti znakove upozorenja i zabrane korištenja dizala u slučaju požara (HRN EN 81-58:2003).
U slučaju nestanka napona, osobno se dizalo spušta na glavnu evakuacijsku stanicu- npr. prizemlje2, ili na slijedeću najbližu (ako je požar na glavnoj evakuacijskoj stanici), otvaraju se vrata za izlazak osoba koje su se eventualno zatekle te nakon određenog zateznog vremena zatvaraju se vrata i rad dizala je blokiran (tek nakon resetiranja).
2.14. Elektroinstalacije
Električne instalacije
Energetske kabele za sigurnosne sustave kao i opremu za nošenje (npr. obujmice/kanalice) predvidjeti iste vatrootpornosti (odgovarajućeg presjeka) kao i konstrukcija.
Trase električnih instalacija u područjima zona za evakuaciju ljudi (hodnici) mora zadovoljiti uvjete negorivosti i ne kapljivosti tako da ne ugrožava evakuaciju (kapanje) ili će se voditi zid.
Na prolazima električnih kabela na granicama požarnih odjeljaka predvidjeti vatrootporno brtvljenje, a otpornost na požar materijala za vatrootporno brtvljenje će biti jednaka otpornosti na požar te konstrukcije (E60), prema odgovarajućim normama (HRN DIN 4102-9 ili HRN 13501).
Tipkalo za daljinski isklop napona
Prijedlog je na vanjskom otvorenom prostoru, na zidu u blizini prostora agregatnice i trafostanice (izlaz u nuždi, jug), predvidjeti tipkala (2) za daljinsko isključivanja cjelokupnog mrežnog i agregatskog napona, a koje bi se stavilo pod ključ, u posebne ormariće i bilo bi isključivo za korištenje u slučaju nužde od strane ovlaštene osobe- zapovjednik vatrogasne intervencije.
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 21
PRIKAZ MJERA ZAŠTITE OD POŽARA
Sustav zaštite od djelovanja munje
Za građevinu je izveden sustav zaštite od djelovanje munje, a vizualnim pregledom može se zaključiti da je stanje sustava solidno. Zapisnik o ispitivanju nije bio dostupan
Sigurnosna- protupanična rasvjeta
Obirom na novi raspored prostorija i na opće stanje protupanične rasvjete, predvidjeti kompletnu zamjenu postojeće prtotupanične rasvjete. Stoga, potrebno je na svim izlaznim evakuacijskim putovima (izlazna vrata, mjesta gdje se lomi smjer kretanja, itd.) predvidjeti sigurnosnu protupaničnu rasvjetu odgovarajuće autonomije rada (2 h). Za svjetiljke sigurnosne rasvjete predvidjeti rezervno napajanje (npr. vlastite baterije), i automatsko uključivanje pri nestanku mrežnog napona. Nivo rasvjete na putovima evakuacije predvidjeti minimalno 1 lx mjereno na nivou poda u sigurnosnom režimu. Sigurnosnu rasvjetu projektirati i izvesti u skladu sa normom HRN EN 1838.
Sigurnosni sustavi
Za napajanje sigurnosnih sustava- sustav za dojavu požara; prozori (4) u sustavu za odvod dima i topline i panik rasvjeta, predvidjeti rezervni izvor napajanja (vlastite baterije). Važno je napomenuti, da je u sklopu posebne prostorije (neovisna prostorija izvan građevine) izvedena agregatnica, u kojoj je postavljen diesel agregat (125 kVA) kao rezervno napajanje pojedinih potrošača u građevini (nije sigurnosni) za koje nisu bili dostupni podaci o ispravnosti.
2.15. Strojarske instalacije
Od strojarske opreme i instalacija predviđeni su sustavi klimatizacije (grijanje/hlađenje prostora preko dizalica topline), prisilne ventilacije pojedinih prostora čiji su elementi smješteni tako da nisu zapriječeni nužni izlazi iz građevine. Odsisna ventilacija pojedinih sanitarnih čvorova, predviđena je zasebno.
Sve elemente na instalacijama, ventilacije i klimatizacije, predvidjeti od negorivog materijala (čeličnih i bakrenih bešavnih cijevi) te ih postaviti na lako pristupačnim mjestima radi održavanja.
Na prolazima ventilacijskih kanala kroz različite požarne odjeljke predvidjeti oblaganje kanala ili postaviti protupožarne zaklopke (60 minuta), koje je potrebno povezati na sustav za dojavu požara.
Navedene instalacije i pripadajuće komponente, uz pridržavanje uputa od strane proizvođača (redovito servisiranje itd.) u normalnoj eksploataciji ne predstavljaju potencijalnu opasnost za nastanak požara.
N & N PROJEKT d.o.o. Split, Gundulićeva 26 ZOP: A - 10/17 - GP
INVESTITOR : SVEUČILIŠTE U SPLITU, LIVANJSKA 5, SPLIT, OIB: 29845096215
PROJEKTANT : LAĐAN ANTONINI mag.ing.aedif.
T. D. 43 P/17
OBJEKT : ADAPTACIJA – PROJEKT
UNUTARNJEG UREĐENJA POSTOJEĆE
POSLOVNE ZGRADE BRODOMERKUR SPLIT
DATUM : listopad 2017. LIST 22
PRIKAZ MJERA ZAŠTITE OD POŽARA
3. GRAFIČKI PRILOZI
LEGENDA SIMBOLA
- granica požarnogodjeljka
- oznaka požarnogodjeljka
- prilaz vatrogasnogvozila
- smjer evakuacije
- otpornost otvora napožar 60 minuta
- vatrogasni aparat(12JG, 6kg prah)
- prostor pokrivenprotupanik rasvjetom
- oznaka nosivosti(resistance)
- oznaka cjeovitosti(etancheite)
- oznaka toplinskeizolacije (isolation)
PO
OD
R
E
I
- sustav za odvoddima i topline
- otpornostkonstrukcije na požar90 minuta
- oznakasamozatvaranjaC
- oznaka za toplinskozračenjeW
12JG
PL
panik brava (HRN EN1125)
A4 1:100
6JG- vatrogasni aparat(6JG, 5kg Co2)
- tipkalo za daljinskiisklop napona
N & N PROJEKT d.o.o. Split, Gundulićeva 26Z.O.P.:
INVESTITOR :
OBJEKT : POSLOVNA ZGRADA
BRODOMERKUR- ADAPTACIJA
PROJEKTANT :
DATUM :
T.D.
LIST :
A - 10/17 - GP
43 P/17LAĐAN ANTONINI
listopad 2017.
SVEUČILIŠTE U SPLITU,
1
mag.ing.aedif.
LIVANJSKA 5, SPLIT
A=195,50 m2
A=29,90 m2
8 10 11 189 12 13 14 15 16 17 2019 21 2322 24
8 10 11 18 2019 21 239 12 13 14 15 16 17 22 24
A
B
C
D
EI60-C
EI60
EW60
PO15PO
3OD
12JG
12JG
12JG
ZAHTJEV ZA OTPORNOST KONSTRUKCIJE
I ELEMENATA NA POŽAR
- sva nosiva ili nenosiva konstukcija (zidovi,
strop, itd.) i drugih elemenata (vrata, zaklopke,
itd.) na granicama požarnih odjeljaka moraju
zadovoljiti otpornost na požar od 60 minuta
N & N PROJEKT d.o.o. Split, Gundulićeva 26Z.O.P.:
INVESTITOR :
OBJEKT : POSLOVNA ZGRADA
BRODOMERKUR- ADAPTACIJA
PROJEKTANT :
DATUM :
T.D.
LIST :
A - 10/17 - GP
43 P/17LAĐAN ANTONINI
listopad 2017.
SVEUČILIŠTE U SPLITU,
2
mag.ing.aedif.
-3.60 /37.10/
12*15cm/30cm
12*15cm/30cm
12*15cm/30cm
12*15cm/30cm
-3.60 /37.10/
7*15cm/30cm
7*15cm/30cm
10*15cm
/30cm
7*15cm/30cm
7*15cm/30cm
7*15cm
/30cm-3.60
/37.10/-3.60 /37.10/
-3.60 /37.10/
-3.60 /37
.10/
-4.40
-3.60 /37.10/
1 2 3 4 5 6 7 8 10 11 189 12 13 14 15 16 17 2019 21 2322 24
A
B
C
D
2 3 4 5 6 7 8 10 11 18 2019 21 239 12 13 14 15 16 17 22 24
A
B
C
D
1
p=10
5cm
vp=71cm
vp=12
4cm postojeći izlaz
185
postojeći izlaz
h=70cmrampa nagiba 6%
visinsku kotu provjeriti na terenu
A=42,35 m2epoksidni pod
A=62,45 m2epoksidni pod
A=62,20 m2epoksidni pod
A=62,15 m2epoksidni pod
A=46,40 m2epoksidni pod
A=46,65 m2epoksidni pod
A=71,85 m2epoksidni pod
A=47,20 m2epoksidni pod
A=45,75 m2epoksidni pod
A=37,00 m2epoksidni pod
A=44,25 m2epoksidni pod
A=45,70 m2epoksidni pod
A=45,80 m2epoksidni pod
A=45,80 m2epoksidni pod
A=46,95 m2epoksidni pod
A=12,55 m2keramika
A=19,65 m2tepison
A=19,65 m2tepison
A=18,60 m2tepison
A=16,20 m2tepison
VATROOTPORNO
A=6,10 m2k.pločice
A=21,40 m2k.pločice
A=23,20 m2k.pločice
A=17,60 m2k.pločice
A=19,70 m2k.pločice
A=5,20 m2k.pločice
A=135,70 m2kamene ploče
A=23,60 m2kamene pločeA=4,60m2
A=4,50 m2
A=3,20 m2
A=64,70 m2k.pločice
A=38,50 m2k.pločice
A=9,30 m2
A=9,60 m2
A=6,90 m2
A=16,25 m2
A=5,30 m2 A=12,10 m2 A=6,20 m2
A=34,30 m2
A=27,80 m2
A=22,20 m2
A=79,60 m2kamene ploče
A=19,60 m2kam. ploče
A=151,00 m2A=14,10 m2
A=2,70 m2A=6,20 m2
A=6,40 m2
A=12,80 m2 A=11,40 m2 A=13,80 m2 A=14,80 m2 A=16,40 m2
A=9,00 m2
A=2,70 m2
A=6,40 m2 A=10,20 m2 A=33,20 m2
A=23,00 m2
A=117,70 m2
A=6,10 m2
A=8,7 m2
A=2,8 m2A=15,80 m2
A=14,80 m2 A=11,80 m2 A=11,80 m2 A=6,4 m2
A=13,50 m2
A=2,6 m2
A=16,2 m2A=26,90 m2
A=28,00 m2
A=24,40 m2
A=19,00 m2
A=27,50 m2A=35,40 m2
R
E
I
6
0
R
E
I
6
0
EI60-C
EI6
0
EI60-C
EI60-C
EI60-C
EI60-C
EI60-C
EI60-C
PO 5
PO10
PO 7
PO9
PO11 OD
PO 3 OD
EI60-C
EI60-C
POe2
POe1
PL
PL
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V3
95/210
V3
95/210
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V1
100/210+50
V2
110/210+50
PM-V1
140+45/210+50
PM-V
2 100/210
PM-V
2 100/210
PM-V
2 100/210
PM-V2
100/210
PS-V
2 190/210(230/260) PS
-V2 190/210
(230/260)
PS-V3 190/210
(260+665+195/260)
V3
95/210
PP-A1
1.14 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.14
SIGURNOSNO STAKLO4*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
120/210+125
PP-A3
134/
230
PP-A4
130+250/220
PL
PL
PO 8
PL
PL
IZLAZ
LIVANJSKA 5, SPLIT
IZLAZ
EI6
0
EI6
0
REI60
REI60
RE
I6
0
EI60-C
RE
I6
0
PO 1 PO
2 OD
OD
PLPL
EI6
0
EI60
U slučaju evakuacije, vrata moraju biti u
otvorenom položaju (uređaj za fiksiranje, da
dži vrata u otvorenom položaju, zbog
dovodnog zraka za potrebe odvoda dima).
12JG 12JG 12JG
12JG 12JG12JG
12JG
12JG
12JG 12JG
12JG
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
ZAHTJEV ZA OTPORNOST KONSTRUKCIJE
I ELEMENATA NA POŽAR
- sva nosiva ili nenosiva konstukcija (zidovi,
strop, itd.) i drugih elemenata (vrata, zaklopke,
itd.) na granicama požarnih odjeljaka moraju
zadovoljiti otpornost na požar od 60 minuta
PRIJENOS POŽARA
- horizontalni prijenos između požarnih odjeljaka- min. 2m
- vertikalni prijenos između požarnih odjeljaka- min. 1,2m
ELEMENTI PROČELJA
Elementi pročelja koji moraju biti od sigurnosnog stakla (min 80x120cm)
radi sigurne akcije spašavanja i gašenja uz kojeg mora biti natpis:
''PROZOR ZA SPAŠAVANJE - RAZBITI STAKLO U SLUČAJU OPASNOSTI'
PO 4
EW60
PO 6
EI60-C
R
E
I
6
0
PO16
EI60
EI60
EI60-C
EI60-C
Prozor spojiti na sustav za dojavu požara (u
alarmnom stanju se otvara) radi dovoda
zraka za odimljavanje
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
IZLAZ
Vrata spojiti na sustav za dojavu požara
(vrata su u otvorenom položaju, a u
alarmnom stanju se zatvaraju)
Prijedlog pozicije tipkala za
daljinski isklop mrežnog i agregatskog
napajanja isključivo namijenjen
vatrogascima za nužno isključivanje
(ormarić pod ključem)
RE
I6
0
12JG
12JG 12JG
6JG
12JG
12JG12JG
12JG12JG
12JG
12JG12JG
12JG
ŠAHTE
Energetske šahte čine posebni požarni odjeljak, tako da je na svim prodarima
instalacija/cjevovoda u šahte,potrebno predvidjeti postavljanje odgovarajućih
elementa za sprječavanja širenja požara (obujmice, brtvljenje itd.) .
PL
E
I
6
0
12JG
EI60 PO18
PO15
Šahta je dio požarnog
odjeljka podruma (potrebno je
oblaganje- EI90)
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
N & N PROJEKT d.o.o. Split, Gundulićeva 26Z.O.P.:
INVESTITOR :
OBJEKT : POSLOVNA ZGRADA
BRODOMERKUR- ADAPTACIJA
PROJEKTANT :
DATUM :
T.D.
LIST :
A - 10/17 - GP
43 P/17LAĐAN ANTONINI
listopad 2017.
SVEUČILIŠTE U SPLITU,
3
mag.ing.aedif.
LIVANJSKA 5, SPLIT
SANITARIJE ŽENE
SANITARIJEMUŠKI
±0.00 /40.70/
±0.00 /40.70/
±0.00 /40.70/
12*15cm/30cm
12*15cm/30cm
12*15cm/30cm
12*15cm/30cm
SANITARIJE ŽENE
150
7*15cm/30cm
7*15cm/30cm
10*15cm
/30cm
7*15cm/30cm
7*15cm/30cm
7*15cm
/30cm
p=90cm p=150cm p=150cm p=210cm
120
vp=25cm
vp=22cm
p=63 (75) cmA
B
C
D
2 3 4 5 6 7 8 10 11 18 2019 21 239 12 13 14 15 16 17 22 24
A
B
C
D
1
1 2 3 4 5 6 7 8 10 11 189 12 13 14 15 16 17 2019 21 2322 24
REFERADA
visinsku kotu provjeriti na terenu
vp=15cmrampa nagiba 6%
A=39,60 m2epoksidni pod
A=29,80 m2epoksidni pod
A=14,25 m2keramika
A=29,60 m2epoksidni pod
A=38,10 m2epoksidni pod
A=38,00 m2epoksidni pod
A=88,85 m2epoksidni pod
A=87,20 m2epoksidni pod
A=64,20 m2epoksidni pod
A=64,75 m2epoksidni pod
A=64,15 m2epoksidni pod
A=64,80 m2epoksidni pod
A=42,90 m2epoksidni pod
A=44,95 m2epoksidni pod
A=327,65 m2epoksidni pod
A=63,40 m2epoksidni pod
VATROOTPORNO
A=15,00 m2tepison
A=78,55 m2tepison
A=15,00 m2tepison
A=15,00 m2 A=15,00 m2 A=15,00 m2 A=15,00 m2 A=15,00 m2 A=15,00 m2 A=15,00 m2tepison
A=15,00 m2 A=18,80 m2tepison
A=15,90 m2
A=6,90 m2
A=6,10 m2k.pločice
A=21,20 m2k.pločice
A=22,30 m2k.pločice
A=9,40 m2k.pločice
A=19,70 m2k.pločice
A=5,20 m2k.pločice
A=8,90 m2
A=9,30 m2 A=11,90 m2
A=16,40 m2kamene pločeA=4,60m2
A=168,20 m2kamene ploče
A=32,26 m2A=23,80 m2A=21,30 m2
A=53,30 m2
A=42,50 m2 A=27,30 m2 A=18,20 m2 A=7,70 m2
A=2,20 m2
A=20,60 m2A=10,40 m2A=10,40 m2
A=4,60 m2
A=4,80 m2
A=29,95 m2
A=20,2 m2ker.pločice
A=30,40 m2kam. ploče
A=11,60 m2
A=1,70 m2
A=18,80 m2 A=17,40 m2
REFERADA
PO 2
PO 3
OD
EI60-C
EI60-C
R
E
I
6
0
R
E
I
6
0
EI6
0
RE
I6
0
EI6
0
REI60
PO12
PO11 OD
EI60-C
PO 1OD
POe2
POe1 PO
e3
V2
110/210+50
V2
110/210
V2
110/210+50
V2
110/210
V2
110/210
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50
V2
110/210+50V4
100/210
V4
100/210
PS-V
4 2*190/210(590/260)
V3
95/2
10
PS-V
2 190/210(230/260)
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO4*143X53, p=95/155
PP-A1
120/210+125
PP-A5
240/
220
480/
260
PP-A6 680/270
190/220 190/220
190/220190/220
100/220
PP-A7
143/
260
IZLAZ
IZLAZ
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
VDC
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
Prijedlog za smještaj VDC (PP ormarić- 60
min sa automatskim prosljeđivanjem signala
prema mjestu stalnog dežurstva)- prijedlog
"JVP SPLIT"
IZLAZ
Vrata predvidjeti opremljena uređajem za
fiksiranje u stalno otvorenom položaju
(zbog dovodnog zraka za odimljavanje).
EI60
Vrata spojiti na sustav za dojavu požara
(vrata su u otvorenom položaju, a u
alarmnom stanju se zatvaraju)
12JG
12JG
12JG
12JG 12JG
12JG 12JG
12JG
12JG
12JG
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
ZAHTJEV ZA OTPORNOST KONSTRUKCIJE
I ELEMENATA NA POŽAR
- sva nosiva ili nenosiva konstukcija (zidovi,
strop, itd.) i drugih elemenata (vrata, zaklopke,
itd.) na granicama požarnih odjeljaka moraju
zadovoljiti otpornost na požar od 60 minuta
PRIJENOS POŽARA
- horizontalni prijenos između požarnih odjeljaka- min. 2m
- vertikalni prijenos između požarnih odjeljaka- min. 1,2m
ELEMENTI PROČELJA
Elementi pročelja koji moraju biti od sigurnosnog stakla (min 80x120cm)
radi sigurne akcije spašavanja i gašenja uz kojeg mora biti natpis:
''PROZOR ZA SPAŠAVANJE - RAZBITI STAKLO U SLUČAJU OPASNOSTI'
EW60
R
E
I
6
0
EI60
PO16
EI60
Prozor spojiti na sustav za dojavu požara (u
alarmnom stanju se otvara) radi dovoda
zraka za odimljavanje
OD
EI60-C
IZLAZ
12JG
12JG
12JG
12JG
12JG
12JG
12JG
ŠAHTE
Energetske šahte čine posebni požarni odjeljak, tako da je na svim prodarima
instalacija/cjevovoda u šahte,potrebno predvidjeti postavljanje odgovarajućih
elementa za sprječavanja širenja požara (obujmice, brtvljenje itd.) .
EI60
PO18
Vrata predvidjeti opremljena uređajem za
fiksiranje u stalno otvorenom položaju
(zbog dovodnog zraka za odimljavanje).
PO15
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
N & N PROJEKT d.o.o. Split, Gundulićeva 26Z.O.P.:
INVESTITOR :
OBJEKT : POSLOVNA ZGRADA
BRODOMERKUR- ADAPTACIJA
PROJEKTANT :
DATUM :
T.D.
LIST :
A - 10/17 - GP
43 P/17LAĐAN ANTONINI
listopad 2017.
SVEUČILIŠTE U SPLITU,
4
mag.ing.aedif.
LIVANJSKA 5, SPLIT
7*15cm/30cm
7*15cm/30cm
10*15cm
/30cm
SANITARIJE ŽENE
SANITARIJEMUŠKI
A
B
C
D
2 3 4 5 6 7 8 10 11 18 2019 21 239 12 13 14 15 16 17 22 24
A
B
C
D
1
1 2 3 4 5 6 7 8 10 11 189 12 13 14 15 16 17 2019 21 2322 24
12*15cm/30cm
12*15cm/30cm
12*15cm/30cm
12*15cm/30cm
7*15cm/30cm
7*15cm/30cm
7*15cm
/30cm
p=149cm
SANITARIJE ŽENE
SANITARIJEMUŠKI
A=4,15 m2keramika
A=7,75 m2epoksidni pod
PP-A8
58/635
VATROOTPORNO
A=44,10 m2 A=17,00 m2 A=17,00 m2 A=34,40 m2 A=17,00 m2 A=34,20 m2 A=17,00 m2 A=17,00 m2 A=17,00 m2 A=34,40 m2 A=34,40 m2 A=17,00 m2 A=34,20 m2 A=34,20 m2 A=17,00 m2 A=39,10 m2 A=39,10 m2 A=17,90 m2
A=16,80 m2
A=21,40 m2
SANITARIJE ŽENE
SANITARIJEMUŠKI
A=6,10 m2k.pločice
A=21,20 m2k.pločice
A=22,30 m2k.pločice
A=12,40 m2 A=12,40 m2 A=12,40 m2 A=12,40 m2
A=11,30 m2 A=10,70 m2 A=10,70 m2 A=10,70 m2 A=10,80 m2 A=21,70 m2 A=11,30 m2
A=48,90 m2 A=48,90 m2 A=57,00 m2A=24,20 m2 A=16,00 m2 A=57,00 m2 A=16,00 m2 A=16,00 m2 A=57,00 m2 A=48,90 m2
A=17,60 m2k.pločice
A=19,70 m2k.pločice
A=5,20 m2k.pločice A=9,30 m2 A=11,50 m2
A=35,00 m2kamene pločeA=4,60m2
A=18,10 m2
A=4,75 m2
A=26,10 m2
A=34,10 m2
A=15,50 m2
A=17,60 m2
A=14,30 m2
A=22,40 m2
A=15,10 m2
A=82,20 m2
A=10,60 m2 A=10,60 m2 A=10,60 m2 A=18,70 m2
A=4,60 m2A=14,80 m2A=14,80 m2A=19,90 m2
A=23,00 m2
A=24,60 m2
A=26,70 m2 A=30,40 m2 A=31,10 m2
A=30,40 m2kam. ploče
A=11,60 m2
A=1,70 m2
A=18,80 m2 A=17,40 m2
RE
I6
0
REI60
EI60-C
PO11 OD
PO 13
POe2
POe1 PO
e3
PS-V7
190/21
0(29
0+280
/260)
PS-V
8 190/210(215/260)
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGUR
NOSN
O STA
KLO
2*14
3X53
, p=95
/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO
2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO4*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
PP-A2
120/210+66PL
PO 1OD
EI60-C
PO 2
R
E
I
6
0
R
E
I
6
0
R
E
I
6
0
E
I
6
0
PL
OD
RE
I6
0
EI60-C
EI60 EI60
PL
Vrata spojiti na sustav za dojavu požara
(vrata su u otvorenom položaju, a u
alarmnom stanju se zatvaraju)
12JG
12JG
12JG 12JG
12JG 12JG
12JG
12JG 12JG
12JG
12JG
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
ZAHTJEV ZA OTPORNOST KONSTRUKCIJE
I ELEMENATA NA POŽAR
- sva nosiva ili nenosiva konstukcija (zidovi,
strop, itd.) i drugih elemenata (vrata, zaklopke,
itd.) na granicama požarnih odjeljaka moraju
zadovoljiti otpornost na požar od 60 minuta
PRIJENOS POŽARA
- horizontalni prijenos između požarnih odjeljaka- min. 2m
- vertikalni prijenos između požarnih odjeljaka- min. 1,2m
ELEMENTI PROČELJA
Elementi pročelja koji moraju biti od sigurnosnog stakla (min 80x120cm)
radi sigurne akcije spašavanja i gašenja uz kojeg mora biti natpis:
''PROZOR ZA SPAŠAVANJE - RAZBITI STAKLO U SLUČAJU OPASNOSTI'
EW60
PO16
EI60
PO 3 OD
IZLAZ
Vrata spojiti na sustav za dojavu požara
(vrata su u otvorenom položaju, a u
alarmnom stanju se zatvaraju)
12JG
12JG
12JG 12JG
ŠAHTE
Energetske šahte čine posebni požarni odjeljak, tako da je na svim prodarima
instalacija/cjevovoda u šahte,potrebno predvidjeti postavljanje odgovarajućih
elementa za sprječavanja širenja požara (obujmice, brtvljenje itd.) .
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
Predvidjeti sigurnosno staklo za
vatrogasnu intervenciju (maksimalna
udaljenost između otvora 25m)
N & N PROJEKT d.o.o. Split, Gundulićeva 26Z.O.P.:
INVESTITOR :
OBJEKT : POSLOVNA ZGRADA
BRODOMERKUR- ADAPTACIJA
PROJEKTANT :
DATUM :
T.D.
LIST :
A - 10/17 - GP
43 P/17LAĐAN ANTONINI
listopad 2017.
SVEUČILIŠTE U SPLITU,
5
mag.ing.aedif.
LIVANJSKA 5, SPLIT
7*15cm/30cm
7*15cm/30cm
10*15cm
/30cm
7*15cm/30cm
7*15cm/30cm
7*15cm
/30cm
SANITARIJE ŽENE
SANITARIJEMUŠKI
A
B
C
D
2 3 4 5 6 7 8 10 11 18 2019 21 239 12 13 14 15 16 17 22 24
A
B
C
D
1
1 2 3 4 5 6 7 8 10 11 189 12 13 14 15 16 17 2019 21 2322 24
PP-A8
58/105
(635)
PP-A8
120/
127(
247)
A=10,10 m2
A=1,70 m2
A=18,80 m2 A=17,40 m2
KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE KUPOLE ZA ODIMLJAVANJE
A=61,30 m2
A=7,70 m2
A=18,20 m2
A=3,40 m2
A=6,30 m2
A=5,80 m2A=11,50 m2
A=9,30 m2 A=8,20 m2
A=66,45 m2
A=17,10 m2 A=54,70 m2 A=39,65 m2 A=36,40 m2 A=36,60 m2 A=36,80 m2 A=18,00 m2 A=18,90 m2
A=33,00 m2
A=35,00 m2kamene pločeA=4,60m2
A=73,90 m2
A=11,30 m2 A=11,00 m2 A=11,00 m2 A=11,00 m2 A=11,00 m2 A=11,00 m2 A=22,30 m2 A=11,00 m2 A=11,00 m2 A=11,00 m2 A=11,00 m2 A=11,00 m2 A=12,50 m2
A=21,50 m2 A=21,50 m2 A=21,60 m2 A=43,10 m2 A=44,00 m2 A=21,50 m2 A=21,50 m2 A=43,50 m2 A=45,10 m2
A=30,40 m2kam. ploče
A=11,00 m2 A=11,00 m2
EI60-C
EI60-C
RE
I6
0
RE
I6
0
REI60
EI60-C
RE
I6
0
Odvod dima i topline sa stubišta
efektivne površine min. 1 m2
PO 3
PO13
PO11 OD
RE
I6
0
POe3
PS-V
9 110/210(130/260)
PS-V10
190/210(290/260)
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO2*143X53, p=95/155
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
SIGURNOSNO STAKLO1*140X178, p=95
PL
PO 2OD
Vrata spojiti na sustav za dojavu požara
(vrata su u otvorenom položaju, a u
alarmnom stanju se zatvaraju)
Odvod dima i topline sa stubišta
efektivne površine min. 1 m2
R
E
I
6
0
R
E
I
6
0
PL
PL
EI60-C
R
E
I
6
0
U uredima predvidjeti sigurnosno staklo min.
dim. 80x120cm, parapet 90cm za vatrogasnu
intervenciju
U uredima predvidjeti sigurnosno staklo min.
dim. 80x120cm, parapet 90cm za vatrogasnu
intervenciju
U podu predvidjeti požarno odvajanje
energetske vertikale (zaklopke, brtvljenje,
oblaganje)
Predvidjeti prirodno provjetravanje
instalacijske šahte preko pp ekspandirajuće
rešetke kao Komjate tip PER 140
ZAHTJEV ZA OTPORNOST KONSTRUKCIJE
I ELEMENATA NA POŽAR
- sva nosiva ili nenosiva konstukcija (zidovi,
strop, itd.) i drugih elemenata (vrata, zaklopke,
itd.) na granicama požarnih odjeljaka moraju
zadovoljiti otpornost na požar od 60 minuta
PRIJENOS POŽARA
- horizontalni prijenos između požarnih odjeljaka- min. 2m
- vertikalni prijenos između požarnih odjeljaka- min. 1,2m
ŠAHTE
Energetske šahte čine posebni požarni odjeljak, tako da je na svim prodarima
instalacija/cjevovoda u šahte,potrebno predvidjeti postavljanje odgovarajućih
elementa za sprječavanja širenja požara (obujmice, brtvljenje itd.) .
ELEMENTI PROČELJA
Elementi pročelja koji moraju biti od sigurnosnog stakla (min 80x120cm)
radi sigurne akcije spašavanja i gašenja uz kojeg mora biti natpis:
''PROZOR ZA SPAŠAVANJE - RAZBITI STAKLO U SLUČAJU OPASNOSTI'
EW60
PO16
EI60
Odvod dima i topline sa stubišta
efektivne površine min. 1 m2
OD
12JG
12JG 12JG12JG
12JG 12JG12JG
12JG
Minimalna efektivna površina kupola zo
ovod dima i topline je 15,8 m2, koje je
potrebno pravilno rasporediti na površini
krova