powerhouse systems · current 21a (max.) 20a (max.) psophometric noise < 2mv at full load, over 600...
TRANSCRIPT
-
Revised 09.10.2012
an R&D TechnologyGroup Company
PowerhouseSystems
ContentsPhase Control DC Systems 2Modular DC Systems 3Modular Inverters 6Modular Static Switches 7Modular DC/DC Converters 8Power Factor Correction 9Transformers 14Power Supplies 15
Uninterruptable power supplies (UPS)
Surge Protection
Offline
Line Interactive
True Online
Compuguard Series 16
Safeguard Series 18Defender Series 20Commander Rack Tower 22UPS Software 24
Centurion Tower 26Centurion Rackmount 29Centurion 3 to 1 32Platinum Series 34Power Plus Series 36
Surge Boards 43Zone Defender Pro 44Zone Defender 2 48
-
2 Power Conditioning CataloguePhase Control DC Systems
SPECIFICATIONS
Powerhouse’s Phase Control DC systems are of constant voltage and current limited type. Utilising SCR phase control design they provide a rugged and highly reliable DC supply.
Available with single and three phase inputs, the Powerhouse Phase Control series are ideal for charging sealed lead acid, vent-ed lead acid and lithium phosphate batteries.
Phase Control DC systems are in widespread usage throughout Australia to supply LV & HV switchboards, DC substations, emergency power and lighting systems, and switch tripping. As a result, HILITE chargers are found in both commercial and industrial operations, in areas such as hospitals, airports, utilities, communications, mining and petrochemical industries.
Dependant upon rating, DC systems can be housed in wall-mount or free standing enclosures, which will normally accommodate optional equipment and batteries without increased size. Larger enclosures are available for more complex systems.
PHA
SE C
ON
TRO
L DC
SYS
TEM
S
Input Voltage 220/240 Single Phase +/- 10%380/400/415 Three Phase +/- 10%
Input Frequency 50-60Hz ± 3Hz
Output Voltage 24, 32, 48, 110, 125 VDC
Charging Voltages
Sealed Lead Acid: Float 2.2-2.25V per cell, Boost: 2.3-2.4V per cellVented Lead Acid: Float 2.2-2.25V per cell, Boost: 2.3-2.5V per cellLithium Iron Phospate (LiFePO4): 3.6V per cellThe above settings will vary with cell manufacturer, cell type, duty and ambient conditions.
Output Power Single Phase < 6KWThree Phase > 6KW
Ripple VoltageRMS ripple voltage across the battery will not exceed 2% of the nominal system voltage when a battery of Ah capacity of 4 times that of the charger nominal current rating is connected.
RegulationOutput voltage regulation of +/- 0.5% and current regulation of ± 1%, providing the mains input variations do not exceed ± 10% Voltage, ± 5% frequency and for load changes 0-100%.
Temperature Range
Operational: -10ºC to +40ºC +40ºC to +65ºC (de-rate current by 1% per ºC)
Cooling Air Convection (fan assist - high power units)
Efficiency 80-93% dependant on system voltage and power rating.
AlarmsCharger Fail, Low Volts, High Volts, Low Electrolyte and Earth Fault with audible warning.
Meters Charge Current, Load Current and Battery/Charger Voltage.
Indicators LED Panel: Power On, Boost, Float, Charger fail, Low Volts, High Volts, Low Electro-lyte and Earth Fault.
Controls Input and Output Circuit Breakers, Alarm Reset and Boost Initiation Push buttons.
Options Voltage free contacts for all alarms, Battery Test, Low Voltage Disconnect and Mains Failure alarm contact.
Enclosure
Suitable for operation in industrial environments and tropical conditions. Sheet steel to IP42 with powercoat finish (colour to customer requirements). Alternative materials and IP ratings available on request. Batteries can be housed within the enclosure in a separate compartment.
AS Standards AS1939, 1955, 2293, 2374, 2735, 3000, 3108, 3901 & 4044
-
3www.powerhousesystems.com.auModular DC Systems
MO
DULA
R DC
SYS
TEM
S
Powerhouse’s Modular DC power system (1UDC+) provides clean DC power to sensitive equipment while simultaneously charging the battery bank, sup-plying backup power during mains failure.
The 1UDC+ contains a 19” 1U subrack that can house up to 3 hot-plugged rectifiers, or 2 rectifiers & controller and an ELVD device. Max system capacity: up to 13 subrack (38 rectifiers + controller), 1266A with height of 13U
Basic shelf: 1U DC + type II – includes a 19” 1U shelf (subrack) with up to 3 rectifiers
Electronic Shelf: 1U DC+ type I – includes a 19” 3U shelf with up to 2 rectifiers + SC 1UDC + control-ler and an electronic ELVD device
FEATURES:• Very high efficiency: 96%• 100A for each 1U shelf• Intelligent power module, digitally controlled• One to three hot-swap rectifiers in each shelf• Active current sharing among rectifiers• Universal input voltage• A built-in dual 70 A Electronic Low Voltage Disconnect device (ELVD) for
battery protection• Option to connect 2 external LVD contactors of up to 1600 A• A high-performance, hot-swap system controller (SC 1UDC+) to measure,
monitor and control voltages, current, power, battery, temperature, etc.• USB (SC1U DC+) or TCP/IP+USB communication (SC 1UDC+ NET)• Advanced battery management• Up to two battery sets handled in one system• Automatic and pre-programmed battery test (for each battery set)• Automatic and pre-programmed equalize charging mode• Breaking alert by modem (option)
-
4 Power Conditioning Catalogue
The PS1UDC+ power system is comprised of four main subsystems:
• Shelf Unit: Type I: 1U DC+ type I – includes a 19” 3U shelf with up to 2 rectifiers + SC 1UDC + controller and an electronic ELVD device
Type II: 1U DC + type II – 19” 1U shelf (subrack) with up to 3 rectifiers
• System controller: Monitors and controls the system and also communicates with an external PC or network. This is done by an RS232 serial port (standard) or via PPP/SNMP/TCP-IP protocol (optional).
• Rectifier module(s): Convert(s) ac input to dc output.
• Electronic Low Voltage Disconnect (ELVD) device: Disconnects the battery from the load, preventing the damage to the battery that results from over-discharging. The PS1UDC+ has a true semiconductor-based LVD with no moving parts (such as relays or contactors). This ensures reliable operation and a long MTBF. The ELVD of the PS1UDC+ uses power MOSFETs to perform the switching. The ELVD has two branches that can handle two independent battery sets. (For loads higher than 120 A, battery disconnection is performed by a dc contactor (LVD).)
MO
DULA
R DC
SYS
TEM
S
The rectifiers are “hot pluggable” and operate in parallel. This means the rec-tifiers can be added or replaced with no impact on the power supply to the load devices and with no impact on the battery charging current. The parallel configuration of the rectifiers also enables the user to define an “N+1” or “N+2” redundant system.Each rectifier has its own current sharing system, and provides complete, precise current sharing among rectifiers.Output terminals for connecting the load and battery sets are mounted on the connecting busbars of the motherboard, located behind the removable metal rear panel.OPTION: On customer request, the the PS1UDC+ power system can include a special additional rack containing dc–dc converters.
BLOCK DIAGRAM OF PS1UDC+
-
5www.powerhousesystems.com.au
MO
DULA
R DC
SYS
TEM
S
1UDC+ SPECIFICATIONSINPUT 1UDC 24V 1UDC 48V 1UDC 48V EE
Nominal Voltage 230V
Voltage Range 85Vac - 285Vac, with derating
Maximum Current1 (@ full load) Nx6A Nx10A
Frequency 47Hz - 63Hz
Power Factor (@ Full Load) > 0.99
Protection Relay disconnects input for >300V Fused Relay disconnects
input for >300V
OUTPUT
Voltage (default) 27 ± 0.2Vdc 54 ± 0.2Vdc
Adjustable Range 23Vdc - 30Vdc 47Vdc - 58Vdc
Regulation (line & load) ±1%, ±0.25% with controller
Nominal Current1Nx40A (Vin>195V) Nx20A (Vin=110V) (max 38 modules)
Nx33.3A (Vin>195V) Nx16A (Vin=110V) (max 38 modules)
Ripple & Noise @ BW=30MHz 200mVp/p, 20mVrms
Psophometric Noise -52dbm over 600 Ω (
-
6 Power Conditioning Catalogue
MO
DULA
R IN
VERT
ERS
POWER 0.5kVA 24V 1kVA 48V
Topology Dual high frequency conversion
Control Dual 8-bit RISC Microcontroller
INPUT
Voltage 24Vdc (nominal) 21- 30Vdc 48Vdc (nominal) 42 - 60Vdc
Current 21A (max.) 20A (max.)
Psophometric noise < 2mV at full load, over 600 Ω
Low voltage shutdown 21Vdc ± 0.5 42Vdc ± 0.5
OUTPUT
Voltage 220/230Vac
Power 500VA / 300W 1000VA / 700W
Efficiency (dc-ac) 88% @ 24VDC 90% @ 48VDC
Frequency 50/60Hz ± 0.1% (free-mode)
Synchronization system Active current sharing
Waveform Pure sinewave
THD 1.5% max. for linear load 4% max. for non-linear load
Crest factor 3:1 max. for non-linear load
Voltage regulation (line & load) ±1% (static) recovery within 500mS
GENERAL Parallel Configuration Up to 30 units in parallel
Isolation voltage 1500VAC input-output
1500VAC output-chassis500VDC input-chassis
Protection Output over-voltage, output overload
& short circuit (inherent by pulse-by-pulse) LVD (low input voltage disconnection), over-temperature
Display 5 LEDs and load bar graph
Safety IEC 950 (EN 60950)
EMC (including the shelf ) EN300-386-2, EN 50082-1, EN 55022
Audible noise < 50dBA @ 1.5m
Temperature -10OC - +50OC -10OC - +45OC
Signalization 1 dry contact (fault indication)
Dimensions WxHxD (mm) 202 x 44 x 243
Weight (without shelf ) 1.5Kg
SPECIFICATIONS
Model IPU1000
Features • Up to 30 units in parallel, 30kVA • Employs high frequency PWM technology • A microprocessor controls all diagnostics and operation • Power density (2kVA in 1U 19” shelf; • 1kVA in 1U 9.5” cabinet) Lightweight • Standalone or parallel operation Parallel capability for N+1 redundancy
High efficiency • Continuous input DC curent • Optional: bypass (for standalone operation)
All specifications are typical and subject to change without prior notice
Modular Inverters
-
7www.powerhousesystems.com.au
MO
DULA
R ST
ATIC
SW
ITCHE
SAC input and output Three phase with a common neutral is available Nominal power 10 ~ 250 kVA
Input voltage range 196 V ~ 253 V (Phase to Neutral), other values are available
Input frequency range 46 Hz ~ 64 Hz, other values are available
Transition time in synchronized mode1 < 3 msec
Transition time in non-synchronized mode < 200 msec
Signals and indicators 5 LEDs, 3 keys, audible alarm
Efficiency 99.90%
Regulations Complies with the IEC950 standard
AC input and output Single phase with common neutral Nominal power 3 to 30 kVA Input voltage range 187–253 Vac, other ranges also available Input frequency range 46 Hz–64 Hz, other ranges also available Signals and indicators 6 6 LEDs, 3 keys, audible alarm, RS232 interfaceEfficiency 99.90%Size in mm (H × W × D) 132 × 483 × 250 (3U) Weight
-
8 Power Conditioning Catalogue
MO
DULA
R DC
/DC
CO
NVE
RTER
S INPUT SINGLE DC-DC 48-24 MODULE Voltage range 42 - 61.5VDC Current 17A (max) Efficiency >88% Protection Against reserve polarity connection Low Voltage Protection Stops at Vin < 42VDC Restart operation Automatic at Vin > 46VDC
OUTPUT
Voltage 24VDC Current limit 25A (folds back to 9A at short circuit) Voltage adjustment ±5% Voltage regulation ±1% Ripple 50mVrms Protection Over load, output OVP, Over-temperatureDisplay 4 LED bar-graph display the load level Parallel operation Active current-sharing
General
Ambient temperature -10°C - 50°C Humidity 0-95 % Dimensions (mm) Weight (Kg) 146 (W); 44 (H); 260 (D) 0.8
Withstand voltage Input – Output: 1500VDCInput – chassis: 1500VDC
Output – chassis: 1500VDC
Cooling Forced, fan speed control Safety IEC950, EN60950
EMC EN55022, EN6100-4-2 2,3,4,5,6,11
EN61000-3-2 EN6100-3-2, EN61000-3-3
48/24 600W Modules This dc-dc converter module simply converts a nominal 48 V (42 V-61.5 V) into 24 V (25 A maximum) accurate voltage at the output. The unit comes with the option to parallel several similar modules in order to gain more power and redundant operation (N+1).
- All specifications are subject to change without prior notice - All images are for illustration only
DC POWER SYSTEMS - 130912
Modular DC/DC Converters
-
9www.powerhousesystems.com.au
The following is a general description of the Powerhouse Systems standard Automatic Power Factor Correction system and the components used.The Powerhouse Systems Power Factor Correction equipment is based on many years of experience with the application and installation of automatic power Factor cor-rection equipment in Australia for Australian conditions and using the latest Australian and Overseas standards.
The following Standards are used in the Powerhouse Systems equipment:
IEC 831 - Part 1 and 2 - Manufacturing Standard for Power Factor Correction Ca-pacitors AS 1013 - 1971 - Shunt Capacitors - Where applicable AS 3000 - 2007 - Wiring rulesAS 3008 - 1.1.1998 - Selection of CablesAS 2005 - FusesAS 1028 - Reactors and TransformersISO 9000 - Quality standardsLocal Supply Authority - Service and installation Rules
The kVAr rating of the Powerhouse Systems Power factor correction equipment are based on -
Volts - 415 Volts (+10%) Phase - 3 Phase plus Earth + NeutralFrequency - 50 HzTemperature - 45ºC Continuous Maximum Ambient
The basis of the Powerhouse Systems Power Factor Correction equipment is safety and reliability. All equipment is front accessible and modular in constructionA freestanding 2mm sheet steel, powder coated cubicle is supplied to house all equipment. Forced ventilation, designed to extract air from the top of the cubicle via base screened vents is included. Two(2) High reliability ball bearing cooling fans, ther-mostat controlled, are mounted in the roof and provide a minimum airflow rate of 710m3/h each.Highest quality capacitors are mounted in a separate enclosure, attached to the standard enclosure. This cubicle is separately ventilated.
Modular ConceptThe design utilizes a Modular concept with 100kVAr withdrawable modules contain-ing all required parts. The modules can be removed and replaced within 30 min-utes.
AUT
OM
ATIC
PO
WER
FA
CTO
R C
ORR
ECTIO
N
RATING
GENERAL
DESIGN
GENERAL
Power Factor Correction
-
10 Power Conditioning Catalogue
CONTACTORS
Detailed Specifications of Capacitors
Standards - IEC 831 1+2/88, VDE 560-46+47 3/95Overvoltages - +10% (8 hours daily) - +15% (30mins daily) - +20% (up to 5 mins) - +30% (up to 1 min)Overcurrent - 1.3In - 1.5 In with 10% Overvoltage , 15% over capacitance and harmonics included, continuous operation.Test Voltages - Terminal/ Terminal - 2.15 Ucn AC 2 Seconds - Terminal/ Casing - 4800 VAC, 2 SecondsTemperature - Category - -25/D ( max. 55 Deg C) To IEC 831 - Max Case Temp. 65 Deg CInrush Current - maximum 200 Times Rated CurrentRated Capacitor Voltage - Ucn: Standard - 440Volts (& 480 Volts) Detuned - 525 Volts
Capacitors are mounted in a separately ventilated cubicle, away from reac-tors, contactors and any heat generating equipment.
Standards - IEC 947-4-1 - AS3947-3Contactors designed especially for switching low inductive capacitive loads are used. These contactors are used for switching capacitors mentioned above and are protected against contact welding for a prospective current of 200 x I e . i.e. 200*72 Amps.
Contactors have magnetically switched early make contacts and damping resistors. These reduce the inrush current to
-
11www.powerhousesystems.com.au
Standards - IEC947-3Fully shrouded fused isolators are used to isolate and protect either the Power Factor Correction system and/or the individual steps. These are busbar mount-ed and contain DIN fuses suitably rated for protection of each capacitor step and connecting cables (125 Amp for 50kVAr and 63 Amp for 25kVAr steps).
Switching ratings - Step Switch-Fuse - 160 Amp- Making Capacity - 40kA- Impulse Voltage - 8kV
Main Isolator - 400 Amp , 630 Amp, 800, 1250 Amp - Making capacity - 100kA - Impulse Voltage - 12kV Fuses - DIN - To IEC 269-2-1 Breaking Capacity 120kA (size 00-2)
(Monitors power factor and controls capacitor steps)
The reactive control relay is mounted on the front door of the cubicle and monitors the incoming voltage and current from the main switchboard. Based on target power factor and actual switchboard power factor, it switches capacitor steps in or out of circuit ensuring that connection and reconnection times are met.
Reactive Controller Features• Microprocessor Based• Digital Display of Power Factor, step Number op-
erating and all setup information.• Circular switching i.e. all capacitor steps are equal duty shared.• Zero Voltage Tripping i.e. On mains failure, all steps are switched out and , upon
mains restoration capacitors are switched in again only after the correct block-ing delay
• High resistance to faults due to mains harmonics i.e. input circuits have a band pass filter fitted
• Alarm output and indication of (a) Failure to achieve target power factor. (b) Mains failure (c) Temperature (d) Harmonic levels (voltage and Current) (e) Voltage and Current levels (f) Display of Volts, Amps, Kw, KVA, KVAr, Harmonics, temperature, Contactor switchings and duration of contactor operation (g) All maximums data logged for future reference
• Options - serial output RS485, RS232 (profiBus and ModBus )• Front Panel protection - IP 54
(Protects and isolates Capacitor Steps)
AUT
OM
ATIC
PO
WER
FA
CTO
R C
ORR
ECTIO
N
SWITCHES - FUSES
REACTIVE CONTROL RELAY
-
12 Power Conditioning Catalogue
(Where fitted, Tunes Capacitor Bank below Harmonics)
Standard - AS 1028Harmonic detuning reactors are placed in circuit prior to capacitors to “detune” the capacitor bank to below harmonic frequencies e.g. 5th (250Hz) 7th (350Hz) 11th (550Hz) etc. which are usually caused by power switching devices e.g. Variable speed drives, UPS Systems, Arc Furnaces etc.
Type - Dry Type, Air CooledTuned Frequency - 189 Hz (7%) detuningCurrent Rating (Min) - 70 Amps I1, 51 Amps I5, 86 Amps I total, 100A Flux Density - < 0.80TeslaWinding Temp rise - Not more than 40ºCQ factor - 38Insulation Class - Class H - 180°C Dielectric Strength - 3kV for 1 Minute to IEC 76/3Core Type - High Permeability silicon Grain Oriented Laminated Core.Losses - 86Watts/50kVAr StepConductor and Termination - Copper and busbar connection
MountingWiring to reactors is via single flexible lugged cables. Reactors are mounted on non-magnetic brackets (Aluminium) to Eliminate eddy currents and reduce noise and heat loss.
Standard - AS3439.1 - IP31 standard, IP54 Optional.Cubicle construction is sheet steel minimum thickness 2mm, powder coated X15 orange to AS2700 (any other colour to AS2700 powder coat available).
Features• 100mm (or 75mm) heavy duty Galvanized Plinth• Door mounted screened vents on all doors• Three(3) point locking on doors above 1200mm• Gland plate, 3mm thick, non-magnetic fitted to roof of cubicle, positioned
over incoming connections. Bottom cable entry available• Dust proof seals are mounted on all doors
HARMONIC DETUNING REACTORS
CUBICLE CONSTRUCTION
TESTING AND COMMISSIONING
(To house all components and provide environmental protection)
Before dispatch, all power factor correction systems are tested as follows
• Insulation check – 2,000 Volt for 15 Seconds ph-ph and Earth
• All connections and joints checked • Capacitance and wiring check of each step• Reactive relay setup and test• Full load current check of each step including harmonic checks• Completion of test/commissioning report.
-
13www.powerhousesystems.com.au Power Factor Correction system - 250912
AUT
OM
ATIC
PO
WER
FA
CTO
R C
ORR
ECTIO
N
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099 Gloucester P: +61 2 6558 2986 F: + 61 2 6558 1002Mackay P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
A complete instruction manual is included with each system shipped, which in-cludes the following major items:
• General Description of Power Factor and Installation• Description of Equipment with Specifications and test reports• Commissioning instructions• Component detailed data sheets and performance specifications.• Schematic and wiring diagrams• Maintenance Instructions
INSTRUCTION MANUAL
-
14 Power Conditioning Catalogue
Product Information
R&D Technology Pty Ltd Specialised Engineering ProductsNewcastle P: +61 2 4014 9000 F: + 61 2 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected]
website: www.rdtechnology.com.au
Simply contact R&D Technology to obtain the product that suits you...!!Note: all information is subject to change & images are for illustration purposes only.
Below will show you just some of what we candesign and build to your specifi cations and needs....
Transformers
Transformers Brochure - Rev A
Auto transformers - 7.5kw - 1000kw
Three phase transformers from 100va - 500kva...
We can handle almost anythingbig or small, all to Australian standards.
We make single phase 100va - 100kva transformers
AUSTRALIANMADE &OWNED
Custom
Designs
Availabl
e
Transformers
an R&D TechnologyGroup Company
PowerhouseSystems
-
15www.powerhousesystems.com.au
Product Information
We supply one of the widest selection of dc/dc converters and powersupply products including ac/dc power supplies, dc/dc converters, battery chargers, laboratory/lab power supplies, medical power supplies, dc/ac power inverters, etc., and offer facilities to customise power supply solutions to customers’ specifi cations.
Power Supplies
Power Supplies Brochure - Rev APower Supplies
an R&D TechnologyGroup Company
PowerhouseSystems
-
16 Power Conditioning Catalogue
CompuGuard
features• Designed specifically to protect todays modern computer
• Unique inverter design allows it to support the most severe Active Power
Factor Corrected power supply units
• Compact size
• Sleak tower design can stand vertically next to your computer
• Low profile design lies flat and you can even put your monitor on top
• Flush wall design for mounting to wall or under desk
• Excellent microprocessor control guarantees high reliability
• Auto restart while AC is recovering
• Cold start function
• Full protection: Discharge, overcharge, short circuit,
and thermal protection
The sophisticated CompuGuard UPS is PowerShield’s
latest development and has been designed by our
engineers specifically to protect today’s modern
computer. This low cost, slimline UPS has three Australian
sockets, two for battery backup and one for surge
protection. This UPS has the smallest footprint in the
PowerShield range but still packs a lot of power due
to an increased 9 amp hour battery in every unit. It is
designed to support computer power supplies that have
either Passive or Active Power Factor Corrected power
supplies. Furthermore it has been designed to protect
these Power Factor Corrected power supply units at full
load rating and at all phase angles.
applications include:•smallofficeandhomeofficeequipment
•standalonepersonalcomputers
•workstations
•smallperipherals
COMPUGUARD
MODEL PSCG650
CAPACITY 650VA / 390W
INPUT
Voltage 240Vac (Nominal)
Acceptable Voltage Range 180 - 270 VAC
Voltage Range
Low Line Transfer 180 ± 5 %
Low Line Comeback 190 ± 5%
High Line Transfer 270 ± 5%
High Line Comeback 260 ± 5%
Frequency 50Hz or 60Hz (Auto sensing)
OUTPUT
Output Voltage (Batt. Mode) 240 VAC ± 10%
Frequency Range (Batt. Mode) 50Hz or 60Hz ± 1Hz
Transfer Time (Typical) 2~6 ms
Waveform (Batt. Mode) Simulated sine wave
Australian Outlets - UPS Protection 2
Australian Outlets - Surge Protection 1
BATTERY
Battery 12 V* 9AH
Backup Time (one-PC load @100W) 25 min.
Typical Recharge Time 8 hours recover to 90% capacity
PROTECTION
Full Protection Overcharge, discharge, short circuit, and thermal protection
Safety EN62040-1-1 2003, IEC60950-1:2001
EMC EN62040-2 2006
COMMUNICATIONS & MANAGEMENT
USB Interface PowerShield NetGuard Supports Windows®, Linux, Unix, and MAC
INDICATIONS
AC Mode Green LED illuminated
Battery Mode Green flashing LED every 10 seconds
Low Battery (Batt. Mode) Green flashing LED every second
Fault Red LED illuminated
ALARM
Battery Mode 2 beeps every 30 seconds
Low Battery (Batt. Mode) Sounding every second
Fault Continuously sounding
PHYSICAL
Dimension, D x W x H (@ vertically stand) (232 x 83 x 200)mm
Net Weight (kgs) 3.6
OPERATING ENVIRONMENT
Humidity 0-90 %
Temerature 0- 40°C (non-condensing)
* Product specifications are subject to change without further notice* Product not intended for servers.
CircuitBreaker
7A
SurgeProtection
UPS+
SurgeProtection
Compuguard Series
-
17www.powerhousesystems.com.au
CompuGuard
features• Designed specifically to protect todays modern computer
• Unique inverter design allows it to support the most severe Active Power
Factor Corrected power supply units
• Compact size
• Sleak tower design can stand vertically next to your computer
• Low profile design lies flat and you can even put your monitor on top
• Flush wall design for mounting to wall or under desk
• Excellent microprocessor control guarantees high reliability
• Auto restart while AC is recovering
• Cold start function
• Full protection: Discharge, overcharge, short circuit,
and thermal protection
The sophisticated CompuGuard UPS is PowerShield’s
latest development and has been designed by our
engineers specifically to protect today’s modern
computer. This low cost, slimline UPS has three Australian
sockets, two for battery backup and one for surge
protection. This UPS has the smallest footprint in the
PowerShield range but still packs a lot of power due
to an increased 9 amp hour battery in every unit. It is
designed to support computer power supplies that have
either Passive or Active Power Factor Corrected power
supplies. Furthermore it has been designed to protect
these Power Factor Corrected power supply units at full
load rating and at all phase angles.
applications include:•smallofficeandhomeofficeequipment
•standalonepersonalcomputers
•workstations
•smallperipherals
COMPUGUARD
MODEL PSCG650
CAPACITY 650VA / 390W
INPUT
Voltage 240Vac (Nominal)
Acceptable Voltage Range 180 - 270 VAC
Voltage Range
Low Line Transfer 180 ± 5 %
Low Line Comeback 190 ± 5%
High Line Transfer 270 ± 5%
High Line Comeback 260 ± 5%
Frequency 50Hz or 60Hz (Auto sensing)
OUTPUT
Output Voltage (Batt. Mode) 240 VAC ± 10%
Frequency Range (Batt. Mode) 50Hz or 60Hz ± 1Hz
Transfer Time (Typical) 2~6 ms
Waveform (Batt. Mode) Simulated sine wave
Australian Outlets - UPS Protection 2
Australian Outlets - Surge Protection 1
BATTERY
Battery 12 V* 9AH
Backup Time (one-PC load @100W) 25 min.
Typical Recharge Time 8 hours recover to 90% capacity
PROTECTION
Full Protection Overcharge, discharge, short circuit, and thermal protection
Safety EN62040-1-1 2003, IEC60950-1:2001
EMC EN62040-2 2006
COMMUNICATIONS & MANAGEMENT
USB Interface PowerShield NetGuard Supports Windows®, Linux, Unix, and MAC
INDICATIONS
AC Mode Green LED illuminated
Battery Mode Green flashing LED every 10 seconds
Low Battery (Batt. Mode) Green flashing LED every second
Fault Red LED illuminated
ALARM
Battery Mode 2 beeps every 30 seconds
Low Battery (Batt. Mode) Sounding every second
Fault Continuously sounding
PHYSICAL
Dimension, D x W x H (@ vertically stand) (232 x 83 x 200)mm
Net Weight (kgs) 3.6
OPERATING ENVIRONMENT
Humidity 0-90 %
Temerature 0- 40°C (non-condensing)
* Product specifications are subject to change without further notice* Product not intended for servers.
CircuitBreaker
7A
SurgeProtection
UPS+
SurgeProtection
R&D Technology Pty Ltd Specialised Engineering ProductsNewcastle P: +61 2 4014 9000 F: + 612 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected]
website: www.rdtechnology.com.au
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346
Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected] website: www.rdtechnology.com.au
E: [email protected]: www.powerhousesystems.com.au
an R&D TechnologyGroup Company
PowerhouseSystems
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
-
18 Power Conditioning Catalogue
Small telephone with 4 handsets 60 minutes
Medium telephone with 16 hand sets 23 minutes
DVR and 4 cameras 62 minutes
DVR and 16 cameras 37 minutes
Computer with 17” LCD monitor 17 minutes
Computer with 24” LCD monitor 12 minutes
Typical run Times
SIX S CKETS
SPECIFICATIONS PSG750
Model PSG750
Topology Line interactive
INPUT
Voltage 240Vac
Voltage range 177Vac to 290Vac
Frequency 50Hz
OUTPUT
Nominal voltage 240Vac
Voltage regulation +/-10%
Battery transfer time 6 msec ( typical )
VA/Wattage 750VA/450W
BATTERY
Type Sealed lead acid maintenance free battery
Capacity 12V/9Ah
Full load backup time 2.5 min
Data protection Tel/modem/Lan, RJ45 connector
Software PowerShield NetGuard for Windows, Linux & Mac
Interface USB interface
Audible noise
-
19www.powerhousesystems.com.au
Small telephone with 4 handsets 60 minutes
Medium telephone with 16 hand sets 23 minutes
DVR and 4 cameras 62 minutes
DVR and 16 cameras 37 minutes
Computer with 17” LCD monitor 17 minutes
Computer with 24” LCD monitor 12 minutes
Typical run Times
SIX S CKETS
SPECIFICATIONS PSG750
Model PSG750
Topology Line interactive
INPUT
Voltage 240Vac
Voltage range 177Vac to 290Vac
Frequency 50Hz
OUTPUT
Nominal voltage 240Vac
Voltage regulation +/-10%
Battery transfer time 6 msec ( typical )
VA/Wattage 750VA/450W
BATTERY
Type Sealed lead acid maintenance free battery
Capacity 12V/9Ah
Full load backup time 2.5 min
Data protection Tel/modem/Lan, RJ45 connector
Software PowerShield NetGuard for Windows, Linux & Mac
Interface USB interface
Audible noise
-
20 Power Conditioning Catalogue
DEFENDER LINE INTERACTIVE UPSMODEL PSD1200 PSD1600
CAPACITY 1200 VA / 720 W 1600 VA / 960 W
INPUT
Voltage (Nominal) 240 VAC (Australia)
Voltage Range 177-290 VAC
Frequency Range 50/60 Hz +/-5Hz (auto sensing)
OUTPUT
Output Voltage 240Vac Australia
Output Voltage Regulation 240Vac±10%
Frequency AC mode tracks utility. Battery Mode 50Hz+/-1%
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ±1 Hz
Transfer Time Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode) Simulated Sine Wave
Australian Outlets - UPS Protection 3 3
Australian Outlets - Surge Protection 3 3
BATTERY
Battery Type & Number 12V*7AH (x2) 12V*9AH (x2)
Backup Time (One PC load @ 120 W) 40 min. 45 min.
Typical Recharge Time 4-6 hours recover to 90% capacity
PROTECTION
Full Protection Overload, discharge, and overcharge protection
Safety EN62040-1-1 2003, IEC60950-1:2001
EMC EN62040-2 2006
COMMUNICATIONS & MANAGEMENT
USB interace PowerShield NetGuard Supports Windows®, Linux, Unix, and MAC
Smart LCD
AUDIBLE ALARM
Battery Mode 2 beeps every 30 secs
Low Battery Rapid Beep (one sec intervals)
Overload Constant Beeping
Battery Replacement Alarm Constant Beeping
Fault Constant Beeping
OPERATING ENVIRONMENT
Humidity 0-90 % RH @ 0-40°C (non-condensing)
Noise Level Less than 40dB
PHYSICAL
Dimension, D X W X H (mm) 397 x 146 x 205
Net Weight (kgs) 11.1 11.5
* Product specifications are subject to change without further notice
1. Input voltage2. Output voltage3. AC mode indicator4. Battery mode indicator5. Load level indicator, flashing indicates overload6. Battery capacity indicator, flashing indicates low battery level
1 23
456
Defender Range
features• Excellentmicroprocessorcontrolguaranteeshighreliability
• AustralianoutletsforUPSProtection(x3)
• AustralianoutletsforSurgeprotection(x3)
• BoostandbuckAVRforvoltagestabilization
• Userreplaceablebatteries
• SilentOperation(Nofansincluded)
• AutorestartswhileACisrecovering
• Off-modecharging
• Coldstartfunction
• USBcommunicationwithsophisticatedNetGuardsoftware
TheDefenderrangeusesAutomaticVoltageRegulation
(AVR) tominimisefluctuations in inputvoltage.TheUPS
takes this inconsistent voltage then provides clean,
consistent output for the equipment it protects. AVR
keeps your business running through even the most
frequent brownouts and power sags.
applications include:•homeofficeequipment
•workstations
•rackequipment
•pointofsaleequipment
Defender Series
-
21www.powerhousesystems.com.au
DEFENDER LINE INTERACTIVE UPSMODEL PSD1200 PSD1600
CAPACITY 1200 VA / 720 W 1600 VA / 960 W
INPUT
Voltage (Nominal) 240 VAC (Australia)
Voltage Range 177-290 VAC
Frequency Range 50/60 Hz +/-5Hz (auto sensing)
OUTPUT
Output Voltage 240Vac Australia
Output Voltage Regulation 240Vac±10%
Frequency AC mode tracks utility. Battery Mode 50Hz+/-1%
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ±1 Hz
Transfer Time Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode) Simulated Sine Wave
Australian Outlets - UPS Protection 3 3
Australian Outlets - Surge Protection 3 3
BATTERY
Battery Type & Number 12V*7AH (x2) 12V*9AH (x2)
Backup Time (One PC load @ 120 W) 40 min. 45 min.
Typical Recharge Time 4-6 hours recover to 90% capacity
PROTECTION
Full Protection Overload, discharge, and overcharge protection
Safety EN62040-1-1 2003, IEC60950-1:2001
EMC EN62040-2 2006
COMMUNICATIONS & MANAGEMENT
USB interace PowerShield NetGuard Supports Windows®, Linux, Unix, and MAC
Smart LCD
AUDIBLE ALARM
Battery Mode 2 beeps every 30 secs
Low Battery Rapid Beep (one sec intervals)
Overload Constant Beeping
Battery Replacement Alarm Constant Beeping
Fault Constant Beeping
OPERATING ENVIRONMENT
Humidity 0-90 % RH @ 0-40°C (non-condensing)
Noise Level Less than 40dB
PHYSICAL
Dimension, D X W X H (mm) 397 x 146 x 205
Net Weight (kgs) 11.1 11.5
* Product specifications are subject to change without further notice
1. Input voltage2. Output voltage3. AC mode indicator4. Battery mode indicator5. Load level indicator, flashing indicates overload6. Battery capacity indicator, flashing indicates low battery level
1 23
456
Defender Range
features• Excellentmicroprocessorcontrolguaranteeshighreliability
• AustralianoutletsforUPSProtection(x3)
• AustralianoutletsforSurgeprotection(x3)
• BoostandbuckAVRforvoltagestabilization
• Userreplaceablebatteries
• SilentOperation(Nofansincluded)
• AutorestartswhileACisrecovering
• Off-modecharging
• Coldstartfunction
• USBcommunicationwithsophisticatedNetGuardsoftware
TheDefenderrangeusesAutomaticVoltageRegulation
(AVR) tominimisefluctuations in inputvoltage.TheUPS
takes this inconsistent voltage then provides clean,
consistent output for the equipment it protects. AVR
keeps your business running through even the most
frequent brownouts and power sags.
applications include:•homeofficeequipment
•workstations
•rackequipment
•pointofsaleequipment
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346
Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected] website: www.rdtechnology.com.au
E: [email protected]: www.powerhousesystems.com.au
an R&D TechnologyGroup Company
PowerhouseSystems
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
-
22 Power Conditioning Catalogue
Commander RT
features• Pure sine wave output
• Rack/Tower design
• Microprocessor-based line interactive design
• Built-in boost and buck AVR
• Output power factor 0.8
• Programmable power management outlets
• ECO mode operation for energy saving (ECO)
• Emergency Power Off Function (EPO)
• Hot-swappable battery design
• Long-run models available
• Multiple communication available • User-friendly and easy-s
LCD display
With pure sine wave output, the Commander
Rackmount Tower guarantees compatibility for all kinds
of loads. It’s perfect power protection for versatile
applications such as networking, telecom and other
mission-critical applications.
The ECO mode function allows cost-effective
operation of UPS Systems as high as 98%. In this
operation mode, load is supplied by the mains.
In the event of a mains failure, the inverter takes
over the load and provides supply continuity to the
connected systems.
To provide longer backup time the 2kVA and 3kVA
models are expandable to include an additional
battery bank.
Multiple communication available
- USB port
- RS-232 port
- SNMP slot (option)
- AS400 card (option)
- PowerShield NetGuard® software included
Commander Rack Tower
-
23www.powerhousesystems.com.au
Commander rT BaTTerY BanKS
modeL PSCrT800 PSCrT1100 PSCrT2000 PSCrT3000 PSCrTBB8 PSCrTBB12
CAPACITY 800VA/640 W 1100VA/880W 2000VA/1600W 3000VA/2400W Suits PSCRT2000 only Suits PSCRT3000 only
InPUT
Input voltage range 162-290 VAC
frequency range 50/60 Hz (auto sensing) +/-5Hz
oUTPUT
Voltage Regulation (AC Mode) 240Vac (Selectable208/220/230Vac) +/-10% AVR
Voltage Regulation (Batt. Mode) ±3% (before battery alarm)
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 5% max @ 100% linear load, 10% max @ 100% non-linear load (before alarm)
Transfer Time Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode) Pure Sine Wave
eFFICIenCY
ECO Mode 97% 97% 97%
Buck & Boost Mode 90% 90% 90%
Battery Mode 83% 89% 87%
eFFICIenCY
Standard Model
Battery Type & Number 12 V*9Ah x 2 12 V*9Ah x 2 12 V*9Ah x 4 12 V*9Ah x6 12 V*9Ah x 8 12 V*9Ah x 12
Typical Recharge Time 4 hours recover to 90% capacity
Additional Battery Banks N/A N/A PSCRTBB8 (x1) PSCRTBB12 (x1)
IndICaTorS
LCD Display AC Mode, Battery Mode, Load Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery, Battery time remaining
ProTeCTIon
Full Protection Overload, discharge, and overcharge protection
aLarm
Battery Mode Sounding 2 beeps every 30 seconds
Low Battery Sounding 1 beep every second
Overload Sounding 2 beeps every 2 seconds
Fault Continuously sounding
PHYSICaL
Standard Model
Dimension DxWxH (mm) 380 x 438 x 88 600 x 438 x 88 380 x 438 x 88 600 x 438 x 88
Net/Gross weight (kg) 15/16 15/16 23/25 32/35 25/27 35/37
envIronmenT
Operating Humidity 0-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 45dB
manaGemenT
Smart RS232PowerShield NetGuard® software - supports Windows based operating systems, Linux, Unix
USB
Optional SNMP Power management from SNMP manager and web browser (Intelligent Slot)
Optional AS400 AS400 dry contact communication card (intelligent Slot)
PSCRT3000PSCRT800/1100/2000
w w w . p o w e r s h i e l d . c o m . a u
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
-
24 Power Conditioning Catalogue
Software/SNMP
Allows control and monitoring of multiple
UPSs via LAN and INTERNET
User-friendly power analysis graph: event
statistics, history data chart export
Real-time dynamic graphs of UPS data
(voltage, frequency, load level,
battery level)
Safely OS shutdown and protection from
data loss during power failure
Warningnotificationsviaaudiblealarm,
broadcast, mobile messenger, and e-mail
Scheduled UPS on/off, battery test, programmable
outlet control, and audible alarm control
Password security protection and remote
access management
Supports multiple languages
Bundled with the PowerShield CompuGuard, SafeGuard,
New Defender and Centurion Series is the NetGuard
UPS management software. Users can remotely monitor
and manage from one to multiple UPSs in a networked
environment, either LAN or over the INTERNET. It prevents
data loss from power outage by safely shutting down
systems avoiding hard shutdowns. Also this software has
the ability to store programming data and schedule
shutdown UPSs.
This new version allows remote control and monitoring for
multiple UPSs via networked environment. Besides, it also
provides event statistic and power flow information in
diagram for corporate MIS to analyse the power status. To
avoid outside hackers, it also provides password security
protection for control and management.
PSCSNMP Simple Network Management Protocol card that allows for remote monitoring and shutdown of UPSs over the internet. This unit is especially designed for the
Commander tower and rackmount range.
PSCESNMP Simple Network Management Protocol card that allows for remote monitoring and shutdown of UPSs over the internet. This unit is especially designed for the
Centurion tower and rackmount range.
PSCSNMPee Simple Network Management Protocol card that allows for remote monitoring and shutdown of UPSs over the internet. This unit is especially designed to
take an environmental monitoring plugin that allows the user to monitor temperature,
humidity, opening and closing of server room doors and windows.
AS400For an easy connection to dry contacts featured in manufacturing applications and
building management systems, the AS400 card can be inserted into the backs of both
the Commander and Centurion Ranges.
The PowerShield Commander, Centurion, Centurion 3/1 and the
Platinum have in-built facilities for a Simple Network Management
Protocol (SNMP) card. These cards offer remote access of the
UPS anywhere where there is internet access. No PC is required
to access the UPS as it has its own LAN connection with a unique
IP address.
NetAgent Mini is an ultra-compact, light and fast tool to remotely
monitor and manage any UPS system. It can perform multi-servers
shutdown with ClientMate (Freeware for Windows, Linux and
FreeBSDOS),auto-sendnotifications,displayreal-timeinput-output
status, battery status, current UPS temperature and much more.
NetAgent II is also a tool to remotely monitor and manage any
Commander, Centurion or Platinum system. In addition, to the
features of the NetAgent Mini, the NetAgent II has the option to
add NetFeeler Lite to detect temperature, humidity, smoke and
security sensors, making the NetAgent II a versatile management
tool. Like the Mini, the NetAgent II also supports multiple languages
and is setup for web-based auto language detection.
SNMPSoftwarefeatures
UPS Software
-
25www.powerhousesystems.com.au
Software/SNMP
Allows control and monitoring of multiple
UPSs via LAN and INTERNET
User-friendly power analysis graph: event
statistics, history data chart export
Real-time dynamic graphs of UPS data
(voltage, frequency, load level,
battery level)
Safely OS shutdown and protection from
data loss during power failure
Warningnotificationsviaaudiblealarm,
broadcast, mobile messenger, and e-mail
Scheduled UPS on/off, battery test, programmable
outlet control, and audible alarm control
Password security protection and remote
access management
Supports multiple languages
Bundled with the PowerShield CompuGuard, SafeGuard,
New Defender and Centurion Series is the NetGuard
UPS management software. Users can remotely monitor
and manage from one to multiple UPSs in a networked
environment, either LAN or over the INTERNET. It prevents
data loss from power outage by safely shutting down
systems avoiding hard shutdowns. Also this software has
the ability to store programming data and schedule
shutdown UPSs.
This new version allows remote control and monitoring for
multiple UPSs via networked environment. Besides, it also
provides event statistic and power flow information in
diagram for corporate MIS to analyse the power status. To
avoid outside hackers, it also provides password security
protection for control and management.
PSCSNMP Simple Network Management Protocol card that allows for remote monitoring and shutdown of UPSs over the internet. This unit is especially designed for the
Commander tower and rackmount range.
PSCESNMP Simple Network Management Protocol card that allows for remote monitoring and shutdown of UPSs over the internet. This unit is especially designed for the
Centurion tower and rackmount range.
PSCSNMPee Simple Network Management Protocol card that allows for remote monitoring and shutdown of UPSs over the internet. This unit is especially designed to
take an environmental monitoring plugin that allows the user to monitor temperature,
humidity, opening and closing of server room doors and windows.
AS400For an easy connection to dry contacts featured in manufacturing applications and
building management systems, the AS400 card can be inserted into the backs of both
the Commander and Centurion Ranges.
The PowerShield Commander, Centurion, Centurion 3/1 and the
Platinum have in-built facilities for a Simple Network Management
Protocol (SNMP) card. These cards offer remote access of the
UPS anywhere where there is internet access. No PC is required
to access the UPS as it has its own LAN connection with a unique
IP address.
NetAgent Mini is an ultra-compact, light and fast tool to remotely
monitor and manage any UPS system. It can perform multi-servers
shutdown with ClientMate (Freeware for Windows, Linux and
FreeBSDOS),auto-sendnotifications,displayreal-timeinput-output
status, battery status, current UPS temperature and much more.
NetAgent II is also a tool to remotely monitor and manage any
Commander, Centurion or Platinum system. In addition, to the
features of the NetAgent Mini, the NetAgent II has the option to
add NetFeeler Lite to detect temperature, humidity, smoke and
security sensors, making the NetAgent II a versatile management
tool. Like the Mini, the NetAgent II also supports multiple languages
and is setup for web-based auto language detection.
SNMPSoftwarefeatures
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346
Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected] website: www.rdtechnology.com.au
E: [email protected]: www.powerhousesystems.com.au
an R&D TechnologyGroup Company
PowerhouseSystems
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
-
26 Power Conditioning Catalogue
features• TrueOnlineDoubleConversion
• Wideinputvoltagerange(110-300VAC)
• Inputpowerfactorcorrection0.98
• 50Hz/60Hzfrequencyconvertermode
• Programmablepoweroutlets
• Emergencypowerofffunction(EPO)
• OptionalEco-modeoperationforenergysaving
• Generatorcompatible
• Backuptimeforallmodelsiseasilyextendedbysimplypluggingadditionalbatterybanks
• Batterybanksareavailablewithinternalchargertoenablefastrechargeevenwithlargebatterybanks
• Chargercapacityexpansionto9Aforlong-runmodels
• USB,RS232,SNMPandAS400multiplecommunicationsavailalble
• Externalmaintenancebypassavailableforallmodels
• N+Xparallelredundancyavailablefor6K/10Kmodels
• MonitoringandShutdownSoftwareincluded
Centurion Tower
The Centurion is designed to protect critical computer
and communications equipment as well as industrial and
automation applications where losses as a result of power
failure may accumulate at frightening speed. A true online
double conversion UPS, the Centurian is designed to
guarantee trouble-free operation of protected equipment in
anyphysicalorsystemenvironment.Versatilemanagement
and hardware options offer the flexibility to build up a
power protection solution to fit any application. When
the mission is critical, get the best UPS in the PowerShield
range. This new range now comes with two sets of sockets
on the back. One row of output sockets are programmable
meaning that in times of limited backup time, the user can
program the sockets to turn off after a prescribed time. This
will leave valuable backup time to the equipment that is
most critical. The LCD display is amongst the easiest.
applications include:•criticalservers
•smallnetworks
•CriticalITapplications
•PLCs
•Telecomapplications
•securityequipment
•manufacturing
Centurion Tower
-
27www.powerhousesystems.com.au23
TOWER MODELS BATTERY BANKS
MODEL PSCEBB6 PSCEBB12 PSCEBB18CH PSCEBB40 PSCEBB60CH
SUITS UPS PSCE1000 PSCE2000/3000 PSCE2000/3000 PSCE6000/10K PSCE6000/10K
BATTERY
Type 12V*9AH 12V*9AH 12V*9AH 12V*9AH 12V*9AH
Number 6 12 18 40 60
Nominal DC 36Vdc 72Vdc 72Vdc 240Vdc 240Vdc
Charger From UPS From UPS Internal 3Amp From UPS Internal 3.5Amp
PHYSICAL
Dimensions (D x W x H)cm 397 x145 x 220 421 x 190 x 318 534 x 190 x 318 592 x 285 x 576 830 x 250 x 576
Weight N et/Gross KG 21/22Kg 42/44Kg 62/64Kg 125/132Kg 190/205Kg
PROTECTION DC Circuit breaker
VIRTUALLY UNLIMITED RUN TIMES CAN BE ACHIEVED BY ADDING BATTERY BANKS TO STANDARD MODELS
Notes: Unlimited Numbers of batteries banks can be added however it is recommended to add a Battery Bank that has an internal charger (PSCEBB18CH
or PSCEBB60CH) if large battery banks are added and fast charging is required. Usually these should be added as the second, third or fourth battery
bank depending on your requirements. When these battery banks with chargers are added, it is possible to substantially increase the number of regular
battery banks. The following battery banks have built-in chargers. These also have more batteries than regular battery banks. PSCEBB18CH - Suits 2k & 3K
• PSCEBB60CH - Suits 6k & 10K
VA LOAD MODEL
PSCE1000 PSCEBB6 PSCEBB6 PSCEBB6
1000VA 100% 12 minutes 45 minutes 80 minutes 115 minutes500VA 50% 25 minutes 105 minutes 170 minutes 250 minutes
PSCE2000 PSCEBB12 PSCEBB18CH PSCEBB12
2000VA 100% 12 minutes 50 minutes 115 minutes 145 minutes1000VA 50% 25 minutes 110 minutes 215 minutes 320 minutes
PSCE3000 PSCEBB12 PSCEBB18CH PSCEBB12
3000VA 100% 5 minutes 27 minutes 60 minutes 100 minutes1500VA 50% 16 minutes 60 minutes 145 minutes 185 minutes
PSCE6000 PSCEBB40 PSCEBB60CH PSCEBB40
6000VA 100% 13 minutes 50 minutes 110 minutes 170 minutes3000VA 50% 35 minutes 110 minutes 260 minutes 320 minutes
PSCE10K PSCEBB40 PSCEBB60CH PSCEBB40
10KVA 100% 5 minutes 27 minutes 60 minutes 100 minutes5000VA 50% 16 minutes 60 minutes 145 minutes 205 minutes
MODEL PSCE1000 (L) PSCE2000 (L) PSCE3000 (L) PSCE6000 (L) PSCE10K (L)
CAPACITY 1000VA / 800W 2000VA / 1600W 3000 VA / 2400W 6000VA / 4800W 10000VA / 8000 W
INPUT
Voltage Range
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
176 VAC @ 100% load110 VAC @ 50% load
Low Line Comeback 175 VAC ± 5 % 186 VAC @ 100% load120 VAC @ 50% load
High Line Transfer 300 VAC ± 5 % 300 VAC
High Line Comeback 47.5Hz ~ 52.5 Hz or 57Hz ~ 63Hz 290 VAC
Frequency Range 47.5Hz ~ 52.5 Hz or 57Hz ~ 63Hz 46~54 Hz ◎ 50Hz / 56~64Hz ◎ 60Hz
Phase Single phase with ground
Power Factor ◎ 0.98 ◎ 0.99 @ 100%load
OUTPUT
AC Voltage Regulation (Batt. Mode) ± 3% ± 1%
Frequency Range (Synchronized Range) 48 ~ 52 Hz or 57 ~ 63 Hz 46~54 Hz ◎ 50 Hz / 56~64 Hz ◎ 60 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 3 % THD (Linear Load) 6 % THD (Non-linear Load)
◎ 4 % THD (Linear Load) ◎ 7 % THD (Non-linear Load)
◎ 2 % THD (Linear Load) ◎ 6 % THD (Linear Load)
Transfer Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical) zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode 85% 88% 90%
Battery Mode 83% 88%
BATTERY
Standard Model
Battery Type 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH
Numbers 3 6 6 20 20
Typical Recharge Time 4 hours recover to 90% capacity 7 hours recover to 90% capacity
7 hours recover to 90% capacity
Charging Current (max.) 1.0 A 1.0 A
Charging Voltage 41.0 VDC ± 1% 82.1 VDC ±1% 273.0 VDC
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
LED Panel UPS status, Load level, Battery level, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
PHYSICAL
Dimension, D X W X H (mm) 338.5 X 145 X 220 387 X 190 X 318 526 X 250 X 576.5
Net Weight (kgs) 14 7 29.5 16 29.5 16 90 35 93 38
ENVIRONMENT
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 45dBA @ 1 Meter Less than 55dB @ 1 Meter
MANAGEMENT
Smart RS232PowerShield NetGuard Software - Supports Windows Based Operating Systems, Linux & Unix
USB
Optional SNMP Power management from SNMP manager and web browser (Intelligent Slot)
AS400 AS400 dry contact communication card (Intelligent Slot)
* L means long-run model
* Product specifications are subject to change without further notice
PSC
E100
0
PSC
E200
0
PSC
E300
0
PSC
E600
0
PSC
E100
00
-
28 Power Conditioning Catalogue
23
TOWER MODELS BATTERY BANKS
MODEL PSCEBB6 PSCEBB12 PSCEBB18CH PSCEBB40 PSCEBB60CH
SUITS UPS PSCE1000 PSCE2000/3000 PSCE2000/3000 PSCE6000/10K PSCE6000/10K
BATTERY
Type 12V*9AH 12V*9AH 12V*9AH 12V*9AH 12V*9AH
Number 6 12 18 40 60
Nominal DC 36Vdc 72Vdc 72Vdc 240Vdc 240Vdc
Charger From UPS From UPS Internal 3Amp From UPS Internal 3.5Amp
PHYSICAL
Dimensions (D x W x H)cm 397 x145 x 220 421 x 190 x 318 534 x 190 x 318 592 x 285 x 576 830 x 250 x 576
Weight N et/Gross KG 21/22Kg 42/44Kg 62/64Kg 125/132Kg 190/205Kg
PROTECTION DC Circuit breaker
VIRTUALLY UNLIMITED RUN TIMES CAN BE ACHIEVED BY ADDING BATTERY BANKS TO STANDARD MODELS
Notes: Unlimited Numbers of batteries banks can be added however it is recommended to add a Battery Bank that has an internal charger (PSCEBB18CH
or PSCEBB60CH) if large battery banks are added and fast charging is required. Usually these should be added as the second, third or fourth battery
bank depending on your requirements. When these battery banks with chargers are added, it is possible to substantially increase the number of regular
battery banks. The following battery banks have built-in chargers. These also have more batteries than regular battery banks. PSCEBB18CH - Suits 2k & 3K
• PSCEBB60CH - Suits 6k & 10K
VA LOAD MODEL
PSCE1000 PSCEBB6 PSCEBB6 PSCEBB6
1000VA 100% 12 minutes 45 minutes 80 minutes 115 minutes500VA 50% 25 minutes 105 minutes 170 minutes 250 minutes
PSCE2000 PSCEBB12 PSCEBB18CH PSCEBB12
2000VA 100% 12 minutes 50 minutes 115 minutes 145 minutes1000VA 50% 25 minutes 110 minutes 215 minutes 320 minutes
PSCE3000 PSCEBB12 PSCEBB18CH PSCEBB12
3000VA 100% 5 minutes 27 minutes 60 minutes 100 minutes1500VA 50% 16 minutes 60 minutes 145 minutes 185 minutes
PSCE6000 PSCEBB40 PSCEBB60CH PSCEBB40
6000VA 100% 13 minutes 50 minutes 110 minutes 170 minutes3000VA 50% 35 minutes 110 minutes 260 minutes 320 minutes
PSCE10K PSCEBB40 PSCEBB60CH PSCEBB40
10KVA 100% 5 minutes 27 minutes 60 minutes 100 minutes5000VA 50% 16 minutes 60 minutes 145 minutes 205 minutes
MODEL PSCE1000 (L) PSCE2000 (L) PSCE3000 (L) PSCE6000 (L) PSCE10K (L)
CAPACITY 1000VA / 800W 2000VA / 1600W 3000 VA / 2400W 6000VA / 4800W 10000VA / 8000 W
INPUT
Voltage Range
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
176 VAC @ 100% load110 VAC @ 50% load
Low Line Comeback 175 VAC ± 5 % 186 VAC @ 100% load120 VAC @ 50% load
High Line Transfer 300 VAC ± 5 % 300 VAC
High Line Comeback 47.5Hz ~ 52.5 Hz or 57Hz ~ 63Hz 290 VAC
Frequency Range 47.5Hz ~ 52.5 Hz or 57Hz ~ 63Hz 46~54 Hz ◎ 50Hz / 56~64Hz ◎ 60Hz
Phase Single phase with ground
Power Factor ◎ 0.98 ◎ 0.99 @ 100%load
OUTPUT
AC Voltage Regulation (Batt. Mode) ± 3% ± 1%
Frequency Range (Synchronized Range) 48 ~ 52 Hz or 57 ~ 63 Hz 46~54 Hz ◎ 50 Hz / 56~64 Hz ◎ 60 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 3 % THD (Linear Load) 6 % THD (Non-linear Load)
◎ 4 % THD (Linear Load) ◎ 7 % THD (Non-linear Load)
◎ 2 % THD (Linear Load) ◎ 6 % THD (Linear Load)
Transfer Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical) zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode 85% 88% 90%
Battery Mode 83% 88%
BATTERY
Standard Model
Battery Type 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH 12 V / 9 AH
Numbers 3 6 6 20 20
Typical Recharge Time 4 hours recover to 90% capacity 7 hours recover to 90% capacity
7 hours recover to 90% capacity
Charging Current (max.) 1.0 A 1.0 A
Charging Voltage 41.0 VDC ± 1% 82.1 VDC ±1% 273.0 VDC
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
LED Panel UPS status, Load level, Battery level, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
PHYSICAL
Dimension, D X W X H (mm) 338.5 X 145 X 220 387 X 190 X 318 526 X 250 X 576.5
Net Weight (kgs) 14 7 29.5 16 29.5 16 90 35 93 38
ENVIRONMENT
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 45dBA @ 1 Meter Less than 55dB @ 1 Meter
MANAGEMENT
Smart RS232PowerShield NetGuard Software - Supports Windows Based Operating Systems, Linux & Unix
USB
Optional SNMP Power management from SNMP manager and web browser (Intelligent Slot)
AS400 AS400 dry contact communication card (Intelligent Slot)
* L means long-run model
* Product specifications are subject to change without further notice
PSC
E100
0
PSC
E200
0
PSC
E300
0
PSC
E600
0
PSC
E100
00
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346
Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected] website: www.rdtechnology.com.au
E: [email protected]: www.powerhousesystems.com.au
an R&D TechnologyGroup Company
PowerhouseSystems
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
-
29www.powerhousesystems.com.au
features• Truedouble-conversion
• Wideinputvoltagerange(110-300VAC)
• Inputpowerfactorcorrection0.98
• 50Hz/60Hzfrequencyconvertermode
• Programmablepoweroutlets
• Emergencypowerofffunction(EPO)
• Eco-modeoperationforenergysaving(ECO)
• Generatorcompatible
• Backuptimeforallmodelsiseasilyextendedbysimplypluggingadditionalbatterybanks
• Chargercapacityexpansionto8Aforlong-runmodels
• USB+RS232+SNMP+AS400multiplecommunications
• Maintenancebypassavailableforallmodels
• N+Xparallelredundancyavailablefor6K/10Kmodels
Centurion Rackmount
The Centurion resolves utility power problems and delivers
superior power to equipment requiring critical power.
As a True Online Double-conversion UPS, the UPS takes
the AC signal, converts it to DC and then back to AC,
thus eliminating any noise or electrical interference and
delivering perfect 240 voltage and 50 Amps frequency to
all equipment. It is this seamless transfer to batteries that will
continue to feed equipment even after the front half of the
UPS has failed or if there is a mains fail.
The Centurion Rack comes complete with NetGuard
software to enable the UPS to softly shutdown the system
after a prescribed amount of time designated by the user.
The Centurion Rackmount, like its Tower counterpart, also
has programmable sockets on the back so that the user
may get more backup on more critical equipment. SNMP
and AS400 card slots are present on the back of the unit for
remote management and dry contact communications.
applications include:•manufacturing
•serversandnetworkinggear
•telecommunications,VoIPandsecuritysystems
•medicalsystems
•Miningapplications
Centurion Rackmount
-
30 Power Conditioning Catalogue
MODEL PSCERBB6 PSCERBB12 PSCERBB20
SUITS UPS PSCER1000 PSCER2000/3000 PSCER6000L/10KL
BATTERY
Type 12V*9AH 12V*9AH 12V*9AHNumber 6 12 20Nominal DC 36Vdc 72Vdc 240Charger From UPS From UPS From UPS
PHYSICAL
Dimensions (D x W x H)cm 420 X 438 X 88 (2U) 580 X 438 X 133 (3U) 580 X 438 X 133 (3U)Weight Nett/Gross KG 21Kg 37Kg 57Kg
PROTECTION DC Circuit breaker
LOAD VA
PSCER1000 Internal Batteries 1x PSCERBB6 2 x PSCERBB6 3 x PSCERBB6
1000VA 12 45 80 115500VA 25 105 170 250
PSCER2000 1x PSCERBB12 2 x PSCERBB12 3 x PSCERBB12
2000VA 12 50 90 1151000VA 25 110 170 250
PSCER3000 1x PSCERBB12 2 x PSCERBB12 3 x PSCERBB12
3000VA 5 27 50 801500VA 16 60 110 170
PSCE6000 1x PSCERBB20 2x PSCERBB20 3x PSCERBB20
6000VA 12 30 553000VA 30 85 120
PSCE10K 1x PSCERBB20 2x PSCERBB20 3x PSCERBB20
10KVA 5 16 285000VA 16 38 60
MODEL PSCER1000 (L) PSCER2000 (L) PSCER3000 (L) PSCER6000L PSCER10KL
CAPACITY 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Voltage Range
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
176 VAC @ 100% load110 VAC @ 50% load
Low Line Comeback 175 VAC ± 5 % 186 VAC @ 100% load120 VAC @ 50% load
High Line Transfer 300 VAC ± 5 % 300 VAC
High Line Comeback 290 VAC ± 5 % 290 VAC
Frequency Range 47.5Hz ~ 52.5 Hz or 57Hz ~ 63 Hz 46-54 Hz or 56-64 Hz
Phase Single phase with ground
Power Factor ≧ >0.98 ≧ >0.99 @ >100% load
OUTPUT
Voltage (selectable) 240Vac (Selectable 208,220,230Vac)
AC Voltage Regulation (Batt. Mode) ± 3% ± 1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion
-
31www.powerhousesystems.com.au
MODEL PSCERBB6 PSCERBB12 PSCERBB20
SUITS UPS PSCER1000 PSCER2000/3000 PSCER6000L/10KL
BATTERY
Type 12V*9AH 12V*9AH 12V*9AHNumber 6 12 20Nominal DC 36Vdc 72Vdc 240Charger From UPS From UPS From UPS
PHYSICAL
Dimensions (D x W x H)cm 420 X 438 X 88 (2U) 580 X 438 X 133 (3U) 580 X 438 X 133 (3U)Weight Nett/Gross KG 21Kg 37Kg 57Kg
PROTECTION DC Circuit breaker
LOAD VA
PSCER1000 Internal Batteries 1x PSCERBB6 2 x PSCERBB6 3 x PSCERBB6
1000VA 12 45 80 115500VA 25 105 170 250
PSCER2000 1x PSCERBB12 2 x PSCERBB12 3 x PSCERBB12
2000VA 12 50 90 1151000VA 25 110 170 250
PSCER3000 1x PSCERBB12 2 x PSCERBB12 3 x PSCERBB12
3000VA 5 27 50 801500VA 16 60 110 170
PSCE6000 1x PSCERBB20 2x PSCERBB20 3x PSCERBB20
6000VA 12 30 553000VA 30 85 120
PSCE10K 1x PSCERBB20 2x PSCERBB20 3x PSCERBB20
10KVA 5 16 285000VA 16 38 60
MODEL PSCER1000 (L) PSCER2000 (L) PSCER3000 (L) PSCER6000L PSCER10KL
CAPACITY 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Voltage Range
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
176 VAC @ 100% load110 VAC @ 50% load
Low Line Comeback 175 VAC ± 5 % 186 VAC @ 100% load120 VAC @ 50% load
High Line Transfer 300 VAC ± 5 % 300 VAC
High Line Comeback 290 VAC ± 5 % 290 VAC
Frequency Range 47.5Hz ~ 52.5 Hz or 57Hz ~ 63 Hz 46-54 Hz or 56-64 Hz
Phase Single phase with ground
Power Factor ≧ >0.98 ≧ >0.99 @ >100% load
OUTPUT
Voltage (selectable) 240Vac (Selectable 208,220,230Vac)
AC Voltage Regulation (Batt. Mode) ± 3% ± 1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion
-
32 Power Conditioning Catalogue
Centurion 3/1
features• True double-conversion
• DSP technology guarantees high performance
• Wide input voltage range (110-300 VAC)
• Input power factor correction in all phases
• 50Hz/60Hz frequency converter mode
• Eco mode operation for energy saving (ECO)
• Programmable power outlets
• Emergency power off function (EPO)
• Generator compatible
• All models are Long Run
• USB+RS232 + SNMP + AS400 multiple communications
• Maintenance bypass available
• N+X parallel redundancy available
CENTURION 1G THREE PHASE/SINGLE PHASE SELECTION GUIDE
MODEL PSCE10KL3/1 PSCE15KL3/1 PSCE20KL3/1CAPACITY 10000 VA / 8000 W 15000 VA / 12000 W 20000 VA / 16000 WINPUTPhase Three Phase in/One Phase Out or One Phase in/One Phase out (User selectable)Voltage (Nominal) 240/415Vac (User Selectable)
Voltage Range
Low Line Transfer 176 VAC (phase voltage)@ 100% load110VAC (phase voltage) @ 50% load
Low Line Comeback 186 VAC (phase voltage) @ 100% load120VAC (phase voltage) @ 50% load
High Line Transfer 276 VAC (phase voltage) @ 100% load300VAC (phase voltage) @ 50% load
High Line Comeback 266 VAC (phase voltage) @ 100% load290VAC (phase voltage) @ 50% load
Frequency Range 46~54 Hz or 56~64Hz Power Factor ≧ 0.99 @ 100% loadTHDi < 6% @ 100% loadOUTPUTVoltage (ac mode) 240Vac (220, 230Vac User Selectable)AC Voltage Regulation (Batt. Mode) ± 1%Frequency Range (Synchronized Range) 46~54Hz or 56~64HzFrequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 HzCurrent Crest Ratio 3:1 (max.)
Harmonic Distortion ≧ 2 % THD (Linear Load) 5 % THD (Non-linear Load)
Transfer TimeAC Mode to Batt. Mode zeroInverter to Bypass zero
Waveform (Batt. Mode) Pure Sine WaveEFFICIENCYAC Mode 89%Battery Mode 86% 88% 87%BATTERY
Standard Model
Battery Type 12 V / 9 AHNumbers 20 40 40Typical Recharge Time 9 hours recover to 90% capacity 9 hours recover to 90% capacityCharging Current (max.) 1A 2A 2ACharging Voltage 273Vdc
Long-run Model
Battery TypeDepending on the capacity of external batteries
NumbersCharging Current (max.) 4A 8A 8ACharging Voltage 273Vdc
INDICATORSLCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditionsALARMBattery Mode Sounding every 4 secondsLow Battery Sounding every secondOverload Sounding twice every secondFault Continuously soundingPHYSICAL
Standard ModelDimension, D X W X H (mm) 592 X 250 X 576 815 x 250 x 826Net Weight (kgs) 83 164 164
Long-run ModelDimension, D X W X H (mm) 592 X 250 X 576 592 X 250 X 576 592 X 250 X 576Net Weight (kgs) 28 37 37
ENVIRONMENTOperation Humidity 0-95 % RH @ 0- 40°C (non-condensing)Noise Level Less than 58dB @ 1 MeterMANAGEMENTSmart RS232
PowerShield NetGuard software supports Windows, Linux, Unix, and MACUSBOptional SNMP Power management from SNMP manager and web browser
* L means long-run model * Product specifications are subject to change without further notice
In applications where only three phase power is available yet
single phase power is necessary the PowerShield Centurion
3/1 ticks all the boxes. Recommended in manufacturing
applications the Centurion 3/1 Series has all of the features of
the Centurion range with the added ability of accepting three
phase power to its input.
Like the Centurion range , the 3/1 range boasts the same User
friendly LCD display that allows the operator to interrogate
and program the UPS on the front panel as well as with the
included software. It also has a small footprint which will fit
any tight space requirement.
Models come standard with internal batteries. If a longer
back up time is required, the long run models with extra large
chargers are available. Back up from 5 minutes to 5 days with
the Centurion 3/1.
Centurion 3 to 1
-
33www.powerhousesystems.com.au
Centurion 3/1
features• True double-conversion
• DSP technology guarantees high performance
• Wide input voltage range (110-300 VAC)
• Input power factor correction in all phases
• 50Hz/60Hz frequency converter mode
• Eco mode operation for energy saving (ECO)
• Programmable power outlets
• Emergency power off function (EPO)
• Generator compatible
• All models are Long Run
• USB+RS232 + SNMP + AS400 multiple communications
• Maintenance bypass available
• N+X parallel redundancy available
CENTURION 1G THREE PHASE/SINGLE PHASE SELECTION GUIDE
MODEL PSCE10KL3/1 PSCE15KL3/1 PSCE20KL3/1CAPACITY 10000 VA / 8000 W 15000 VA / 12000 W 20000 VA / 16000 WINPUTPhase Three Phase in/One Phase Out or One Phase in/One Phase out (User selectable)Voltage (Nominal) 240/415Vac (User Selectable)
Voltage Range
Low Line Transfer 176 VAC (phase voltage)@ 100% load110VAC (phase voltage) @ 50% load
Low Line Comeback 186 VAC (phase voltage) @ 100% load120VAC (phase voltage) @ 50% load
High Line Transfer 276 VAC (phase voltage) @ 100% load300VAC (phase voltage) @ 50% load
High Line Comeback 266 VAC (phase voltage) @ 100% load290VAC (phase voltage) @ 50% load
Frequency Range 46~54 Hz or 56~64Hz Power Factor ≧ 0.99 @ 100% loadTHDi < 6% @ 100% loadOUTPUTVoltage (ac mode) 240Vac (220, 230Vac User Selectable)AC Voltage Regulation (Batt. Mode) ± 1%Frequency Range (Synchronized Range) 46~54Hz or 56~64HzFrequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 HzCurrent Crest Ratio 3:1 (max.)
Harmonic Distortion ≧ 2 % THD (Linear Load) 5 % THD (Non-linear Load)
Transfer TimeAC Mode to Batt. Mode zeroInverter to Bypass zero
Waveform (Batt. Mode) Pure Sine WaveEFFICIENCYAC Mode 89%Battery Mode 86% 88% 87%BATTERY
Standard Model
Battery Type 12 V / 9 AHNumbers 20 40 40Typical Recharge Time 9 hours recover to 90% capacity 9 hours recover to 90% capacityCharging Current (max.) 1A 2A 2ACharging Voltage 273Vdc
Long-run Model
Battery TypeDepending on the capacity of external batteries
NumbersCharging Current (max.) 4A 8A 8ACharging Voltage 273Vdc
INDICATORSLCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditionsALARMBattery Mode Sounding every 4 secondsLow Battery Sounding every secondOverload Sounding twice every secondFault Continuously soundingPHYSICAL
Standard ModelDimension, D X W X H (mm) 592 X 250 X 576 815 x 250 x 826Net Weight (kgs) 83 164 164
Long-run ModelDimension, D X W X H (mm) 592 X 250 X 576 592 X 250 X 576 592 X 250 X 576Net Weight (kgs) 28 37 37
ENVIRONMENTOperation Humidity 0-95 % RH @ 0- 40°C (non-condensing)Noise Level Less than 58dB @ 1 MeterMANAGEMENTSmart RS232
PowerShield NetGuard software supports Windows, Linux, Unix, and MACUSBOptional SNMP Power management from SNMP manager and web browser
* L means long-run model * Product specifications are subject to change without further notice
In applications where only three phase power is available yet
single phase power is necessary the PowerShield Centurion
3/1 ticks all the boxes. Recommended in manufacturing
applications the Centurion 3/1 Series has all of the features of
the Centurion range with the added ability of accepting three
phase power to its input.
Like the Centurion range , the 3/1 range boasts the same User
friendly LCD display that allows the operator to interrogate
and program the UPS on the front panel as well as with the
included software. It also has a small footprint which will fit
any tight space requirement.
Models come standard with internal batteries. If a longer
back up time is required, the long run models with extra large
chargers are available. Back up from 5 minutes to 5 days with
the Centurion 3/1.
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346
Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099E: [email protected] website: www.rdtechnology.com.au
E: [email protected]: www.powerhousesystems.com.au
an R&D TechnologyGroup Company
PowerhouseSystems
R&D Technology Pty Ltd Specialised Engineering Products
Powerhouse Systems Pty Ltd
Newcastle P: +61 2 4014 9000 F: + 61 2 4014 9099Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099Regional QLD P: +61 7 4952 3833 F: + 61 2 4014 9099
E: [email protected] website: www.rdtechnology.com.au
Brisbane P: +61 7 3846 2644 F: + 61 7 3846 2346 E: [email protected]: www.powerhousesystems.com.auan R&D Technology
Group Company
PowerhouseSystems
-
34 Power Conditioning Catalogue
Platinum
features• CentralisedcontrolcoordinatesthePFCrectifierandinverterbyDSP
• Switchingfrequency:15kHZ–lessnoise(higherfrequency)
• LowinputcurrentdistortionTHDi
• ExcellentoutputsupportsbothleadingandlaggingPowerfactorof0.1
• Unitypowerfactor(0.99)atlowoutputload(10%)
• IGBTtechnologyintheInverterandRectifier
• EasytouseLCDdisplayforalarmcontrol
Platinum
The New PowerShield Platinum Three Phase UPS
technology has been tried and tested throughout the
world. Designed by a leading Italian UPS manufacturer,
the Platinum model takes its place as the standard in
three phase applications. PowerShield has sourced this
UPS for our exclusive use in Australia.
Its specifications speak for themselves with perfect
uninterruptible power for sensitive data centres, medical
applications and manufacturing environments. The
space saving footprint design with a User Friendly LCD
screen makes the Platinum UPS the obvious three phase
choice.
The team at PowerShield can design a three phase
solution to suit all three phase solutions according to
loads and scalable runtimes for each application.
When a centralised uninterruptible power supply in
necessary, the PowerShield Platinum is the always the
best solution.
Model PSP10K PSP15K PSP20K PSP30K PSP40K PSP60K PSP80K
Nominal rating (kVA) 10kVA 15kVA 20kVA 30kVA 40kVA 60kVA 80kVA
Nominal rating (kW) 8KW 12KW 16KW 24KW 32KW 48KW 64KW
Input
Nominal voltage 240/415Vac (3Ph + N)
Input voltage Range +15%or–20%
Frequency 50/60 Hz ± 5 %
Total Harmonic Distortion (THDi) < 1.5% @ 100% load< 2.5% @ 50% load< 6.0% @ 10% load
< 1.0% @ 100% load< 2.0% @ 50% load< 5.0% @ 10% load
Power Factor 1.0
Inverter
Nominal Voltage 240/415Vac (3Ph + N)
Precision Stationary: ±1% Transitory: ±2% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±4 %With mains absent ±0.05%
Max. Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv)
-
35www.powerhousesystems.com.au
Platinum
features• CentralisedcontrolcoordinatesthePFCrectifierandinverterbyDSP
• Switchingfrequency:15kHZ–lessnoise(higherfrequency)
• LowinputcurrentdistortionTHDi
• ExcellentoutputsupportsbothleadingandlaggingPowerfactorof0.1
• Unitypowerfactor(0.99)atlowoutputload(10%)
• IGBTtechnologyintheInverterandRectifier
• EasytouseLCDdisplayforalarmcontrol
Platinum
The New PowerShield Platinum Three Phase UPS
technology has been tried and tested throughout the
world. Designed by a leading Italian UPS manufacturer,
the Platinum model takes its place as the standard in
three phase applications. PowerShield has sourced this
UPS for our exclusive use in Australia.
Its specifications speak for themselves with perfect
uninterruptible power for sensitive data centres, medical
applications and manufacturing environments. The
space saving footprint design with a User Friendly LCD
screen makes the Platinum UPS the obvious three phase
choice.
The team at PowerShield can design a three phase
solution to suit all three phase solutions according to
loads and scalable runtimes for each application.
When a centralised uninterruptible power supply in
necessary, the PowerShield Platinum is the always the
best solution.
Model PSP10K PSP15K PSP20K PSP30K PSP40K PSP60K PSP80K
Nominal rating (kVA) 10kVA 15kVA 20kVA 30kVA 40kVA 60kVA 80kVA
Nominal rating (kW) 8KW 12KW 16KW 24KW 32KW 48KW 64KW
Input
Nominal voltage 240/415Vac (3Ph + N)
Input voltage Range +15%or–20%
Frequency 50/60 Hz ± 5 %
Total Harmonic Distortion (THDi) < 1.5% @ 100% load< 2.5% @ 50% load< 6.0% @ 10% load
< 1.0% @ 100% load< 2.0% @ 50% load< 5.0% @ 10% load
Power Factor 1.0
Inverter
Nominal Voltage 240/415Vac (3Ph + N)
Precision Stationary: ±1% Transitory: ±2% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±4 %With mains absent ±0.05%
Max. Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave
Total Harmonic Distortion (THDv)
-
36 Power Conditioning Catalogue
�����������������������������
������������������������
������������������������
� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �
�����������������
������������