Pillar Fire Hydrant SAPHIR BRONZE Series A1 42
BAYARD - Series A1 42 - T19020-EN
2
1 - Information
1 - 1. Applications :
• Non-freezing pillar fire hydrant with apparent outlets SAPHIR for connection
above ground of the mobile equipment of fire protection services on a
network under pressure.
• SAPHIR: Traffic type and non Traffic type Series A1 42.
• Public or private firefighting networks, under permanent pressure
or on request.
• For suction facilities, refer to our Intake Hydrants series A1 94 or A1 95.
1 - 2. Features:
• DN 80 to 150.
• Made in France since 1950 in Vénissieux, then in Meyzieu.
• Series according to European standards, outlets with French Standards:
- NF EN 14384.
- NF EN 1074 - 6.
- NF EN 14384/CN.
- Conformity certificate CE 0679 - CPR - 0213.
- NF label holder.
- Certified in conformity with UE N°305/2011 regulation.
- NF E 29 - 572, symmetrical outlets.
- NF EN 12266 - 1, sealing rate A, torque level 1.
- EN 1092 - 2, flanges drilling ISO PN 10/16.
- Drinking Water Certified.
- Paint RAL 3000.
Pillar Fire Hydrant SAPHIR BRONZE - Description
Airclap
Anti-water hammer and anti-vibration main valve guide
Internal/external epoxy coating
360°Rotation
DN 80 to DN 150
Traffic type and Non traffic type
Spare parts guarantee 5 years 5 years 10 years
Stationary drain
Removable drain
Upper Part: red polyester paint
Stainless steel components
Bronze seat
BAYARD - Series A1 42 - T19020-EN
3Pillar Fire Hydrant SAPHIR BRONZE - Description
1 - 3. Design: - Outlets with symmetric coupling (French Norm). - The DN 65 outlet has an Airclap cap (Fig. 1) letting the air in for
drainage. It also allows to check that the hydrant is not under pressure before opening the cap. A simple tap of your finger is enough to make it work and ensure the safety of users.
- Warning stickers are affixed on all caps. - Thermoplastic cover on cap for Saphir with reflective strips for increased
visibility at night. - Clockwise closing
- The specific design of the main valve guide is anti-water hammer and anti-vibration providing a smooth opening/closing (Fig. 2 and Fig. 10 Item 4 p5)
- The thick valve gasket helps the sealing even in presence of foreign bodies(Fig. 2 and Fig. 10 Item. 5 p5).
- Hydraulic ball drain.
- Drain protection with the anti-root system 01 (Fig. 3).
- Duckfoot with loose flanges 02 (Fig. 3).
Fig. 1
13 turns
Smooth closing, blue curve.1 2 3 4 5 6 7 8 9 10 11 12 13 turns
Standard equipment on all hydrants models
Flow value example according to the number of opening torques of a DN100hydrant. Sudden stop with standard
valve (water hammer). Progressive stop with our anti
water-hammer valve
Fig. 2
Fig. 3
01
02
Air inlet Airclap andwarning sticker
BAYARD - Series A1 42 - T19020-EN
4Pillar Fire Hydrant SAPHIR BRONZE - Description
1 - 4. Performances:
• Low operating torque over time.
- Bubble tight shut-off.
- Non-freezing type.
- Kv above the norm (see table page 7).
• Anticorrosion protection:
- Upper barrel with internal and external epoxy coating, by cataphoresis +
red polyester paint with UV protection (RAL 3000).
• Easy to install:
- 360° Rotating upper part, degree by degree without diggingt (Fig. 4).
- It is possible to fit a BAYARD sleeve, between the seat and duckfoot,
to raise the hydrant during installation, (heights 0.05 - 0.15 and 0.25 cm)
(Fig. 5).
- A polystyrene packing, fully recyclable, pprotects the hydrant from any
projection during installation (Fig. 6). (DN 150 in wooden crate).
• Quick and easy commissioning:
- Suitable with universal Drainkit to ease drainage on DN 80 and 100, DN 150
(Fig. 7).
- Option: our drain is threaded and possibly funneled with a simple
connection, according to the site’s constraint (Fig. 8).
- Operating square 30x30.
Fig. 4
Fig. 7
Fig. 8
Fig. 6
Fig. 5
BAYARD - Series A1 42 - T19020-EN
5Pillar Fire Hydrant SAPHIR BRONZE - Description
Fig. 10
06
07
05
04
Fig. 9
• Advantages of our range to reduce maintenance costs (Fig. 9 and 10) :
- Complete spare parts available. Interchangeability since 1971 with
past versions (for DN 80-100).
- Quick and easy dismantling of the upper operating set, through
the upper part.
- Quick and safe dismantling of the lower operating set.
- Extension sleeve kit of 0.20 m after installation, without digging on
DN 80 (2016) and 100 (>2003).
- Conversion of a non traffic hydrant into a traffic version
(traffic) without digging with the mini kit CHOC (Fig.10 Item. 6).
• Our fire hydrant is eco-friendly:
- 99% of its components are recyclable.
- Our PSE (polystyrene) packing is made of 2% of recycled material
and 98% of air.
It needs very little energy to manufacture, is 100% recyclable for life by
grinding, compaction and extrusion of PES granules.
LIVRET PIÈCES DE RECHANGE
POTEAUX D’INCENDIE APRÈS 2016
W16001A
LIVRET PIÈCES DE RECHANGE
POTEAUX D’INCENDIE AVANT 2016BOUCHES D’INCENDIE
W15019B
BAYARD - Series A1 42 - T19020-EN
6Pillar Fire Hydrant SAPHIR BRONZE - Description
Cast iron, Bronze or aluminum badges
Stickers
• Options:
Stickers, special colors, special outlets, several heights ….
HYDRANTS CUSTOMIZATION SPECIAL HYDRANTS
Our automatic solution for leak detection, with daily acoustic correlation integrated in our fire hydrants.
The solution for precise leak location: - Sharp filtering of unwanted noises, - Dedicated software to analyze data in a few minutes, - An expert system to optimize the number of modules to be deployed
and their location.
To fight against ”street pooling” or wild opening of hydrants restricting their use to firefighting and authorized persons
KIT SECURE
100% web-based asset management solution.Provides tools to organize maintenance and create work orders on all firefighting equipment. The created data base allows to share follow-up onhydrants through NFC tags, with real-time data updating, with authorities,town halls, companies …
TAGUATM
This real-time alert system allows: - evaluation of drawn volumes, - monitoring water drawings, - fighting against suspicious water drawing
COPERNICTM
Reduced height
BAYARD - Series A1 42 - T19020-EN
7Pillar Fire Hydrant SAPHIR BRONZE - Description
b b
a
a±5° b±5°
DN 80 DN 100 DN 150 DN 80 DN 100 DN 150
1 outlet 3 outlets - 3 outlets 1 outlet 3 outlets - 3 outlets
Saphir 70° 70° 70° - 0° 65° 65° -
Saphir Traffic - - 70° 70° - - 65° 65°
1 - 6. Sizes, weight, and performances:
Prepared ground level
B
E
DN
30x30xOperating square
* Kv is the maximum flow, in m3/h, measured separately per outlet, according to norm EN14384.Torque Level 1.Total number of turns for opening: 13 ± 1 turns for DN 80 and 100 and 17 ± 1 turns for DN 150.Number of dead turns: maximum 2.
DN TRAFFICNON TRAFFIC
Bmm
Length
Amm
Cmm
Dmm
Emm
Flow expressed
in m3/h
Nboutlets
Kv* outlet WeightkgDN 40 DN 65 DN 100
n° 2 - 80 (60/65) NON TRAFFIC 1000 760 430 535 120 30 1 x 65 - 134 - 64
n° 2 - 80 (60/65) NON TRAFFIC 1200 760 430 535 120 30 1 x 65 - 134 - 66
n° 2 - 80 NON TRAFFIC 1000 760 430 535 135 30 1 x 65 - 137 - 65
n° 2 - 80 TRAFFIC 1000 760 430 535 135 30 1 x 65 - 136 - 65
n° 2 - 80 NON TRAFFIC 1200 760 430 535 135 30 1 x 65 - 137 - 66
n° 2 - 80 TRAFFIC 1200 760 430 535 135 30 1 x 65 - 136 - 66
n° 3 - 80 NON TRAFFIC 1000 760 430 535 135 30 1 x 65 + 2 x 40 45 137 - 77
n° 3 - 80 TRAFFIC 1000 760 430 535 135 30 1 x 65 + 2 x 40 45 136 - 77
n° 3 - 80 NON TRAFFIC 1200 760 430 535 135 30 1 x 65 + 2 x 40 45 137 - 83
n° 3 - 80 TRAFFIC 1200 760 430 535 135 30 1 x 65 + 2 x 40 45 136 - 83
n° 4 - 100 NON TRAFFIC 1000 760 430 535 180 60 1 x 100 + 2 x 65 - 126 236 93
n° 4 - 100 TRAFFIC 1000 760 430 535 180 60 1 x 100 + 2 x 65 - 132 226 93
n° 4 - 100 NON TRAFFIC 1200 760 430 535 180 60 1 x 100 + 2 x 65 - 126 236 104
n° 4 - 100 TRAFFIC 1200 760 430 535 180 60 1 x 100 + 2 x 65 - 132 226 104
n° 5 - 150 TRAFFIC 1000 750 540 400 220 120 2 x 100 + 1 x 65 - 143 261 170
n° 5 - 150 TRAFFIC 1200 750 540 400 220 120 2 x 100 + 1 x 65 - 143 261 170
A
D
C
DN 150
A
D
C
DN 80 to 100
BAYARD - Series A1 42 - T19020-EN
8Pillar Fire Hydrant SAPHIR BRONZE - DescriptionDN 80 to DN 100 - Non traffic type
1 - 7. Working conditions:• Maximum Working Pressure
(PFA) 16 bar• Normalized flow = 30 m3/h
for DN 80 - 60 m3/h for DN 100.• Working tamperatures = + 1°C
to + 65°C.• Drinking water or 2 mm screened
water.• Nonfreezing height = 1,00 m, others
possible height, (please consult us).
18
01
02
19
10
11
17
23
32
21
13
12
28
06
15
Item Designation Qty Materials Standards
01 1/2 tightening flange 2 Ductile iron GS NF EN156302 1/2 Support plate 2 Thermoplastic03 Sym. Cap DN65 or DN100 1 Aluminum-silicon NF EN170604 Sym. Cap. DN40 or DN65 with «AIRCLAP» 1 Aluminum-silicon NF EN170605 Sym. Cap DN40 or DN65 without «AIRCLAP» 1 Aluminum-silicon NF EN170606 Bolting 10 Steel + GEOMET07 Bonnet + screw M8x20 1 Thermoplastic08 DN100 or DN65 Sym. Nozzle cap 1 Thermoplastic09 DN65 Sym. Nozzle cap (for DN100) 2 Thermoplastic10 Operating square 30x30 + screw + washer 1 Cast iron GL NF EN156111 Chapeau DN100 + guide 1 Ductile iron GS NF EN156312 DN100 main valve + screw and gasket 1 Elastomer NF EN681-113 Lower barrel 1 Ductile iron GS NF EN156314 Drain body 1 Brass NF EN1216415 DN100 Duck-foot with loose flange 1 Ductile iron GS NF EN156316 O-ring 1 Brass NF EN1216417 Operating nut 1 Brass18 Foot cover 2 Cast iron GL NF EN156119 Valve guide 1 Cast iron GL NF EN156120 O-ring Ø106x6 1 Elastomer/EPDM NF EN681-121 O-ring Ø123x7 1 Elastomer/EPDM NF EN681-122 O-ring Ø8.9xØ2.7 1 Elastomer/EPDM NF EN681-123 Saphir head 1 Ductile iron GS NF EN156324 Support plate 1 Cast iron GL NF EN156125 Central symmetrical outlet (NF E 29-572) DN65 or DN100 1 Alu-silicium NF EN170626 Lateral symmetrical outlet (NF E 29-572) DN40 or DN65 2 Alu-silicium NF EN170627 Packing box 28 with gaskets 1 Brass NF EN1216428 Seat DN100 with gaskets 1 Ductile iron GS NF EN156330 Upper operating stem 1 Stainless steel 304 NF EN 1008831 Anti-root tube 1 A.B.S.32 Lower operating stem (non traffic type) 1 Galvanized steel34 Locking screw 1 Brass NF EN12164
16
20
27
30
07
25
03
08
04
26
09 05
DN 100
22
34
14
31
DNadmission
Centraloutlet
Lateraloutlets
65 65 without
80 - 1 outlet 65 without
80 - 3 outlets 65 2x40
100 100 2x65
24
BAYARD - Series A1 42 - T19020-EN
9Pillar Fire Hydrant SAPHIR BRONZE - DescriptionDN 80 to DN 100 - Traffic type
1 - 8. Working conditions:• Maximum Working Pressure
(PFA) 16 bar• Normalized flow = 30 m3/h
for DN 80 - 60 m3/h for DN 100.• Working temperatures = + 1°C
to + 65°C.• Drinking water or 2 mm screened
water.• Nonfreezing height = 1,00 m, others
possible height, (please consult us).
10
11
32
24
22
31
17
34
13
25
15
06
Item Designation Nb Materials Standards
01 1/2 tightening flange 2 Ductile iron GS NF EN156302 1/2 Support plate 2 Thermoplastic03 Sym. Cap DN65 or DN100 1 Aluminum-silicon NF EN170604 Sym. Cap. DN40 or DN65 with «AIRCLAP» 1 Aluminum-silicon NF EN170605 Sym. Cap DN40 or DN65 without «AIRCLAP» 1 Aluminum-silicon NF EN170606 Bolting 10 Steel + GEOMET07 Bonnet + screw M8x20 1 Thermoplastic08 DN100 or DN65 Sym. Nozzle cap (for DN100) 1 Thermoplastic09 DN65 Sym. Nozzle cap (DN100) and DN40 (DN80) 2 Thermoplastic10 Operating square 30x30 + screw + washer 2 Cast iron GL NF EN156111 Bonnet DN100 + guide 1 Ductile iron GS NF EN156312 DN100 main valve + screw and gasket 1 Elastomer NF EN681-113 Lower barrel 1 Ductile iron GS NF EN156314 Drain body 1 Brass NF EN1216415 DN100 Duck-foot with loose flange 1 Ductile iron GS NF EN156316 O-ring 4 Brass NF EN1216517 Operating nut 1 Brass18 Spacer stem holder 1 Stainless steel NF EN156319 Foot cover 2 Cast iron GL NF EN156120 Valve guide 1 Cast iron GL NF EN156121 O-ring Ø106x6 1 Elastomer/EPDM NF EN681-122 O-ring Ø123x7 1 Elastomer/EPDM NF EN681-123 O-ring Ø8.9xØ2.7 1 Elastomer/EPDM NF EN681-124 Saphir head 1 Ductile iron GS NF EN156325 Support plate 1 Cast iron GL NF EN156126 Central symmetrical outlet (NF E 29-572) DN65 or DN100 1 Aluminum-silicon NF EN170627 Lateral symmetrical outlet (NF E 29-572) DN40 or DN65 2 Aluminum-silicon NF EN170628 Packing box 28 with gaskets 1 Brass NF EN1216429 Seat DN100 with gaskets 1 Ductile iron GS NF EN156331 Operating stem 1 Stainless steel 304 NF EN 1008832 CHOC type operating stem 1 Stainless steel 304 NF EN 1008833 Anti-root tube 1 A.B.S.34 Upper operating set 1 Stainless steel 304 NF EN1002536 Lower operating set 1 Galvanized steel37 Locking screw 1 Brass NF EN12164
07
20
19
02
18
36
12
29
16
28
26
21
03
08
01
09
04
27
05
23
37
14
33
DN 100
DNadmission
Centraloutlet
Lateraloutlets
80 - 1 outlet 65 without
80 - 3 outlets 65 2x40
100 100 2x65
BAYARD - Series A1 42 - T19020-EN
10Pillar Fire Hydrant SAPHIR BRONZE - DescriptionDN 150 - Traffic
05
14
31
34
23
01
30
33
17
11
10
21
28
20
24
16
08
02
26
04
15
1 -9. Working conditions SAPHIR DN 150 - Traffic:
• Maximum Working Pressure (PFA) 16 bar
• Normalized flow = 120 m3/h.• Minimum inlet pressure for this
flow = 1 bar• Working tamperatures = + 1°C to + 65°C.• Drinking water or 2 mm screened water.• Range: - DN 150 admission 150 - Traffic type -
1 symmetrical DN 65 and 2 symmetrical DN 100 outlet.
• Nonfreezing height = 1,00 m, others possible height, (please consult us).
Item Designation Qty Materials Standards
01 1/2 tightening flange 2 Ductile iron NF EN156302 1/2 Support plate 2 Thermoplastic03 Sym. cap DN100 2 Aluminum-silicon NF EN170604 Sym. cap DN65 with ”AIRCLAP” 1 Aluminum-silicon NF EN170605 Bonnet + screw 1 Thermoplastic06 Nozzle cap DN 100 2 Thermoplastic07 Nozzle cap DN 65 1 Thermoplastic08 Operating square 30x30 + screw + washer 2 Cast iron NF EN156109 Bonnet DN 150 + guide 1 Ductile iron NF EN156310 DN 150 Main valve 1 Elastomer NF EN681-111 Lower barrel 1 Ductile iron NF EN156312 Drain body 1 Brass NF EN1216413 Duckfoot DN150 with loose flange 1 Ductile iron NF EN156314 O-ring 2 Brass NF EN1216415 Operating nut 1 Cast iron NF EN1216416 Spacer stem holder 1 Stainless steel NF EN156317 Foot cover 2 Cast iron NF EN156118 Valve guide 1 Cast iron NF EN156119 O-ring Ø158x7 1 Elastomer /EPDM NF EN681-120 O-ring Ø171x7 2 Elastomer /EPDM NF EN681-121 O-ring Ø171x7xØ6.99 1 Elastomer /EPDM NF EN681-122 O-ring Ø8.9xØ2.77 1 Elastomer /EPDM NF EN681-123 Saphir 5 nose 1 Ductile iron NF EN156324 Support plate 1 Cast iron NF EN156125 Symmetrical outlet DN100 (NF E 29-572) 2 Aluminum-silicon NF EN170626 Symmetrical outlet DN65 (NF E 29-572) 1 Aluminum-silicon NF EN170627 Packing box 28 with gaskets 1 Brass NF EN1216428 Seat DN150 with gaskets 1 Ductile iron NF EN156330 Operating stem 1 Stainless steel 304 NF EN 1008831 CHOC operating stem 1 Stainless steel 304 NF EN 1008832 Anti-root tube 1 A.B.S.33 Lower operating set 1 Galvanized steel34 Upper operating set 1 Stainless steel 304 NF EN1008835 Drain protecting tube 1 ABS37 Locking screw 1 Brass NF EN12164
Bolting Steel + GEOMET
18
13
25
07
03
06
27 09
19
22
37
12
32
BAYARD - Series A1 42 - T19020-EN
11Hydrants SAPHIR BRONZESetting up and implementation of a project
Security and environment:• Installation, maintenance and repair operations must comply
with the local regulations in force, relating to safety at work and respect for the environment.
• Insist that workers wear the appropriate personal protective equipment. Make sure that the lifting accessories and power tools used comply with the regulations in force. Enforce their terms of use.
• Installation, maintenance and repair work will be carried out by qualified, trained and authorized personnel in accordance with current legislation.
• From an environmental point of view, the device is recyclable. Advise to deposit the packaging in a recovery container.
* Adjustable surface box with fire cover Series G4 15
Universal DrainkitSeries A3 40
* Dry stones for correct drainage
* Major Stop for DI or PVC Series C1 30 / 35
with pipe.
Major Stop for DI or PVC
Series C1 30 / 35
Flanged TeesSeries C4 20
* Operating stemSeries B5 20
* Gate valve SeriesB1 15
Extension sleeve between seat and
duckfoot for Series A3 40L = 0,05 mL = 0,15 mL = 0,25 m
A
L
Femal elbow with swivel nut G 1/2“ x PE DN 20
Series G7 50.
or
Implementation:• The specifications for the supply, installation and reception of
fire hydrants must refer to standard NF S 62-200.
• Installation, commissioning and maintenance are described in the manual W18022 supplied with the hydrant.
• Our fire hydrants are protected in their polystyrene packing for DN 80 and 100 and in wooden crates fort DN 150, which preserve paint during installation.
Storage and handling:• Store the device lying down, elbow facing down, for a maximum
of one year, at a temperature not exceeding 65 ° C and protected from shocks.
• Handle it with care in its packaging. Lifting for installation is possible by means of a strap passed through the packaging or under the outlets.
Control and maintenance:• The control and maintenance of fire hydrants is described in
standard NF S 62-200.
* Concrete squareSeries A3 40
* Concrete block
* S-bend Series A3 10
Size L = +/- 0.50 mSize A :
DN 65 = 0,24 mDN 80 = 0,28 m
DN 100 = 0,28 mDN 150 = 0,32 m
2 - 4. Definition of equipment for installation according to: NORM NF S 62-200*
Our threaded drain funneled with a simple
connection for PE DN 20 pipe laid on a 3cm/m slope
Your Choice in Waterflow Control
TALIS is the undisputed Number One for water transport and water
flow control. TALIS has the best solutions available in the fields of
water and energy management as well as for industrial and communal
applications. We have numerous products for comprehensive
solutions for the whole water cycle - from hydrants, butterfly valves
and knife gate valves through to needle valves. Our experience,
innovative technology, global expertise and individual consultation
processes form the basis for developing long-term solutions for the
efficient treatment of the vitally important resource “water”.
BAYARD
ZI - 4 avenue Lionel Terray
CS 70047
69881 Meyzieu cedex France
TEL. + 33 (0)4 37 44 24 24
FAX + 33 (0)4 37 44 24 25
WEBSITE : www.bayard.fr
Specifications and performance may be changed without notice as a result of technical developments. Images and photos given for illustration purposes only.