plugs into cn61 on indoor pcb
DESCRIPTION
6. 5. 4. 3. 2. 1. Adaptor For Run/Fault Indication & Remote On/Off For VRF, DI & SDI( Part Number TRF ). FAULT SIGNAL. For Run / Fault Indication. COM (+12VDC). RUN SIGNAL. 6. Local on/off prohibit. - PowerPoint PPT PresentationTRANSCRIPT
5
6
4Plugs
Into CN61on indoor PCB
Adaptor For Run/Fault Indication & Remote On/Off For VRF, DI & SDI( Part Number TRF )
6
5
4
3
2
1
Local on/off prohibit
RUN SIGNAL
COM (+12VDC)
FAULT SIGNAL
ON/Off Control
1
3
5
4
2
6
Max 10m between indoor PCB and relay ( Field
Supplied )
For Run / Fault Indication
COM (Volt Free)
3
2
1
Used For Remote on/off (jumper 01 on master PCB must be cut – otherwise it responds to pulse) & local on/off control prohibit
Field supply relay
no
nc
Cooling signal
Notes.When contact 1 – 2 made unit on with full use of remote controller ie on / off button works. During cooling on signal (2 – 3 made) remote controller is completely locked.When cooling signal off unit automatically restarts.