power system calculations—part ii
TRANSCRIPT
![Page 1: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/1.jpg)
Power System Power System Calculations—Part IICalculations Part II
Kurt B. Ederhoff, Ph.D., P.E.
2010 Industry Applications Society Annual Meeting - Houston, TXOctober 3-7, 2010
![Page 2: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/2.jpg)
2
I d iIntroduction
• Topics• Topics▫ Per Unit Basis
S t i l C t▫ Symmetrical Components▫ Component Modelling
l k▫ Faults & Sequence Networks
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 3: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/3.jpg)
![Page 4: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/4.jpg)
4
P U i C iPer Unit Conversion• Per Unit Definition• Per Unit Definition
A quantity a (voltage, current, power, impedance, admittance, etc.) in per unit is defined as the ratio , ) pof that quantity to a selected base quantity of the same nature (i.e. voltage, current, power, i d d itt t )impedance, admittance, etc.)
[actual units] [units][per unit] [pu]a a
a a= =[actual units] [units]b b
a aa a
= =
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 5: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/5.jpg)
5
P U iPer Unit• Example:• Example:
If V = 120 [V] and we select Vb = 80 [V], then[ ] b [ ],
[pu] 120 [V] 1.5 [pu]80 [V]
V = =80 [V]
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 6: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/6.jpg)
6
P U iPer Unit• Percent Definition• Percent Definition
If the per unit value is multiplied by 100, the quantity is expressed in percent with respect to q y p p pthe base quantity.
F th i l th lt i For the previous example, we say the voltage is 150% (1.5 x 100) of the base voltage of 80 [V].
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 7: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/7.jpg)
7
P U iPer Unit• Per unit conversion requires us to select a base • Per unit conversion requires us to select a base
quantity• How do we make the selection?How do we make the selection?▫ Answer: Select two quantities as the base from the
following: voltage, current, power, impedance, admittance
• Which do we choose?A G ll h lt d ▫ Answer: Generally choose voltage and power.
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 8: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/8.jpg)
8
P U iPer Unit• Why Voltage and Power?Why Voltage and Power?▫ Voltage. For each voltage level in our system, we
know the rated voltage of equipment, and even if loading changes the voltage does not deviate too much loading changes, the voltage does not deviate too much from the rated value.
▫ Power. The range of power flowing in a section of the system is quadratically related with the voltage As system is quadratically related with the voltage. As such, the range of expected power flow is known for an area. Note, for transmission level analysis, it is c sto a to select a base o e of 100 MVAcustomary to select a base power of 100 MVA.Note: The base power is usually selected to be the same for the entire network.
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 9: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/9.jpg)
9
C iConventions• Unless specifically stated the following • Unless specifically stated, the following
quantities are always complex numbers:V, I, Z, Y, S, t, , , , ,
• All other quantities are real numbers, such asR, X, G, B, L, C, P, Q
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 10: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/10.jpg)
10
T i lTerminologyV Voltage L InductanceV VoltageI CurrentZ Impedance
L InductanceC CapacitanceP Active Power
Y AdmittanceS Complex Powert Turn Ratio
Q Reactive Power|S| Apparent Power
t Turn RatioR ResistanceX Reactance
• Pet Peeve #1: There is no “real power" anywhere
G ConductanceB Susceptance
here
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 11: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/11.jpg)
11
P U iPer Unit• Selecting Quantities• Selecting Quantities
bV VS S
f f-==
▫ Voltage Usually selected as the nominal phase-to-phase voltage at each
3bS S f=
y p p gvoltage level
▫ Power Usually selected in the range of 3-phase power flowing in the y g 3 p p g
network (i.e. whatever network is being analyzed) For transmission level analysis, it is customary to select a base
power of 100 MVA.
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
The base power is usually selected to be the same for the entire network.
![Page 12: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/12.jpg)
12
P U i F lPer Unit Formulas
[VA] [V]3[A] [V]b bS V
I Vf f f-= = [V]
2
, 3 3n b n b
b
I VVf f
f f- -
-
= =
( )2[V][ ] [Siemens]
[VA] [ ]3
1, bb b
b b
VZ Y
S Zf f
f
-WW= =
3 b bf
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 13: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/13.jpg)
13
P U i f E iPer Unit for Equipment• Per unit quantities for equipment is defined at • Per unit quantities for equipment is defined at
the equipment level▫ Ex: 25 MVA, 110-33 kV transformer5 , 0 33 a s o e
Z = 8.3%
k h ff▫ Ex: 4 kV, 1500 hp, 0.88 PF, 93.5% effXd” = 0.155 pu
motor1500 [hp] 0.746 [hp/kW]
0.88 PF 0.935 eff1360 [kVA]
bS S´
= =´
=
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
1360 [kVA]=
![Page 14: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/14.jpg)
14
P U i C iPer Unit Conversion• Equipment ratings vary• Equipment ratings vary• Selection of base quantities vary• Analysis requires use of a common base• Analysis requires use of a common base
[units] [units][pu.old base] [pu.new base]
[units] [units];A AA A
A A= =[units] [units]
b.old b.new
[pu.old base] [units] [pu.new base] [units]b ld b
A A
A A A A=b.old b.new
[units][pu.new base] [pu.old base] b old
A A A A
AA A
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
[pu.new base] [pu.old base] b.old[units]b.new
A AA
=
![Page 15: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/15.jpg)
15
P U i C iPer Unit Conversion• Particularly for impedances• Particularly for impedances
Remember:( )2[V]
bV( )[ ][VA]
bb
b
VZ
SW =
[ ]Z Wæ ö[ ][pu.new base] [pu.old base] b.old
[ ]b.new
ZZ Z
Z W
æ ö÷ç ÷= ç ÷ç ÷çè ø
2[V] [VA][pu.old base] b.old b.new
[V] [VA]
V SZ
V S
æ ö æ ö÷ ÷ç ç÷ ÷= ç ç÷ ÷ç ç÷ ÷ç ç
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
[V] [VA]b.new b.oldV Sç ç÷ ÷ç çè ø è ø
![Page 16: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/16.jpg)
16
Ad Of P U iAdvantages Of Per Unit• Equipment Parameters. For a given type of equipment, and Equipment Parameters. For a given type of equipment, and
disregarding the size and voltage, the parameters in per unit are within a narrow, known range
• Eliminate Turn Ratio. For two adjacent networks of different jvoltage levels, if the selected base power is the same throughout and the selected base voltages match the turn ratio of the transformer between the networks, then all quantities in per unit have the same value regardless of which voltage level they are defined. In essence, the transformer is eliminated.
• Eliminate Coefficients. For almost all equations with quantities defined in per unit, the numerical coefficients are eliminated.
• Voltage. In per unit, the line-to-neutral voltage equals the phase-to-phase voltage, and during normal operation both quantities are l i
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
close to unity.
![Page 17: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/17.jpg)
![Page 18: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/18.jpg)
18
HiHistory• Charles LeGeyt FortescueCharles LeGeyt Fortescue▫ 1876 – Born in York Factory, Manitoba▫ 1898 – First engineer to graduate from Queens
University at Kingston in OntarioUniversity at Kingston in Ontario▫ Joined Westinghouse after graduation and spent his
entire career thereh d f hi h▫ 1913 – Co-authored paper on measurement of high
voltage using sphere gap, a method still used to this day (97 years later)
▫ Obtained 185 patents in his career in design transformers, insulators, and DC and AC power circuits
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 19: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/19.jpg)
19
HiHistory• Charles LeGeyt Fortescue (cont’d)• Charles LeGeyt Fortescue (cont d)▫ 1921 – Elected AIEE Fellow▫ 1930 – Paper in Electric Journal that outlined 1930 Paper in Electric Journal that outlined
“direct stroke theory”, which is said to have completely revolutionized the approach to the li h i bl L d d i f h d lightning problem. Led to adoption of overhead static lines.
▫ 1936 – Died in December at age 601936 Died in December at age 60
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 20: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/20.jpg)
20
HiHistory• Charles LeGeyt Fortescue (cont’d)Charles LeGeyt Fortescue (cont d)▫ 1918 - Transactions of the American Institute of
Electrical Engineers (AIEE) included the classic paper Method of Symmetrical Co-Ordinates Applied to the f y ppSolution of Polyphase Networks 88 pages long 24 additional pages of discussion
b d i 303 numbered equations “bewildering exhibit of subscripts to be found in it is
something that will, well, make one pause” Vladimir Karapetoff suggested that the term Vladimir Karapetoff suggested that the term
“symmetrical components” was a “more correct and descriptive” expression
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 21: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/21.jpg)
21
S i l “C O di ”Symmetrical “Co-Ordinates”• What are Symmetrical Components?What are Symmetrical Components?▫ Any set of N unbalanced phasors — that is, any such
“polyphase” signal — can be expressed as the sum of Nsymmetrical sets of balanced phasorssymmetrical sets of balanced phasors.
▫ Only a single frequency component is represented by the phasors. This is overcome by using techniques such as Fourier or LaPlace transformssuch as Fourier or LaPlace transforms.
▫ Absolutely general and rigorous and can be applied to both steady state and transient problems.
h hl bl h d l h l▫ It is thoroughly established as preeminently the only effective method of analyzing general polyphasenetwork problems
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 22: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/22.jpg)
22
Th Ph S N kThree-Phase Sequence Networks• Three-Phase SystemsThree Phase Systems▫ Three sets of symmetrical components, where each set
is referred to as a sequence.▫ First set of phasors, called the positive sequence, has p , p q ,
the same phase sequence as the system under study (say ABC)
▫ The second set, the negative sequence, has the reverse h ( AC)phase sequence (BAC)
▫ The third set, the zero sequence, phasors A, B and C are in phase with each other.M th d t t f th h i t th ▫ Method converts any set of three phasors into three sets of symmetrical phasors, which makes asymmetric analysis more tractable.
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 23: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/23.jpg)
23
S i l CSymmetrical Components• Set of three phasors say X X and X can be • Set of three phasors, say Xa, Xb and Xc can be
represented as a sum of the three sequence setsX X X X= + +0 1 2
0 1 2
0 1 2
a a a a
b b b b
X X X XX X X XX X X X
= + += + += + +0 1 2
0 0 0
where , , is the zero sequence set
c c c c
a b c
X X X X
X X X
+ +
0 0 0
1 1 1
2 2 2
q, , is the positive sequence set, , is the negative sequence set
a b c
a b c
a b c
X X XX X X
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 24: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/24.jpg)
24
S i l CSymmetrical Components
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 25: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/25.jpg)
25
S i l CSymmetrical ComponentsOnly three of the sequence values are unique
1 2
Only three of the sequence values are unique, , ,
The others can be determined. First, we define aa a aX X X
120
,complex operator .
1 120ja
a e = 2 240
3 3601 2401 360 1
j
ja ea e
= = = = =
21 0a a+ + =
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 26: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/26.jpg)
26
S i l CSymmetrical ComponentsThen, we relate phases within a sequence to the reference,
0 0 0 0 0
Then, we relate phases within a sequence to the reference,which is a-phase in this example
: ,a b a c aX X X X X= =0 0 0 0 02
1 1 1 1 12
2 2 2 2 2
::
a b a c a
a b a c a
a b a c a
X X a X X aXX X aX X a X
= == =a b a c a
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 27: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/27.jpg)
27
S i l CSymmetrical ComponentsRearrange the equations
0 1 22
0 1 2
Rearrange the equationsa a a a
b
X X X XX X a X aX
= + += + +0 1 2
20 1 2
which in matrix form looks like this:
b a a a
c a a a
X X a X aXX X aX a X
+ += + +
02
1
1 1 11
aa
b a
XXX a a X
é ùé ùé ù ê úê úê ú ê úê ú=ê ú ê úê úê ú 221c a
X a a Xê úê úê ú ê úê úê úë û ë û ë û
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 28: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/28.jpg)
28
S i l CSymmetrical ComponentsUsing simple notation, we can convert from symmetrical
phase sym
component reference to the phase reference as follows:
h=X TX
2
where1 1 11é ùê úê úT 2
211
Of course the following equation can convert from
a aa a
ê úê úê úë û
T
theOf course, the following equation can convert from
1h
thephase reference to the symmetrical component reference:
-=X T X
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
sym phaseX T X
![Page 29: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/29.jpg)
29
S i l CSymmetrical ComponentsThe inverse of the transformation matrix is
1 21 1 1
1 1 a a-
é ùê úê ú= ê úT
23 1which in detail, results in the following equations:
a aê úê úë û
02
1
1 1 11 13
aa
a b
XXX a a X
é ùé ùé ù ê úê úê ú ê úê ú=ê ú ê úê úê ú 22
3 1a cX a a X
ê úê úê ú ê úê úê úë û ë û ë û
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 30: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/30.jpg)
30
S C E l 1Sym. Components – Example 1
Let10 0
10aI
Ié ù é ùê ú ê úê ú ê úI
10
10Then
b
c
II
= =ê ú ê úê ú ê úê ú ê úë û ë û
I
1s
Then
1 1 1 10 0
-=é ù é ù é ùê ú
I T I
2
2
1 1 1 10 01 1 10 10 03 10 01
a aa a
é ù é ùê ú ê ú ê úê ú= =ê ú ê úê ú ê ú ê úê ú ê ú ê úë û ë ûë û
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
1 a aê ú ê ú ê úë û ë ûë û
![Page 31: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/31.jpg)
31
S C E l 2Sym. Components – Example 2
IfIf10 0
10é ùê ú
= ê úI
1010
Then
= ê úê úê úë û
I
s
Then00
é ùê ú
= ê úê ú
Is
10 0ê úê úë û
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 32: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/32.jpg)
32
S C E l 3Sym. Components – Example 3IfIf
8.0 06 0 90
aVVé ù é ù ê ú ê úê ú = ê ú6.0 90
16.0 143.1Then
b
c
VVê ú = -ê úê ú ê ú ê ú ê úë ûë û
0
Then2.0 143.19 8 18 4
VVé ù é ù ê ú ê úê ú = ê úê ú1
2
9.8 18.44.3 86.2
VVê ú = ê úê ú ê ú - ê ú ê úë ûë û
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 33: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/33.jpg)
33
S i l CSymmetrical Components
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 34: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/34.jpg)
34
S i l CSymmetrical Components
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 35: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/35.jpg)
35
S i l CSymmetrical Components
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 36: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/36.jpg)
36
O W Vi liOne Way to Visualize• Positive Sequence• Positive Sequence▫ Can be thought of as a “source” that rotates a
machine in a particular directionp• Negative Sequence▫ This “source” rotates a machine in a direction
opposite of that of the positive sequence• Zero Sequence
C t ti l f b t i t d f ▫ Causes no rotational force, but instead forms an oscillating (not rotating) field in the machine
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 37: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/37.jpg)
37
C S CComments on Sym. Components• The transformations apply only for linear systems, The transformations apply only for linear systems,
that is, systems with constant parameters (impedance, admittance) independent of voltages and currents
• The quantities used for X can be phase-to-neutral or phase-to-phase voltages, or line or line-to-line currents.
• For some connections, the zero sequence component is always zero▫ Line currents for an ungrounded wye connectionLine currents for an ungrounded wye connection▫ Line currents for a delta connection▫ Line-to-line voltages for a delta connection
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 38: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/38.jpg)
38
M CMore Comments• Symmetrical components is a important tool for Symmetrical components is a important tool for
analyzing unbalanced states▫ Three-phase unsymmetrical network and state is
converted to three symmetrical networks and statesconverted to three symmetrical networks and states▫ Symmetrical networks can be solved using single
phase techniquesWi h i l l h ▫ With symmetrical components we solve three interconnected symmetrical networks using single phase analysis, which is easy.
▫ Once solved, we use transformation equations to obtain phase quantities
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 39: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/39.jpg)
39
M CMore Comments• Equipment Parameters• Equipment Parameters▫ Symmetrical components has advantage that
parameters in system components are easier to p y pdefine
▫ Because each sequence is a symmetrical three-h h b d fi d i phase case, the parameters can be defined using
typical three-phase tests.
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 40: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/40.jpg)
40
Complex Power with Symmetrical Complex Power with Symmetrical Components
( )For wye connections
S V I V I V I V I I I** * *= + + + + +( )
( ) ( ) ( ) an a bn b cn c n a b c
an n a bn n b cn n c
S V I V I V I V I I IV V I V V I V V I
V I V I V I
* * *
* * *
= + + + + +
= + + + + += + +
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
a a b b c cV I V I V I= + +
![Page 41: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/41.jpg)
41
Complex Power with Symmetrical Complex Power with Symmetrical Components
For delta connectionsab ab bc bc ca caS V I V I V I* * *= + +
( ) ( ) ( )( ) ( ) ( )
ab ab bc bc ca ca
a b ab b c bc c a ca
a ab ca b bc ab c ca bc
V V I V V I V V I
V I I V I I V I I
* * *
* * *
+ += - + - + -
= - + - + -
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
( ) ( ) ( )
a ab ca b bc ab c ca bc
a a b b c cV I V I V I* * *
+ += + +
![Page 42: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/42.jpg)
42
Complex Power with Symmetrical Complex Power with Symmetrical Components
In matrix form
T
In matrix form
aIS V V V I
*
*
é ùê ú
é ù ê ú V ITphase phase
We have the following transforms
a b c b
c
S V V V II
*é ù ê ú= =ë û ê úê úë û
V I
phase sym
phase sym
We have the following transforms==
V TVI TIphase sym
T Tsym sym
Then the complex power becomesS * *= V T T I
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
sy sy
![Page 43: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/43.jpg)
43
Complex Power with Symmetrical Complex Power with Symmetrical Components
T
The product1 0 0
3 3 0 1 0*
é ùê úê úT T IT
identity3 3 0 1 00 0 1
Then the complex power becomes
* = = ê úê úê úë û
T T I
( )Tsym sym
Then the complex power becomes33
SV I V I V I
*
* * *
== + +
V I
( )0 0 1 1 2 2 3If the voltages and current are defined inper unit, the "3" disappears
a a a a a aV I V I V I= + +
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
p , pp
![Page 44: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/44.jpg)
44
U f S i l CUse of Symmetrical Components• Consider the following wye connected load• Consider the following wye connected load
n a b c
Y
I I I IV Z I Z I
= + += +
( )( )
a Y a n n
a Y n a n b n c
b n a Y n b n c
V Z I Z IV Z Z I Z I Z IV Z I Z Z I Z I
+= + + += + + +
( )c n a n b Y n cV Z I Z I Z Z I= + + +
a Y n n n a
b n Y n n b
V Z Z Z Z IV Z Z Z Z Ié ù é ù é ù+ê ú ê ú ê ú
= +ê ú ê ú ê úê ú ê ú ê ú
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
c n n Y n cV Z Z Z Z Iê ú ê ú ê ú+ê ú ê ú ê úë û ë û ë û
![Page 45: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/45.jpg)
45
U f S i l CUse of Symmetrical Componentsa Y n n n aV Z Z Z Z Ié ù é ù é ù+ê ú ê ú ê úb n Y n n b
c n n Y n c
V Z Z Z Z IV Z Z Z Z I
ê ú ê ú ê ú= +ê ú ê ú ê ú
ê ú ê ú ê ú+ê ú ê ú ê úë û ë û ë ûV ZI
sym
===
V ZIV TVI TIsym
sym sym1-
==
=
I TITV ZTIV T ZTIsym sym
13 0 0
0 0y nZ Z
Z-
é ù+ê úê ú=ê ú
V T ZTI
T ZT
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
0 00 0
y
yZê úê úë û
![Page 46: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/46.jpg)
46
U f S i l CUse of Symmetrical Components0 03 0 0Y
V IZ Zé ù é ùé ù+ê ú ê úê ú0 0
1 1
2 2
3 0 00 00 0
Y n
Y
Y
Z ZV Z I
ZV I
+ê ú ê úê úê ú ê ú= ê úê ú ê úê úê ú ê úê úë ûë û ë û2 2
0 0
Systems are decoupled( 3 )Y nV Z Z I
ë ûë û ë û
= +
1 1
2 2
Y
Y
V Z IV Z I
==
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 47: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/47.jpg)
![Page 48: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/48.jpg)
![Page 49: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/49.jpg)
52
GGenerators• Fault Behavior• Fault Behavior▫ Sudden change in voltage and current, such as
those in faults, produces transients, p▫ Armature current divided into two components Symmetrical AC component – whose associated
i h fi ld i DC component in the field is a DC current DC component – whose associated component in the
field is an AC current
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 50: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/50.jpg)
53
GGenerators• Symmetrical Component ModellingSymmetrical Component Modelling▫ Principle concern is with symmetrical component and its
associated constants▫ DC component often eliminated from studiesDC component often eliminated from studies Usually not necessary to apply or set protective relays If necessary (e.g. circuit breaker applications), various factors
are available from standards, manufacturers, or other sources, ,▫ For synchronous machines, symmetrical AC component can
be resolved into three distinct components Subtransient component – the double prime (“) values Transient component – the single prime (‘) values The steady-state component
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 51: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/51.jpg)
54
GGenerators• Subtransient Component• Subtransient Component▫ Occurs during onset of fault▫ Subtransient reactance (Xd”) approaches armature Subtransient reactance (Xd ) approaches armature
leakage reactance but is higher as a result of damper windings, and so on.
▫ Subtransient time constant (Td”) is very low (because damper windings have relatively high resistance) typically around 0 01–0 05 secondsresistance), typically around 0.01 0.05 seconds
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 52: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/52.jpg)
55
GGenerators• Transient ComponentTransient Component▫ Armature current demagnetizes the field and decrease
flux linkages with the field winding▫ Transient reactance (Xd’) includes effect of both ( d )
armature and field leakages and is higher than armature leakage reactance, and thus higher than the subtransient reactance
i i ( ’) i i ll f ▫ Transient time constant (Td’) varies typically from 0.35 to 3.3 seconds
• Steady-State Componenti ll d▫ Transient eventually decays
▫ For faults, eventually becomes unsaturated direct axis reactance (Xd)
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 53: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/53.jpg)
56
GGenerators
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 54: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/54.jpg)
57
GGenerators• Negative SequenceNegative Sequence▫ Subtransient reactance can be measured by blocking
the rotor with the field winding shorted and applying single phase voltage across any two terminalssingle phase voltage across any two terminals
▫ As position of rotor is changed, measured reactance varies considerably if machine has salient poles without dampers (and very little damper winding without dampers (and very little damper winding exists) or if the machine has a round rotor
▫ For negative sequence, similar phenomenon exists t t i t f ith l ti t fi ld t b except rotor is at 2f with relation to field set up by
applied voltage▫ Good approximation: ( )1
2 2 d qX X X¢¢ ¢¢= +
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
( )q
![Page 55: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/55.jpg)
58
GGenerators• Zero Sequence• Zero Sequence▫ Varies quite a lot▫ Depends largely on pitch and breadth factors of Depends largely on pitch and breadth factors of
armature winding▫ Generally, X0 is much smaller than X1 and X2
values
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 56: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/56.jpg)
59
GGenerators
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 57: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/57.jpg)
60
G & N k E i lGenerators & Network Equivalents• “Strong” Remote Strong Remote
Systems▫ Assume X1 = X2
▫ Calculate X1 from 3-phase fault dutyC l l t X f ▫ Calculate X0 from SLG fault duty
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 58: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/58.jpg)
I d i M hiInduction Machines• Positive SequencePositive Sequence▫ Changes from stalled to
running▫ ~0.15 pu stalled (Xd”)5 p ( d )▫ 0.9–1.0 pu running
• Negative Sequence▫ Remains effectively constante a s e ect e y co sta t▫ ~0.15 pu (Xd”)
• Zero Sequence▫ 0.0 if wye ungrounded or 0.0 if wye ungrounded or
delta connected
![Page 59: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/59.jpg)
62
T fTransformers• Modelling• Modelling▫ Usually modelled as a series impedance▫ Shunt parameters can be calculated by review of Shunt parameters can be calculated by review of
transformer tests.▫ Shunt parameters don’t generally impact analysis▫ Transformer winding configuration determines
sequence networks▫ Three winding transformers have interesting ▫ Three winding transformers have interesting
sequence networks, but close inspections shows them to be intuitive
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 60: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/60.jpg)
T f S N kTransformer Sequence Networks
![Page 61: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/61.jpg)
64
3 Wi di T f I d3 Winding Transformer Impedance• 3 Winding Transformer Impedance3 Winding Transformer Impedance▫ Usually given as a winding-to-winding (delta)
impedances in per cent▫ Convert to equivalent wye impedances for sequence q y p q
network analysis▫ Often times, the base power is different for various
impedances▫ Ex: 100 MVA auto with 35 MVA tertiary
May show ZHM on 100 MVA baseMay show ZHL and ZML on 35 MVA base
Must convert delta impedance to common basebefore converting to equivalent wye network
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 62: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/62.jpg)
65
3 Wi di T f I d3 Winding Transformer Impedance• Delta Wye Conversion Formula• Delta-Wye Conversion Formula
( )12H HM HL MLZ Z Z Z= + -( )( )
12
12
M HM ML HL
L HL ML HM
Z Z Z ZZ Z Z Z
= + -= + -
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 63: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/63.jpg)
66
Zi Z T fZig-Zag Transformer
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 64: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/64.jpg)
67
T i i LiTransmission Lines• Positive and Negative Sequence Impedance• Positive and Negative Sequence Impedance▫ Passive component▫ Assume line transpositionsAssume line transpositions
01 2 ln [H/m]
2mD
L LD
mp
= =
7
22
4 10 ln [ /m]
s
m
DX L fL
DX X
pw p
p -
= =
= = ´ W1 2
1 2
4 10 ln [ /m]
conductor AC resistance (tables)s
X XD
R R
p= = ´ W
= =
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 65: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/65.jpg)
68
T i i LiTransmission Lines
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 66: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/66.jpg)
69
T i i LiTransmission Lines• Zero Sequence Impedance• Zero Sequence Impedance▫ More involved▫ AssumptionsAssumptions Zero sequence current divides equally between
conductorsC d ll l d Conductors are parallel to ground
Earth is a solid with a plane surface, infinite in extent, and of uniform conductivity, y
▫ None of the assumptions are true▫ We get acceptable error with these assumptions
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
▫ Line design affects calculation techniques
![Page 67: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/67.jpg)
70
T i i Li Z STransmission Line Zero Sequence
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 68: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/68.jpg)
71
T i i Li Z STransmission Line Zero Sequence
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 69: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/69.jpg)
72
T i i Li Z STransmission Line Zero Sequence
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 70: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/70.jpg)
73
T i i Li Z STransmission Line Zero Sequence
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 71: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/71.jpg)
74
T i i Li Z STransmission Line Zero Sequence
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 72: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/72.jpg)
75
Wh W W ’ CWhat We Won’t Cover• What We Won’t CoverWhat We Won t Cover▫ Capacitive Reactance of Transmission Lines▫ Mutual Impedance of Transmission Lines
C bl M d lli (l k i t bl t t ▫ Cable Modelling (look up in table or contact manufacturer)
• So What’s the General Idea?▫ Produce a positive, negative, and zero sequence model
for your components.▫ Simple model for equipment is a series impedanceSimple model for equipment is a series impedance▫ Connect the models according to system topology▫ Analyze imbalances by connecting systems
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 73: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/73.jpg)
![Page 74: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/74.jpg)
77
F lFaults• DefinitionDefinition▫ A fault is any condition in a system considered
abnormal▫ Basic Typesyp Short-Circuit Faults Open-Circuit Faults Combined Faults
• Shunt Faults▫ Three-Phase (3Ph)▫ Phase-To-Phase (LL)( )▫ Phase-To-Phase-To-Ground (LLG)▫ Single-Line-To-Ground (SLG)
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 75: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/75.jpg)
78
F lFaults• Series Faults• Series Faults▫ Open phase▫ Open neutralOpen neutral▫ Two open phases▫ Impedance in a phase
• Combination Faults▫ See connection diagrams
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 76: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/76.jpg)
79
Sequence Connections – Shunt Sequence Connections Shunt Faults
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 77: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/77.jpg)
80
Sequence Connections – Shunt Sequence Connections Shunt Faults
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 78: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/78.jpg)
81
Sequence Connections – Series Sequence Connections Series Faults
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 79: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/79.jpg)
82
Sequence Connections – Series Sequence Connections Series Faults
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 80: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/80.jpg)
83
Sequence Connections –Sequence Connections Combination Faults
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 81: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/81.jpg)
84
E l 1 S PExample 1 – System Parameters
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 82: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/82.jpg)
85
E l 1 S PExample 1 – System Parameters
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 83: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/83.jpg)
86
E l 1 S PExample 1 – System Parameters
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 84: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/84.jpg)
87
Example 2 – Delta Wye Transformer Example 2 Delta Wye Transformer 3-Ph Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 85: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/85.jpg)
88
Example 2 – Delta Wye Transformer Example 2 Delta Wye Transformer 3-Ph Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 86: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/86.jpg)
89
Example 3 – Delta Wye Transformer Example 3 Delta Wye Transformer SLG Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 87: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/87.jpg)
90
Example 3 – Delta Wye Transformer Example 3 Delta Wye Transformer SLG Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 88: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/88.jpg)
91
Example 4 – Delta Wye Transformer Example 4 Delta Wye Transformer LL Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 89: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/89.jpg)
92
Example 4 – Delta Wye Transformer Example 4 Delta Wye Transformer LL Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 90: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/90.jpg)
93
D l W SDelta-Wye Summary• 3-Phase Fault3▫ Behaves as expected, same
current both sides• LL Fault▫ Must coordinate full fault ▫ Must coordinate full fault
current on primary with 0.866 factor on secondary (i.e. coordination interval)
SLG F lt• SLG Fault▫ For solidly grounded
system, shift damage curve by 0.577 to protect against y 577 p gfull fault current on secondary
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 91: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/91.jpg)
94
E l 5 R i EffExample 5 – Resistor Effect
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 92: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/92.jpg)
95
E l 6 O Ph F lExample 6 – Open Phase Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 93: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/93.jpg)
96
E l 6 O Ph F lExample 6 – Open Phase Fault
POWER SYSTEM CALCULATIONS—PART II IEEE IAS 2010 - Copyright: IEEE
![Page 94: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/94.jpg)
![Page 95: Power System Calculations—Part II](https://reader030.vdocuments.mx/reader030/viewer/2022012510/6188750902c9e2352c07b63d/html5/thumbnails/95.jpg)