    Operation and Maintenance Manual3304B & 3306B INDUSTRIAL AND EPG GENERATOR SET DIESEL ENGINE

    Maintenance Schedule-3306B Engines

    Use fuel consumption or service hours, whichever occurs first, to determine maintenance intervals.

    NOTE: Experience has shown that maintenance intervals are most accurately scheduled on the basis of fuelconsumed rather than service hours.

    Daily

    Walk-Around Inspection - Inspect engine for leaks and loose connections

    Engine Crankcase - Check oil level

    Cooling System - Check coolant level

    Clutch - Check/Adjust/Lubricate

    Air Starter & Air Tank (if equipped) - Check

    Engine Air Cleaner - Check service indicator

    SR4 Generator - Inspect/Check

    Every 1,900 L (500 gal) of Fuel or 50 Service Hours*

    Dust Collector - Clean

    Light Duty Air Cleaner (If Equipped) - Replace

    Every 4,250 L (1,100 gal) of Fuel or 125 Service Hours*

    Clutch - Check/Adjust/Lubricate

    Generator Space Heaters - Check

    Every 8,500 L (2,200 gal) of Fuel or 250 Service Hours*

    Shutdown SIS

    Previous Screen

    Product: GEN SET ENGINEModel: 3306 GEN SET ENGINE 85ZConfiguration: 3306 Generator Set 85Z03764-UP

    Media Number -SEBU6328-05 Publication Date -01/11/1999 Date Updated -30/01/2002

    Page 1 of 33306 Generator Set 85Z03764-UP(SEBP2007 - 29) - Document Structure

    25.09.2013https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb...

  • 7/27/2019 PM 250 3306B

    2/3

    Scheduled Oil Sampling (SOS)1 - Obtain Sample

    Engine Oil and Filter(s)1 - Change

    Crankcase Breather1 - Clean

    Engine Valve Lash (Between First 250 and 1000 Service Hours Only)1

    - Check/Adjust

    Cooling System - Test for supplemental coolant additive concentration

    Fuel System - Clean/Replace filters, Drain water from fuel tank

    Radiator Fins, Aftercooler, Belts, and Hoses - Inspect/Check

    Fan Drive Bearing - Lubricate

    Batteries - Clean/Check

    Magnetic Pickup (At First Oil Change Only - Inspect/Clean

    1These maintenance requirements are to be performed between the 250 and the 1000 Service Hour intervalfor engines equipped with turbochargers (T, TA & ATAAC) ONLY. Refer to 500 Hour interval for

    Naturally Aspirated (NA) Engines.

    Every 17,000 L (4,500 gal) of Fuel or 500 Service Hours (NA Only)*

    Scheduled Oil Sampling (SOS) - Obtain Sample

    Engine Oil and Filter(s) - Change

    Crankcase Breather - Clean

    Engine Valve Lash (Between First 500 and 1000 Service Hours Only) - Check/Adjust

    Every 34,000 L (9,000 gal) of Fuel or 1000 Service Hours*

    Engine Protection Devices - Inspect

    SR4 Generator and Control Panel - Inspect

    Fuel Control Linkage - Lubricate

    Every 67,000 L (18,000 gal) of Fuel or 2000 Service Hours*

    Engine Valve Lash, Valve Rotators, Fuel Ratio Control, Set Point, and Low Idle - Check/Adjust

    Fuel Injection Nozzles - Test/Clean/Replace

    Page 2 of 33306 Generator Set 85Z03764-UP(SEBP2007 - 29) - Document Structure

    25.09.2013https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb...

  • 7/27/2019 PM 250 3306B

    3/3

    Turbocharger - Inspect

    Engine Mounts - Inspect

    Crankshaft Vibration Damper - Inspect

    SR4 Generator - Check/Inspect Clean/Lubricate

    Every 91,000 L (24,000 gal) of Fuel or 3000 Service Hours or Two Years*

    Cooling System - Add Extender (Extended Life Coolant Only) -

    Cooling System - Drain/Clean/Replace Coolant - Conventional Coolant/Antifreeze Only

    Water Pump Seal - Inspect/Replace

    Hoses - Replace

    Thermostat - Replace

    Every 136,000 L (36,000 gal) of Fuel or 4000 Service Hours*

    Magnetic Pickup - Inspect/Clean

    SR4 Generator - Check/Inspect/Clean/Lubricate

    Every 204,000 L (54,000 gal) of Fuel or 6,000 Service Hours or Four Years

    Cooling System - Drain/Flush/Replace Coolant (Extended Life Coolant Only)

    *Perform previous maintenance interval items first.

    Copyright 1993 - 2013 Caterpillar Inc.All Rights Reserved.Private Network For SIS Licensees.