Technical Document Revision 1.0 March, 2009 www.cermate.com PLC Connection Guide TN512D Communication settings between Siemens S7-200 PPI and PanelMaster HMI Revision Record Revision Date Content Owner

Upload: haquynh

Post on 06-Mar-2018

295 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

Technical Document

Revision 1.0

March, 2009

www.cermate.com

PLC Connection Guide

TN512D Communication settings between

Siemens S7-200 PPI and PanelMaster HMI

◎Revision Record

Revision Date Content Owner

Page 2: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 2 of 9 www.cermate.com

Preface

This tech note introduces how to connect Siemens S7-200 PPI Port with PanelMaster

HMI.

<S7-200 CPU>

1) PLC Parameter setting:

Execute the “STEP 7 MicroWIN” software to link with the S7-200 PLC via PPI Adapter program cable.

PPI Port (Port0 & Port1)

Page 3: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 3 of 9 www.cermate.com

Create a new project and select the CPU to set its communication format from “System Block”.

NOTE: The standard format is 9600, 8, Even, 1 and the PLC Address is “2”

Execute “Set PG/PC Interafce” --- “PC/PPI cable(PPI)” option to select the correct communication port

on PC side.

Page 4: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 4 of 9 www.cermate.com

Execute “Communication” option, it can find out the PLC automatically.

If the communication port is correct, you can execute the download/upload function to change the “PLC

Page 5: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 5 of 9 www.cermate.com

Address”/”Baud Rate”…etc.

Connection Cable diagram

HMI Side PLC Cable Side

COM1 9-PIN Male PPI Port 9-PIN Male (RS485)

485 + 1 3 485+

485 - 6 8 485-

SG 5 5 SG

HMI Side PLC Cable Side

COM2 T.B. 5-PIN PPI Port 9-PIN Male (RS485)

485 TX+ 1 3 485+

485 TX- 4 8 485-

SG 5 5 SG

2) HMI setting:

Page 6: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 6 of 9 www.cermate.com

(a) S7-200 (PPI; 1-to-1) Setting: (Without Token Command)

Select Device/Server:Siemens AG → Simatic S7-200 (PPI; 1-to-1)

NOTE: Driver Name --- C39001.dll / C39001.mod

Set the HMI link port parameter identical with PLC communication parameter

(b) S7-200 (PPI; Network) Setting: (With Token Command)

Page 7: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 7 of 9 www.cermate.com

Select Device/Server: Siemens AG → Simatic S7-200 (PPI; Network)

NOTE: Driver Name --- C39011.dll / C39011.mod

Set the HMI link port parameter identical with PLC communication parameter

Note: The network driver is using token command to link with PLC and HMI, it can be used

to link with different devices that support PPI Network protocol.

Page 8: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 8 of 9 www.cermate.com

3) PLC Memory Address

Bit Devices (PPI; 1-to-1 & Network)

Word Devices (PPI; 1-to-1 & Network)

NOTE: Device named DBWn specified same as VWn.

Page 9: PLC Connection Guide -  · PDF filePLC Connection Guide ... Siemens S7-200 PPI and PanelMaster HMI ... ,1´VRIWZDUHWROLQNZLWKW KH6 -200 PLC via PPI Adapter program cable. PPI

TND512-E0

Page 9 of 9 www.cermate.com

Technical Support Information Cermate (Shanghai) 屏通科技(上海)有限公司 Phone: +86-21-51758590~2 FAX : +86-21-51758589 E-mail: [email protected] Cermate (Shenzhen) 屏通科技(深圳)有限公司 Phone: +86-755-83572781, 755-83562179, FAX : +86-755-83562294 E-mail: [email protected] Cermate Technologies Inc. 屏通科技股份有限公司(台灣) 7F-1, No. 168, Lien-Cheng Road, Chung-Ho City, Taipei, Taiwan 235 R.O.C. Phone: 886-2-22437000 FAX : 886-2-22499933 E-mail: [email protected]

Brand Label Contact Windows:

China: 86-13823788405 [email protected]

Taiwan: 886-910011915 [email protected]

Worldwide: 886-910011914 [email protected]