Page 1: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32

Page 2: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

2

1 -Information

1 - 1. Applications:

• Non-freezing pillar fire hydrant with hood ÉMERAUDE, for connection

above ground of the mobile equipment of fire protection services on a

network under pressure.

• EMERAUDE: Traffic type and non Traffic type Series A1 32.

• Public or private firefighting networks, under permanent pressure or on

request.

• For suctions facilities, refer to our Intake Hydrants series A1 94 or A1 95.

1 - 2. Features:

• DN 80 to 150.

• Made in France since 1950 in Vénissieux, then in Meyzieu (France).

• Series according to European standards, outlets at French standards:

- NF EN 14384.

- NF EN 1074 - 6.

- NF EN 14384/CN.

- Conformity certificate CE 0679 - CPR - 0213.

- NF Label holder.

- Conformity certificate with UE N° 305/2011.

- NF E 29 - 572, symmetrical outlets.

- NF EN 12266 - 1, sealing rate A, torque level 1.

- EN 1092 - 2, flanges drilling ISO PN 10/16.

- Drinking water certificate (ACS).

- Paint RAL 3000.

Pillar Fire Hydrant EMERAUDE BRONZE - Description

Airclap

Anti-water hammer and anti-vibration main valve guide

Internal/external epoxy coating

360°Rotation

DN 80 to DN 150

Traffic type and Non Traffic type

Spare parts guarantee 5 years 5 years 10 years

Stationary drain

Removable drain

Upper Part: red polyester paint

Stainless steel components

Bronze seat

Page 3: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

3Pillar Fire Hydrant EMERAUDE BRONZE - Description

1 - 3. Design: - Outlets with symmetric coupling (French Norm). - The DN65 outlet has an Airclap cap (Fig. 1) letting the air in for drainage.

It also allows to check that the hydrant is not under pressure before opening the cap. A simple tap of your finger is enough to make it work and ensure the safety of users.

- Warning stickers are affixed on all caps. - Clockwise closing.

- The specific design of the main valve guide is anti-water hammer and anti-vibration providing a smooth opening/closing (Fig. 2 and Fig. 13 Item 4 p5).

- The thick valve gasket helps the sealing even in presence of foreign bodies(Fig. 2 and Fig. 13 Item. 5 p5).

- Hydraulic ball drain.

- Drain protection with the anti-root system 01 (Fig. 3).

- Duckfoot with loose flange 02 (Fig. 3).

Clapet d’entrée d’air Airclap et autocollants de mise en garde

Fig. 1

13 turns

Smooth closing, blue curve.1 2 3 4 5 6 7 8 9 10 11 12 13 turns

Standard equipment on all hydrants models

Flow value example according to the number of opening turns of a DN 100hydrant. Sudden stop with standard valve

(water hammer). Progressive stop with our anti

water-hammer valve

Fig. 2

Fig. 3

01

02

Page 4: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

4Pillar Fire Hydrant EMERAUDE BRONZE - Description

1 - 4. Performances:

• Low operating torque over time.

- Bubble tight shut-off.

- Non-freezing type

- Kv above the norm (see table page 7).

• Anticorrosion protection:

- Nose with black epoxy coating, applied by cataphoresis.

- Hood in red colored composite material, flame retardant and corrosion

resistant, with a red finish coating insensitive to U.V. It protects internal

parts against harmful elements (snow, salt, urine, etc…) (Fig. 4).

• Easy to install:

- 360°Rotating upper part, degree by degree without digging (Fig. 5).

- It is possible to fit a BAYARD sleeve to raise the hydrant during installation,

between the seat and duckfoot (heights 0.05 - 0.15 and 0.25 cm) (Fig. 6).

- A polystyrene packing, fully recyclable, protects the hydrant from any

projection during installation (Fig. 7). (DN 150 in wooden case).

- Liftable hood after installation: 90 mm without digging (Fig. 8).

• Quick and easy commissioning:

The hood:

- is delivered assembled

- protects people against protruding hydrant parts (Fig. 4).

- total outlet clearance, lateral doors clearance with no effort.

Fig. 4

Fig. 7

Fig. 6

90 m

m

min maxFig. 8

Fig. 5

Page 5: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

5Pillar Fire Hydrant EMERAUDE BRONZE - Description

07

05

04

Fig. 9

Fig. 10

• Quick and easy commissioning (continuation):

- Suitable with universal Drainkit to ease drainage on DN 80 and 100, DN 150

(Fig. 9).

- Option: our drain is threaded and possibly funneled with a simple connection,

according to the site’s constraint (Fig. 10).

- Operating square 30x30.

• Advantages of our range to reduce maintenance costs (Fig. 11 and 12) :

- Complete spare parts available. Interchangeability since 1971 with past

versions (for DN 80-100).

- Quick and easy dismantling of the upper operating set, through the upper

part.

- Quick and safe dismantling of the lower operating set.

- Extension sleeve kit of 0.20 m after installation, without digging

on DN 80 (2016) and 100 (>2003).

- Conversion of a non-traffic hydrant into a traffic version (Traffic) without

digging with the mini kit Choc (Fig. 12 item. 6).

• Our fire hydrant is eco-friendly:

- 99% of its components are recyclable.

- Our PSE (polystyrene) packing is made of 2% of recycled

material and 98% of air.

It needs very little energy to manufacture, is 100% recyclable for life

by grinding, compaction and extrusion of PES granules.

LIVRET PIÈCES DE RECHANGE

POTEAUX D’INCENDIE APRÈS 2016

W16001A

LIVRET PIÈCES DE RECHANGE

POTEAUX D’INCENDIE AVANT 2016BOUCHES D’INCENDIE

W15019B

Fig. 11

06

Page 6: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

6Pillar Fire Hydrant EMERAUDE BRONZE - Description

Cast iron,Bronze or aluminum badges

Stickers

• Options:

Stickers, special colors, special outlets, several heights ….

HYDRANTS CUSTOMIZATION SPECIAL HYDRANTS

Our automatic solution for leak detection, with daily acoustic correlationintegrated in our fire hydrants.The solution for precise leak location: - Sharp filtering of unwanted noises, - Dedicated software to analyze data in a few minutes, - An expert system to optimize the number of modules to be deployed

and their location.

To fight against “street pooling »or wild opening of hydrants restricting theiruse to firefighting and authorized persons.

KIT SECURE

100% web-based asset management solution.Provides tools to organize maintenance and create work orders on all firefightingequipment. The created data base allows to share follow-up on hydrantsthrough NFC tags, with real-time data updating, with authorities, town halls,companies.

TAGUATM

This real-time alert system allows: - Evaluation of drawn volumes, - Monitoring water drawings, - Fighting against suspicious water drawing

COPERNICTM

Reduced height

Page 7: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

7Pillar Fire Hydrant EMERAUDE BRONZE - Description

1 - 3. Sizes, weight, and performances:

B

A

Prepared ground level

30x30 operating square

DN TRAFFICNON TRAFFIC

Cmm

Length

Amm

Bmm

Dmm

Emm

Fmm

Flow expressed

in m3/h

Nboutlets

Kv* outlet WeightkgDN 40 DN 65 DN 100

n° 2 - 80 (60/65) NON TRAFFIC 1000 350 800 500 600 120 30 1 x 65 - 132 - 77

n° 2 - 80 (60/65) NON TRAFFIC 1200 350 800 500 600 120 30 1 x 65 - 132 - 88

n° 2 - 80 NON TRAFFIC 1000 350 800 500 600 135 30 1 x 65 - 133 - 78

n° 2 - 80 TRAFFIC 1000 350 800 500 600 135 30 1 x 65 - 131 - 78

n° 2 - 80 NON TRAFFIC 1200 350 800 500 600 135 30 1 x 65 - 133 - 78

n° 2 - 80 TRAFFIC 1200 350 800 500 600 135 30 1 x 65 - 131 - 78

n° 3 - 80 NON TRAFFIC 1000 350 800 500 600 135 30 1 x 65 + 2 x 40 40 133 - 79

n° 3 - 80 TRAFFIC 1000 350 800 500 600 135 30 1 x 65 + 2 x 40 40 131 - 79

n° 3 - 80 NON TRAFFIC 1200 350 800 500 600 135 30 1 x 65 + 2 x 40 40 133 - 90

n° 3 - 80 TRAFFIC 1200 350 800 500 600 135 30 1 x 65 + 2 x 40 40 131 - 90

n° 4 - 100 NON TRAFFIC 1000 350 800 500 600 180 60 1 x 100 + 2 x 65 - 133 214 85

n° 4 - 100 TRAFFIC 1000 350 800 500 600 180 60 1 x 100 + 2 x 65 - 124 214 85

n° 4 - 100 NON TRAFFIC 1200 350 800 500 600 180 60 1 x 100 + 2 x 65 - 133 214 104

n° 4 - 100 TRAFFIC 1200 350 800 500 600 180 60 1 x 100 + 2 x 65 - 124 214 104

n° 5 - 150 TRAFFIC 1000 350 800 400 535 220 120 2 x 100 + 1 x 65 - 137 253 145

n° 5 - 150 TRAFFIC 1200 350 800 400 535 220 120 2 x 100 + 1 x 65 - 137 253 145

* Kv is the maximum flow, in m3/h, measured separately per outlet, according to norm EN14384.

Torque Level 1.Total number of turns for opening: 13 ± 1 turns for DN 80 and 100 and 17 ± 1 turns forDN 150. Number of dead turns: maximum 2.

b b

a

a±5° b±5°

DN 80 DN 100 DN 150 DN 80 DN 100 DN 1501 outlet 3 outlets - 3 outlets 1 outlet 3 outlets - 3 outlets

Emeraude 75° 70° 75° - 0° 65° 65° -

Emeraude Traffic - - 75° 75° - - 65° 65°

C

E

D

DN

F

DN 80 and 100

E

D

DN 150

Page 8: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

8Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type

12

07

13

18

27

32

14

06

01

11 26

08

21

03

22

28

16

02

09

24

25

30

19

20

1 - 4. Working conditions:• Maximum working pressure

(PFA) 16 bar.• Normalized flow = 30 m3/h

for DN 80 - 60 m3/h for DN 100.• Working temperature = + 1°C

to + 65°C.• Drinking water or 2 mm screened

water.• Nonfreezing height = 1,00 m, others

possible height, (please consult us).

Item Designation Qty Material Standards

01 1/2 tightening flange 2 Ductile iron NF EN156302 1/2 Support plate 2 Thermoplastic03 Sym. Cap DN65 or DN100 1 Aluminum-silicon NF EN170604 Sym. Cap DN40 or DN65 with «AIRCLAP» 1 Aluminum-silicon NF EN170605 Sym. Cap DN40 or DN65 without «AIRCLAP» 1 Aluminum-silicon NF EN170606 Bolting 10 Steel + GEOMET07 Bonnet DN100 + guide 1 Ductile iron NF EN156308 DN100 main valve + screw and washer 1 Elastomer09 Lower barrel 1 Ductile iron NF EN156310 Drain body 1 Brass NF EN1226411 DN100 Duck-foot with loose flange 1 Ductile iron NF EN156312 1/2 tightening ring 2 Brass NF EN1216413 Operating screw 1 Brass NF EN1216414 Valve guide 1 Cast iron NF EN156115 O-ring Ø106x6 1 Elastomer/EPDM NF EN681-116 O-ring Ø123x7 1 Elastomer/EPDM NF EN681-117 O-ring Ø8.9xØ2.7 1 Elastomer/EPDM NF EN681-118 Emeraude nose 1 Cast iron NF EN156319 Door with lock 1 Composite20 Door without lock 1 Composite21 Support plate 1 Cast iron NF EN156122 Central symmetrical outlet (NF E 29-572) DN65 or DN100 1 Aluminum-silicon NF EN170623 Lateral symmetrical outlet (NF E 29-572) DN40 or DN65 2 Aluminum-silicon NF EN170624 Packing box 28 with gaskets 1 Brass NF EN1216425 Locking kit 1 Cupro alloy NF EN1216526 Seat DN100 with gaskets 1 Fonte GS NF EN156327 Rear hood base 1 Composite28 Front hood base 1 Composite30 Operating stem 1 Stainless steel 304 NF EN 1008831 Anti-root tube 1 A.B.S.32 Lower operating stem (non traffic type) 1 Galvanized steel34 Locking screw 1 Brass NF EN12164

15

DN 65/80

DN 100

04

23

05

17

34

10

31

Page 9: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

9Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Traffic

13

17

33

20

01

29

18

07

32

37

09

16

30

02

15

14

10

23

08

27

24

03

35

26

21

1 - 5. Working conditions:• Maximum Working Pressure

(PFA) 16 bar• Normalized flow = 30 m3/h

for DN 80 - 60 m3/h for DN 100.• Working temperatures = + 1°C

to + 65°C.• Drinking water or 2 mm screened

water.• Nonfreezing height = 1,00 m, others

possible height, (please consult us).

22

Item Designation Qty Material Standards

01 1/2 tightening flange 2 Ductile iron GS NF EN156302 1/2 Support plate 2 Thermoplastic03 Sym. Cap DN65 or DN100 1 Aluminum-silicon NF EN170604 Sym. Cap. DN40 or DN65 with «AIRCLAP» 1 Aluminum-silicon NF EN170605 Sym. Cap DN40 or DN65 without «AIRCLAP» 1 Aluminum-silicon NF EN170606 Bolting 10 Steel + GEOMET07 Operating square 30x30 + screw + washer 1 Cast iron NF EN156108 Bonnet DN100 + guide 1 Ductile iron NF EN156309 DN100 main valve + screw and gasket 1 Elastomer10 Lower barrel 1 Ductile iron NF EN156311 Drain body 1 Brass NF EN1226412 DN100 Duck-foot with loose flange 1 Ductile iron NF EN156313 ½ tightening ring 4 Brass NF EN1216414 Operating nut 1 Brass NF EN1216415 Spacer stem holder 1 Stainless steel NF EN156316 Valve guide 1 Cast iron NF EN156117 O-ring Ø106x6 1 Elastomer/EPDM NF EN681-118 O-ring Ø123x7 1 Elastomer/EPDM NF EN681-119 O-ring Ø8.9xØ2.7 1 Elastomer/EPDM NF EN681-120 Emeraude nose 1 Ductile iron NF EN156321 Door with lock 1 Composite22 Door without lock 1 Composite23 Support plate 1 Cast iron NF EN156124 Central symmetrical outlet (NF E 29-572) DN65 or DN100 1 Aluminum-silicon NF EN170625 Lateral symmetrical outlet (NF E 29-572) DN40 or DN65 2 Aluminum-silicon NF EN170626 Packing box 28 with gaskets 2 Brass NF EN1216427 Locking kit 1 Cupro alloy NF EN1216528 Seat DN100 with gaskets 1 Ductile iron NF EN156329 Rear hood base 1 Composite30 Front hood base 1 Composite32 Operating stem 1 Stainless steel 304 NF EN 10088 33 CHOC operating stem 1 Stainless steel 304 NF EN 10088 34 Anti-root tube 1 A.B.S.35 Upper operating set 1 Stainless steel 30437 Lower operating set 1 Galvanized steel38 Locking screw 1 Brass NF EN12164

28

06

12

DN 80

DN 100

25

0405

19

38

11

34

Page 10: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

10Pillar Fire Hydrant EMERAUDE BRONZE - DescriptionDN 150 - Traffic type

32

11

06

19

35

01

05

31

28

12

34

21

07

27

08

13

29

24

04

26

25

02

1 -6. Working conditions EMERAUDE DN 150 - Traffic:

• Maximum Working Pressure (PFA) 16 bar.

• Normalized flow= 120 m3/h.• Minimum inlet pressure for this flow =

1 bar.• Working temperatures = + 1°C to + 65°C. • Drinking water or 2 mm screened

water.• Range: DN 150 admission 150 - Traffic type - 1 symmetrical DN 65 and 2 symmetrical DN 100 outlets• Nonfreezing height = 1,00 m, others possible height, (please consult us).

Item Designation Qty Material Standards

01 1/2 tightening flange 2 Ductile iron NF EN156302 1/2 Support plate 2 Thermoplastic 03 Sym. cap DN100 2 Aluminum-silicon NF EN170604 Sym. cap DN65 with ”AIRCLAP” 1 Aluminum-silicon NF EN170605 Operating square 30x30 + screw + washer 1 Cast iron NF EN156106 Bonnet DN150 + guide 1 Ductile iron NF EN156307 DN150 main valve + screw and gasket 1 Elastomer08 Lower barrel 1 Ductile iron NF EN156309 Drain body 1 Brass NF EN1226410 Duckfoot DN150 with loose flange 1 Ductile iron NF EN156311 ½ tightening ring 2 Brass NF EN1216412 Operating nut 1 Cast iron NF EN1216413 Spacer stem holder 1 Cast iron NF EN156314 Valve guide 1 Cast iron NF EN156115 O-ring Ø158x7 1 Elastomer /EPDM NF EN681-116 O-ring Ø171x7 2 Elastomer /EPDM NF EN681-117 O-ring Ø177.17xØ6.99 1 Elastomer /EPDM NF EN681-118 O-ring Ø8.9xØ2.7 1 Elastomer /EPDM NF EN681-119 Emeraude 5 noze 1 Cast iron NF EN156320 Door with lock 1 Composite21 Valve holder 1 Cast iron NF EN156122 Door without lock 1 Composite23 Symmetrical outlet DN100 (NF E 29-572) 2 Aluminum-silicon NF EN170624 Symmetrical outlet DN65 (NF E 29-572) 1 Aluminum-silicon NF EN170625 Packing box 28 with gaskets 1 Brass NF EN1216426 Locking kit 1 Cupro alloy27 Seat DN150 with gaskets 1 Ductile iron NF EN156328 Rear hood base 1 Composite29 Front hood base 1 Composite30 Removable drain support 1 Cupro alloy31 Operating stem 1 Brass NF EN1216432 CHOC Operating stem 1 ABS NF EN1216433 Anti-root tube 1 Galvanized steel34 Lower operating set 1 Stainless steel 30435 Upper operating set 1 ABS NF EN1008836 Drain protecting tube 1 Brass37 Locking screw 1 Cast iron NF EN1216438 Operating square 1 Steel + GEOMET NF EN1561

Bolting Acier + GEOMET

17

14

16

10

15

18

37

09

33

20

38

22

03

23

Page 11: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

BAYARD - Series A1 32 - T19021-EN

11Hydrant EMERAUDE BRONZESetting up and implementation of a project2 - 4. Definition of equipment for installation according to: NORM NF S 62-200*

* Adjustable surface box with fire cover Series G4 15

Universal DrainkitSeries A3 40

* Dry stones for correct drainage

* Major Stop for DI or PVC Series C1 30 / 35

with pipe.

Major Stop for DI or PVC

Series C1 30 / 35

Flanged TeesSeries C4 20

* Operating stemSeries B5 20

* Gate valve Series B1 15

Extension sleeve between seat and

duckfoot for DN 100 Series A3 40L = 0,05 mL = 0,15 mL = 0,25 m

A

L

Femal elbow with swivel nut G 1/2“ x PE DN 20

Series G7 50.

or

* Concrete squareSeries A3 40

* Concrete block

* S-bend Series A3 10

Size L = +/- 0.50 mSize A :

DN 65 = 0,24 mDN 80 = 0,28 m

DN 100 = 0,28 mDN 150 = 0,32 m

Our threaded drain funneled with a simple

connection for PE DN 20 pipe laid on a 3cm/m slope

Security and environment:• Installation, maintenance and repair operations must comply

with the local regulations in force, relating to safety at work and respect for the environment.

• Insist that workers wear the appropriate personal protective equipment. Make sure that the lifting accessories and power tools used comply with the regulations in force. Enforce their terms of use.

• Installation, maintenance and repair work will be carried out by qualified, trained and authorized personnel in accordance with current legislation.

• From an environmental point of view, the device is recyclable. Advise to deposit the packaging in a recovery container.

Implementation:• The specifications for the supply, installation and reception of

fire hydrants must refer to standard NF S 62-200.

• Installation, commissioning and maintenance are described in the manual W18022 supplied with the hydrant.

• Our fire hydrants are protected in their polystyrene packing for DN 80 and 100 and in wooden crates fort DN 150, which preserve paint during installation.

Storage and handling:• Store the device lying down, elbow facing down, for a maximum

of one year, at a temperature not exceeding 65 ° C and protected from shocks.

• Handle it with care in its packaging. Lifting for installation is possible by means of a strap passed through the packaging or under the outlets.

Control and maintenance:• The control and maintenance of fire hydrants is described in

standard NF S 62-200.

Page 12: Pillar Fire Hydrant EMERAUDE BRONZE Series A1 32 · 2020. 2. 17. · Pillar Fire Hydrant EMERAUDE BRONZE - Description DN 80 to DN 100 - Non traffic type 12 07 13 18 27 32 14 06 01

Your Choice in Waterflow Control

TALIS is the undisputed Number One for water transport and water

flow control. TALIS has the best solutions available in the fields of

water and energy management as well as for industrial and communal

applications. We have numerous products for comprehensive

solutions for the whole water cycle - from hydrants, butterfly valves

and knife gate valves through to needle valves. Our experience,

innovative technology, global expertise and individual consultation

processes form the basis for developing long-term solutions for the

efficient treatment of the vitally important resource “water”.

BAYARD

ZI - 4 avenue Lionel Terray

CS 70047

69881 Meyzieu cedex France

TEL. + 33 (0)4 37 44 24 24

FAX + 33 (0)4 37 44 24 25

WEBSITE : www.bayard.fr

Specifications and performance may be changed without notice as a result of technical developments. Images and photos given for illustration purposes only.

Your Choice in Waterflow Control

TALIS is the undisputed Number One for water transport and water

flow control. TALIS has the best solutions available in the fields of

water and energy management as well as for industrial and communal

applications. We have numerous products for comprehensive

solutions for the whole water cycle - from hydrants, butterfly valves

and knife gate valves through to needle valves. Our experience,

innovative technology, global expertise and individual consultation

processes form the basis for developing long-term solutions for the

efficient treatment of the vitally important resource “water”.

BAYARD

ZI - 4 avenue Lionel Terray

CS 70047

69881 Meyzieu cedex France

TEL. + 33 (0)4 37 44 24 24

FAX + 33 (0)4 37 44 24 25

WEBSITE : www.bayard.fr

Specifications and performance may be changed without notice as a result of technical developments. Images and photos given for illustration purposes only.