power quality seminar report

40
Power Quality Seminar Report ‘03 1. INTRODUCTION Since last 25 years there has been an increase in the use of solid state electronic technology. This new, highly efficient, electronic technology provides product quality with increased productivity. Today, we are able to produce products at costs less than in the years passed, with the introduction of automation by using the solid state electronic technology .This new technology requires clear electric power. The conventional speed control systems are being replaced by modern power electronic systems, bringing a verity of advantages to the users. Classic examples are DC $ AC drives, UPS, soft stators, etc. Since the thrusters converter technology is rapidly gaining in the modern industrial plants, the power supply systems are contaminated as the ideal sinusoidal current and voltage waveforms are getting distorted. This is in turn is 1

Upload: abhishek-dasari

Post on 15-Oct-2014

321 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Power Quality Seminar Report

Power Quality Seminar Report ‘03

1. INTRODUCTION

Since last 25 years there has been an increase in the use of solid state electronic

technology. This new, highly efficient, electronic technology provides product quality

with increased productivity. Today, we are able to produce products at costs less than in

the years passed, with the introduction of automation by using the solid state electronic

technology .This new technology requires clear electric power.

The conventional speed control systems are being replaced by modern power

electronic systems, bringing a verity of advantages to the users. Classic examples are

DC $ AC drives, UPS, soft stators, etc. Since the thrusters converter technology is

rapidly gaining in the modern industrial plants, the power supply systems are

contaminated as the ideal sinusoidal current and voltage waveforms are getting

distorted. This is in turn is affecting the performance of the equipment in the electrical

network.

1

Page 2: Power Quality Seminar Report

Power Quality Seminar Report ‘03

2. WHAT IS POWER QUALITY?

Adequate to superior power quality is essential for the smooth functioning of

critical industrial processes. As industries expand, utilities become more interconnected

and usage of electronically controlled equipment increases, power quality is

jeopardized. Most large industrial and commercial sites are served by overhead lines

with feeders that are subject to unpredictable and sporadic events, e.g. lightning and

contact with tree limbs. Most distribution circuits have resoling devices that clear

temporary faults through a timed series of trip and close operations.

This minimizes the possibility of long-term outages but leads to a number of

minor power disturbances. These typically occur several times a month. Many electric

utilities have increased the voltage at which they distribute power. This allows a single

circuit to serve more customers or deliver higher loads, and reduces energy losses in the

system. But it often means the overhead distribution circuit is longer, with more

exposure to disturbances. And disturbances travel farther because of lower system

impedances associated with higher voltage circuits. Sophisticated new systems are

providing vastly increased efficiency and control in critical processes. But with their

high sensitivity even to brief variations in electric power quality, today's computer-

driven devices fail when power is disturbed for even a few milliseconds.

2

Page 3: Power Quality Seminar Report

Power Quality Seminar Report ‘03

3. HARMONICS-BASIC CONCEPTS

A pure sinusoidal voltage is conceptual quantity produced by an ideal AC

generator build with finely distributed stator and field windings that operate in a

uniform magnetic field. Since neither the winding distribution nor the magnetic field is

uniform in a working AC machine, voltage waveform distortion is created, and the

voltage time relation-ship deviates from the pure sine function. The distortion at the

point of generation is very small (about 1%to 2%), but nonetheless it exists.

Because this is a deviation from a pure sine wave, the deviation is in the form of

a periodic function and by definition, the voltage distortion contains harmonics. When a

sinusoidal voltage is applied to a certain type of load, the current drawn by the load is

proportional to the voltage and impedance and follows the envelope of the voltage wave

form .These loads are referred to as linear loads (loads where the voltage and current

follow one another without any distortion to their pure sine waves).examples of

nonlinear loads are resistive heaters, incandescent lamps and constant speed induction

and synchronous motors.

In contrast some loads cause the current to vary disproportionately with the

voltage during each half cycle. These loads are classified as nonlinear loads and the

current and voltage have waveforms that are non sinusoidal containing distortions

where by 50 Hz waveform has numerous additional waveforms superimposed upon it

3

Page 4: Power Quality Seminar Report

Power Quality Seminar Report ‘03

creating multiple frequencies within the normal 50 Hz sine wave .The multiple

frequencies are harmonics of the fundamental frequency.

Normally current distortion produce voltage distortions .However when there is

a stiff sinusoidal voltage source there is a low impedance path from the power source

which has sufficient capacity so that loads placed upon it will not affect the voltage one

need not be concerned about current distortions producing voltage distortions Examples

of non linear loads are battery chargers, electronic ballasts; variable frequency drives,

and switched mode power supplies.

As nonlinear currents flows through a facility's electrical system and the

distribution - transmission lines, additional voltage distortions are produced due to the

impedance associated with the electrical network. Thus as electrical power is generated,

distributed and utilized, voltage and current waveforms distortions are produced.

Power systems designed to function at the fundamental frequency which is 50

Hz in India are prone to unsatisfactory operation and at times failure when subjected to

voltages and currents that contains substantial harmonic frequency elements. Very often

the operation of electrical equipment may seem normal but under a certain combination

of conditions the impact of harmonics is enhanced with damaging results.

4

Page 5: Power Quality Seminar Report

Power Quality Seminar Report ‘03

4. THE AFFECTS

The actual problems of any building/industry will vary depending on the type

and number of installed harmonics producing loads. Most electrical network can

withstand nonlinear loads of up to 15% of the total electrical system capacity without

concern but when the nonlinear loads exceed 15% some non expected negative

consequences can be expected. .for electrical networks , they have on linear loading of

more than 25% particular problems can be apparent.

The following is a short summery of most problems caused by harmonics:

Blinking of incandescent lights-transformer saturation

Capacitor failure-harmonics resonance

Circuit breaker tripping-inductive heating and over loading

Computer malfunctioning-voltage distortion

Transformer failure-inducting

Motor failure-inductive heating

Fuses blowing for no apparent reason-inductive heating & over load

Electronic component shut down- voltage distortion

Flickering of florescent lights-transformer saturation

The heating effects of harmonic currents can cause destruction of equipment,

conductors, and fires. The results can be unpredictable legal and financial ramifications

5

Page 6: Power Quality Seminar Report

Power Quality Seminar Report ‘03

apart from safety risks. Voltage distortions can lead to over heating of equipment

failure, expensive down time and maintenance difficulties. Harmonic currents and

voltage distortions are becoming the most severe and complex electrical challenge for

the electrical industry .The problems associated with nonlinear loads were once limited

to isolated devices and computer rooms, but now the problem can appear through the

entire network and utility system

The point at which the harmonic limits are applied is called the point of

common coupling (PCC). When the input transformer is the point of measurement then

the PCC refers to this point where the facility electrical system is common to the

facility of additional consumers. If there is a distortion present on the electrical power

system at this point it may be experienced by the neigh boring facilities as well. So we

need to avoid this situation

6

Page 7: Power Quality Seminar Report

Power Quality Seminar Report ‘03

5. SOLUTION

Users of variable frequency drives often have strict demands placed on them to

mitigate harmonic distortion caused by the nonlinear loads. Many choices are available

to them including line reactors, harmonic traps, 12 pulse rectifier, 18 pulse rectifiers,

and low pass filters.

5.1 LINE REACTORS

The input harmonic current distortion can be reduced by simple addition of

input line reactance. The inductive reactance of an input line reactor allows 50 Hz or 60

Hz currents to pass easily but presents considerably higher impedance to all other

harmonic frequencies. Harmonic currents are thus attenuated by the reactance offered

by the line reactor.

These reactors are also used to solve the problems in variable frequency drive

installations.Eg: harmonic attenuation , drive tripping .The line reactors are always used

in the line side or input of the variable frequency drives. Thus they are called the line

reactors. The line reactors cannot be used at the output of the variable frequency drives

Because the reactors are over heated due to the harmonic content of the output

waveform of the VFD Harmonic compensated reactors can be used on the either side of

the variable frequency drives .Due to the introduction of the Harmonic compensated

reactors the following problems are eliminated: motor noise, low efficiency of the

motors, temperature rise in motors and variable frequency drives short circuit problem.

7

Page 8: Power Quality Seminar Report

Power Quality Seminar Report ‘03

5.2 HARMONIC FILTERS

In some cases, reactors alone will not be capable of reducing the harmonic

current distortion to the desired levels. In these cases, a more sophisticated filter will be

required. The common choices include shunt connected, tuned harmonic filters

(harmonic traps) and series connected low pass filters (broad band suppressors). They

consist of a capacitor and an inductor which are tuned to a single harmonic frequency.

Since they offer very low impedance to that frequency, the specific (tuned) harmonic

current is supplied to the drive by the filter rather than from the power source. If tuned

harmonic filters (traps) are selected as the mitigation technique, then multiple tuned

filters are needed to meet the distortion limits which are imposed.

When employing tuned harmonic filters, we need to take special precautions to

prevent interference between the filter and the power system. A harmonic trap presents

a low impedance path to a specific harmonic frequency regardless of its source. The

trap cannot discern harmonics from one load versus another. Therefore, the trap tries to

absorb that entire harmonic which may be present from all combined sources (non-

linear loads) on the system. This can lead to premature filter failure.

Since harmonic trap type filters are connected in shunt with the power system,

they cause a shift in the power system natural resonant frequency. If the new frequency

is near any harmonic frequencies, then it is possible to experience an adverse resonant

condition which can result in amplification of harmonics and capacitor or inductor

failures. Whenever using harmonic trap type filters, one must always perform a

complete system analysis. You must determine the total harmonics which will be

8

Page 9: Power Quality Seminar Report

Power Quality Seminar Report ‘03

absorbed by the filter, the present power system resonant frequency, and the expected

system resonant frequency after the filter (trap) is installed. Field tuning of this filter

may be required if adverse conditions are experienced.

5.3 12 PULSE RECTIFIERS

12 Pulse drives are frequently specified by the engineers for heating, ventilating

and air conditioning applications because their ability to reduce harmonic current

distortion. In the mid 1960s when power semiconductors were only available in limited

ratings, twelve-pulse drives provided a simpler and more cost effective approach to

achieving higher current ratings than direct paralleling of power semiconductors.

A typical diagram of a large twelve-pulse drive appears in figure the drive's

input circuit consists of two six-pulse rectifiers, displaced by 30 electrical degrees,

operating in parallel. The 30-degree phase shift is obtained by using a phase shifting

transformer. The circuit in figure simply uses an isolation transformer with a delta

primary, a delta connected secondary, and a second wye connected secondary to obtain

the necessary phase shift. Because the instantaneous outputs of each rectifier are not

equal, an inter phase reactor is used to support the difference in instantaneous rectifier

output voltages and permit each rectifier to operate independently. The primary current

in the transformer is the sum of each six-pulse rectifier or a twelve-pulse wave form.

Theoretical input current harmonics for rectifier circuits are a function of pulse

number and can be expressed as:

h = (np + 1) where n= 1, 2, 3, and p = pulse number

9

Page 10: Power Quality Seminar Report

Power Quality Seminar Report ‘03

For a six-pulse rectifier, the input current will have harmonic components at the

following multiples of the fundamental frequency.

5, 7, 11, 13, 17, 19, 23, 25, 29, 31, etc.

For the twelve-pulse system shown in figure 1, the input current will have

theoretical harmonic components at the following multiples of the fundamental

frequency:

11, 13, 23, 25, 35, 37, etc.

Note that the 5th and 7th harmonics are absent in the twelve-pulse system. Since

the magnitude of each harmonic is proportional to the reciprocal of the harmonic

number, the twelve-pulse system has a lower theoretical harmonic current distortion.

12 PULSE RECTIFIERS

10

Page 11: Power Quality Seminar Report

Power Quality Seminar Report ‘03

Figure shows the actual measurement of input current harmonic distortion for 12

pulse rectifier supplied from a balanced 3 phase voltage source while operating at full

load conditions. For test purpose transformer has delta primary and delta,wye secondary

windings. To obtain the best results, the bridge rectifier is connected in series so equal

dc windings. To obtain the best results, the bridge rectifier is connected in series so

equal dc

The data shows when the current through both sets of the rectifiers is equal,

harmonics can be as low as 10% to 12% total harmonic current distortion, at full load.

Current sharing reactors will help parallel connected bridge rectifiers to share current

equally. Even with balanced current harmonic current distortion can increase

appreciably at light loaded conditions. Even with perfectly balanced line voltages, the

resultant % total harmonic current distortion increases as the load increases. As the load

reduced, that is 23% total harmonic current distortion at 20% load.

11

Page 12: Power Quality Seminar Report

Power Quality Seminar Report ‘03

5.4 18 PULSE RECTIFIER

A typical diagram of a series connected eighteen pulse drive constructed from a

standard six-pulse drive, two external rectifiers and a conventional 18 pulse isolation

transformer appears in figure 1. The drive has terminals available to connect a DC link

choke. These terminals are used to connect the two external rectifiers in series with the

drives internal rectifier. The eighteen pulse transformer is designed to provide one third

the normal input voltage to each of the three rectifiers at a 20 degree phase

displacement from each other. The 20-degree phase shift is obtained by phase shifting

the transformers secondary windings. The circuit in figure 1 simply uses an isolation

transformer with a delta primary, and three delta connected secondary windings, one

shifted + 20 degrees, one shifted -20 degrees and one in phase with the primary.

The primary current in the transformer is the sum of each six-pulse rectifier or

an eighteen-pulse wave form.

Theoretical input current harmonics for rectifier circuits are a function of pulse

number and can be expressed as:

h = (np ± 1) where n= 1, 2, 3,... and p = pulse number

For a six-pulse rectifier, the input current will have harmonic components at the

following multiples of the fundamental frequency.

5, 7, 11, 13, 17, 19, 23, 25, 29, 31, 35, 37, 41, 43, 47, 49, 53, 55, etc.

For the eighteen-pulse system shown in figure 1, the input current will have

theoretical harmonic components at the following multiples of the fundamental

frequency:

12

Page 13: Power Quality Seminar Report

Power Quality Seminar Report ‘03

17, 19, 35, 37, 53, 55, etc.

Note that the 5th and 7th, 11th and 13th harmonics are absent in the theoretical

eighteen-pulse system. Since the magnitude of each harmonic is proportional to the

reciprocal of the harmonic number, the eighteen-pulse system has a lower theoretical

harmonic current distortion.

To determine how an eighteen-pulse drive system operates under unbalanced

line voltage conditions, we constructed a 30 HP eighteen-pulse drive from a

conventional isolation transformer and standard six-pulse drive using the series bridge

connection shown in figure 1. An auto transformer could have been used in place of the

isolation transformer. The auto transformer costs less and requires less mounting space,

but the isolation transformer was selected because it provides better performance and is

readily available as a modified standard transformer.

Care was taken in the physical construction of the transformer to balance the

leakage reactance and output voltage of the three secondary windings. The system was

tested with line voltage unbalance ranging from 0% to 3% and with loads ranging from

5% to 100%. The input total harmonic current distortion, THID, is shown in figure 3.

THID varied from 7.4% at full load with balanced line voltages to 59% at 30% load

with a 3% unbalance. The data show that the harmonic performance of eighteen-pulse

drives degrades rapidly with increasing line voltage unbalance and decreasing load.

Simply focusing on harmonic performance under the best operating conditions,

perfectly balanced line voltages and full load, is not a useful indicator of performance

under practical operating conditions. In heating, ventilating and air conditioning

13

Page 14: Power Quality Seminar Report

Power Quality Seminar Report ‘03

applications where drives will operate for long periods of time at 30% to 60% load

eighteen pulse drives to not meet expectations.

18 PULSE RECTIFIER

To determine how an eighteen-pulse drive system operates under unbalanced line

voltage conditions, we constructed a 30 HP eighteen-pulse drive from a conventional

isolation transformer and standard six-pulse drive using the series bridge connection

shown in figure 1. An auto transformer could have been used in place of the isolation

transformer. The auto transformer costs less and requires less mounting space, but the

isolation transformer was selected because it provides better performance and is readily

available as a modified standard transformer. Care was taken in the physical

construction of the transformer to balance the leakage reactance and output voltage of

the three secondary windings. The system was tested with line voltage unbalance

ranging from 0% to 3% and with loads ranging from 5% to 100%. The input total

harmonic current distortion, THID, is shown in figure 3. THID varied from 7.4% at full

load with balanced line voltages to 59% at 30% load with a 3% unbalance. The data

14

Page 15: Power Quality Seminar Report

Power Quality Seminar Report ‘03

show that the harmonic performance of eighteen-pulse drives degrades rapidly with

increasing line voltage unbalance and decreasing load. Simply focusing on harmonic

performance under the best operating conditions, perfectly balanced line voltages and

full load, is not a useful indicator of performance under practical operating conditions.

In heating, ventilating and air conditioning applications where drives will operate for

long periods of time at 30% to 60% load eighteen pulse drives to not meet expectations.

Figure 3

Obviously, any unbalance in the eighteen-pulse transformer's leakage reactance

and output voltage will degrade performance. Unfortunately perfect transformers can

not be built. Output voltage depends on turns ratios which are limited to plus or minus

one turn. As a result the output voltage of the three secondary windings cannot be

perfectly balanced. Leakage reactance is a function of coil position and volume. Clever

Mechanical design of the transformer windings will help to minimize the differences in

15

Page 16: Power Quality Seminar Report

Power Quality Seminar Report ‘03

leakage reactance between the three groups of secondary windings but perfect balance

can not be achieved. Data for the transformer used in this test appears in Tables 1 and 2.

Transformer Design

Secondary

Winding Phase Shift

Degrees

Leakage

Reactance

%

Nominal Output Voltage

Based on Turns Ratios

Volts

0 3.67 160.00

-20 4.73 160.50

+20 5.33 160.50

Table 1

Transformer Full Load Data

Secondary

Winding

Phase Shift

Degrees

Secondary Phase Voltage

At Full Load

Unbalance

Per

Secondary

Group

%

Unbalance

Across

Secondary

Groups

%

Volts

A B C Average

0 154.3 154.4 154.1 154.26 0.10  

-20 157.9 157.0 157.6 157.50 0.32  

+20 156.6 155.4 156.9 156.30 0.57  

16

Page 17: Power Quality Seminar Report

Power Quality Seminar Report ‘03

Average 156.02   1.12

Table 2

The addition of 5% line reactors at the input to each of the three rectifiers results

in a significant improvement in the operation Drives are applied in heating, ventilating,

and air conditioning applications because loads are variable and users demand energy

efficiency and comfort. Varying loads result in load unbalances within building power

distribution systems which add to the utility line voltage unbalance at the point of

common coupling. Harmonic mitigation techniques which are not effective with line

voltage unbalances of 1% to 3% at the point of utilization will not as a practical matter

achieve useful results. The data in this report show that a standard six-pulse drive fed

from a low pass Matrix Filter provides superior harmonic performance to an eighteen-

pulse drive in applications with variable loads and line voltage unbalances ranging from

0% to 3%.

5.5 LOW PASS HARMONIC SUPPRESSORS

Low pass harmonic filters, also referred to as broad band harmonic suppressors,

offer a non-invasive approach to harmonic mitigation. Rather than being tuned for a

specific harmonic, they filter all harmonic frequencies, including the third harmonic.

They are connected in series with the non-linear load with a large series connected

17

Page 18: Power Quality Seminar Report

Power Quality Seminar Report ‘03

impedance, therefore they don’t create system resonance problems. No field tuning is

required with the low pass filter.

Due to the presence of the large series impedance, it is extremely difficult for

harmonics to enter the filter / drive from the power source. Rather they are supplied to

the drive via the filter capacitor. For this reason, it is very easy to predict the distortion

levels which will be achieved and to guarantee the results.

A low pass (broad band) harmonic filter can easily offer guaranteed harmonic

current levels, right at the drive / filter input, as low as 8% to 12% THID. (To achieve

8% maximum current distortion one can typically select the broad band harmonic

suppressor based on a HP / KW rating which is 25-30% larger than the total drive load

to be supplied). In most cases, this results in less than 5% THID at the facility input

transformer and meets most international standards.

Fig. 6 Actual input current waveform for VFD fitted with Broad Band

Harmonic Suppressor.

The low pass filter not only offers guaranteed results, it is also more economical

than 12 or 18 pulse rectifier systems, active filters or in many cases even harmonic

traps. They are intended for use with 6-pulse drives having a six diode input rectifier in

variable torque applications. This typically means fan and pump applications. For the

18

Page 19: Power Quality Seminar Report

Power Quality Seminar Report ‘03

sake of economy, a single Broad Band Harmonic Suppressor may be used to supply

several drives (VFDs). When operating at reduced load, the THID at the filter input will

be even lower than the guaranteed full load values.

6. BENEFITS

MOTOR TEMPERATURE REDUCTION

Motors operated on a VFD tend to run warmer than when they are operated on

pure 60hz, such as in an across-the-line stator application. The reason is that the output

waveform of the VFD is not pure 60hz,, but rather it contains harmonics which are

currents flowing at higher frequencies. The higher frequencies cause additional watts

loss and heat to be dissipated by the iron of the motor, while the higher currents cause

additional watts loss and heat to be dissipated by the copper windings of the motor.

Typically the larger horsepower motors (lower inductance motors) will experience the

greatest heating when operated on a VFD.

Reactors installed on the output of a VFD will reduce the motor operating

temperature by actually reducing the harmonic content in the output waveform. A five

percent impedance, harmonic compensated reactor will typically reduce the motor

temperature by 20 degrees Celsius or more. If we consider that the typical motor

insulation system has a "Ten Degree C Half Life" (Continual operation at 10 degrees C

above rated temperature results in one half expected motor life), then we can see that

motor life in VFD applications can easily be doubled. Harmonic compensated reactors

19

Page 20: Power Quality Seminar Report

Power Quality Seminar Report ‘03

are actually designed for the harmonic currents and frequencies whereas the motor is

not.

MOTOR NOISE

Because the carrier frequency and harmonic spectrum of many Pulse Width

Modulated (PWM) drives is in the human audible range, we can actually hear the

higher frequencies in motors which are being operated by these drives. A five percent

impedance harmonic compensated reactor will virtually eliminate the higher order

harmonics (11th & up) and will substantially reduce the lower order harmonics (5th &

7th). By reducing these harmonics, the presence of higher frequencies is diminished and

thus the audible noise is reduced. Depending on motor size, load, speed, and

construction the audible noise can typically be reduced from 3 - 6 dB when a five

percent impedance harmonic compensated reactor is installed on the output of a PWM

drive. Because we humans hear logarithmically, every 3dB cuts the noise in half to our

ears. This means the motor is quieter and the remaining noise will not travel as far.

MOTOR EFFICIENCY

Because harmonic currents and frequencies cause additional watts loss in both

the copper windings and the iron of a motor, the actual mechanical ability of the motor

is reduced. These watts are expended as heat instead of as mechanical power. When a

harmonic compensated reactor is added to the VFD output, harmonics are reduced,

causing motor watts loss to be reduced. The motor is able to deliver more power to the

load at greater efficiency. Utility tests conducted on VFD's with and without output

20

Page 21: Power Quality Seminar Report

Power Quality Seminar Report ‘03

reactors have documented efficiency increases of as much as eight percent (at 75%

load) when the harmonic compensated reactors were used. Even greater efficiency

improvements are realized as the load is increased.

SHORT CIRCUIT PROTECTION

When a short circuit is experienced at the motor, very often VFD transistors are

damaged. Although VFD's typically have over correct protection built-in, the short

circuit current can be very severe and its rise time can be so rapid that damage can

occur before the drive circuitry can properly react. A harmonic compensated reactor

(3% impedance is typically sufficient) will provide current limiting to safer values, and

will also slow down the short circuit current rise time. The drive is allowed more time

to react and to safely shut the system down. You still have to repair the motor but you

save the drive transistors.

The above methods solve other problems on the load side of VFD's in

specialized applications also. Some of these include: Motor protection in IGBT drive

installations with long lead lengths between the drive and motor, Drive tripping when a

second motor is switched onto the drive output while another motor is already running,

and Drive tripping due to current surges from either a rapid increase or decrease in the

load.

21

Page 22: Power Quality Seminar Report

Power Quality Seminar Report ‘03

7. CONCLUSION

VFD users have many choices when it comes to harmonic filtering. Of course

they may do nothing, or they may choose to employ one of the many techniques of

filtering available. Each filtering technique offers specific benefits and has a different

cost associated with it. Some may have the potential to interfere with the power system

while others will not.

For best overall results when using reactors or harmonic filters, be sure to install

them as close as possible to the non-linear loads which they are filtering. When you

minimize harmonics directly at their source you will be cleaning up the internal facility

mains wiring. This will also reduce the burden on upstream electrical equipment such as

circuit breakers, fuses, disconnect switches, conductors and transformers. The proper

application of harmonic filtering techniques can extend equipment life and will often

improve equipment reliability and facility productivity.

22

Page 23: Power Quality Seminar Report

Power Quality Seminar Report ‘03

8. REFERENCES

INDUSTRIAL REFERENCE MAY 2003 PAGE 178

WWW.POWERQUALITY.COM

WWW.ECONOMICSOULTIONSTOMEETHARMONICDISTORTION.COM

WWW.POWERQUALITYUSINGREACTORS.COM

23

Page 24: Power Quality Seminar Report

Power Quality Seminar Report ‘03

ABSTRACT

Power quality is essential for smooth functioning of industrial process. As

industries expand, utilities become more interconnected and usage of electrically

equipment increases, power quality is jeopardized. The quality of power in the power

system is severely affected by the presence of harmonics. This harmonics adversely

effects the power system performance. Some of the effects are over heating of metal

parts, noise in motors, low efficiency in motors etc. The effects produced by the

harmonics are reduced by adopting some corrective measures.

24

Page 25: Power Quality Seminar Report

Power Quality Seminar Report ‘03

CONTENTS

1. INTRODUCTION 1

2. WHAT IS POWER QUALITY? 2

3. HARMONICS BASIC CONCEPT 3

4. THE AFFECTS 5

5. SOLUTION 7

5.1. LINE REACTORS 7

5.2. HARMONIC TRAPS 8

5.3. 12 PULSE RECTIFIER 9

5.4.18 PULSE RECTIFIER 12

5.5. LOW PASS SUPPRESSORS 17

6. BENEFITS 19

7. CONCLUSION 22

8. REFERENCES 23

25

Page 26: Power Quality Seminar Report

Power Quality Seminar Report ‘03

ACKNOWLEDGEMENT

I express my sincere gratitude to Dr.Nambissan, Prof. & Head,

Department of Electrical and Electronics Engineering, MES College of

Engineering, Kuttippuram, for his cooperation and encouragement.

I would also like to thank my seminar guide Mrs. Nafeesa K.

(Lecturer, Department of EEE), Asst. Prof. Gylson Thomas. (Staff in-charge,

Department of EEE) for their invaluable advice and wholehearted cooperation

without which this seminar would not have seen the light of day.

Gracious gratitude to all the faculty of the department of EEE &

friends for their valuable advice and encouragement.

26