The DANLERS range of passive infra-red occupancy switches is designed for the automatic control of lighting, heating, ventilation or air conditioning loads.
The PIR switch will switch on the connected load automatically when an area is occupied, and then switch it off automatically when the area has been vacant for a chosen duration. This has the benefits of reduced energy bills and automatic control. When being used to control lighting, the built-in photocell can be used to keep the lights off on bright days.
• Offices
• Factories
• Warehouses
• Schools
• Leisure centres
• Hospitals
• Canteens
• Staff rooms
• Corridors and stairwells
• Residential homes
• Military accommodation
• Student accommodation
• Toilet blocks
• Changing rooms
• Plus many other uses
PIR occupancy switches are ideal for:
PIR OCCUPANCY SWITCHES
PIR occupancy switches
PIR OCCUPANCY SWITCHES
7
PIR occupancy switch functions
Each PIR occupancy switch in the DANLERS range has a passive infra-red quad person detector. This detects the movement of a warm body moving within its detection zone. When such a movement is detected the load is switched on. There is a time lag function which is adjusted using a spindle on the side of the product. The time lag is the time that must elapse with no movement detected before the PIR occupancy switch will switch off.
There is a built-in, adjustable, photocell override which can be used to keep lights off when there is sufficient daylight available. The photocell can only be used in this way if the amount of natural daylight exceeds the level of the artificial lights. The photocell can be set to inactive when controlling heating, ventilation or air conditioning. The photocell is also adjusted by a spindle on the side of the product.
Each PIR occupancy switch contains a relay suitable for switching any type of load, including fluorescent lights and fans.
A few PIR occupancy switches may be wired in parallel to control the same load. However, there are minimum load restrictions with the WAPIR model only (see page 19).
The PIR occupancy switches require a mains supply.
Simple adjustment spindles
Night, Unoccupied – Lighting OFF
Night, Occupied – Lighting ON
Enough daylight, Unoccupied – Lighting OFF
Enough daylight, Occupied – Lighting OFF
PIR occupancy switch brings lights on – only when needed
Function demonstrated with the lighting in an office
PIR OCCUPANCY SWITCHES
8
PIR occupancy switch specifications
PIR detector
Passive infra-red quad person detector.
Adjustable time lag
Time lag adjustable in 9 steps (approximate values):
10 seconds 1.25 minutes 10 minutes 20 seconds 2.5 minutes 20 minutes40 seconds 5 minutes 40 minutes
Adjustable photocell
"Inhibit on" photocell. The photocell will inhibit the lights from switching on when somebody enters an area with plenty of ambient light. However, if somebody is already occupying an area with the lights switched on, the lights will remain on while the area is occupied, regardless of any increase in the ambient light level. This is to avoid any nuisance switching off when somebody is in the middle of a task or meeting.
Range 100-1000 lux (and inactive), falling on the working plane.
Loading
All models can switch up to 6 amps (1500W at 230VAC) of resistive, inductive or fluorescent lighting loads, or up to 1amp (250W) of fans. For the WAPIR model there are some minimum load requirements (details on page 19).
Wiring in parallel
A few PIR switches can be wired in parallel to control the same load. Again for the WAPIR model there are some minimum load requirements (details on page 19).
Start-up Mode
(Relevant to all models except WAPIR)
When the mains supply is initially connected to the PIR occupancy switch it goes through its Start-up Mode. This means it switches on for about 1 minute, then switches off and enters its Operating Mode. If a manual wall switch is feeding the PIR occupancy switch (see wiring diagrams on appropriate product pages) then it will go through the Start-up Mode each time the wall switch is switched on.
By wiring the manual wall switch in the alternative position, the supply to the PIR occupancy switch is uninterrupted and it remains in Operating Mode. It does not go through its Start-up Mode each time the wall switch is switched on.
PIR OCCUPANCY SWITCHES
Selecting the appropriate PIR occupancy switch
WALL MOUNTEDCEILING MOUNTED
360˚ detection zone
120˚ detection
angle
Long rangedirectional
narrow beam
120˚ directionaldetection
angle
Flush mounted (false or plasterboard ceilings)
Surface mounted
Surface mounted
Surface mounted
Hard wired
Hard wired
Hard wired
Plug andsocket
Hard wired
Plug andsocket
Plug andsocket
Plug andsocket
No neutralwire
needed
Needsneutral
wire
CEFL PIR
Page 12
CEFL PIRSEALED
Page 12
CEFL PIR 10A
Page 12
CEFLP PIR + CESO
Page 12
CESF PIR
Page 13
CELO + CESO SQ
Page 14
CEDR 6P + CESO
Page 16
CEDR 6PLR + CESO
Page 17
WACE PIR
Page 18
WAPIR
Page 19
Plaster depth(16mm) wall box
9
5m 10m0
Scale
PIR OCCUPANCY SWITCHES
10
Application diagram
The diagram illustrates PIR occupancy switch siting within a typical office/factory facility. The coloured zones emanating from the controls show strong detection zones (darker tints with solid coloured line) and secondary detection zones (lighter tint with broken coloured line).
Ceiling flush mounted CEFL PIR spaced every 5 metres to cover the open plan office and control the lights. The CEFL PIR can be wired in groups in parallel, to control the lighting in zones.
Long range directional CEDR 6PLR to detect people in the 25 metre corridor.
Two ceiling flush mounted CEFL PIR controlling the lights in a meeting room. In this, and other offices, a manual wall switch is retained to override the lights to off, e.g. for a video presentation.
Small offices are covered by a single ceiling flush mounted CEFL PIR.
The wall switch has been replaced by a wall mounted WAPIR.
BOARD ROOM OFFICE
OFFICE
OFFICE
CORRIDOR
OPEN PLAN OFFICES
RECEPTION
STAIRWELL
TOILETS
FACTORY AREA
HIGH BAY RACKING
MACHINE SHOP
OP
EN
STA
IRC
AS
E
HIGH BAY RACKING
SHOWER ROOM
TOILET LOBBY
11
Long range directional CEDR 6PLR detects people in a racking storage aisle.
Ceiling surface mounted CESF PIR spaced every 5 metres to give total coverage of the open plan factory area.
Ceiling flush mounted CEFL PIR spaced every 5 metres to cover the open plan reception area and control the lights.
Ceiling plug-in CELO mounted on BESA box on ceiling conduit. Spaced at 5 metre intervals to control the lights in the machine shop.
In the shower room a CEFL PIR SEALED is used, as it has protection against light splashes and condensation.
In the toilets a ceiling flush mounted CEFL PIR has been wired in parallel with a wall mounted WACE PIR in the lobby, to control the lighting in both rooms together.
Two ceiling surface mounted CESF PIR (one on each landing) wired in parallel to control the lighting in the stairwell.
Ceiling directional CEDR 6P covers the open staircase.
BOARD ROOM OFFICE
OFFICE
OFFICE
CORRIDOR
OPEN PLAN OFFICES
RECEPTION
STAIRWELL
TOILETS
FACTORY AREA
HIGH BAY RACKING
MACHINE SHOP
OP
EN
S
TAIR
CA
SE
HIGH BAY RACKING
SHOWER ROOM
TOILET LOBBY
PIR OCCUPANCY SWITCHES
12
Special versions
Plug and socket version: CEFLP PIR
Model CEFLP PIR is provided with a plug suitable for the CESO Ceiling socket shown on page 15.
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Splash-proof version: CEFL PIR SEALED
Model CEFL PIR SEALED is protected against light splashes and condensation when installed in the ceiling. Ideal for bathrooms, shower rooms, etc.
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
10 amp version: CEFL PIR 10A
Model CEFL PIR 10A is suitable for switching up to 10 amps (2500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Ceiling flush-mounted PIR occupancy switch
Control plugged into a CESO on
a BESA box
These neat and unobtrusive models are ideal for flush mounting through suspended or plasterboard ceilings. They have a 2m cable, for quick and easy installation.
Order code: CEFLP PIR
Order code: CEFL PIR
Order code: CEFL PIR SEALED
Order code: CEFL PIR 10A
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 1 and 2 below
Dimensions: 72mm diameter x 68mm
NN
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areas For best coverage the CEFL PIR should be spaced every 5m in either direction
CEFL PIR Strong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zonePlan view of detection e S
Detection diagrams
L
load
optional manual wall switch for overriding off
A few CEFL PIR230 VAC
L
load
CEFL PIR
optional manual wall switch for overriding off
1. Single CEFL PIR
230 VAC
alternative position for optional wall switch (see p.8 “Start-up Mode”)
2. A few CEFL PIR wired in parallel
alternativeposition for optional wall switch (see p.8 “Start-up Mode”)
Dimensions in mm
1. Single CEFL PIR 2. A few CEFL PIR wired in parallel
Wiring diagrams
Ideal for false or plasterboard
ceilings
55
3
2m cable
60
72
72
side plan
66
Requires 63 or 64mm (2.5") diameter hole in a false or plasterboard ceiling
38
PIR OCCUPANCY SWITCHES
13
These surface-mounted models are ideal for solid ceilings.
Ceiling surface-mounted PIR occupancy switch
Can be mounted on a square pattress box, order code: PABO.
Order code: CESF PIR
The CESF PIR is a hard wired version and can be mounted on a square pattress box.
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 3 and 4 below
Dimensions: 86 x 86 x 22mm. Requires back box depth 16mm
L
Nload
A few CESF PIR230 VAC
L
N
load
CESF PIR
optional manual wall switch for overriding off
3. Single CESF PIR
230 VAC
4. A few CESF PIR wired in parallel
Dimensions in mm Wiring diagrams
Fig. 201 Ceiling mounted PIR occupancy switch
Up to 5m
Up to 7m
Up to 5m
Up to 7m
Up to 5m
Up to5m
In open plan areasFor best coverage the CESF PIR should be spaced every 5m in either direction
CESF PIRStrong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zonePlan view of detection e S
Detection diagrams
plan side
22
86
86
alternative position for optional wall switch (see p.8 “Start-up Mode”)
alternativeposition for optional wall switch (see p.8 “Start-up Mode”)
optional manual wall switch for overriding off
Requires 16mm deep box
PIR OCCUPANCY SWITCHES
14
Ceiling surface-mounted plug-in PIR occupancy switch
These surface-mounted models are ideal for solid ceilings.
Order code: CELORequires socket, order code:CESO SQ or CESO(see page 15)
The CELO has a built-in plug suitable for the CESO SQ Ceiling socket (or CESO Ceiling socket). CESO SQ can be mounted on a square pattress box (or CESO can be mounted on a BESA box).
Specification
Detection zone: 360°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: (Each circuit) up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 5, 6, 7 below
Dimensions: 88 x 88 x 47mm
L
load
optional manual wall switch for overriding off
CELOCELOCELO230 VAC
5. Single CELO 6. A few CELO wired in parallel
Dimensions in mm
5. Single CELO 6. A few CELO wired in parallel
Wiring diagrams
7. Ceiling mounted socket (CESO SQ or CESO)
L N SL CELO Not to scale
CESO SQor CESO
Pattress box orBESA box
luminaire
L N
SL
N
L
load
CELO
optional manual wall switch for overriding off
230 VAC
N
plan side
47
88
88
(CESO SQ)
alternativeposition for optional wall switch (see p.8 “Start-up Mode”)
alternative position for optional wall switch (see p.8 “Start-up Mode”)
Up to 5m
Up to 7m
Up to 5m
Up to 7m Up to 5m
Up to5m
In open plan areasFor best coverage the CELO should be spaced every 5m in either direction
CELOStrong detection zone
Secondary detection zone
Strong detection zone i.e. person moving arm
Secondary detection zone i.e. person walking (less sensitive when walking straight towards PIR switch)
For optimum coverage recommended mounting height between 2.4 and 5m.
PIR Quad detector gives 124 detection areas within the zone.
Plan view of detection zone Several PIR occupancy switchesPerspective view of detection zonePlan view of detection e Se SPerspective e S
Detection diagrams
Ceiling socket (CESO SQ)
ANCILLARY PRODUCTS
15
Ceiling socket: CESO
For use with DANLERS plug-in ceiling controls. Can be mounted on a BESA box.
Wiring diagram: See diagram 8 below
Dimensions: 74mm diameter x 13mm
Order code: CESO
Sockets for plug-in ceiling controls
8. Ceiling mounted socket (CESO or CESO SQ) for plug-in ceiling controls
L N SLplug-in ceiling control Not to scale
CESO or CESO SQ
BESA box orpattressbox
luminaire
L N
SL
L1
N1
CE2SLplus plug-in switch
separate circuit
230 VAC
optional manual wall switch for overriding off
SL1
load
L1
SL2N/C
N1
CESLplus plug-in switch
separate circuit
optional manual wall switch for overriding off
230 VAC load
SL1
SL2N/O
C2 SL2N/O
SL2N/C
SL3N/O
SL3N/C
C3C2
separate circuit
10. Plug-in control plus double slave relay with volt free changeover contacts (CE2SL) controlling two extra circuits
9. Plug-in control plus slave relay with volt free changeover contacts (CESL) controlling one extra circuit
Wiring diagrams
Ceiling socket (CESO)
side
plan
74
13
Ceiling slave relays (CESL / CE2SL)
plan side
41
87
87
87
Dimensions in mm
Order code: CESO SQ
plan side
13
87
87
87
Slave relays for plug-in ceiling controls
Ceiling socket with slave relay: CESL
Ceiling socket with slave relay with isolated changeover contacts. Enables the switching of an additional circuit with its own supply, e.g. the corridor lights outside an office or a separate low voltage control circuit.
Loading: (Each circuit) up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans
Wiring diagram: See diagram 9 below
Dimensions: 87 x 87 x 41mm
Ceiling socket with double slave relay: CE2SL
Ceiling socket with a double slave relay with isolated changeover contacts. Enables the switching of two additional circuits, each with its own supply, e.g. the corridor lights outside an office, plus the extractor fans inside the office. Also ideal for controlling two separate low voltage control circuits.
Loading: (Each circuit) up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans
Wiring diagram: See diagram 10 below
Dimensions: 87 x 87 x 41mm
Order code: CESL or CE2SL
Also available as a square socket.
Ceiling socket: CESO SQ
Can be mounted on a square pattress box.
Wiring diagram: See diagram 8 below
Dimensions: 87 x 87 x 13mm
PIR OCCUPANCY SWITCHES
16
Ceiling directional PIR occupancy switch
Standard rangeOrder code:CEDR 6PRequires socket, order code: CESO(see page 15)
Standard range version
Designed to give a directional view of the activity to be monitored.Detection angle 120°.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 11, 12, 13 below
Dimensions: See below
CEDR 6P can be rotated and lowered
to a 45º angle
These directional PIR switches plug into a ceiling mounted socket. The socket can be mounted on a BESA box.
L
load
optional manual wall switch for overriding off
A few CEDR 6P230 VAC
L
load
CEDR 6P
optional manual wall switch for overriding off
11. Single CEDR 6P
230 VAC
12. A few CEDR 6P wired in parallel 13. Ceiling mounted socket (CESO)11. Single CEDR 6P 12. A few CEDR 6P wired in parallel 13. Ceiling mounted socket (CESO)
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone
60° 120°
CEDR 6P
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone
60° 120°
CEDR 6P
Plan view Side elevation
CEDR 6P
Detection diagrams
Dimensions in mm
Wiring diagrams
L N SL CEDR 6P Not to scale
CESO
BESA box
luminaire
L N
SL
NN
alternative position for optional wall switch (see p.8 “Start-up Mode”)
alternativeposition for optional wall switch (see p.8 “Start-up Mode”)
60
74
64
102
side
(CESO)
Perspective view
PIR OCCUPANCY SWITCHES
17
Ceiling directional PIR occupancy switch
Long rangeOrder code:CEDR 6PLRRequires socket, order code: CESO(see page 15)
Long range version
With a long range, narrow detection beam. Designed for corridors and storage aisles.
Specification
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 14, 15, 16 below
Dimensions: See below
These directional PIR switches plug into a ceiling mounted socket. The socket can be mounted on a BESA box.
L
load
optional manual wall switch for overriding off
A few CEDR 6PLR230 VAC
L
load
CEDR 6PLR
optional manual wall switch for overriding off
14. Single CEDR 6PLR
230 VAC
alternative position for optional wall switch (see p.8 “Start-up Mode”)
15. A few CEDR 6PLR wired in parallel
alternativeposition for optional wall switch (see p.8 “Start-up Mode”)
16. Ceiling mounted socket (CESO)
L N SL CEDR 6PLR Not to scale
CESO
BESA box
luminaire
L N
SL
14. Single CEDR 6PLR 15. A few CEDR 6PLR wired in parallel 16. Ceiling mounted socket (CESO)
Wiring diagrams
Up to 25m
CEDR 6PLR
Strong Detection Zonei.e. person moving arm
Secondary Detection Zonei.e. person walking across the zone
Up to 10m Up to 25m
CEDR 6PLR
15mUp to 10m
15m
6°
Plan view
Side elevation
Detection diagrams
CEDR 6PLR
Ideal mounting height between 2.2 and 3m
Dimensions in mm
NN
60
74
64
115
side
(CESO)
CEDR 6PLR can be rotated and lowered
to a 45º angle
Perspective view
PIR OCCUPANCY SWITCHES
18
Wall or ceiling mounted PIR occupancy switch
The WACE PIR is suitable for either wall or ceiling mounting. It fits either into a plaster depth (16mm) wall box or onto a ceiling mounted square pattress box. It requires a neutral wire.
Order code: WACE PIR
Applications
Suitable for stairwells, corridors, toilet lobbies, etc.
Version incorporating override off button, enabling lights to be held off during video presentations etc, available by request.
Specification
Detection angle: 120°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 17 and 18 below
Dimensions: 86 x 86 x 22mm. Wall box depth 16mm
17. Single WACE PIR 18. A few WACE PIR wired in parallel, eg. in a stairwell
17. Single WACE PIR 18. A few WACE PIR wired in parallel,
Wiring diagramsDimensions in mm
Requires 16mm deep box
Up to 5m Up to 10m
WACE PIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone 45°
90° WACE PIR
Up to 5m Up to 10m
WAPIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone 45°
90° WAPIR
Plan view Side elevation
Wall mounted PIR occupancy switch
Ideal mounting height between 1 and 1.8m
Detection diagrams
L
Nload
A few WACE PIR
230 VAC
load
L
N
WACE PIR
230 VAC
plan side
2286
86
Perspective view
PIR OCCUPANCY SWITCHES
19
The WAPIR model replaces an existing wall switch – no neutral wire is needed. It fits into a plaster depth (16mm) wall box. The WAPIR model also has a manual override off switch on the front of the plate.
Wall mounted PIR occupancy switch
Order code: WAPIR
Applications
The WAPIR requires a permanent live supply and should only be used in applications where the lights would not be on for more than 12 hours per day. This is to allow its rechargeable battery enough time to recharge itself from the mains supply.
The WAPIR is suitable for small offices, meeting rooms, tutoring rooms, etc.
The override off button enables the lights to be held off during video presentations, etc.
For wall mounting only.
Specification
Detection angle: 120°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 100 to 1000 lux, and inactive
Maximum Load: 1500W (6 amps) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Minimum Load: 40W resistive or approximately 100W inductive per WAPIR in the circuit. Load capacitors (order code CAPLOAD) can be supplied to augment small loads.
Wiring diagram: See diagram 19 below
See diagram 20 below for wiring in parallel
Dimensions: 86 x 86 x 22mm. Wall box depth 16mm
19. Single WAPIR 20. A few WAPIR wired in parallel
Dimensions in mm
19. Single WAPIR 20. A few WAPIR wired in parallel
Wiring diagrams
Requires 16mm deep wall box
Up to 5m Up to 10m
WACE PIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone 45°
90° WACE PIR
Up to 5m Up to 10m
WAPIR Strong Detection Zone
Secondary Detection Zone 60°
120°
Up to 5m Up to 10m
Strong Detection Zone
Secondary Detection Zone 45°
90° WAPIR
Plan view Side elevation
Wall mounted PIR occupancy switch
Ideal mounting height between 1 and 1.8m
Detection diagrams
L
Nload
WAPIR WAPIR WAPIR
230 VAC
L
N
230 VAC
load
WAPIRplan side
2286
86
Perspective view
These modules are suitable for mounting onto Eurodata plates and fit into a 35mm deep wall box. They are also suitable for building into luminaires (see page 64 for fixing bezel). They require a neutral wire.
Order code: GREUW PIR5X
5m detection - concealed adjustment spindles
Adjustment spindles hidden behind front surface lid for a neat finish (module must be removed from wall plate or luminaire to adjust).Can be suited in with other Eurodata modules.
Specification
Detection angle: 100°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 21 and 22 below
Dimensions: 50 x 25 x 38mm, minimum wall box depth of 35mm
21. Single PIR occupany switch module 22. A few PIR occupany switch modules wired in parallel, eg. in a stairwell
21. Single PIR occupany switch module 22. A few PIR occupany switch modules
Wiring diagramsDimensions in mm
L
Nload
A few PIR occupancy switch modules
230 VAC
load
L
N
PIR occupancy switch module
230 VAC
PIR OCCUPANCY SWITCH MODULES
20
Dimensions in mmGREUW PIR5X, GREUW PIR5E.Requires wall box depth of 35mm
3825
50
front side
Order code: GREUW PIR5E
5m detection - visable adjustment spindles
Adjustment spindles visable on front surface for quick and convenient adjustment. Can be suited in with other Eurodata modules.
Specification
Detection angle: 100°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 21 and 22 below
Dimensions: 50 x 25 x 38mm, minimum wall box depth of 35mm
Up to 7m
GREUW PIR5X or GREUW PIR5E
Detection zone
For optimum coveragerecommended mounting height between 2.4 and 5m
Up to5m
Plan view (wall mounted)
GREUW PIR5X or GREUW PIR5E
Side elevation (wall mounted)
GREUW PIR5X or GREUW PIR5E
Perspective view (ceiling mounted)
Up to 5m
DetectionZone40°
80°
Up to 5m
DetectionZone50°
100°
Detection diagrams
These modules are suitable for mounting onto Eurodata plates. They are also suitable for building into luminaires (see page 64 for fixing bezel). They require a neutral wire.These versions are best suited for use in areas such as warehouses, sports halls and circulation areas, where there is likely to be a significant level of movement.
Order code: GREUW PIR10X
10m detection - concealed adjustment spindles
Adjustment spindles hidden behind front surface lid for a neat finish (module must be removed from plate or luminaire to adjust).Can be suited in with other Eurodata modules.
Specification
Detection zone: 360°
Detection angle: 110°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 23 and 24 below
Dimensions: 50 x 25 x 38mm, minimum back box depth of 35mm
23. Single PIR occupany switch module 24. A few PIR occupany switch modules wired in parallel, eg. in a stairwell
23. Single PIR occupany switch module 24. A few PIR occupany switch modules
Wiring diagramsDimensions in mm
L
Nload
A few PIR occupancy switch modules
230 VAC
load
L
N
PIR occupancy switch module
230 VAC
Dimensions in mmGREUW PIR10X, GREUW PIR10E.Requires back box depth of 35mm
3825
50
front side
Order code: GREUW PIR10E
PIR OCCUPANCY SWITCH MODULES
21
10m detection - visable adjustment spindles
Adjustment spindles visable on front surface for quick and convenient adjustment. Suitable for mounting onto a Eurodata plate. Can be suited in with other Eurodata modules.
Specification
Detection zone: 360°
Detection angle: 110°
Time lag range: 10 seconds to 40 minutes in 9 steps
Photocell range: 15 to 1000 lux, and inactive
Loading: Up to 6 amps (1500W) of resistive, fluorescent or inductive lighting loads, or up to 1 amp (250W) of fans.
Wiring diagram: See diagrams 23 and 24 below
Dimensions: 50 x 25 x 38mm, minimum back box depth of 35mm
Up to 15m
GREUW PIR10X or GREUW PIR10E
Detection zone
For optimum coveragerecommended mounting height between 5 and 10m
Up to12m
Perspective view (ceiling mounted)