power ups hpm presentation-r2

55
AUSTRALIA AUSTRALIA PowerUps UPS PowerUps UPS HPM3300 Series HPM3300 Series

Upload: rickyhwk

Post on 25-Jul-2015

275 views

Category:

Engineering


13 download

TRANSCRIPT

Page 1: Power ups   hpm presentation-r2

AUSTRALIA AUSTRALIA

PowerUps UPSPowerUps UPS

HPM3300 SeriesHPM3300 Series

Page 2: Power ups   hpm presentation-r2

HPM seriesDecentralized Parallel Modular Online UPS System

3:3 Phase

HPM3300 Series

3:3 Phase

HPM3300 Series

Page 3: Power ups   hpm presentation-r2

HPM3300-60K/100K

HPM3300-90/150K

HPM 3300-200K

HPM3300-60K/100K

HPM3300-90/150K

HPM 3300-200K

HPM3300-200K

HPM3300-250K

HPM3300-320K

HPM3300-200K

HPM3300-250K

HPM3300-320K10K/15K/20/25/30/40KVA Module

10K/15K/20/25/30/40KVA Module

3/3 system:

60K/100/200KVA (10/15/20k module)250KVA (25k module)90/150/300KVA (30k module)200/320/400/520KVA (40k module)

PF=0.9 and 1 are available

HPM3300-400K

HPM3300-520K

HPM3300-400K

HPM3300-520K

Page 4: Power ups   hpm presentation-r2

HPM 3/3 Module

Model Power Dimension Weight

HPM3310-RM 10KVA 443x580x131mm 3U 26.0 kg

HPM3315-RM 15KVA 443x580x131mm 3U 30.0 kg

HPM3320-RM 20KVA 443x580x131mm 3U 31.0 kg

HPM3325-RM 25KVA 443x580x131mm 3U 32.0 kg

HPM3330-RM 30KVA 443x580x131mm 3U 33.0 kg

HPM3340-RM 40KVA 443x580x131mm 3U 34.0 kg

Page 5: Power ups   hpm presentation-r2

HPM UPS Cabinet (3/3)

Model Application Dimension (W*D*H) mm Net Weight

HPM3300-60K max. (3+1) x 10/15/20KVA Modules 600x840x1400 145 kg

HPM3300-100K max. 5 x 10/15/20KVA Modules 600x840x1400 170 kg

HPM3300-200K max. 10 x 10/15/20KVA Modules 600x1100x2000 270 kg

HPM3300-250K max. 10 x 25KVA modules 600x1100x2000 290 kg

HPM 3300-90k max. (3+1) x 30KVA Modules 600x840x1400 149 kg

HPM 3300-150K max. 5 x 30KVA Modules 600x840x1400 152 kg

HPM 3300-300K max. 10 x 30KVA modules 600x1100x2000 310 kg

HPM3300-200K max. 5 x 40KVA Modules 600x860x1600 205 kg

HPM3300-320k max. 8 x 40KVA Modules 600x860x2000 310 kg

HPM3300-400/520k max. 8/13 x 40KVA Modules 1200x860x2000 450 kg

Page 6: Power ups   hpm presentation-r2

Operator Centres, Servers, Computer rooms

Telecom Switchgear & Infrastructures

Bank, Hospital, Healthcare Equipment

Security Systems, Emergency Lighting, Fire Protection

Airport Infrastructure

Processing Control Equipments

Operator Centres, Servers, Computer rooms

Telecom Switchgear & Infrastructures

Bank, Hospital, Healthcare Equipment

Security Systems, Emergency Lighting, Fire Protection

Airport Infrastructure

Processing Control Equipments

Mission critical & industrial applications

Mission critical & industrial applications

Page 7: Power ups   hpm presentation-r2

Fit into standard 19” Rack Cabinet

Decentralized Parallel Structure Concept

Compact in Size, only 3U Height

Modular N+X Parallel Redundancy

Parallel Operation up to 10 Units for each Rack

Invest as You Grow

High Power Density to 520KVA per Rack

Common Battery

Fit into standard 19” Rack Cabinet

Decentralized Parallel Structure Concept

Compact in Size, only 3U Height

Modular N+X Parallel Redundancy

Parallel Operation up to 10 Units for each Rack

Invest as You Grow

High Power Density to 520KVA per Rack

Common Battery

Main FeaturesMain Features

Page 8: Power ups   hpm presentation-r2

Wide input voltage: 208~478Vac (3/3)

Sinusoidal input current THDI <3%

High input power factor up to 1 (0,99)

High efficiency up to 95.5%

Output power factor up to 1

Plug-and-Play Hot Swappable Module

Remote EPO Function

Control Monitoring with Touch-screen LCD Graphic Display

Wide input voltage: 208~478Vac (3/3)

Sinusoidal input current THDI <3%

High input power factor up to 1 (0,99)

High efficiency up to 95.5%

Output power factor up to 1

Plug-and-Play Hot Swappable Module

Remote EPO Function

Control Monitoring with Touch-screen LCD Graphic Display

Main FeaturesMain Features

Page 9: Power ups   hpm presentation-r2

Superior MTBF (> 220,000 hrs) and MTTR ( < 30 min. )

Powerful Charger Built-in Module and UPS Cabinet

Matching Battery Module also Available

Megatec/Mod Bus Protocol

Versatile Communication Interface

Superior MTBF (> 220,000 hrs) and MTTR ( < 30 min. )

Powerful Charger Built-in Module and UPS Cabinet

Matching Battery Module also Available

Megatec/Mod Bus Protocol

Versatile Communication Interface

Main FeaturesMain Features

Page 10: Power ups   hpm presentation-r2

NO SPOF (Single Points of Failure)

Highest Availability 0.999998

Safe Swappable Modular Concept

NO SPOF (Single Points of Failure)

Highest Availability 0.999998

Safe Swappable Modular Concept

Decentralized Parallel Structure ConceptDecentralized Parallel Structure Concept

Page 11: Power ups   hpm presentation-r2

Single Line Module Diagram Single Line Module Diagram

EMI AC/DC Converter BUSDC/AC Inverter

Static Bypass

Battery

DC/DC Converter Charger

I/P O/PEMI

Page 12: Power ups   hpm presentation-r2

Only 3U Height

10KVA/15KVA/20KVA/25KVA/30KVA/40KVA Modules Available

Only 3U Height

10KVA/15KVA/20KVA/25KVA/30KVA/40KVA Modules Available

Compact in Size Compact in Size

Page 13: Power ups   hpm presentation-r2

Parallel up to 13 Modules

Load Sharing

More than 1 Module can be set at Redundancy

Parallel up to 13 Modules

Load Sharing

More than 1 Module can be set at Redundancy

Modular N + X Parallel RedundancyModular N + X Parallel Redundancy

H=1.4MH=1.4M

H=2.0MH=2.0MPay as you grow

Pay as you grow

Page 14: Power ups   hpm presentation-r2

H=1.4M/1.6M : up to 5 Modules

H=2.0M : up to 13 Modules

UPS Modules/Battery Modules

System Parallel Maximum: 4

H=1.4M/1.6M : up to 5 Modules

H=2.0M : up to 13 Modules

UPS Modules/Battery Modules

System Parallel Maximum: 4

Parallel up to 13 Units for Each RackParallel up to 13 Units for Each Rack

UPS Modules Battery Modules

Page 15: Power ups   hpm presentation-r2

Sizing What You Need Now

Pay as You Grow

Flexibility/Scalability for Future Expansion

Low Service Contracts

Sizing What You Need Now

Pay as You Grow

Flexibility/Scalability for Future Expansion

Low Service Contracts

Invest as You GrowInvest as You Grow

No over-sizing UPS &

Add power w/o increasing footprint

No over-sizing UPS &

Add power w/o increasing footprint

Page 16: Power ups   hpm presentation-r2

High Power Density High Power Density

Footprint Reduction, less Surface Costs

Easy to upgrade from 10KVA up to 520KVA per Rack

Footprint Reduction, less Surface Costs

Easy to upgrade from 10KVA up to 520KVA per Rack

Page 17: Power ups   hpm presentation-r2

HPM Cabinet DiagramHPM Cabinet Diagram

Monitor Module

LCD displayer Communication

UPS Module 13#

UPS Module 9#

UPS Module 2#

UPS Module 1#

Maintain Bypass

I/P O/P

Battery

BPS InductorBPS

Output Switch

Page 18: Power ups   hpm presentation-r2

High Input Power Factor up to 1High Input Power Factor up to 1

Page 19: Power ups   hpm presentation-r2

Low Input Current THDI <3% Low Input Current THDI <3%

Page 20: Power ups   hpm presentation-r2

High Efficiency up to 95.5% High Efficiency up to 95.5%

Page 21: Power ups   hpm presentation-r2

Plug-and-Play Hot Swappable ModulePlug-and-Play Hot Swappable Module High Power Density Reduced Footprint

Flexibility/Scalability

Lowest Service Cost

Lowest Installation Cost

Page 22: Power ups   hpm presentation-r2

Common Battery Common Battery

Several UPS Modules share one battery module

3/

Page 23: Power ups   hpm presentation-r2

Powerful Charger Powerful Charger Module: 10A (Max) Charge Current (A):

HPM3300-60/100k HPM3300-200/250k HPM3300-300/400K HPM3300-520K

Max. 30A Max. 60A Max. 100A Max. 130A

Max. Charging Current Settable

Page 24: Power ups   hpm presentation-r2

3-Stage Intelligent Charging Modes3-Stage Intelligent Charging Modes

Constant current

Constant voltage

Floating Charge

Page 25: Power ups   hpm presentation-r2

Battery Voltage Configurable Battery Voltage Configurable

3:3 phase

± 192Vdc/ ± 204Vdc/ ± 216Vdc/ ± 228Vdc/ ± 240Vdc Configurable

Decrease Initial Investment

Increase Competition

Page 26: Power ups   hpm presentation-r2

HPM-BF36100 or BF36120 36pcs of 100AH or 120AH

Matching battery Frame

Page 27: Power ups   hpm presentation-r2

Matching Battery Module Also Available Matching Battery Module Also Available Battery Module: for Max. 18pcs 7AH/9AH bat.

Simply plug into UPS System

Only 3U Height

Page 28: Power ups   hpm presentation-r2

Module LCD Display

Input Voltage/Frequency Output Voltage/Frequency Load Capacity, Battery Voltage/Current Charge Modes/Charger Status Internal/Ambient Temperature Module ID/Status Alarm Codes

Page 29: Power ups   hpm presentation-r2

Control Monitoring with Touch-screen LCDGraphic Display

Control Monitoring with Touch-screen LCDGraphic Display

Page 30: Power ups   hpm presentation-r2

Full-Screen status for Input, Output, Battery, Modules

ONLINE 30KVA 22-12-2008ID:01 08:30

◄Outp

utModu

leInput

BattStat

e►

APhase Voltage (v) 220Phase Current (A) 1Frequency (HZ) 50Active Power ( KW) 0.0Apparent Power (KVA) 0.0Load percent(%) 0Load crest factor 0.0   

  

ONLINE 30KVA 22-12-2008ID:01 08:30

◄Outp

utModu

leInput

BattStat

e►

Module01 A B C Invert Voltage (V) 380 380

380 Invert Current (A) 220 220

220 Frequency (HZ) 50 Positive Bus Voltage (V) 400 Negative Bus Voltage (V) 400 Code 8000-8000 D800-8000 0000-0000 0000-0000 

Back

 

ONLINE 30KVA 22-12-2008ID:01 08:30

◄Outp

utModul

eInpu

tBatt

State

Mains A B C Phase Voltage (V) 380 380

380 Phase Current (A) 220 220

220 Frequency (HZ) 50 Power Factor 0.97 0.97

0.97 Bypass Phase Voltage (V) 220 220

220 Frequency (HZ) 50

 

ONLINE 30KVA 22-12-2008ID:01 08:30

◄Outp

utModul

eInpu

tBat

tStat

e►

 Positive Battery Voltage (V) 240.0Negative Battery Voltage (V) 240.0Positive Battery Current (A) 10.0Negative Battery Current (A) 10.0Battery State ChargeBattery Temperature (℃) 28Lasting (min) 90

 

Page 31: Power ups   hpm presentation-r2

Command

Battery Test

Buzzer Set

Default Set

Command

Battery Test

Buzzer Set

Default Set

ONLINE   

30KVA 22-12-2008 ID:01 08:30

◄ Comma

ndSetting

Record

Version

Battery TestBuzzer Set MuteDefault Set

 

Self-Test Date Mode: Weekly ▲ Week: SAT Time: 18:36 ▼ Lasting: 60min

Ensure Cancel

LBS Group Setting

▼Master▲

Ensure Cancel

Page 32: Power ups   hpm presentation-r2

Setting

Language

System Parameters

Working Modes

Setting

Language

System Parameters

Working Modes

ONLINE    30KVA 22-12-2008 ID:01 08:30

◄Comman

d Setting Record

Version

Language Change Password Date Setting 2008-12-22 08:30:00 Back-Light Delay 10Min Contrast 20 Self-Test Date STA 18:36 FOR:60min Back Timing of ON/OFF ON:MON 08:48 OFF:SUN 17:25 Next

 

  ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Comman

dSettin

gRecor

dVersion ►

Work Mode Single LBS Group Setting Master System Voltage Level 220V System Frequency Level 50HZ Auto Turn-on Enable Bypass Frequency Range 2% Bypass Volt. Upper Limit 10% Back Bypass Volt. Lower Limit -30% O/P Volt Micro tuning 0% Next

 

Page 33: Power ups   hpm presentation-r2

Setting

Parallel ID

Battery Voltage/Capacity

Setting

Parallel ID

Battery Voltage/Capacity ONLINE   30KVA 22-12-2008 ID:01 08:30

◄ Comma

ndSettin

gRecor

dVersion ►

Parallel ID 01M/S hot standby Cyc. 6 MonUPS Output EnablePre-Alarm Time 14 MinFloat Volt Revise 0.001Parallel Amount 04Parallel Redundancy 01 Back 

Next

 

ONLINE 30KVA 22-12-2008 

ID:01 08:30

◄ Command  Setting Record Version ►

Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

Page 34: Power ups   hpm presentation-r2

Record All Events/Alarm Message Display Up to 49 events 50 alarm messages

ONLINE 30KVA 22-12-2008ID:01 08:30

◄ Command  Setting Record Version ►

 

Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

Page 35: Power ups   hpm presentation-r2

Hot Standby Mode

ONLINE 30KVA 22-12-2008 

 ID:01 08:30

◄  Command Setting Record Version ►

Parallel ID 01M/S hotstandby Cyc. 6 MUPS Output EnaPre-Alarm Time 14 Float Volt Revise 0.00Parallel Amount 04Parallel Redundancy 01 Back  Next

 

M/S hot standby Cyc.

▼ 3 ▲

Ensure Cancel

Page 36: Power ups   hpm presentation-r2

Battery Setti

ng

ONLINE 30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ►

Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

ONLINE 30KVA 22-12-2008

 ID:01 08:30 ◄  Command Setting Record Version ►

 

Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next

 

ONLINE30KVA 22-12-2008 ID:01 08:30

◄  Command Setting Record Version ►  

 

Single Battery Capa.

1000

7 8 9Cancel

4 5 6 ←

1 2 3 →

. 0Ensure

Battery Number

▼ 20 ▲

Ensure Cancel

Battery Group

▼ 1 ▲

Ensure Cancel

Page 37: Power ups   hpm presentation-r2

Charging Current Setti

ngCharging

Current Setting

Page 38: Power ups   hpm presentation-r2

Independent Separate Bypass Independent Separate Bypass

Each Individual Modular has its own Bypass Switch

Maintenance bypass switch

Page 39: Power ups   hpm presentation-r2

Versatile Communication InterfacesVersatile Communication Interfaces RS485 Ports RS232 Port Mod Bus Port 2 x Intelligent slot (SNMP, relay option)

Network Management Card replacement

1 : Dry Contact Relay

2 : SNMP port

Page 40: Power ups   hpm presentation-r2

Versatile Communication InterfacesVersatile Communication Interfaces MEGAtec Protocol Supported SNMP Card

Page 41: Power ups   hpm presentation-r2

Versatile Communication InterfacesVersatile Communication Interfaces Dry Contact Relay

Pin Function

1

O/P

Utility Failure

2 /

3 Battery Low

4 On bypass

5 UPS Fault

6 Inverter On

7 UPS Alarm

8 Common

9I/P

+12V

10 0V

Page 42: Power ups   hpm presentation-r2

Cabinet Outlook --H=1.4M ( 5 Modules )Cabinet Outlook --H=1.4M ( 5 Modules )

Front View Front View Rear ViewRear View

Page 43: Power ups   hpm presentation-r2

Cabinet Outlook --H=1.6M ( 5 Modules )

Page 44: Power ups   hpm presentation-r2

Cabinet Outlook --H=2M ( 8 Modules )

Page 45: Power ups   hpm presentation-r2

Cabinet Outlook --H=2M ( 10 Modules )Cabinet Outlook --H=2M ( 10 Modules )

Front View Front View Rear ViewRear View

Page 46: Power ups   hpm presentation-r2

Cabinet Outlook --H=2M ( 10 Modules )

Page 47: Power ups   hpm presentation-r2

Cabinet Outlook --H=2M ( 13 Modules )

Page 48: Power ups   hpm presentation-r2

Module Outlook Module Outlook

Front ViewFront View Rear ViewRear View

10K/15K/20K/25k/30k

40k Front ViewFront View Rear ViewRear View

Page 49: Power ups   hpm presentation-r2

Product Specifications

Page 50: Power ups   hpm presentation-r2

Product Specifications

Page 51: Power ups   hpm presentation-r2
Page 52: Power ups   hpm presentation-r2
Page 53: Power ups   hpm presentation-r2

Special Models HPM-SA for Standard 19” Frame

can be used as a single unitModel HPM3315/HPM3320/HPM3325-SA

Capacity 15KVA/13.5KW, 20KVA/18KW, 25KVA/22.5KW

Input Voltage 208Vac~478Vac

Output Voltage 380/400/415Vac

Battery Voltage 384V/408V/432/480Vdc Settable

Parallel Quantity 4(default), 5~6 or 7~10 Settable(remove J31 & J31/J30)

Dimension(WxHxD) 443x131x580

Net Weight(w/o battery) 31.0

Model HPM-BR32007

Battery Type/Quantity HC1221W(12V/21W)/32pcs

Dimension 483x132x680mm

Net Weight(w/o battery) 76.0

Page 54: Power ups   hpm presentation-r2

Standard 19” Rack SolutionThe HPM3300-SA is designed to be the most versatile UPS on the market and provides the best technical & commercial solutions to meet individual power protection needs.

It fixes in various depths of standard

19” rack cabinet.

Page 55: Power ups   hpm presentation-r2