Page 1: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

Water and Wastewater Engineering Department

PPoottaabbllee WWaatteerr CCoonnssttrruuccttiioonn DDeettaaiillss

Page 2: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

WATER MAIN, PROPOSED

PLUG

BLOW-OFF ASSEMBLY

GATE VALVE & BOX

BUTTERFLY VALVE

WM

R

ARV

DC

RP

REDUCED PRESSURE ZONE BFP

PRESSURE REGULATOR

AIR RELEASE VALVE

REDUCER FITTING

DOUBLE CHECK BFP

POST INDICATOR VALVE

WM WATER MAIN, EXISTING

WM

WM

WM

WM

WM

WM

WM

WM

WM

WM CAP

SYMBOLS

Page: W-1.0

W-1.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

4/24/06

Page 3: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

FITTING

FIRE HYDRANT W/ THRUST BLOCK

FIRE HYDRANT ASSEMBLY

GANG WATER METER ASSEMBLY

DUAL SERVICE WATER METER

POTABLE WATER METER

TXELECTRIC TRANSFORMER

SYMBOLS

Page: W-1.1

W-1.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/9/2012

Page 4: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1. THESE PIPES ARE ADEQUATE FOR THE RATED WORKING PRESSURE PLUS A SURGE

ALLOWANCE OF 100 PSI. FIGURE INCLUDES 2.0 SAFETY FACTOR TIMES THE

SUM OF WORKING PRESSURE AND 100 PSI SURGE ALLOWANCE OF D.I.P.

2. AN ALLOWANCE FOR SINGLE H-20 TRUCK WITH 1.5 IMPACT FACTOR IS INCLUDED

FOR ALL SIZES AND ALL DEPTHS OF COVER.

3. MINIMUM ALLOWABLE DEPTH OF COVER IS 2.5 FEET (*NOTE: MAXIMUM DEPTH OF

COVER IS 3 FEET, PER GRU STANDARDS).

NOTES:

PIPE SIZE

(IN)

24

20

18

16

12

6

8

4

NOMINAL

THICKNESS

(IN)

PRESSURE

CLASS

(PSI)

300

250

350

300

200

350

250

350

250

300

350

0.36

0.38

0.33

0.40

0.43

0.37

0.34

0.34

0.36

0.33

0.31

250

300

350

350

350

350

0.28

0.32

0.30

0.25

0.25

0.25

GENERAL DATA - DUCTILE IRON PIPE

Page: W-1.2

W-1.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/22/2016

Page 5: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

INITIAL

BACKFILL

HAUNCHING

BEDDING

FOUNDATION

EMBEDMENT

PIPE

A FOUNDATION MAY BE REQUIRED IN VERY POOR SOIL (CLASS IV & V MATERIAL) CONDITIONS.

BEDDING IS REQUIRED PRIMARILY TO BRING THE TRENCH BOTTOM UP TO GRADE. BEDDING

MATERIALS SHALL PROVIDE A UNIFORM AND ADEQUATE LONGITUDINAL SUPPORT UNDER THE

PIPE. IN DRY SOIL CONDITIONS CLASS II OR CLASS III MATERIAL SHALL BE HAND PLACED

4" TO 6", LIGHTLY COMPACTED, UNIFORM AND NOT FINER THAN THE FOUNDATION MATERIAL.

IN WET SOIL CONDITIONS CLASS I, CLASS II OR CLASS III SHALL BE HAND PLACED,

4" TO 6", UNIFORM AND NOT FINER THAN THE FOUNDATION MATERIAL. WHEN UTILIZING

CLASS I MATERIAL, SUFFICIENT AMOUNTS OF CLASS II OR CLASS III MATERIAL SHALL BE

ADDED TO FILL ALL VOIDS CREATED BY THE CLASS I MATERIAL.

HAUNCHING MATERIAL SHALL BE HAND PLACED TO THE SPRINGLINE OF THE PIPE. CLASS II OR

CLASS III MATERIAL SHALL BE CONSOLIDATED UNDER THE PIPE AND HAND TAMPED TO

PROVIDE ADEQUATE SIDE SUPPORT.

INITIAL BACKFILL MATERIAL SHALL BE CLASS II OR CLASS III. IT SHALL BE HAND PLACED

TO 12" ABOVE THE TOP OF THE PIPE. THE SOIL SHALL BE CONSOLIDATED BY HAND

TAMPING OR WALKING THE SOIL IN PLACE.

FINAL BACKFILL MATERIAL MAY BE MACHINE PLACED. THE MATERIAL SHALL BE CLASS II

OR CLASS III MATERIAL. CLASS IV MATERIAL MAY BE INSTALLED OUTSIDE OF THE ROADWAY.

FINAL BACKFILL UNDER ROADWAYS MAY REQUIRE SPECIAL COMPACTION AND DENSITY TESTS.

5.

4.

3.

2.

1.

PIPE BELL WIDTH

5

4

3

2

1

BACKFILL

FINAL

NOTES:

FIELD DETERMINATION WILL BE PROVIDED BY GRU INSPECTOR. TYPICAL FOUNDATION THICKNESS

SHALL BE 12", BUT MAY VARY ACCORDING TO NATURAL MATERIAL.

REFER TO CITY, COUNTY, OR FDOT STANDARDS, AS APPLICABLE.

BACKFILLING REQUIREMENTS

Page: W-2.0

W-2.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/08

Page 6: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

PIPE ZONE TERMINOLOGY

EMBEDMENT MATERIALS

CLASS I: ANGULAR, 1/4" TO 1-1/2", GRADED STONE, INCLUDING A NUMBER OF FILL

MATERIALS THAT HAVE REGIONAL SIGNIFICANCE SUCH AS CORAL, SLAG, CINDERS,

CRUSHED STONE AND CRUSHED SHELLS.

COARSE SANDS AND GRAVELS WITH MAXIMUM PARTICLE SIZE OF 1-1/2",

INCLUDING VARIOUS GRADED SANDS AND GRAVELS CONTAINING SMALL PERCENTAGES

OF FINES, GENERALLY GRANULAR AND NON-COHESIVE, EITHER WET OR DRY. AASHTO

SOIL TYPES A-1 AND A-2 ARE INCLUDED IN THIS CLASS.

FINE SAND AND CLAYEY GRAVELS, INCLUDING FINE SANDS, SAND-CLAY MIXTURES

AND GRAVEL-CLAY MIXTURES. AASHTO SOIL TYPES A-3 AND A-4 ARE INCLUDED IN

THIS CLASS.

SILT, SILTY CLAYS, AND CLAYS, INCLUDING INORGANIC CLAYS AND SILTS OF

MEDIUM TO HIGH PLASTICITY AND LIQUID LIMITS. AASHTO SOIL TYPES A-5, A-6, A-7

AND A-8 ARE INCLUDED IN THIS CLASS. THESE MATERIALS AREA NOT TO BE USED

FOR BEDDING, HAUCHING OR INTIAL BACKFILL.

THIS CLASS INCLUDES THE ORGANIC SOILS, AS WELL AS SOILS CONTAINING FROZEN

EARTH, DEBRIS, ROCKS LARGER THAN 1-1/2" IN DIAMETER AND OTHER

FOREIGN MATERIALS. THESE MATERIALS ARE NOT TO BE USED FOR BEDDING,

HAUNCHING OR INITIAL BACKFILL.

CLASS II:

CLASS III:

CLASS IV:

CLASS V:

INITIAL

BACKFILL

HAUNCHING

BEDDING

MAX. 6"

FOUNDATION

(MAY NOT BE REQUIRED)

MATERIAL

EMBEDMENT

12"

SPRING

LINE OF

PIPE

SOIL CLASSIFICATION

Page: W-2.1

W-2.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/2008

Page 7: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

D

h

H

45° MIN.

UNDISTURBED

SOIL

NOMINAL PIPE

DIAMETER

(INCHES)

DEAD ENDS

11-1/4°

BEND

22-1/2°

BEND

45° BEND 90° BEND

BEARING AREA REQUIRED

(SQ. FT.)

NOTE: TABLE CALCULATED FOR A SOIL BEARING CAPACITY OF 3000 POUNDS PER SQUARE FOOT

AND HYDROSTATIC TEST PRESSURE OF 150 PSI.

NOTES:

1. THE BLOCK HEIGHT (h) SHOULD BE EQUAL TO OR LESS THAN HALF THE DEPTH OF BURY

(H). DO NOT ALLOW (h) TO BE LESS THAN (D) THE DIAMETER OF THE PIPE.

2. BEARING AREA = w x h, WHERE (w) IS THE WIDTH OF THE REACTION BLOCK AGAINST

UNDISTURBED SOIL. DETERMINE THE BEARING AREA FROM THE TABLE ABOVE AND DIVIDE

BY (h), E.G. FOR A 10" PIPE WITH A 45° BEND, THE REQ'D THRUST BLOCK AREA

WOULD BE 4 SQ. FT. (FROM TABLE ABOVE). IF H = 4 FT, THEN h MUST BE BETWTEEN

10 IN. (PIPE DIA.) AND 2 FT. (1/2 H). ASSUME h = 2 FT., THEN:

w = BEARING AREA / h = 4 SQ. FT. / 2 FT. = 2 FT.

2724

36

30

58

41

10

16

20

18

14

12

4

8

6

5

12

19

14

9

7

1

4

2

116

12

8 16

23

1

3

4

3

2

2

1

1

1

2

5

8

6

4

3

1

2

1

3721

31

45 82

57

4

6

10

7

14

11

3

1

2

7

17

26

20

13

10

2

5

3

THRUST BLOCK DESIGN - BEARING AREA

Page: W-2.2

W-2.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/08

Page 8: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

NOMINAL

PIPE

DIAMETER

(IN.)

DEAD ENDS

11-1/4°

BEND

22-1/2°

BEND

45° BEND 90° BEND

4"

6"

8"

10"

12"

14"

16"

18"

20"

24"

30"

36"

27428

172814

120638

78419

54965

41798

35669

5609

20528

14516

9648

2715

5376

33875

23648

15372

10775

8782

6992

1100

4025

2846 *

1892

533

10700

67414

47061

30591

21441

16305

13914

2189

8009

5663

3764

1059

20993

132266

92336

60021

42071

31992

27300

4293

15711

11110

7385

2078

38789

244394

170691

110900

77732

59111

50442

7932

29030

20528

13644

3840

FORCE = THRUST IN POUNDS

AT 150 P.S.I.

IN COMPUTING THE THRUST FORCE TO BE RESISTED BY FORCE BLOCKING THE FORMULA

F = 2PA SIN (0/2) SHALL BE USED FOR DIFFERENT TYPES OF BENDS AND F = PA FOR DEAD

END PIPE.

* EXAMPLE: WITH 10" DIA. D.I.P. (11.1" O.D.) & 11-1/4" BEND.

F = 2 x 150 P.S.I. x (PI x (11.1/2) x SIN(11.25/2) = 2846 LBS.

NOTE: 1. THE SOIL BEARING CAPACITY VALUE MOST COMMONLY USED IN GRU SERVICE AREA

3,000 LB./SQ. FT.

2. THE O.D. OF THE PIPE IS USED IN DETERMINING THE AREA BECAUSE THE PRESSURE

IS DISTRIBUTED TO THE GASKET FOR MECHANICAL AND SLIP JOINTS.

3. MULTIPLY TABLE VALUES BY 0.67 TO DETERMINE THE THRUST AT 100 PSI.

2

THRUST BLOCK DESIGN - THRUST FORCE

Page: W-2.3

W-2.3

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/08

Page 9: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

SAFE RANGE IN POUNDS

PER SQ. FT.

8,000

2,000

4,000

12,000

10,000

4,000

8,000

12,000

20,000

40,000

60,000

200,000

UNDISTURBED SOIL TYPE

-SAND

QUICK SAND, ALLUVIAL SOIL

SAND -

SAND

HARDPAN, CEMENTED SAND & GRAVEL

CLAY

CLAY

CLAY

ROCK

ROCK

ROCK

LODGE ROCK, GRANITE, TRAP ROCK & SIMILAR

-

-

-

-

-

-

-

BEARING CAPACITIES OF UNDISTURBED SOIL

1,000

4,000

2,000

8,000

4,000

8,000

2,000

30,000

8,000

10,000

50,000

50,000

TO

TO

TO

TO

TO

TO

TO

TO

TO

TO

TO

TO

EQUAL TO GOOD MASONARY

EQUAL TO BEST BRICK

EQUAL TO POOR BRICK

ALWAYS DRY

MODERATELY DRY

SOFT

COMPACTED FIRM

CLEAN, DRY, MEDIUM, COMPACT

FINE LOOSE

NOTES:

1. THE SOIL BEARING CAPACITY VALUE MOST COMMONLY USED IN GRU SERVICE AREA IS 3,000 LB./SQ. FT.

THRUST BLOCK DESIGN - SOIL BEARING CAPACITY

Page: W-2.4

W-2.4

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/08

Page 10: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

UNDISTURBED SOIL

ITEM DESCRIPTION

D.I. MJ1

2 2500 PSI MIN. (FDOT CLASS I)

38 MILS THICKNESS (MIN.) or 15 Ib (MIN.)

M A T E R I A L S

4

90°, 45°, 22-1/2°, 11-1/4° BEND

3

2

1

BEARING AREA

4 D.I. or PVC

1. SEE W-2.2 DATA FOR THE BEARING AREA FOR THE CONCRETE REACTION BLOCK.

2. A NON-POROUS MATERIAL SHALL BE PLACED AROUND THE ENTIRE FITTING TO PROTECT

THE BOLTS FROM THE CONCRETE.

3. LOCATING WIRE REQUIRED ON ALL PVC WATER MAINS.

NOTES:

VISQUEEN or FELT

CONCRETE

PIPE

THRUST BLOCK - BEND

Page: W-2.5

W-2.5

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/08

Page 11: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

ITEM DESCRIPTION

D.I., M.J.1

2 2500 PSI

3 8 MILS THICKNESS (MIN.) or 15 Ib (MIN.)

4 D.I. or PVC (DR-18)

M A T E R I A L S

1. SEE W-2.2 FOR BEARING AREA REQUIRED.

NOTES:

TEE

2. A NONPOROUS MATERIAL 8 MILS (MIN.) VISQUEEN OR 15 Ib (MIN.) FELT

5

6

SHOULD BE PLACED BETWEEN THE CONCRETE AND ENTIRE FITTINGS.

VISQUEEN or FELT

5

3

4

6

2

1

3

6

CONCRETE

PIPE

VALVE BOX

2500 PSICONCRETE THRUST BLOCK

4

7 W/ 4 RODS (MIN.) - 3/4" DIA.WING BLOCK

7

GATE, MJ

THRUST BLOCK - TEES

Page: W-2.6

W-2.6

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 12: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

ITEM DESCRIPTION

D.I., M.J.1

2 2500 PSI

3 M.J., E.B.A.A. MEGALUG

4 D.I. or PVC (DR-18)

5 GATE, M.J.

6 8 MILS THICKNESS (MIN.) or 15 Ib (MIN.)

UNDISTURBED

EARTH

UNDISTURBED

EARTH

7 W/ 4 RODS (MIN.) - 3/4" DIA.

5

NOTES:

2. A NONPOROUS MATERIAL 8 MILS (MIN.) VISQUEEN OR 15 Ib (MIN.) FELT

SHOULD BE PLACED BETWEEN THE CONCRETE AND THE ENTIRE FITTING.

2

2

2

6

3

3

6

7

CROSS

CONCRETE

CAP

PIPE

VALVE

VISQUEEN or FELT

WING BLOCK

1. SEE W-2.2 FOR BEARING AREA REQUIRED.

41

5

2

7

THRUST BLOCK - CROSSES

Page: W-2.7

W-2.7

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 13: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

MINIMUM TOTAL LENGTH OF RESTRAINT

FOR BEND

M

I

N

I

M

U

M

T

O

T

A

L

L

E

N

G

T

H

O

F

R

E

S

T

R

A

I

N

T

F

O

R

B

E

N

D

BEND

A

PLUG, CAP, OR VALVE

MIN

IM

UM

T

OT

AL

L

EN

GT

H O

F R

ES

TR

AIN

T

FO

R P

LU

G \ C

AP

A

RESTRAIN "A" (LF)

FITTING

11

1

4

° BEND

22

1

2

° BEND

45°/OFFSET

90° BEND

A=MINIMUM FOOTAGE OF PIPE TO BE RESTRAINED.

1. THIS TABLE IS BASED ON THE RESTRAINT CALCULATION SOFTWARE

PROVIDED FREE OF CHARGE BY EBAA IRON INC. AT http://www.ebaa.com/engineering.htm

AND THE FOLLOWING INPUT VARIABLES:

A. MAXIMUM TEST PRESSURE OF 150 PSI

B. LAYING CONDITION TYPE 3 (SEE DETAILS ON PAGE W-3.0)

C. POOR SOIL CONDITIONS (SOIL TYPE ML)

D. USING D.I.P.

E. 2 FEET OF COVER (NOTE: 2.5 TO 3 FEET OF COVER REQUIRED BY GRU)

F. HORIZONTAL BENDS ONLY - ENGINEER TO SUBMIT

CALCULATIONS FOR VERTICAL RESTRAINTS

G. SAFETY FACTOR = 1.5 TO 1

2. FOR POLYWRAPPED D.I.P., MULTIPLY THE FOOTAGE BY 1.50

3. FOR PVC PIPE, MULTIPLY FOOTAGE BY 1.34

4. RESTRAINED PIPE SHALL BE MANUFACTURED RESTRAINED PIPE,

PUSH-ON RESTRAINTS OR MECHANICAL RESTRAINTS.

5. ANY ADDITIONAL FITTINGS WITHIN THE RESTRAINED SECTION SHALL

BE RESTRAINED ACCORDINGLY.

NOTES:

4" 6" 8" 12" 16" 20" 24" 30" 36"

3 4 5 6 98 10 12 13

5 7 9 12 1715 20 23 26

10 14 18 24 3530 40 47 53

24 33 42 58 8572 97 112 126

42 58 75 104 157131 181 213 243DEAD END

NOTE: THIS TABLES IS FOR DIP ONLY; SEE NOTES BELOW FOR PVC

RESTRAINED JOINT STANDARD

Page: W-2.8

W-2.8

FOR BENDS, PLUGS, AND CAPS

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 14: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

RESTRAIN "A" (LF)

FITTING 4" 6" 8" 12" 16" 20" 24" 30" 36"

90° BEND

DEAD END

45°/OFFSET

4533

57 78

14 19

7857

101 140

24 33

11

1

4

° BEND

22

1

2

° BEND 7 10

4 6

12 16

7 8

13097 114

211176 243

4741 54

169150

286 326

63 71

2320 27

1211 14

31 35

16 18

1805024x12

211

157

24x24

24x16

24x20

104

*

133

72

6x6

146

180

6920x12

24x6

24x8

20x16

20x20

A.T.

A.T.

125

20x6

20x8

16x12

16x16

11

A.T.

89

133

213

225

*

74

174

189

*

75

12x12

16x6

16x8

12x6

12x8

110

A.T.

28

50

15

8x6

8x8

12x4

8x4

38

A.T.

73

A.T.

50

*

149

129

75

102

43

121

*

72

*

TEE "A"

RESTRAIN (LF)

FITTING SIZE

4x4

6x4 14

28

REDUCER

"B"

40

*

30x12

A.T.=RESTRAINT REQUIRED AT TEE ONLY.

*-NOT APPLICABLE

36x24

36x36

36x30

292

217

146

*

100

179

36x6

36x12

36x8

36x20

36x16

30x20

30x24

30x16

30x30

10

54

100

A.T.

A.T.

287

259

223

307

315

126

254

179

77

27

156

*

101

201

238

TEE "A"

30x6

30x8

FITTING SIZE

REDUCER

"B"

RESTRAIN (LF)

A.T.

A.T.

263

272

NOTE: THESE TABLES ARE FOR PVC PIPE ONLY; SEE W-2.8 OR W-2.9 FOR DIP.

PVC RESTRAINED JOINT STANDARD

Page: W-2.8.1

W-2.8.1

FOR BENDS, PLUGS, AND CAPS

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 15: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete
Page 16: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

TYPE 1 *

FLAT-BOTTOM TRENCH. ** LOOSE

BACKFILL.

TYPE 2

FLAT-BOTTOM TRENCH. ** BACKFILL

LIGHTLY CONSOLIDATED TO

CENTERLINE OF PIPE.

TYPE 3

PIPE BEDDED IN 4-INCH MINIMUM

LOOSE SOIL. *** BACKFILL LIGHTLY

CONSOLIDATED TO TOP OF PIPE.

TYPE 4

PIPE BEDDED IN SAND, GRAVEL, OR

CRUSHED STONE TO DEPTH OF 1/8

PIPE DIAMETER, 4-INCH MINIMUM.

BACKFILL COMPACTED TO TOP OF

PIPE (APPROXIMATELY 80% STANDARD

PROCTOR, AASHTO T-99).

TYPE 5

PIPE BEDDED TO ITS CENTERLINE IN

COMPACTED GRANULAR MATERIAL, 4-INCH

MINIMUM UNDER PIPE. COMPACTED GRANULAR

OR SELECT MATERIAL*** TO TOP OF PIPE

(APPROXIMATELY 90% STANDARD PROCTOR,

AASHTO T-99).

NOTES

CONSIDERATION OF THE PIPE-ZONE EMBEDMENT

CONDITIONS INCLUDED IN THIS FIGURE MAY BE

INFLUENCED BY FACTORS OTHER THAN PIPE

STRENGTH. FOR ADDITIONAL INFORMATION ON

PIPE BEDDING AND BACKFILL, SEE ANSI/AWWA C600.

**FLAT BOTTOM IS DEFINED AS UNDISTURBED EARTH

*FOR NOMINAL PIPE SIZES 14-INCH AND LARGER,

CONSIDERATION SHOULD BE GIVEN TO THE USE OF

LAYING CONDITIONS OTHER THAN TYPE 1.

***"LOOSE SOIL" OR "SELECT MATERIAL" IS DEFINED

AS "NATIVE SOIL EXCAVATED FROM THE TRENCH,

FREE OF ROCKS, FOREIGN MATERIAL, AND

FROZEN EARTH".

Page: W-3.0

W-3.0

PIPE LAYING CONDITIONS

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

02/20/08

Page 17: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1. PVC PLASTIC PIPE SHALL REQUIRE AN INSULATED COPPER WIRE TAPED EVERY 10 FEET

ON THE BOTTOM OF THE PIPE AND WRAPPED AROUND EACH FIRE HYDRANT AT FINAL

GRADE. THE WIRE SHALL BE CONTINUOUS AND ALL SPLICES REQUIRE

2. DEPTH OF PIPE MAY BE FIELD ADJUSTED TO MEET SPECIAL CONDITIONS AS DETERMINED

BY GRU ENGINEER OR INSPECTOR. PIPE INSTALLED WITH LESS THAN 30" OR GREATER

NOTES:

1 WATER MAIN PIPE

ITEM DESCRIPTION

48" MAX.

48" MAX.

PIPE OD+12" MIN.

12"

30" MIN.

36" MAX.

2

BELL HOLE

PROPER BACKFILL MATERIAL

FINAL GRADE

FINAL GRADE

36" MAX.

30" MIN.

1

2

BELL HOLE

2

1

2 TRACER WIRE, BLUE, #10 AWG

SILICON FILLED CONNECTORS. TRACER WIRE SHALL CONTINUE ACROSS DIP SECTIONS

OF PIPE, SUCH AS AT ROAD CROSSINGS.

THAN 36" OF COVER SHALL BE DIP.

(36" UNDER

PAVED ROADWAYS)

3

3 VALVE BOX

3. VALVE BOX SHALL BE INSTALLED AT MAXIMUM 500 Ft. INTERVALS FOR

TESTING OF TRACER WIRE.

2" PVC

WATER MAIN CONSTRUCTION

Page: W-3.1

W-3.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 18: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

2"

2"

2"

1. PVC PIPE SHALL BE BLUE AND LABELED "POTABLE WATER."

2. ALL OTHER PIPE MATERIAL SHALL BE IDENTIFIED WITH BLUE PAINT OR AN

ADHESIVE-BACKED TAPE FOR DI PIPE 12" IN DIA. AND LARGER.

3. THERE SHALL BE A MINIMUM OF THREE COLORED STRIPES OR TAPES ALONG

THE PIPE (LOCATED AT 10:00, 12:00, AND 2:00) EACH A MINIMUM OF 2

INCHES WIDE.

4. THERE SHALL BE AN INSULATED BLUE #10 AWG COPPER WIRE INSTALLED WITH

PVC PIPES, NO EXCEPTIONS.

NOTES:

TAPED AT 10:00

TAPED AT 12:00

TAPED AT 2:00

WATER MAIN

(PVC OR D.I., ALL DIA.)

4

WATER MAIN PIPE IDENTIFICATION

Page: W-3.2

W-3.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 19: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1 4", 6", 8", 12"

ITEM DESCRIPTION

2" x 6" L2

3 2" (TAP)

4

PIPE, D.I. OR PVC (DR-18)

2"5

6

7

8

BOX, VALVE

EBAA MEGA LUG

WIRE, COPPER, INSULATED PURPLE, #10 AWG

GATE VALVE, SQUARE NUT, RESILIENT WEDGE

CAP D.I. (THREADED)

LOW LEAD BRASS NIPPLE INTO VALVE

8

4

2

5

7

6

1

3

COMPACTED

BACKFILL

UNDISTURBED EARTH

FINAL GRADE

6

2

4

1

UNDISTURBED EARTH

8

3

SEE W-2.2

(2-3/4") RODDED BACK

TO I-BOLTS

SOCKET CLAMP

(POURED IN PLACE HIGH EARLY

STRENGTH CONCRETE, 4000 psi)

CONCRETE THRUST BLOCK (4000 psi)

PLAN VIEW

PROFILE VIEW

9

9

10 PVC PIPE (SCH 80)2"

10

MIP x PVC COMPRESSION COUPLING

FORD CATALOG #C87-77K OR APPROVED EQUAL

9

WING BLOCK

WATER MAINS REDUCTION OF LINE SIZE

Page: W-3.3

W-3.3

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/9/2012

Page 20: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

ITEM DESCRIPTION

2"2

4 2"

METER BOX

2"5

2"6

7

PVC PIPE

PVC SCREW ON CAP

6

8

5

5

2

5

1

4

4'-0"

FINAL GRADE

PVC 90° BEND

COMPACTED

BACKFILL

5

6

3

3 TRACER WIRE, COPPER, BLUE INSULATED #10 AWG

UNDISTURBED EARTH

3

1

7

9

7

GATE VALVE, SQUARE NUT, RESILIENT WEDGE

MIP x PVC COMPRESSION COUPLING

FORD CATALOG # C87-77 OR APPROVED EQUAL

7

8 VALVE BOX, CI

9 SCH 40 PVC MALE ADAPTER WITH SCREW ON CAP

2" PVC BLOW-OFF ASSEMBLY

Page: W-3.4

W-3.4

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 21: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

ITEM DESCRIPTION

2"2

4 2"

METER BOX

2"5

6

7

2"

GATE VALVE, SQUARE NUT, RESILIENT WEDGE

VALVE BOX, CI

GALVANIZED PIPE

GALVANIZED CAP

6

7

5

5

2

5

1

4

4'-0"

FINAL GRADE

GALVANIZED 90° BEND

COMPACTED

BACKFILL

5

6

3

3 TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

UNDISTURBED EARTH

3

1

2" GALVANIZED PIPE BLOW-OFF ASSEMBLY

Page: W-3.5

W-3.5

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 22: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

FINAL GRADE

NOTE: SAMPLES WILL NOT BE COLLECTED UNDER UNSAFE CONDITION

INCLUDING SAMPLE POINTS BELOW GRADE, UNSTABLE SOIL, POOLED WATER

GREATER THAN AN INCH DEPTH. SAMPLES WILL NOT BE COLLECTED UNDER

RAIN OR MIST CONDITIONS. HOSE CONNECTIONS ARE NOT ALLOWED.

3' MIN.

SAMPLE POINT ASSEMBLY

Page: W-3.5.1

W-3.5.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 23: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

ITEM DESCRIPTION

2

3

4

5

6

7

8

4

2

5

8

7

1

3

COMPACTED

BACKFILL

UNDISTURBED EARTH

10

9

FINAL GRADE

6

9

2

10

WATER MAIN SIZE

3"

3"

3"

CONCRETE WING BLOCK (4000 psi HIGH EARLY STRENGTH)

TAPPED CAP D.I.

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

METER BOX

GALVANIZED PIPE

GALV. CAP

VALVE BOX, C.I.

3" GALV. 45° BEND

GATE VALVE, SQUARE NUT, RESILIENT WEDGE

6" or 8"

1

11

(2-3/4") RODDED BACK

TO I-BOLTS

WING BLOCK

6" X 3" OR 8" X 3"

SOCKET CLAMP

(POURED IN PLACE 4000 PSI

HIGH EARLY STRENGTH

CONCRETE)

4

3

11

11 EBAA MEGALUG, MECHANICALLY RESTRAINED GLAND

5

12 3" LOW LEAD BRASS NIPPLE

12

3" BLOW-OFF ASSEMBLY FOR 6" 8" WM

Page: W-3.6

W-3.6

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 24: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1 6" or 8" X 3"

ITEM DESCRIPTION

3"2

3

4 3" X 6" L

MJ TAPPED TEE (W/ EBAA MEGALUG RESTRAINT)

3" X 45°5

3" X VARIES6

7

PIPE, GALV.

BEND, GALV.

LOW LEAD BRASS NIPPLE

VALVE BOX, C.I.

VALVE, GATE, SQUARE NUT, RESILIENT WEDGE

4

2

3

5

GALV. CAP

TRACER WIRE, BLUE INSULATED, #10 AWG

3"

9

8

30"MIN. 36" MAX.

GRADE

FINAL

8

7

9

METER BOX

5

1

4

6

5

4 6

9

2

7

1

6

3" BLOW-OFF ASSEMBLY, PERPENDICULAR TO MAIN

Page: W-3.7

W-3.7

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 25: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1 12", 16", 20", 24" X 6"

ITEM DESCRIPTION

6"2

3

4 6" X 16" or 72" (PER FIELD CONDITIONS)

MJ ANCHORING TEE WITH EBAA MEGALUG RESTRAINT

6" X 45°5

6" X VARIES6

7

8

9

8 MILS THICKNESS (MIN.) or FELT 15 Ib (MIN.)

PIPE, D.I.P.

BEND, MJ x MJ

ANCHOR COUPLING, MJ x MJ SWIVEL x SOLID

VALVE BOX, C.I.

VALVE, GATE, MJ, RESILIENT WEDGE

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

EBAA MEGA LUG MECHANICALLY RESTRAINED GLAND

11

10

12

6" CAP, D.I., MJ, EBAA MEGALUG

METER BOX

8

1

3

5

1

4

36" MAX.

GRADE

FINAL

10

11

6

8

2

5

30"MIN.

7

6

5

11

12

12

9

9

CONCRETE, THRUST BLOCK (2500 psi)

VISQUEEN

8

9

7

4

13 UNDISTURBED EARTH

13

13

UNLESS SUFFICIENT PIPE EXISTS UPSTREAM & DOWNSTREAM TO PROVIDE RESTRAINT

8

8

6" BLOW-OFF ASSEMBLY

Page: W-3.8

W-3.8

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/22/2016

Page 26: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1 30", 36" x 8"

ITEM DESCRIPTION

8"2

3

4 8" x 16" or 72" (PER FIELD CONDITIONS)

MJ ANCHOR TEE (UP TO 30") OR TEE (36")

8" x 45°5

8" x VARIES6

7

8

9

8 MILS THICKNESS (MIN.) or FELT 15 Ib (MIN.)

PIPE, D.I.P.

BEND, MJ x MJ

ANCHORING COUPLING, MJ x MJ, SOLID x SWIVEL

VALVE BOX, C.I.

VALVE, GATE, MJ, RESILIENT WEDGE

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

EBAA MEGA LUG MECHANICALLY RESTRAINED GLAND

11

10

12

8" CAP, D.I., MJ, EBAA MEGALUG

METER BOX

8

1

3

5

1

4

36" MAX.

GRADE

FINAL

10

11

6

8

2

5

30"MIN.

7

6

5

11

12

12

9

9

CONCRETE, THRUST BLOCK (2500 psi)

VISQUEEN

9

7

4

4

13 UNDISTURBED EARTH

13

13

8

*UNLESS SUFFICIENT PIPE EXISTS UPSTREAM & DOWNSTREAM TO PROVIDE RESTRAINT

36" ONLY

8" BLOW-OFF ASSEMBLY

Page: W-3.9

W-3.9

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/22/2016

Page 27: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1 6"-36"

ITEM

DESCRIPTION

2" (TAP)2

3

4 2"

WATER MAIN

5

6 4' x 4'

7

8

9

GALVANIZED STEEL PLATE

MANHOLE JOINT SEALANT

CONCRETE VAULT (DO NOT BEAR ON PIPE)

LOW LEAD BRASS GATE VALVE HANDWHEEL

LOW LEAD BRASS NIPPLE OUTLET

SERVICE SADDLE 2" NPT

GRAVEL (No. 57 STONE)

AIR RELEASE VALVE

48"

4' x 4'

12"

12"

AS

R

EQ

UIR

ED

7

5

3

4

3

2

1

8

6

9

FINAL

GRADE

12" MIN.

2" x 4"

*

*

*

*

* 30" AND 36" WATERMAIN REQUIRES 3" AIR RELEASE VALVE.

11

12

10

11

12

3/4" GSP NIPPLE

3/4" 90° ELBOW (G.S.P.)

3/4" GSP W/ THREADED ENDS

10

11

8

AIR RELEASE VALVE CONSTRUCTION

Page: W-4.0

W-4.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 28: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

ITEM DESCRIPTION

1

2 GRAVEL DRAIN BED (No. 57 STONE)

3

4

M A T E R I A L S

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

FIRE HYDRANT

EBAA MEGALUG RESTRAINT

30" MIN.

36" MAX.

R/W

UNDISTURBED SOIL

12" 12"

6"

18"

1

4

2

2

1

12"

NOTES:

5

5

1. RESTRAIN MINIMUM 58' OF PIPE.

5 PIPE, D.I.

3

3

Page: W-5.0

W-5.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 29: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

R/W

VARIES

UNDISTURBED SOIL

FINAL GRADE

1

2

4

3

5

6

4

2

1

ITEM DESCRIPTION

FIRE HYDRANT1

2 ANCHOR COUPLING

3 VALVE BOX, C.I.

4 GATE VALVE

5 ANCHOR TEE

6 CONCRETE THRUST BLOCK (2500 psi)

M A T E R I A L S

BEARING AREA

7 GRAVEL DRAIN BED

8 TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

FIRE HYDRANT PERPENDICULAR TO THE MAIN

18"

7

9 ANCHOR 90° BEND, M.J.

NOTES:

2. A NONPOROUS MATERIAL 8 MILS (MIN.) VISQUEEN OR 15 Ib (MIN.) FELT

SHOULD BE PLACED BETWEEN THE CONCRETE AND THE ENTIRE FITTING.

5

8

8

6

1. SEE W-2.2 FOR BEARING AREA REQUIRED.

10 TEE

Page: W-5.1

W-5.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 30: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

R/W

VARIES

UNDISTURBED SOIL

FINAL GRADE

1

2

4

3

ITEM DESCRIPTION

FIRE HYDRANT1

2 ANCHOR COUPLING

3 VALVE BOX, C.I.

4 GATE VALVE

5 ANCHOR TEE

6 CONCRETE THRUST BLOCK (2500 psi)

M A T E R I A L S

7 GRAVEL DRAIN BED

8 TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

1

5

6

4

R/W

18"

7

9 ANCHOR 90° BEND, M.J.

7

9

NOTES:

2. A NONPOROUS MATERIAL 8 MILS (MIN.) VISQUEEN OR 15 Ib (MIN.) FELT

SHOULD BE PLACED BETWEEN THE CONCRETE AND THE ENTIRE FITTING.

5

8

6

FIRE HYDRANT PARALLEL TO THE MAIN

1. SEE W-2.2 FOR BEARING AREA REQUIRED.

10 TEE

Page: W-5.1.1

W-5.1.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 31: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

R/W

VARIES

UNDISTURBED SOIL

FINAL GRADE

1

2

4

3

ITEM DESCRIPTION

FIRE HYDRANT1

2 ANCHOR COUPLING

3 VALVE BOX, C.I.

4 GATE VALVE

5 STANDARD TEE

6 CONCRETE THRUST BLOCK (2500 psi)

M A T E R I A L S

7 GRAVEL DRAIN BED

8 TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

4

2

1

18"

7

10

9 ANCHOR 90° BEND, M.J.

9

NOTES:

2. A NONPOROUS MATERIAL 8 MILS (MIN.) VISQUEEN OR 15 Ib (MIN.) FELT

SHOULD BE PLACED BETWEEN THE CONCRETE AND THE ENTIRE FITTING.

5

8

8

R/W

6

6

1. SEE W-2.2 FOR BEARING AREA REQUIRED.

7

10 TEE

FIRE HYDRANT PARALLEL CLOSE TO THE MAIN

Page: W-5.1.2

W-5.1.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 32: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

Page: W-5.2

W-5.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 33: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

LOT 8

LOT 9

LOT 7

LOT 1

LOT 2

LOT 3

NO ELECTRIC

TRANSFORMERS IN

THIS AREA

3 FT TYPICAL

DUAL SERVICE

WATER METER

SINGLE SERVICE

WATER METER

ELECTRIC

TRANSFORMER

ELECTRIC

CONDUCTOR

4 PVC

SLEEVE

4 PVC SLEEVE (SCH-40)

36" MIN.

42" - 48"

FINAL GRADE

ELECTRIC TRANSFORMER

3'3'

VARIES

WATER MAIN

WATER

METER

ASSEMBLY

PROPOSED OR EXISTING ROADWAY

3 FT TYPICAL

WATER MAIN

PLAN

PROFILE

NOTES: 1. WATER METER SERVICE SHALL BE LOCATED TO AVOID CONFLICT WITH LOCATIONS

OF ELECTRIC TRANSFORMERS AND FIRE HYDRANTS.

2. ELECTRIC CONDUCTORS MAY BE ON EITHER SIDE OF THE ROADWAY. WATERMAIN

3. PVC SLEEVE TO BE 3" SCHEDULE 40 PVC SOLVENT WELD.

SHOULD BE ON THE OPPOSITE SIDE OF TRANSFORMERS.

TX

ROADWAY

ELECTRIC CONDUCTOR

WATER SERVICE

VALVE

WATER

SERVICE

5' OUTSIDE CITY LIMIT

2

1

3 2

1

5 SEAL W/ RAMNEK OR

EQUAL (TYP BOTH ENDS)

4. SEAL BOTH ENDS OF 3" SLEEVE WITH RAMNEK OR EQUAL.

SINGLE & DUAL WATER SERVICE

Page: W-6.0

W-6.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

9/8/08

Page 34: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

LOT 13

LOT 12

LOT 14

LOT 5

LOT 4

LOT 3

LOT 6

LOT 11

LOT 7

LOT 10

3 FT TYPICAL

5 FT WHEN ELECTRIC

TRANSFORMER PRESENT

AT LOT CORNER

3 FT TYPICAL

WW LATERAL

TO CENTER OF LOT

5 FT WHEN FIRE

HYDRANT PRESENT

AT LOT CORNER

3" PURPLE

PVC SLEEVE

LOT LINE

5'

1" PURPLE PVC

1" X 2" TEE

2" PURPLE PVC (DOUBLE)

5' PUE

3 ft typical

SIZE x 2" SADDLE

AND 2" VALVE

5'

R/W

R/W

5' PUE

(VARIES)

5' PUE (VARIES)

WW

CLEAN OUT

(TYP)

5'

SEE DETAIL

FOR METER

ASSEMBLY

(TYP, SEE W-8.0)

2" PURPLE PVC

PR

OP

OS

ED

8

" S

AN

IT

AR

Y

4" PVC

WW LATERAL

SIZE x 2" SADDLE

AND 2" VALVE

VARIES VARIES

POTABLE

WATER MAIN

(SIZE VARIES)

RECLAIMED WATER MAIN

(SIZE VARIES) PURPLE PVC

FIRE

HYDRANT

ASSEMBLY

3" BLUE

PVC SLEEVE

SSMH

SSMH

3' INSIDE CITY LIMITS

WATER, WASTEWATER, AND RECLAIMED WATER FACILITY

Page: W-6.1

W-6.1

ALLOCATION IN RESIDENTIAL DEVELOPMENT

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 35: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

ITEM DESCRIPTION

WATER MAIN (MIN. 6")1

2 FIRE HYDRANT ASSEMBLY

3 REDUCER FITTING AND 2" GATE VALVE

4

5

4" WATER MAIN

6

2" BLOW-OFF AND SAMPLE POINT

M A T E R I A L S

LOT 3 LOT 2 LOT 1LOT 4

LOT 8LOT 5 LOT 7LOT 6

6

4

5

2

1

200' MAX.

3

ELECTRIC TRANSFORMER

TX

7

7 2" SCH 40 PVC WATER MAIN (MAX. 4 SERVICES)

8

77

8 3" BLOW-OFF AND SAMPLE POINT

3

DEAD END WATER MAIN CONSTRUCTION

Page: W-6.2

W-6.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 36: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

ITEM DESCRIPTION

4", 6", 8", 12"2

3 1"MPT X1" COMP.

4

M A T E R I A L S

WATER MAIN

1" POLYETHYLENE TUBING, BLUE, SDR-9

CORPORATION STOP FOR PE TUBING

SERVICE SADDLE W/1" CC (TAPERED THREADS)

NOTES:

R/W

COMPACTED BACKFILL

2. TRACER WIRE SHALL BE SPIRALED AROUND THE TUBING, TAPED EVERY

TEN FEET AND CONNECTED TO THE MAIN LINE TRACER WIRE USING

4", 6", 8", 12"

2

1

3

4

GRADE

SILICONE FILLED CONNECTORS.

5

1. ALL FITTINGS FOR POLYETHYLENE TUBING ARE COMPRESSION TYPE.

ASSEMBLY IS INSTALLED.

3. 1" GATE VALVE PROVIDED TO BE TEMPORARY UNTIL WATER METER

4. SEE W-8.0 FOR WATER METER ASSEMBLY INSTALLATION.

TRACER WIRE, BLUE, # 10 AWG5

30"-36"

COVERUSE WHEN METER IS INSTALLED

ADDITIONAL 6' OF TRACER WIRE FOR FUTURE

6

24" MIN ABOVE GRADE

WATER METER YOKE VALVE - 5/8" X 3/4" (# B94-324W-G-NL)

6

WATER METER YOKE VALVE - 1" (# BL94-344W-G-NL)

POLYETHYLENE TUBING WATER SERVICE MAIN SIDE

Page: W-7.0

W-7.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

04/14/2017

AutoCAD SHX Text
Revision Date:
Page 37: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

R/W LINE

1

ITEM DESCRIPTION

4", 6", 8", 12"2

3 1"MPT X1" COMP.

4

M A T E R I A L S

WATER MAIN

1" POLYETHYLENE TUBING, BLUE, SDR-9

CORPORATION STOP FOR PE TUBING

SERVICE SADDLE W/1" CC (TAPERED THREADS)

NOTES:

2. TRACER WIRE SHALL BE SPIRALED AROUND THE TUBING, TAPED EVERY

TEN FEET AND CONNECTED TO THE MAIN LINE TRACER WIRE USING

4", 6", 8", 12"

SILICONE FILLED CONNECTORS.

1. ALL FITTINGS FOR POLYETHYLENE TUBING ARE COMPRESSION TYPE.

ASSEMBLY IS INSTALLED.

3. 1" GATE VALVE PROVIDED TO BE TEMPORARY UNTIL WATER METER

4. SEE W-8.0 FOR WATER METER ASSEMBLY INSTALLATION.

TRACER WIRE, BLUE, # 10 AWG5

WATER METER YOKE VALVE - 5/8" X 3/4" (# B94-324W-G-NL)

6

WATER METER YOKE VALVE - 1" (# BL94-344W-G-NL)

3

6

6

2

4

4

PROPERTY LINE

3'

3'

1

7

1" BRASS GRIP JOINT TEE OR WYE7

Page: W-7.1

W-7.1

DOUBLE 1 INCH POLYETHYLENE WATER SERVICE

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

09/01/2017

AutoCAD SHX Text
Revision Date:
Page 38: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

R/W LINE

1

ITEM DESCRIPTION

4", 6", 8", 12"2

3 1"

4

M A T E R I A L S

WATER MAIN

1" POLYETHYLENE TUBING, BLUE, SDR-9

GATE VALVE

SERVICE SADDLE W/2" CC (TAPERED THREADS)

NOTES:

2. TRACER WIRE SHALL BE SPIRALED AROUND THE TUBING, TAPED EVERY

TEN FEET AND CONNECTED TO THE MAIN LINE TRACER WIRE USING

4", 6", 8", 12"

SILICONE FILLED CONNECTORS.

1. ALL FITTINGS FOR POLYETHYLENE TUBING ARE COMPRESSION TYPE.

ASSEMBLY IS INSTALLED.

3. 1" GATE VALVE PROVIDED TO BE TEMPORARY UNTIL WATER METER

4. SEE W-8.0 FOR WATER METER ASSEMBLY INSTALLATION.

CTS POLY TUBING 5

WATER METER YOKE VALVE - 5/8" X 3/4" (# B94-324W-G-NL)

6

WATER METER YOKE VALVE - 1" (# BL94-344W-G-NL)

3

2

PROPERTY LINE

1

7

2" BRASS GRIP JOINT WYE OR TEE7

5

2"

ROADWAY

8

2"X6" LONG LOW LEAD BRASS NIPPLE8

6

6

4

4

Page: W-7.3

W-7.3

DOUBLE 2 INCH POLYETHYLENE WATER SERVICE

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

09/01/2017

AutoCAD SHX Text
Revision Date:
Page 39: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

FINAL GRADE

SCH 40 PVC PIPE

YOKE EXPANSION

YOKE BAR - 1"

WATER METER - 5/8" x 3/4"

METER BALL VALVE - 5/8" X 3/4"

6" SCH 80 PVC THREADED NIPPLE

TRACER WIRE, COPPER. BLUE INSULATED, #10 AWG8

7

6

5

METER BOX - 5/8" X 3/4" OR 1"

4

3

2

DESCRIPTIONITEM

1

1

2

3

5

7

4

8

7

6

R/W

(BY GRU)

(BY CONTRACTOR, FORD METER PART NO. Y-504)

(BY GRU)

(BY CONTRACTOR, FORD METER PART NO. B-91-223-W)

STRUCTURE

9

YOKE BAR - 5/8" X 3/4" (BY CONTRACTOR, FORD METER PART NO. Y-502)

(BY CONTRACTOR, CARSON PART NO. 1419-12-6-H-K-WOK-0F0)

METER BALL VALVE - 1" (BY CONTRACTOR, FORD METER PART NO. B-91-344-W)

9

METER END CONNECTOR - 5/8" X 3/4"

METER END CONNECTOR - 1"

(BY CONTRACTOR, FORD METER PART NO. B-91-223-W)

(BY CONTRACTOR, FORD METER PART NO. C-91-44)

WATER METER ASSEMBLY: 5/8" X 3/4", 3/4", AND 1"

Page: W-8.0

W-8.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 40: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

NOTES:

1

ITEM DESCRIPTION

2

3

1. GAINESVILLE REGIONAL UTILITIES WILL INSTALL WATER METERS.

METER BOX

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

2" PVC PIPE

3

7

4

3

7

1

1

1

5

4 1" x 3/4" PVC REDUCER

5 1" 90° BEND

6

1" X 1" X 2" PVC TEE6

5

4

2

5

4

1" PVC PIPE7

Page: W-8.1

W-8.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 41: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

12"

FINAL GRADE

1. GAINESVILLE REGIONAL UTILITIES WILL INSTALL WATER METER ASSEMBLY

NOTE:

1

ITEMDESCRIPTION

2

3

4

2" SCH 40 PVC PIPE 2' ABOVE GRADE WITH 2" MALE ADAPTER

5

6

7

8

9

METER BOX, PRECAST CONC.

1-1/2", 2" WATER METER

2" SCH 40 PVC COUPLING, COMPRESSION

BRASS NIPPLE

VALVE BOX, C.I.

1-1/2", 2" BRASS GATE VALVE

2" SCH 40 PVC FEMALE ADAPTER, OR 2" x 1-1/2" REDUCER

2" SCH 40 PVC 90 DEG ELBOW

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG10

3

1

2

6

5

9

8

1

7

3

10

3

7

14

3

12"

CONTRACTOR

GRU

FLOW

INCLUDING THE WATER METER BOX.

6

GRU PLUMBER

FLOW TO

STRUCTURE

AND THREADED CAP.

WATER METER ASSEMBLY: 1 1/2" & 2" & 3"

Page: W-8.2

W-8.2

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

4/24/06

Page 42: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

NOTES:

1

ITEM DESCRIPTION

3/4"2

3 1-1/2" X 3/4"

4 2" X 1-1/2"

1. MULTIPLE GANG METER ASSEMBLY SHALL BE A MAXIMUM OF (12) TWELVE METERS.

2. GAINESVILLE REGIONAL UTILITIES WILL INSTALL WATER METERS UNLESS OTHERWISE SPECIFIED

WATER METER BOX AND ASSEMBLY

2" X 1-1/2"5

2"6

7

PVC PIPE

PVC TEE

PVC ELBOW

PVC REDUCING BUSHING

PVC PIPE

2

8

3

TRACER WIRE, COPPER, BLUE INSULATED, #10 AWG

SEE W-7.1

FOR SERVICE LATERAL

4

5

6

7

8"

18" MIN.

1

18" MIN. 18" MIN.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION OF THE METER BOX AND

METER YOKE ASSEMBLY. SEE WATER METER ASSEMBLY DETAIL W-8.0.

ON THE APPROVED DRAWINGS.

3

3

3

2

2

6

11

6 METERS MAX.6 METERS MAX.

2" GATE VALVES REQUIRED IF

4 OR MORE METERS PER SIDE

8 PVC TEE (AND 4" X 2" REDUCER, IF NEEDED)2"

2

MULTIPLE GANG METER ASSEMBLY

Page: W-8.3

W-8.3

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 43: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete
DESTEPHENCG
Rectangle
DESTEPHENCG
Text Box
2" CTS POLY
DESTEPHENCG
Rectangle
Page 44: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/22/16

UNDERGROUND BACKFLOW PREVENTER

Page: W-8.4

W-8.4

SCH 40 PVC PIPE

YOKE EXPANSION

YOKE BAR

WATER METER - 5/8" x 3/4"

METER CURB STOP

SCH 80 PVC THREADED NIPPLE

TRACER WIRE, COPPER. BLUE INSULATED, #10 AWG (BY CONTRACTOR)8

7

6

5

METER BOX (BY CONTRACTOR)

4

3

2

DESCRIPTIONITEM

1

(BY GRU)

(BY GRU)

1. CONTRACTOR TO BE RESPONSIBLE FOR 1 YR. WARRANTY PERIOD FOR INSTALLATION OF

NOTE:

WATER METER BOX AND FITTINGS, EXCLUDING ITEMS PROVIDED BY GRU (EFFECTIVE OCTOBER 1, 2007).

2" x 3/4" PVC REDUCER (BY CONTACTOR)9

R/W

STRUCTURE

7

9

2

8

6

5

4

3

1

2

6

7

2" BRASS NIPPLE10

11

10

117

1

FINAL GRADE

7

FINAL GRADE

STRUCTURE

6 3/4"

2"

2 1/2"

1 1/4"

1 1/4"

16 1/2"

APPROX. 44"

2. APPLIES TO RESIDENTIAL POTABLE WATER SERVICE WITHIN RECLAIMED WATER SERVICE AREA.

9

Page 45: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

POTABLE WATER MAIN

ROW/PROPERTY LINE

GATE VALVE & BOX

END OF GRU MAINTENANCE

WRAP W/6 MIL. POLYETHYLENE

MIN 10' FROM STRUCTURE

FIR

E P

RO

TE

CT

IO

N S

YS

TE

M

FIRELINE BFP

(DDC OR RPZ

WITH DETECTOR)

WITH CLEARANCE

AS SPECIFIED BY

MANUFACTURER.

FLOOR TO BE SLOPED SO

THAT WATER RUNS OUT

DOOR- MIN 1/16"/FT SLOPE,

MAX 1/4"/FT SLOPE

- 1/4" GAP

REQUIRED UNDER DOOR.

(NO THRESHOLD)

METERS TO BE OWNED AND

MAINTAINED BY GRU. ALL

OTHER PIPES, METER YOKES,

VALVES, BFPS, ETC. TO

BE PRIVATELY MAINTAINED.

LINES TO BE ENCASED

IN FIBER REINFORCED

CONCRETE, 12" THICK

TOP & SIDES.

POTABLE WATER BFP

(RPZ) WITH CLEARANCE

AS SPECIFIED BY

MANUFACTURER.

NOTES:

1) DETAILED INSTALLATION PLANS SHALL BE SUBMITTED FOR REVIEW TO GRU SHOWING BFP AND METER

INSTALLATION DETAILS.

FLOOR TO BE BROOM

FINISHED CONCRETE

A A'

12" MIN

36" MIN

COVER

EXTERIOR WALL.

EXTERIOR DOOR ON

GROUND FLOOR.

METERS TO BE SPACED

MIN 18" FROM FLOOR &

12" BETWEEN ROWS (5/8"-1")

TO A MAXIMUM HEIGHT OF 6'

TO ALLOW FOR VISUAL READ.

2' MIN

(TYP)

12"

MIN

12"

MIN

SECTION A-A'

PIV

LIGHTING PROVIDED BY OWNER.

GFCI OUTLET & LIGHT SWITCH W/

WEATHERPROOF COVER.

FINISHED

GRADE

PERMANENT SIGNAGE TO BE

PROMINENTLY MOUNTED

READING:

"NO STORAGE OF ANY TYPE

IN THIS ROOM"

MIN 2" HIGH LETTERING.

BACKFLOW PREVENTERS

ASSE APPROVED TO

OPERATE VERTICALLY

MAY BE UTILIZED.

INTERIOR WALL & CEILING

SURFACES MUST BE

WATERPROOF-EQUAL TO

EXPOSED EXTERIOR WALLS

OR SHOWER ENCLOSURE

WALLS.

MAX 10' OF PIPE

TO FIRELINE BFP

LOCK BOX PROVIDED

BY GRU, WITH

KEY PROVIDED

BY OWNER TO GRU.

DOOR LOCK BY OWNER.

MIN. 40" CLEAR SPACE (TYP)

BLOWOFF & SAMPLE POINT REQ'D

DIP

DIP

ALL PIPE MUST

BE EXPOSED

AFTER POINT OF

ENTRY.

METER SETTERS REQUIRE LOCKABLE BALL VALVE

CURB STOP UPSTREAM AND DOWNSTREAM.

METERS TO BE MOUNTED HORIZONTALLY

FLOWING LEFT TO RIGHT.

FDC (OPTIONAL)

A GRU METER ROOM

EASEMENT IS

REQUIRED

A GRU PRIVATE OWNERSHIP

AGREEMENT IS REQUIRED

FOR THE PIPE BETWEEN

HERE AND THE METERS

24"

24"

MIN

MIN

PERMANENT SIGN ON DOOR

READING:

"WATER METER ROOM"

MIN 2" HIGH LETTERING.

24"

MIN

INSIDE WATER METERS - ROOM

Page: W-8.5

W-8.5

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 46: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

18" MINIMUM

SPACING FROM

FLOOR (TYP)

12" ON CENTER

MINIMUM

CLEARANCE

(TYP)

2' MINIMUM

SPACING FROM

WALL OR EQUIPMENT (TYP)

(3' FOR 1" METERS)

2' MINIMUM SPACING

ON CENTER (TYP)

(3' FOR 1" METERS)

TO PLUMBING

OF UNITS

TO PLUMBING

OF UNITS

TO PLUMBING

OF UNITS

6' MAXIMUM

HEIGHT TO ALLOW

FOR ACCURATE

METER READING

WALL

CONCRETE

FLOOR

NOTES: -MAXIMUM FOUR 5/8" METERS PER 1-1/2" BRANCH HEADER.

-MAXIMUM FIVE 3/4" METERS PER 2" BRANCH HEADER.

-ONLY SENSUS iPERL METERS WILL BE USED AND MUST BE MOUNTED

HORIZONTALLY FLOWING LEFT TO RIGHT FOR READABILITY.

-MINIMUM CLEAR SPACE OF 40" IN FRONT AND 24"(5/8"-3/4" ONLY, 36" FOR 1" & LARGER

METERS) TO EACH SIDE OF METERS AND METERING EQUIPMENT SHALL BE MAINTAINED

AT ALL TIMES FOR READING AND TESTING.

-PERMANENTLY LABEL EACH METER YOKE WITH UNIT NUMBER.

-METERS 5/8" TO 1" WILL BE SENSUS iPERL AND MUST BE MOUNTED

HORIZONTALLY FLOWING LEFT TO RIGHT FOR READABILITY.

MAIN HEADER

PIPE

VALVE ON MAIN HEADER

REQ'D AFTER EVERY

12TH METER SERVED

(TYP)

VALVE REQ'D ON BRANCH HEADER

WHEN SERVING MORE THAN 1 METER

(TYP)

BRANCH

HEADER

PIPE

(TYP)

ITEM DESCRIPTION

1

2

3

4

5

6

1

2

3

5

4

6

PVC PIPE

PVC REDUCING BUSHING

PVC ELBOW

PVC TEE

PVC PIPE

PVC TEE

3/4" (1")*

1-1/2" X 3/4" (1")*

1-1/2"

1-1/2"

4" X 1-1/2"

MATERIALS

1-1/2" X 3/4" (1")*

*(FOR 1" METERS)

MOUNT VALVES MAX. 6' ABOVE FLOOR

5/8" - 1" INSIDE WATER METERS-ROOM

Page: W-8.6

W-8.6

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 47: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

2

3

4

4

1

2

3

4

4

UNISTRUT P3300

CHANNEL (TYP)

UNISTRUT P1000

CHANNEL (TYP)

12"

2'

WALL

MATERIALS

ITEM DESCRIPTION

1

2

3

4

YOKE EXPANSION

YOKE BAR - 5/8" X 3/4" FORD METER BOX CO. #Y502

SENSUS iPERL 5/8" METER

METER BALL VALVE - 5/8" X 3/4" FORD METER BOX CO. #B-91-223-W

UNISTRUT

P1000

CHANNEL

(TYP)

(LAGGED

INTO WALL

FRAMING)

ELEVATION VIEW

NOT TO SCALE

PLAN VIEW

NOT TO SCALE

5 U-BOLT WITH WASHERS AND NUTS-SUPERSTRUT U-501/2 OR EQUAL

5

MINIMUM

CLEAR

BETWEEN

METERS

MINIMUM

SPACING

UNISTRUT

P3300

CHANNEL

(TYP)

2'2'

MIN. MIN.

WALL

OR

EQUIP.

(TYP.)

5/8" INSIDE WATER METERS-ROOM

Page: W-8.7

W-8.7

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 48: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

2

3

4

4

1

2

3

4

4

UNISTRUT P3300

CHANNEL (TYP)

UNISTRUT P1000

CHANNEL (TYP)

12"

3'

WALL

MATERIALS

ITEM DESCRIPTION

1

2

3

4

YOKE EXPANSION

YOKE BAR - 1" FORD METER BOX CO. #Y504

SENSUS iPERL 1" METER

METER BALL VALVE - 1" FORD METER BOX CO. #B-91-334-W

UNISTRUT

P1000

CHANNEL

(TYP)

(LAGGED

INTO WALL

FRAMING)

UNISTRUT

P3300

CHANNEL

(TYP)

ELEVATION VIEW

NOT TO SCALE

PLAN VIEW

NOT TO SCALE

5 U-BOLT WITH WASHERS AND NUTS-SUPERSTRUT U-501/2 OR EQUAL

5

MINIMUM

SPACING

MINIMUM

CLEAR

BETWEEN

METERS

3'3'

MIN. MIN.

WALL

OR

EQUIP.

(TYP.)

1" INSIDE WATER METERS-ROOM

Page: W-8.7.1

W-8.7.1

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 49: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

18" MINIMUM

SPACING FROM

FLOOR (TYP)

12" MINIMUM

SPACING

ON CENTER

(TYP)

3' MINIMUM

SPACING FROM

WALL OR EQUIPMENT (TYP)

4' MINIMUM

SPACING

ON CENTER (TYP)

TO PLUMBING

OF UNITS

TO PLUMBING

OF UNITS

6' MAXIMUM

HEIGHT TO ALLOW

FOR ACCURATE

METER READING

WALL

CONCRETE

FLOOR

NOTES: -MAXIMUM FOUR 5/8" METERS PER 1-1/2" BRANCH HEADER.

-MAXIMUM FIVE 3/4" METERS PER 2" BRANCH HEADER.

-MINIMUM CLEAR SPACE OF 40" IN FRONT AND 24"(5/8"-3/4" ONLY, 36" FOR 1" & LARGER

METERS) TO EACH SIDE OF METERS AND METERING EQUIPMENT SHALL BE MAINTAINED

AT ALL TIMES FOR READING AND TESTING.

-PERMANENTLY LABEL EACH METER YOKE WITH UNIT NUMBER.

-PERMANENTLY LABEL EACH LARGE MATER WITH FLOOR OR AREA SUPPLIED.

-1-1/2" & 2" METERS SHALL BE SENSUS OMNI C2 METERS MOUNTED

HORIZONTALLY OR VERTICALLY, FLOWING EITHER DIRECTION.

MAIN HEADER

PIPE

VALVE ON MAIN HEADER

REQ'D AFTER EVERY

12TH 5/8" METER SERVED,

AND AFTER EVERY BRANCH

WITH 1" OR LARGER METERS

(TYP)

BRANCH

HEADER

PIPE

(TYP)

ITEM DESCRIPTION

1

2

3

4

5

6

1

2

3

5

4

PVC PIPE

PVC REDUCING BUSHING

PVC ELBOW

PVC TEE

PVC PIPE

PVC TEE

3/4" (1")*

3" X 3/4" (1")*

3"

3"

4" X 3"

MATERIALS

3" X 3/4" (1")*

18" MINIMUM

SPACING METER

TO METER

1

2

3

5

4

18" MINIMUM

SPACING METER

TO METER

6

3' MAXIMUM

HEIGHT

SEE W-8.9 FOR 1-1/2" & 2" METER MATERIALS

*(FOR 1" METERS)

1"

METER

(TYP.)

1-1/2" OR 2"

METER

(TYP.)

5/8" OR

3/4"

METER

(TYP.)

1-1/2" - 2" METERS 1-1/2" - 2" METERS

5/8" - 2" INSIDE WATER METERS-ROOM

Page: W-8.8

W-8.8

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 50: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

2

3

UNISTRUT P1000

CHANNEL (TYP)

2'

WALL

UNISTRUT

P1000

CHANNEL

(TYP)

(LAGGED

INTO WALL

FRAMING)

ELEVATION VIEW

NOT TO SCALE

PLAN VIEW

NOT TO SCALE

34

5

6

5

4

3

27

MATERIALS

ITEM DESCRIPTION

1

2

3

4

3" X 1-1/2" (2")* PVC TEE

1-1/2" (2")* SCH 80 PVC NIPPLE (THD x SLIP)

1-1/2" (2")* BRASS QUARTER TURN BALL VALVE, PADLOCKABLE

1-1/2" (2")* BRASS NIPPLE (THD x THD)

5 1-1/2" (2")* BRASS TAPPED FLANGE

6

7

4' MINIMUM

1-1/2" (2")* SENSUS OMNI C2 METER

1-1/2" (2")* UNISTRUT PIPE CLAMP

*(FOR 2" METERS)

1

3

2

2

7

7

4

4

5

5

6

3' MINIMUM

TO WALL OR EQUIPMENT

3' MINIMUM

TO WALL OR EQUIPMENT

11/2"-2" INSIDE WATER METERS-ROOM

Page: W-8.9

W-8.9

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 51: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

D.I. 90° BEND, FL X FL, WITH EBAA MEGAFLANGE

PRECAST CONCRETE VAULT

7

6

5

D.I. TEE, FL X FL, WITH EBAA MEGAFLANGE

GATE VALVE, FL X FL, WITH EBAA MEGAFLANGE

FIRELINE/COMPOUND METER

1

4

3

2

ITEM

DIP W.M.

ALUMINUM GRATE VAULT COVER

DESCRIPTION

1

2

3

4

5

5

5

6

77

3

VARIES

GRUCONTRACTOR

1. METER VAULT SIZE WILL BE DETERMINED IN ACCORDANCE WITH METER SIZE AND TYPE.

2. ALL FITTINGS WITHIN VAULT MUST BE FLANGED FITTINGS. ALL FITTINGS SHALL BE

STRUCTURALLY SUPPORTED.

NOTES:

9

FLOW

FROM

EXISTING

GRU SYSTEM

D.I. REDUCER8

8

BACKFLOW

PREVENTER

4

4

4

GATE VALVE, MJ X MJ, WITH EBAA MEGALUG9

BY BY

MAINTAINED

PRIVATELY MAINTAINED

BY GRU

3" OR LARGER METER ASSEMBLY

Page: W-9.0

W-9.0

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 52: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

R/W LINE

POTABLE WATER

SERVICE LATERAL

POTABLE

WATER SERVICE

TO CUSTOMER

GRU

POTABLE

WATER METER

ASSEMBLY

(END OF GRU

MAINTENCE)

ROADWAY

REDUCED PRESSURE ZONE

BACKFLOW PREVENTER WITH

DETECTOR

SEE DETAIL W-10.1

POTABLE

WATER

MAIN

GATE VALVE

END OF GRU

MAINTENANCE

FIRE LINE

TO STRUCTURE

10' MAX.

10' MAX.

Page: W-10.0

W-10.0

POTABLE WATER SERVICE WITH FIRE LINE

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 53: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1 3/4", 1", 1-1/4", 1-1/2", 2"

ITEM DESCRIPTION

2

3

4

REDUCED PRESSURE ZONE BACKFLOW PREVENTER

GALVANIZED PIPE

GALVANIZED 90 DEG ELBOW

LOW LEAD BRASS NIPPLE

4

4"

FINAL GRADE

12"MIN-36"MAX.

TO STRUCTURE

FROM GRU

WATER METER

44

2

2

6

4

1

5 1/4 TURN LOW LEAD BRASS BALL VALVE

5

5

TEST COCK

ON VALVE

3

3

6 GRAVEL BED (NO. 57 STONE)

FLOWFLOW

3/4", 1", 1-1/4", 1-1/2", 2"

3/4", 1", 1-1/4", 1-1/2", 2"

3/4", 1", 1-1/4", 1-1/2", 2"

3/4", 1", 1-1/4", 1-1/2", 2"

3

3

Page: W-10.1

W-10.1

REDUCED PRESSURE ZONE BACKFLOW PREVENTER

SINGLE SERVICE: 3/4", 1", 1-1/4", 1-1/2", 2"

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 54: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

FINAL GRADE

GALV. NIPPLE

PIPE, GALV. (CUT TO LENGTH)

FLANGE, STEEL PIPE, SCREW-TYPE

ELBOW, GALV. 90°

NIPPLE, GALV.

GATE VALVE, NRS, FL X FL

REDUCED PRESSURE CHECK VALVE

1

2

7

6

4

5

5

12"MIN.

4

6

3

TEST COCK # 1

1

ITEM DESCRIPTION

2

3

4

5

6

7

2

4

4

TO STRUCTURE

FROM

GRU

METER

FLOWFLOW

Page: W-10.2

W-10.2

SINGLE SERVICE: 3", 4"

REDUCED PRESSURE BACKFLOW PREVENTER

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

2/20/08

Page 55: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

1

ITEM DESCRIPTION

2

3

4

2", 3", 4", 6", 8", 10" FIRE MAIN

2", 3", 4", 6", 8", 10" BEND 90° FL X FL

VALVE BOX, C.I.

2", 3", 4", 6", 8", 10" GATE VALVE, FL X FL (END GRU MAINTENANCE)

2", 3", 4", 6", 8", 10" DUCTILE IRON PIPE-FLANGE X P.E.5

2", 3", 4", 6", 8", 10" OS & Y TYPE GATE VALVE6

2", 3", 4", 6", 8", 10" BACKFLOW PREVENTOR (DOUBLE CHECK OR REDUCED PRESSURE)7

3/4" SHUTOFF VALVE AND DETECTION BYPASS METER8

9 3/4" DETECTOR CHECK VALVE

10 4" CONCRETE SLAB (3500 PSI)

11 4" GALVANIZED STEEL PIPE (SCH 40) GUARD POST - PAINTED OSHA YELLOW

12 2", 3", 4", 6", 8", 10" D.I. 90° BEND M.J. WITH EBAA MEGA LUG

SIZE VARIES

SIZE VARIES

4' TYP.

NOTE: DETECTOR CHECK VALVE ASSEMBLY MAY NOT BE REQUIRED FOR ALL INSTALLATIONS.

BACKFLOW PREVENTER ASSEMBLY SHALL BE WITHIN 10 FEET OF END OF GRU MAINTENANCE

Page: W-10.3

W-10.3

2", 3", 4", 6", 8", 10" FIRELINE CONNECTION

DOUBLE CHECK OR REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

08/22/2016

Page 56: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

NTS

10'±

L

C

PVC OR DIP WM

DIP WM

PVC OR DIP WM

D

I

P

W

M

10'±

DIP WM SIZE

VARIES, SEE

UTILITY PLAN

STORM SEWER OR

WASTEWATER PIPE,

DIAMETER VARIES

PVC OR DIP

WM SIZE

VARIES, SEE

UTILITY PLAN

FINISH GRADE

FULL LENGTH (20') SECTION OF DIP

SHALL BE INSTALLED CENTERED

AT STORM SEWER OR WASTEWATER

PIPE TO MAXIMIZE JOINT

SEPARATION AT CROSSING.

10'±

10'±

10'±

10'±

NOTE: IF CROSSING PIPE IS

STORM SEWER, DISTANCE BETWEEN

JOINTS WILL VARY, DEPENDING ON

PIPE MANUFACTURER AND TYPE.

TRACER WIRE SHALL BE CONTINUOUS ACROSS DIP SECTION OF PIPE

OFFSET FITTING

Page: W-10.4

W-10.4

ALTERNATE WATERMAIN CROSSING SECTION DETAIL

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/8/2014

AutoCAD SHX Text
%%U ALTERNATE WATERMAIN CROSSING SECTION DETAIL
AutoCAD SHX Text
OFFSET FITTINGS OR 22.5° DI BENDS W/ EBAA MEGALUG (OR EQUAL) GRU APPROVED RESTRAINED FITTING (TYP TO BOTH SIDES). USE BENDS ONLY WHEN APPROPRIATE DIMENSION OF OFFSET IS NOT AVAILABLE.
AutoCAD SHX Text
NOTE: TO BE USED AT DISCRETION OF GRU WATER & WASTEWATER ENGINEERING.
AutoCAD SHX Text
Revision Date:
Page 57: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

ALL DISTURBED EARTH OR NEW BACKFILL SHALL BE

COMPACTED TO 95% OF MODIFIED PROCTOR (ASTM D 1557)

(If installation is open trench)

10' Min

OR STEEL SHEET PILE *

3' Min

(OUTSIDE OF

PIPE TO FACE

OF SHEET PILE)

FLUSH WITH FINISHED GRADE,

BUILDING

SIDEWALK

TREE

CURB

ROADWAY

TREE - WATER SEPARATION

POTABLE WATER MAIN OR SERVICE

VINYL SHEET PILE

SHEET PILE

ALTERNATIVE PIPE PROTECTION FOR SEPARATIONS LESS THAN

7.5 FEET FROM TREES.

*Sheet pile joints to be filled with 50 year silicone caulk prior to placement.

10' M

inim

um

(M

ust extend

below

w

ater m

ain

to a depth sufficient to m

eet

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/31/09

SHEETPILE DETAIL (IN CITY LIMITS)

Page: W-10.5

W-10.5

MIN. 12" X 12" CROSS-SECTION

(NOTE: ONE 1" DIA. HOLE SHALL BE

DRILLED IN EACH PIECE OF SHEET

PILE, 2" FROM TOP EDGE AT MID-POINT,

TO FORM A BOND BETWEEN CONCRETE CAP

AND SHEET PILE. SHEET PILE SHALL BE

EMBEDDED 6" IN CONCRETE CAP.)

structural requirem

ents)

FIBER-REINFORCED CONCRETE CAP,

Page 58: Potable Water Construction Details Cover - GRU€¦ ·  · 2018-02-02thrust block design - bearing area page: w-2.2 ... concrete pipe thrust block - bend page: w-2.5 ... concrete

WA

TE

R LIN

E

C

L

15'

(7.5' FROM CENTERLINE OF PIPE)

20' UTILITY EASEMENT

(NO RESTRICTION ON TREES OUTSIDE THIS ZONE)

SE

E N

OT

E 1

F

OR

T

RE

E P

LA

NT

IN

G

RE

QU

IR

EM

EN

TS

W

IT

HIN

T

HIS

Z

ON

E

7' (3.5' FROM

CENTERLINE

OF PIPE)

SE

E N

OT

E 2

F

OR

T

RE

E P

LA

NT

IN

G

RE

QU

IR

EM

EN

TS

W

IT

HIN

T

HIS

Z

ON

E

NO

N

EW

T

RE

ES

S

HA

LL

B

E P

LA

NT

ED

WIT

HIN

T

HIS

Z

ON

E

SE

E N

OT

E 2

F

OR

T

RE

E P

LA

NT

IN

G

RE

QU

IR

EM

EN

TS

W

IT

HIN

T

HIS

Z

ON

E

SE

E N

OT

E 1

F

OR

T

RE

E P

LA

NT

IN

G

RE

QU

IR

EM

EN

TS

W

IT

HIN

T

HIS

Z

ON

E

NO

N

EW

T

RE

ES

S

HA

LL

B

E P

LA

NT

ED

WIT

HIN

T

HIS

Z

ON

E

ALL TREES PLANTED WITHIN THE UTILITIY EASEMENT SHALL CONFORM TO THE GRU PLANTING MATRIX (SEE APPENDIX C)

NOTE 1:

IF “TREES OF SPECIAL INTEREST” ARE EXISTING WITHIN THIS ZONE, TRENCHLESS INSTALLATION TECHNIQUES, SUCH AS

DIRECTIONAL BORING OR JACKING AND BORING OF A CASING PIPE SHALL BE USED THROUGHOUT THE TREE'S ROOT ZONE

OF INFLUENCE, IF REQUIRED BY CITY ARBORIST .

NOTE 2:

FOR NEW TREES PLANTED WITHIN THIS ZONE (SEE GRU PLANT MATRIX (APPENDIX C), ONE OF THE FOLLOWING SHALL BE

USED IN ORDER TO DETER THE INTRUSION OF ROOTS INTO THE SOIL ZONE AROUND THE UNDERGROUND

INFRASTRUCTURE:

1. SOILS IMMEDIATELY ADJACENT TO THE UNDERGROUND LINES SHALL BE COMPACTED TO A DENSITY OF 98% MODIFIED

PROCTOR. THREE DENSITY TESTS SHALL BE TAKEN AT EACH TREE LOCATION, SPACED 7.5 FEET APART, CENTERED ON

THE TREE. RESULTS SHALL BE SUBMITTED TO GRU FOR APPROVAL; OR

2. ENCASE LINE WITH EXCAVATABLE, FLOWABLE FILL IN ACCORDANCE WITH SECTION 121 - FLOWABLE FILL, FDOT

STANDARDS SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION; OR

3. WRAP TRENCH WITH GEO-TEXTILE FABRIC IMPREGNATED WITH INTEGRAL ROOT BARRIER NODULES, OR

4. SOLID STRUCTURAL BARRIERS SUCH AS CAST-IN-PLACE OR PRE-CAST CONCRETE PANEL, STEEL OR HIGH DENSITY

PLASTIC SHEET-PILE WALL, OR STEEL CASING SIZED PER SECTION VIII.E.1 OF THE DESIGN STANDARDS

5. FOR EXISTING TREES, IF ALLOWED TO REMAIN, TRENCHLESS INSTALLATION TECHNIQUES, SUCH AS DIRECTIONAL

BORING OR JACKING AND BORING OF A CASING PIPE WILL BE REQUIRED THROUGHOUT THE TREE'S ROOT ZONE OF

INFLUENCE.

FOR EACH OF THESE FIVE OPTIONS, THE METHOD SHALL BE USED FOR A MINUMUM HORIZONTAL DISTANCE OF 15 FEET,

CENTERED ON THE TREE.

Gainesville Regional UtilitiesPotable Water Construction Details

M o r e t h a n E n e r g y

Potable Water

Construction Details

8/28/09

TREE SEPARATION FROM POTABLE WATER MAINS AND SERVICES (IN CITY LIMITS)

Page: W-10.9

W-10.9