  • Fire Systems SLC Loop Devices

  • References:

    Document 51253 SLC Wiring

    Document 15378 Device Compatibility

    Datasheets

  • SLC Loop Devices

    A Signaling Line Circuit can contain a variety of devices, each with a specific function to perform.

    Intelligent Detectors to identify a variety of threat conditions various smoke levels, heat, etc.

    Addressable Modules to interface the system to conventional input/output circuits and devices notification appliances, smoke detectors, waterflow and supervisory devices, etc.

    Addressable Pull Stations for manual alarm activation. These devices actually contain an Addressable Module inside.

    Loop Isolators to prevent total loop failure from a SLC short.

  • Communication Protocols

    CLIP Classic Loop Interface Protocol

    Polls devices one at a time in serial order. Limited to 99 detectors and 99 modules per SLC

    Loop. Compatible with NFS640 NFS2-640 and NFS2-

    3030. Solid Technologybut slow. Retrofit solution.

  • Communication Protocols

    FlashScanTM

    Complete product line.

    Permits the largest number of devices per loop in the industry (159 detectors/159 modules).

    Response times offers advanced detection options

    Faster polling and response time - exceed worldwide code requirements (< 3 sec ).

  • Isolator Application Style 4 Riser Classe B

  • Isolator Application Style 6 Classe A

  • Isolator Application Style 7 Classe A

  • FSI-851 Inico

    FSP- 851 Fotoeltrico

    FST-851 Temperatura fixa (57oC / 135oF)

    FST-851R Termovelocimtrico (8,3oC / min) e Temp. Fixa

    FST-851H Temperatura fixa alta (90oC / 195oF)

    FAPT-851 Acclimate fotoeltrico / trmico

    FSL-751 Fotoeltrico a Laser

    FSC-851 Multi-critrio IntelliQuad

    FSB-200 Beam (tipo feixe)

    FSB-200S Beam (tipo feixe) c/ auto-teste

    Detectores FlashScan: Tipos disponveis

  • Acionador Manual enderevel

    Chave resetvel

    Dupla ao (aperte e puxe)

    Pode ser aberto sem causar

    uma condio de alarme!

    LED indicador bicolor

    Verde: normal / Vermelho:

    alarme

    Visualizao pelo atuador

    frontal transparente.

    NBG12LXP: Acionador Manual FlashScan

  • Mdulos de entrada Mdulos monitores

    Simples

    Duplos

    Mini-mdulos

    Mdulo de zona convencional Detectores convencionais

    Mdulos entrada 4-20mA

    Compatvel com sensores industriais em geral:

    temperatura, presso, concentrao de gases,

    etc.

  • Mdulos de sada Mdulos de controle

    Incluem Superviso

    Alimentao 24V

    Mdulos para aplicaes de combate

    Fiao para solenides classe A/B

    supervisionada

    Listados UL/FM

    Protocolo redundante

    Mdulos de sada rel

    Permitem comando de desligamento de

    equipamentos (ex. Recolhimento de

    elevadores)

  • Mdulos de entradas e sadas Mdulos FDRM-1

    2 entradas supervisionadas

    2 sadas de rel (NA/NF)

    Menor custo de instalao

  • Mdulos isoladores Mdulos ISO-X

    Protege contra curto-circuitos

    At 200 mdulos por lao, sem

    perda de capacidade

    Mximo 25 dispositivos entre

    isoladores (20 pela ABNT)

  • XP10-M Ten Class B or five Class A Initiating Device Circuits for normally open alarm contact devices.

    XP6-MA Six Class B or three Class A Initiating Device Circuits for monitoring UL Listed two-wire smoke detectors (requires filtered, resettable 24 volts).

    Mounts in BB-XP backboxes two modules, surface mount. Mount up to six modules on a CHS-6 chassis.

    Addressable Input Modules

    XP6-MA

    BB-XP

  • XP6-C Transponder Control Module. six Notification Appliance Circuits, Class A or B.

    SYNC-1 Synchronization daughter module for XP6-C using System Sensor appliances.

    XP6-R Transponder Relay Module. Six Form-C Dry Contact Relays.

    Mounts in BB-XP backboxes two modules, surface mount. Mount up to six modules on a CHS-6 chassis.

    Addressable Output Modules

    XP6-C

    CHS-6 Chassis

  • Multi-Circuit Module Mounting Options

    BB-25 (Black) / BB-6 (Red)

    Mounts up to 6 XP Multi-Mods

    BB-XP (Black) / BB-2 (Red) Mounts up to two Multi-Mods

  • Mounts in a standard CAB-4 Series enclosure using up to 1-4 CHS-6 chassis for a total of 24 Multi-Mods.

    CAB-4 Series Enclosure with CHS-6 Chassis

    Multi-Circuit Module Mounting Options

  • Base sonora B200S

    Ativa a sirene quando o detector ligado a ela ativado

    Pode ser ativada remotamente pela central

    Padro Temporal 3 e Temporal 4

    Sincroniza com os dispositivos AV da System Sensor

    Necessita alimentao 24VDC externa

  • Diversos modelos:

    P2R udio/visual

    SR somente strobe

    HR somente sirene

    Opes a prova de tempo

    NEMA 4X/IP56

    Sinalizador e placa de montagem

    Intensidade ajustvel

    Montagem simples

    Sinalizadores SpectrAlert Advance