PID Control Loops. Guy Zebrick. Contents. Open & Closed Loops Direct and Reverse Acting Proportional Control Integral Control Derivative Control Definitions Loop Tuning. Open Loop Control / Direct Acting. Mathematical Calculation. Input Control Variable. Setpoint. Output Device - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: PID Control Loops

PID Control Loops

Guy Zebrick

Page 2: PID Control Loops

2 HONEYWELL - CONFIDENTIAL File Number

Contents

•Open & Closed Loops•Direct and Reverse Acting•Proportional Control•Integral Control•Derivative Control•Definitions•Loop Tuning

Page 3: PID Control Loops

3 HONEYWELL - CONFIDENTIAL File Number

Open Loop Control / Direct Acting

InputControlVariable

Output Device0-100%

MathematicalCalculation

Setpoint

Input: Outside Air TemperatureSetpoint: 50’FOutput: Chiller on/off (0-100%)Action: Direct (input output )

Page 4: PID Control Loops

4 HONEYWELL - CONFIDENTIAL File Number

Open Loop Control / Reverse Acting

InputControlVariable

Output Device0-100%

MathematicalCalculation

Setpoint

Input: Outside Air TemperatureSetpoint: 60’FOutput: Boiler on/off (0-100%)Action: Reverse (input output )

Page 5: PID Control Loops

5 HONEYWELL - CONFIDENTIAL File Number

Closed Loop Control Reverse Acting

InputControlVariable

Output Device0-100%

MathematicalCalculation

Setpoint

Input: Room TemperatureSetpoint: 70’FOutput: Radiator Valve (0-100%)

Page 6: PID Control Loops

6 HONEYWELL - CONFIDENTIAL File Number

PID Control by Mathematical calculation

ProportionalOutput varies in PROPORTION to input error

IntegralOutput varies over TIME based on input error

DerivativeOutput varies based RATE of CHANGE of input error

P controlP + I controlP + I + D control (not used in our industry!)

Page 7: PID Control Loops

7 HONEYWELL - CONFIDENTIAL File Number

PID closed loop control – driving at speed

0%

P

30%

PID

40%

PI

60%

PI

0%

PID

40%

PID

70%

PI

25%

PID

40%

PI

Page 8: PID Control Loops

8 HONEYWELL - CONFIDENTIAL File Number

Definition: (SETPOINT)

• The desired value of the input variable

T1 T2 T3 T4 T5 T6

Input Value

Setpoint

Time

Page 9: PID Control Loops

9 HONEYWELL - CONFIDENTIAL File Number

Definition: OFFSET (error)

• The DIFFERENCE between the input variable and the desired setpoint.

T1 T2 T3 T4 T5 T6

Input Value

Setpoint

Time

Offset

Page 10: PID Control Loops

10 HONEYWELL - CONFIDENTIAL File Number

Definition: Throttling Range (Proportional Band)

Throttling Range (Proportional Band)

(10’F)

100%

50%

0%

65° 70° 75°Setpoint

ControllerOutput

T1 T2 T3 T4 T5 T6

Amount of Change in INPUT that equals a 0-100% change in OUTPUT

Page 11: PID Control Loops

11 HONEYWELL - CONFIDENTIAL File Number

Proportional Control (with Offset Error)

T1 T2 T3 T4 T5 T6

Control Point

Setpoint

Time

Offset

0=100%

Page 12: PID Control Loops

12 HONEYWELL - CONFIDENTIAL File Number

Proportional + Integral Control (eliminates offset)

T1 T2 T3 T4 T5 T6

Control Point

Setpoint

Time

Offset

0=100%

Page 13: PID Control Loops

13 HONEYWELL - CONFIDENTIAL File Number

Derivative Calculation based on RATE of CHANGE

T1 T2 T3 T4 T5 T6

Control Point

Setpoint

Time

Offset

DDP + I + D

Not used in our industry!

Page 14: PID Control Loops

14 HONEYWELL - CONFIDENTIAL File Number

Integral Windup Condition

T1 T2 T3 T4 T5 T6

Control Point

Setpoint

Time

100%

Prevented by Disabling Loop when system is OFF

Page 15: PID Control Loops

15 HONEYWELL - CONFIDENTIAL File Number

PID Enhancements

• Setpoint Reset• Setpoint Recovery Ramp• Setpoint Demand Limit “BUMP”• Setpoint Select(s)

• PID Output BIAS• PID Output Start Point• PID Output Start Ramp• PID Output Adjust Delay• PID Output Adjust Threshold• PID AUXILLARY Output• PID Output Sequencer

Page 16: PID Control Loops

16 HONEYWELL - CONFIDENTIAL File Number

Definition: PID Output Bias

T1 T2 T3 T4 T5 T6

100%

50%

0%T1 T2 T3 T4 T5 T6

100%

50%

0%

Output = 50% at Setpoint

Output = 0% at Setpoint

50%

0%

Page 17: PID Control Loops

17 HONEYWELL - CONFIDENTIAL File Number

PID Setpoint RESET

• Requires RESET sensor (typically outside air)• Automatically adjusts setpoint

Page 18: PID Control Loops

18 HONEYWELL - CONFIDENTIAL File Number

PID Setpoint Recovery Ramp

• Degrees/Hr• Requires multiple schedule information

- Current State (occupied/unoccupied)- Next State (occupied/unoccupied)- Time until next state (minutes)

Setpoint

UNOCC

OCC

TimeOCC

Page 19: PID Control Loops

19 HONEYWELL - CONFIDENTIAL File Number

PID options (not available on ALL PID loops)

•Output Start Value (%)-Provides starting value for initial control

•Output Start Ramp (seconds)-limits action during initial startup to prevent overshoot

-Output Dead Band (%)

•Output Adjust Delay & Threshold-Prevents repeated minor adjustment to output

-Prevents needless wear & tear on mechanical devices

Page 20: PID Control Loops

20 HONEYWELL - CONFIDENTIAL File Number

Definition: Hunting (over-reacting)

Proportional BandThrottling Range

(2’F)

100%

50%

0%

69°

70°

71°

Setpoint

ControllerOutput

T1 T2 T3 T4 T5 T6

Time

Page 21: PID Control Loops

21 HONEYWELL - CONFIDENTIAL File Number

Tuning Hints:

• PI control for closed-loop applications only.• The narrower (smaller) the throttling range, the more precise the control operation. The wider (larger) the throttling range, the more stable the control action.

• Generally the throttling range required for PI control is greater than what is used for proportional control only.

• The integral time value is set in seconds. A slow process such as space temperature control requires a long integral time (600 seconds or more), while a fast process such as static pressure control requires a short integral time.

• An integral time of 0 eliminates the integral function for the control loop.

Page 22: PID Control Loops

22 HONEYWELL - CONFIDENTIAL File Number

Typical Values

• From Engineering Manual

• Default Space Temperature Control

(CV AHU controller)

Page 23: PID Control Loops

23 HONEYWELL - CONFIDENTIAL File Number

Field Tuning

1. Integral Time to Zero2. Throttling Range = ½ Input Sensor

Range3. Adjust Throttling Range to point

where about first begins to hunt.4. Increase Throttling Range 1.5 X5. Add Integral Time based on system

response time • (typically 60 – 2500 seconds)

6. Check for Stable Operation

Page 24: PID Control Loops

24 HONEYWELL - CONFIDENTIAL File Number

PID POP Quiz

• Define open loop• Define closed loop• A cooling loop is (direct/reverse) acting• An AHU static pressure control loop is (direct/reverse) acting

• Define P, I, D• Define throttling range• Define integral time• When do you use Differential control?• What adjustment(s) reduce ‘hunting’?

Page 25: PID Control Loops

25 HONEYWELL - CONFIDENTIAL File Number

Questions?