Page 1: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

PowerLogic® E5600 power and energy meter

Page 2: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 2- North American Operating Division

A PowerLogic system can help you…

Submeter and bill tenants and departments● Accurate, economical energy monitoring lets you bill tenants for their actual

usage and eliminate previously uncontrolled utility expenses.

Accurately allocate costs ● Monitor individual cost centers, identify opportunities for demand control, and

check energy consumption patterns. Its low total cost of cost of ownership means you can easily place a PowerLogic E5600 wherever you need it.

Reduce energy costs● Verify the effectiveness of energy efficiency efforts by

monitoring key points within your power distribution system. Collect the data you need to ensure contractual obligations are met and use the PowerLogic E5600 to help achieve LEED certification and green building status.

Page 3: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 3- North American Operating Division

E5600 Product Overview

● Easy to specify, install and wire

● Economical to purchase and own

● Simple to configure and use

● Revenue accurate energy and power measurements

● High quality construction and self diagnostics enhance reliability

● Industry-standard communications

● Excellent upgrade path helps you save money on future expansion

●Part of a complete tenant metering solution

Page 4: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 4- North American Operating Division

Target customersAn ideal choice for:

●Office buildings●Multi-use commercial

●Malls

●Retail operations

●Universities and colleges

●Government facilities

●Hotels

●Multi-use residential

●Airports ●Other transportation facilities

Buildings

Retail

Multi-Residential

Transportation

Institutions

Page 5: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 5- North American Operating Division

Features and benefits

Economical to purchase, own and install

●S-base socket compatibility enables easy retrofit into your existing metering infrastructure

●Self diagnostics and an auto ranging power supply reduces potential wiring errors and installation costs.

●A simple interface and standard configuration software get you up and running quickly

●Easily replace electro-mechanical meters with the accurate, solid state PowerLogic E5600

Page 6: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 6- North American Operating Division

Supported S-Base meter socket form factors include:

Self-contained, class 200 in forms:

● 2S

● 12S

● 16S

Transformer rated, class 20 in forms:

● 9S

● 36S

● 45S

Features and benefitsFeatures and benefits

Page 7: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 7- North American Operating Division

View system data through the easy-to-read LCD screen

●The meter displays measurement data in numeric values, potential indicators, nominal service voltage, service type, power quadrant status, energy flow and name plate data.

●An alternate display provides diagnostic information.

Features and benefits

Page 8: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 8- North American Operating Division

High accuracy measurements

● Meets ANSI C12.20 accuracy standard, a nationally recognized sub-metering benchmark

● Eliminate bulk energy billing and allocate costs to suites, tenants and departments based on their actual use

● Use energy cost tracking and tenant billing to improve tenant retention and quality, meet regulatory requirements and increase property value

● Onboard memory of 128KB provides 82 days of logged data

Features and benefits

30% energy savingsin a building canreduce overalloperating costby 10%

Page 9: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 9- North American Operating Division

Industry standard communications

● Standard Modbus serial protocol

eases billing software, energy

management and building

automation system integration

● Improve efficiency by eliminating

manual meter reading

● Enhance future expansion

possibilities and reduce the costs

associated with proprietary protocols

Features and benefits

Page 10: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 10- North American Operating Division

Meter characteristics (front panel)

Anti-tamper (revenue) lock

LCD display screen

ANSI C12.18 Type II front panel optical

Page 11: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 11- North American Operating Division

Meter characteristics (rear connections)

Input/output and Modbus RS485 cable

Voltage inputs

Current inputs C B A

Current outputs A B C

Page 12: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 12- North American Operating Division

● Meter forms.● Self-contained class 200 in form 2S, 12S, and 16S● Transformer rated class 20 in form 9S, 36S, and 45S

● S-based socket meter.● Auto-ranging voltage inputs for direct connection of 120 - 480V● Supports 4-wire wye, 3-wire wye, 3-wire delta and single phase

● Starting Load:● Class 20: 0.005 amps● Class 200: 0.050 amps

● Power loss duration @ Vn – 100msec minimum.

● High Voltage Line Surges ANSI/IEEE C62 (6kV).

● Surge Withstand Capability (ANSI C37.90A).● Oscillatory: 3 kV ● Fast Transient: 5kV

Meter characteristics

Page 13: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 13- North American Operating Division

● Overvoltage Withstand:● Temporary (0.5 seconds): 150% of rated voltage● Continuous (5 hours): 130% of rated voltage

● Smoked polycarbonate case.● Environmental.

● Operating temperature: -40 to 176 oF (-40 to 80 oC)● Humidity:5% to 95% non-condensing

● Communications.● RS485 serial interface with six foot interfacing cable – flying leads● ANSI C12.18 communications interface

● Utility Grade.● ANSI C12.20, class 0.2

● Security.● Multiple levels of security available via physical seals and passwords

Meter characteristics

Page 14: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 14- North American Operating Division

PowerLogic software

A comprehensive range of cost effective, easy-to-use software for and end to end billing solution.

PowerLogic Tenant Metering - Commercial Edition

Real & reactive energy Flat & tiered rates Demand & power factor Seasonal rates Time of Use Miscellaneous charges

PowerLogic ION Setup Installation set up and meter

configuration software included with the PowerLogic E5600

PowerLogic ION Enterprise Scalable for system growth Integration with 3rd party meters,

equipment and web services Data sharing with BAS and business

systems Advanced power quality analysis,

reporting and control capabilities

PowerLogic System Manager Software

Real time readings Load profile upload Resets for date/time and demand Advanced power quality analysis,

reporting and control capabilities

Page 15: PowerLogic ® E5600 power and energy meter. Schneider Electric 2 - North American Operating Division A PowerLogic system can help you… Submeter and bill

Schneider Electric 15- North American Operating Division

Complete tenant metering solution

● Cost effective: ● Low cost of ownership enables placing meters wherever needed

● Easy installation:● Configuration and diagnostic tools simplify installation into existing utility

sockets utility

● Utility grade accuracy● Allocate cost and provide accurate tenant billing

● Power and energy readings: ● Achieve LEED and energy star certification

● Tenant Metering Commercial Edition Software: ● When combined with the PowerLogic E5600 completes the sub-billing

solution

● Support and services● Optimize your PowerLogic system with our technical expertise and

industry knowledge via the technical support, customer training or engineering services groups.

PowerLogic E5600 – the right meter for office, retail, campus, and government tenant metering applications