Addendum 01 March 25, 2019
To Construction Documents and Specifications for:
Phase 1 –Safety & Security Improvements – Package A
1
Prepared By PBK Architects, Inc.
James Moore, AIA
601 N.W. Loop 410, Suite 400
San Antonio, Texas 78216
PBK Project Number 18397M
Notice to Offerors:
A. Receipt of this Addendum shall be acknowledged on the Proposal Form. B. This Addendum is generally separated into sections for convenience; however, contractors,
subcontractors, material suppliers and other involved parties shall be responsible for reading the Addendum. Failure to list an item(s) in affected sections of this Addendum does not relieve party affected from performing per instructions, provided the information is set forth one time in the Addendum.
C. Each Offeror shall make necessary adjustments and submit his proposal with full knowledge of modifications, clarifications, and supplemental data included therein. Where provisions of the following supplemental data differ from those of the original Contract Documents, this Addendum shall govern.
General Information
A. BID DATE AND TIME: APRIL 9, 2019 AT 2:00PM MT B. DELIVER BIDS TO: BOARD CONFERENCE ROOM
1009 BARNETT STREET, KERRVILLE, TX. 78028
Last date for RFI 04/01/19, last date for Addenda 04/04/19
List of Attachments
1. Add sheets showing location of assumed Fire Walls: A1.06 & A1.09 2. MEPT Addendum 01
Addendum 01 March 25, 2019
To Construction Documents and Specifications for:
Phase 1 –Safety & Security Improvements – Package A
2
Clarification
Specifications:
END OF ADDENDUM
DRESS RR DRY STO BULK STO
FOOD PREPOFFICE
JAN
REF / FZR
WAREWASHSERVERY
CAN WASH
CAFETORIUM STAGE
MUSIC
RR
VEST JAN
RR
VEST
OUTSIDE STO
ELEC
STO
MECH
PAPER STOJAN
RR
RR
DRESS
DRESS
OFFICE / STO
STO STO ENCLOSED PLAY AREA
Room
ELEC
STORR
RR
JAN
WORK AREA
CLASSROOM CLASSROOM
RoomRoom
CLASSROOM CLASSROOM
RoomRoom
CLASSROOM
CORRIDOR
ART
KILN
STO
CORRIDOR CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOM CLASSROOMCLASSROOM
CORRIDOR
ELEC
RR
CLINIC
CORRIDOR CLASSROOM CLASSROOM CLASSROOM
CLASSROOM
VEST
FAC
VEST
RRRR
VEST
JAN
CLASSROOM CLASSROOM
STO
RR CLASSROOM
CLASSROOM CLASSROOMRR
CORRIDOR
TESTING
STORAGE
CLASSROOMCLASSROOM
CLASSROOM CLASSROOM
CORRIDOR
OFFICE / RECEP
CORRIDOR
WORK ROOMPRINCCOUNCELOR
FILES / RECORDSMULTI-USE OFFICECONFERENCEFAC WORK ROOM
RRRR
LOUNGETELE
TEXTBOOK STO
TEACHERS LOUNGE
COFFEE
LOBBYCOMPUTER LAB
Room
STOCORRIDOR
Room
MULTI-USE
MEDIA CENTER
LIBRARIANS OFFICE
LIBRARY STOSTUDY ROOMFILM VIEWING
CLASSROOM
CORRIDOR
RR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
STO
STO
RR
WORKROOM
CLASSROOM
CLASSROOM
ASSUMED EXISTING FIRE WALL
ASSUMED EXISTING FIRE WALL
GENERAL NOTES
1. DO NOT SCALE DRAWINGS, WRITTEN DIMENSIONS TAKE PRECEDENCE, CONTACT ARCH IF CLARIFICATION IS NECESSARY IN ORDER TO DETERMINE THE INTENT OF THE CONTRACT DOCUMENTS
2. DRAWINGS NOTED AS "N.T.S" OR "NTS" ARE NOT TO SCALE3. FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS BEFORE
COMMENCING WORK. NOTIFY ARCH. OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH AFFECTED WORK
Other
Architect
ARCHITECT PBK Architects, Inc.
MEPT
DATE
PROJECT NUMBER
CLIENT
REVISIONS
HOUSTON11 Greenway Plaza, 22nd Floor
Houston, TX 77046713-965-0608 P713-961-4571 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
11 Greenway Plaza, Suite 1510Houston, TX 77046
713-940-3300 P 713-961-4571 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/2
5/2
01
9 1
:48:0
3 P
M
Z:\P
roje
cts
\San
\18
\183
97M
\Div
8-D
wgs\8
a B
IM C
AD
\Arc
h\P
AC
KA
GE
A\K
ISD
_S
TA
RK
EY
ES
_V
2.4
_A
19.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-P
AC
KA
GE
A
100%
CD
A1.06
COMPOSITE PLAN -
STARKEY - 1ST
FLOOR
3/4/2019
18397M
KISD
100% CD
Aut
hor
Che
cker
3/4/2019
1/16" = 1'-0"1 COMPOSITE PLAN
No. Description Date1 ADDENDUM 01 3/25/19
1
GENERAL NOTES
1. DO NOT SCALE DRAWINGS, WRITTEN DIMENSIONS TAKE PRECEDENCE, CONTACT ARCH IF CLARIFICATION IS NECESSARY IN ORDER TO DETERMINE THE INTENT OF THE CONTRACT DOCUMENTS
2. DRAWINGS NOTED AS "N.T.S" OR "NTS" ARE NOT TO SCALE3. FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS BEFORE
COMMENCING WORK. NOTIFY ARCH. OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH AFFECTED WORK
MENTORING CENTER
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
MEDIA CENTER
WORK ROOM
STORAGE
VEST
JAN
RR RR
TEXT BOOK STORAGE
COMPUTER LAB
CORRIDOR
LOBBY
GEN OFFICECONFERENCE
COUNC
OFFICERECORDS
NURSE
RR
PRINC
STORAGE
STAIR
STORAGE
MECH
CAFETORIUM
STAGE
SERVERY
WAREWASH
REF. / FREEZER
DRY STORAGE
MECH OFFICE
FOOD PREP
LOCKER TOILET JAN
STORAGE
STAIR
JAN
CLASSROOM
STORAGE
TELE
RRRR
WORK ROOM
WORK ROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
VEST
RAMP
Room
CORRIDOR
CLASSROOM
Room
Room
Room
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CORRIDOR
Room
Room
Room
Room
VEST
FAC
VESTRR
JAN
VEST RR
ELEC
MECH
PLAY AREA
OFFICE
BOYS DRESS
STORAGE RR
GIRLS DRESS
RRSTORAGE
VEST
ART CLASSROOM
Room Room
CLASSROOM
RAMP
VEST
TESTING
MUSIC CLASSROOM
STORAGE
RAMP
CORRIDOR
CLASSROOM
RESOURCE
CLASSROOM CLASSROOMVEST
FAC
VEST RR
JAN
VEST RR
CORRIDOR
CLASSROOM
OUTDOOR STORAGE
STORAGE
ELEC
CENTRAL STORAGE
CLASSROOM
CLASSROOM
ASSUMED EXISTING FIRE WALL
ASSUMED EXISTING FIRE WALL
Other
Architect
ARCHITECT PBK Architects, Inc.
MEPT
DATE
PROJECT NUMBER
CLIENT
REVISIONS
HOUSTON11 Greenway Plaza, 22nd Floor
Houston, TX 77046713-965-0608 P713-961-4571 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
11 Greenway Plaza, Suite 1510Houston, TX 77046
713-940-3300 P 713-961-4571 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/2
5/2
01
9 1
:32:2
7 P
M
\\P
BK
dfs
\PB
KIn
c\P
roje
cts
\San\ 1
8\1
8397M
\Div
8-D
wgs\8
a B
IM C
AD
\Arc
h\P
AC
KA
GE
A\K
ISD
_T
OM
DA
NIE
LS
ES
_V
2.4
_A
19rv
t.rv
t
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-P
AC
KA
GE
A
100%
CD
A1.09
COMPOSITE PLAN -
TOM DANIELS - 1ST
FLOOR
3/4/2019
18397M
KISD
100% CD
Aut
hor
Che
cker
3/4/2019
1/16" = 1'-0"1 COMPOSITE PLAN
No. Description Date1 ADDENDUM 01 3/25/19
1
Project No. 18397M – Addendum No. 01
601 N.W. Loop 410, Suite 400 \\ San Antonio, Texas 78216 \\ P 210-638-7200 \\ F 210-829-0578 \\ LEAFengineers.com
Addendum Number 01 03/25/2019
To Drawings and Specifications dated 03/04/2019
KISD – Safety and Security improvements – Package A
Prepared by: LEAF Engineers, Inc. 601 NW Loop 410, Suite 400 San Antonio, Texas 78216 LEAF Project No.: 18397M Notice to Proposers: A. Receipt of this Addendum shall be acknowledged on the Proposal Form. B. This Addendum forms part of the Contract documents for the above referenced project and shall be
incorporated integrally therewith. C. Each proposer shall make necessary adjustments and submit his proposal with full knowledge of all
modifications, clarifications, and supplemental data included therein. Where provisions of the following supplemental data differ from those of the original Contract Documents, this Addendum shall govern.
SPECIFICATIONS None DRAWINGS Item No. 01: T1.01 – Nimitz Elementary School – Fire Safety Plan:
1. Updated general note number 14. Item No. 02: T1.02 – Starkey Elementary School – Fire Safety Plan:
1. Updated general note number 14. 2. Added fire fighter relay for fan in gym. 3. Added keyed note number 9 for relay.
Item No. 03: T1.03 – Tivy Education Center – Fire Safety Plan:
1. Updated general note number 14. Item No. 04: T1.04 – Tom Daniels Elementary School – Fire Safety Plan:
1. Updated general note number 14.
END OF ADDENDUM NO. 01
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
03/25/2019
F
F
F
F
F
F
F
F
F
FF
F
F
F F
F
F
F
F
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP S
P
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SPS
P
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SPS
P
SP
SPS
P SP
SP
SP
FA
CP
CO !F
F SP
UPSP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
FFS
P
SP
SP
MDF
IDF
WP
WP
WPWP
WP
WPF5
F3
F2
F1
F4F6
F8 F7
STAIR
D228
CORRIDOR
D229
RECEPTION
D230
OFFICE
D231
Room
D232
OFFICE
D233
OFFICE
D234
OFFICE
D235CONFERENCE
D236
OFFICE
D237
Room
D238
Room
D239
RR
D240
RR
D241 BREAK
D242
Room
D243
OFFICE
D244
VEST
D245
MECH
D246
CLASS
D247
STOR
D248
RR
D249 SHWR
D250
CLASS
D251STOR
D252
STOR
D253
STOR
D254
CLASS
D255
ISO
D256
RR
D257
VEST
D258
CORRIDOR
D259
CORRIDOR
D260
MEDIA CENTER
D261
STAGE
D262
OFFICE
D263
COMP LAB
D264
LOUNGE
D265
CORRIDOR
D266
Room
D267
STOR
D268
STOR
D269RR
D270
RR
D271
OFFICE
D272ART
D273
STOR
D274
STOR
D275
VEST
D276
CAFETERIA
D277STAGE
D278
STOR
D279
STOR
D280
STOR
D281
STOR
D282
PREP
D283
STOR
D284
STOR
D285
PREP
D286
STOR
D287
RISER
D288STOR
D289RR
D290
LOCKER
D291
PREP
D292
SERVING
D293
CORRIDOR
D294
VEST
D295
RR
D296
Room
D297
VEST
D298
RR
D299
VEST
D300
ENCLOSED PLAY AREA
D301
DRESS
D302OFFICE
D303
RR
D304DRESS
D305
JAN
D306
Room
D307
MECH
D308
MENTORING CENTER
M100
IDFIDF F2
F1
F3
F4
CORRIDOR
A201
CLASSROOM
A202
CLASSROOM
A203
CLASSROOM
A204
CLASSROOM
A205
CLASSROOM
A206
CLASSROOM
A207
CLASSROOM
A208
CLASSROOM
A209
CLASSROOM
A210
CLASSROOM
A211
CLASSROOM
A212
CLASSROOM
A213
CORRIDOR
A214
JAN
A215
VEST
A216
RR
A217RR
A218
VEST
A219
FAC
A220
STORAGE
A221
CORRIDOR
B201
CLASSROOM
B202
CLASSROOM
B203
CLASSROOM
B204
CLASSROOM
B205
CLASSROOM
B206
CLASSROOM
B207
CLASSROOM
B208
CLASSROOM
B209
CLASSROOM
B210
CLASSROOM
B211
CORRIDOR
D201
JAN
D202
VEST
D203
RR
D204
FAC
D205
VEST
D206
RR
D207CLASSROOM
D208
CLASSROOM
D209
CLASSROOM
D210
CLASSROOM
D211
CLASSROOM
D212
CLASSROOM
D213
CLASSROOM
D214
CLASSROOM
D215
CLASSROOM
D216
CLASSROOM
D217
CORRIDOR
D218
CLASSROOM
D219
VEST
D220
JAN
D221
VEST
D222
RR
D223
FAC
D224
VEST
D225
RR
D226
STORAGE
D227
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/2
5/2
01
9 1
2:0
9:3
3 P
M
C:\U
sers
\acru
z\D
ocum
ents
\18
397M
- K
ER
RV
ILLE
- N
IMIT
Z_
R19_
acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
T1.01
NIMITZ
ELEMENTARY
SCHOOL - FIRE
SAFETY PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. CONTRACTOR MUST DISCOVER ALL NEW AND EXISTING DUCT DETECTOR LOCATIONS INCOORDINATION WITH THE OWNER.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN - FIRST FLOOR1
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN - SECOND FLOOR2
KEYED NOTES - FIRE SAFETY PLAN
F1 MANUAL FIRE ALARM PULL STATION.
F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATESPHOTOELECTRIC TYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.
F3 COMBINATION SPEAKER OR HORN AND STROBE IN SINGLE COVER. SUBSCRIPT "W"INDICATES WHITE FINISH; OTHERWISE STANDARD RED COLOR. "V" INDICATESLOCAL VOICE EVACUATION SPEAKER FUNCTIONS, "H" INDICATES HIGH VOLUMESPEAKER FUNCTIONS, REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/ORHORN APPLICATIONS.
F4 VISUAL ALARM STROBE. SUBSCRIPT "W" INDICATES WHITE FINISH; OTHERWISESTANDARD RED COLOR.
F5 FIRE ALARM SPEAKER OR HORN. SUBSCRIPT "WP" INDICATES WEATHER PROOFDEVICE. REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/OR HORNAPPLICATIONS. A SUBSCRIPT "S" INDICATES THAT A SPEAKER STROBE TIED TOVOICE EVAC PANEL SHALL BE PROVIDED FOR ALL LOCATIONS INDICATED.
F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL
F7 HEAT DETECTOR; COMBINATION RATE OF RISE AND FIXED TEMPERATURE. "F"INDICATES FIXED TEMPERATURE ONLY; "R" INDICATES RATE OF RISE ONLY. "C"INDICATES RATE COMPENSATION TYPE.
F8 CARBON MONOXIDE DETECTOR.
No. Description Date1 ADDENDUM 01 FOR PKG A 03/25/2019
1
FA
CP
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
F
F
F
F
F
F
F
F
F
F
FS P
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
F
F
F
F
F
F
F
F
F
!F
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
CO
CO
SP
SP
R
5' - 0"
MDF
IDF
F1
F2
F3
F4
F5F6
WP
WP
WP
WP
WP
WP
WP
WP
WP
DRESS
A101
RR
A102DRY STO
A103
BULK STO
A104
FOOD PREP
A105OFFICE
A107
JAN
A109
REF / FZR
A106
WAREWASH
A110
SERVERY
A108
CAN WASH
A112
CAFETORIUM
A111
STAGE
A127
MUSIC
A128
RR
A129
VEST
A130
JAN
A131
RR
A132
VEST
A133
OUTSIDE STO
A114
ELEC
A115
STO
A116
MECH
A117
PAPER STO
A118
JAN
A119
RR
A120
RR
A121
DRESS
A122
DRESS
A123
OFFICE / STO
A124
STO
A125
STO
A126
ENCLOSED PLAY AREA
A135
Room
A136
ELEC
B101
STO
B102
RR
B103
RR
B104
JAN
B105WORK AREA
B106
CLASSROOM
B107
CLASSROOM
B108
Room
B109
Room
B110
CLASSROOM
B111
CLASSROOM
B112
Room
B113
Room
B114
CLASSROOM
B115
CORRIDOR
B116
ART
B118
KILN
B119
STO
B120
CORRIDOR
B121
CLASSROOM
B122
CLASSROOM
B123
CLASSROOM
B124
CLASSROOM
B125
CLASSROOM
B126
CLASSROOM
B127
CLASSROOM
B128
CLASSROOM
B129
CORRIDOR
B131
ELEC
B133
RR
B134CLINIC
B135
CORRIDOR
B136
CLASSROOM
B137
CLASSROOM
B139
CLASSROOM
B140
CLASSROOM
B141
VEST
B142
FAC
B143
VEST
B144
RR
B145
RR
B146
VEST
B147
JAN
B148CLASSROOM
B149
CLASSROOM
B150
STO
B151
RR
B152
CLASSROOM
B153 CLASSROOM
B154
CLASSROOM
B155RR
B156
CORRIDOR
B157
TESTING
B158
STORAGE
B159 CLASSROOM
B160
CLASSROOM
B162
CLASSROOM
B163
CLASSROOM
B164
CORRIDOR
C100
OFFICE / RECEP
C101
CORRIDOR
C102
WORK ROOM
C103PRINC
C104
COUNCELOR
C105
FILES / RECORDS
C106MULTI-USE OFFICE
C107
CONFERENCE
C108
FAC WORK ROOM
C109
RR
C110
RR
C111
LOUNGE
C112
TELE
C113
TEXTBOOK STO
C114
TEACHERS LOUNGE
C115
COFFEE
C116
LOBBY
C117COMPUTER LAB
C118
Room
C119
STO
C122
CORRIDOR
C123
Room
C125
MULTI-USE
C126
MEDIA CENTER
C127
LIBRARIANS OFFICE
C128
LIBRARY STO
C129STUDY ROOM
C130
FILM VIEWING
C131
CLASSROOM
C133
CORRIDOR
C132
RR
C134
CLASSROOM
C135
CLASSROOM
C136
CLASSROOM
C137CLASSROOM
C138
CLASSROOM
C139
CLASSROOM
C140
STO
C141
STO
C142
RR
C143
WORKROOM
C144CLASSROOM
C145
CLASSROOM
C146
F5
F7
F8
F9FIRE ALARM RELAY FOR FAN, CONTRACTOR TO COORDINATE RELAY INSTALLATION WITH OWNER. FAN MUST SHUT DOWN IN THE EVENT OF A FIRE ALARM
1
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/2
5/2
01
9 1
2:5
4:5
3 P
M
C:\U
sers
\acru
z\D
ocum
en
ts\1
839
7M
- K
ER
RV
ILLE
- S
TA
RK
EY
_R
19
_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
T1.02
STARKEY
ELEMENTARY
SCHOOL - FIRE
SAFETY PLAN
03/04/2019
18397M
Kerrville Indepenent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN1
GENERAL NOTES - FIRE SAFETY PLAN
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. CONTRACTOR MUST DISCOVER ALL NEW AND EXISTING DUCT DETECTOR LOCATIONS INCOORDINATION WITH THE OWNER.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
KEYED NOTES - FIRE SAFETY PLAN
F1 MANUAL FIRE ALARM PULL STATION.
F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATESPHOTOELECTRIC TYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.
F3 COMBINATION SPEAKER OR HORN AND STROBE IN SINGLE COVER. SUBSCRIPT "W" INDICATESWHITE FINISH; OTHERWISE STANDARD RED COLOR. "V" INDICATES LOCAL VOICE EVACUATIONSPEAKER FUNCTIONS, "H" INDICATES HIGH VOLUME SPEAKER FUNCTIONS, REFERENCE DIV. 28SPECIFICATIONS FOR SPEAKER AND/OR HORN APPLICATIONS.
F4 VISUAL ALARM STROBE. SUBSCRIPT "W" INDICATES WHITE FINISH; OTHERWISE STANDARDRED COLOR.
F5 FIRE ALARM SPEAKER OR HORN. SUBSCRIPT "WP" INDICATES WEATHER PROOF DEVICE.REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/OR HORN APPLICATIONS. ASUBSCRIPT "S" INDICATES THAT A SPEAKER STROBE TIED TO VOICE EVAC PANEL SHALL BEPROVIDED FOR ALL LOCATIONS INDICATED.
F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL
F7 HEAT DETECTOR; COMBINATION RATE OF RISE AND FIXED TEMPERATURE. "F" INDICATESFIXED TEMPERATURE ONLY; "R" INDICATES RATE OF RISE ONLY. "C" INDICATES RATECOMPENSATION TYPE.
F8 CARBON MONOXIDE DETECTOR.
F9 AUXILIARY CONTROL RELAY REQUIRED FOR FIRE FIGHTER OVERRIDE CONTROL.
No. Description Date1 ADDENDUM 01 FOR PKG A 03/25/2019
11
SP
SP
SP
SP
SP
SP
CLASS
115
CLASS
116
STOR
117
RR
118
CONFERENCE
119
STOR
120STOR
121
RR
122
RR
123
CORRIDOR
124
F2
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/2
5/2
01
9 1
:06:0
6 P
M
C:\U
sers
\acru
z\D
ocum
ents
\1839
7M
- K
ER
RV
ILLE
- T
IVY
ED
UC
AT
ION
CE
NT
ER
_T
19_a
cru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
T1.03
TIVY EDUCATION
CENTER - FIRE
SAFETY PLAN -
AREA F
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. CONTRACTOR MUST DISCOVER ALL NEW AND EXISTING DUCT DETECTOR LOCATIONS INCOORDINATION WITH THE OWNER.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
KEYED NOTES - FIRE SAFETY PLAN
F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATES PHOTOELECTRICTYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.
SCALE: 1/4" = 1'-0"
FIRE SAFETY PLAN - AREA F1
No. Description Date1 ADDENDUM 01 FOR PKG A 03/25/2019
1
FA
CP
FA
CP
MDF
IDF
IDF
IDF F6
MENTORING CENTER
C001
CORRIDOR
A100
CLASSROOM
A101
CLASSROOM
A102
CLASSROOM
A103
CLASSROOM
A104
CLASSROOM
A105
MEDIA CENTER
A106
WORK ROOM
A107
STORAGE
A108
VEST
A109
JAN
A110
RR
A111
RR
A112
TEXT BOOK STORAGE
A113
COMPUTER LAB
A114
CORRIDOR
B101 LOBBY
B100
GEN OFFICE
B102
CONFERENCE
B103
COUNC
B104OFFICE
B105
RECORDS
B106
NURSE
B107
RR
B108
PRINC
B109
STORAGE
B110
STAIR
B111STORAGE
B112
MECH
B113
CAFETORIUM
B114
STAGE
B125
SERVERY
B115WAREWASH
B116
REF. / FREEZER
B117
DRY STORAGE
B118
MECH
B119OFFICE
B120
FOOD PREP
B121
LOCKER
B122TOILET
B123
JAN
B124
STORAGE
B126
STAIR
B127
JAN
B128
CLASSROOM
B129
STORAGE
B131
TELE
B132
RR
B133
RR
B134
WORK ROOM
B135
WORK ROOM
B136
CLASSROOM
B137
CLASSROOM
B138
CLASSROOM
B139
CLASSROOM
B140
CLASSROOM
B141
CLASSROOM
B142
CLASSROOM
B143
VEST
B144
RAMP
B145
Room
B146
CORRIDOR
B130
CLASSROOM
B147
Room
B148
Room
B149
Room
B150
CLASSROOM
B151
CLASSROOM
B152
CLASSROOM
B153
CLASSROOM
B154
CLASSROOM
B155
CLASSROOM
B156
CLASSROOM
B157
CLASSROOM
B158
CORRIDOR
C100
Room
C101
Room
C102
Room
C103
Room
C104
VEST
C105 FAC
C106
VEST
C107
RR
C108
JAN
C109
VEST
C110
RR
C111
ELEC
C112MECH
C113
PLAY AREA
C114
OFFICE
C115
BOYS DRESS
C116
STORAGE
C117
RR
C118
GIRLS DRESS
C119
RR
C120
STORAGE
C121
VEST
C123
ART CLASSROOM
C124
Room
C125
Room
C126
CLASSROOM
C127
RAMP
C128
VEST
C129
TESTING
C130MUSIC CLASSROOM
C131
STORAGE
C132
RAMP
C133
CORRIDOR
C134
CLASSROOM
C135RESOURCE
C136
CLASSROOM
C137
CLASSROOM
C138
VEST
C139
FAC
C140
VEST
C141 RR
C142
JAN
C143
VEST
C144
RR
C145
CORRIDOR
C146
CLASSROOM
C147
OUTDOOR STORAGE
C148
STORAGE
C149
ELEC
C150
CENTRAL STORAGE
C151
CLASSROOM
C152
CLASSROOM
C153
NEW FACP WITH FIBER COMMUNICATION ABILITIES,
TO BE INSTALLED AND CONNECTED VIA EXISTING FIBER.
EXISTING DEVICES TO BE CONNECTED TO NEW FACP.
LOCATIONOF EXISTING FIBER PAIRSTO ANNEX
IDF
F6
CLASSROOM
C154
CLASSROOM
C155
CLASSROOM
C156
CLASSROOM
C157
CLASSROOM
C158
CLASSROOM
C159
CLASSROOM
C160
CLASSROOM
C161
CLASSROOM
C162
CLASSROOM
C163
ELEC / STOR / IDF
C164
RR
C165
RR
C166
ELEC / STOR
C167
CORRIDOR
C168
VEST
C169
NEW FACP WITH FIBER COMMUNICATION ABILITIES,
TO BE INSTALLED AND CONNECTED VIA EXISTING FIBER.
EXISTING DEVICES TO BE CONNECTED TO NEW FACP.
LOCATIONOF EXISTING FIBER PAIRSTO MDF
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/2
5/2
01
9 1
2:1
1:4
2 P
M
C:\U
sers
\acru
z\D
ocum
ents
\1839
7M
- K
ER
RV
ILL
E -
DA
NIE
LS
_R
19_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-
PA
CK
AG
E A
100%
CD
T1.04
TOM DANIELS
ELEMENTARY
SCHOOL - FIRE
SAFETY PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN1
GENERAL NOTES - FIRE SAFETY PLAN
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. CONTRACTOR MUST DISCOVER ALL NEW AND EXISTING DUCT DETECTOR LOCATIONS INCOORDINATION WITH THE OWNER.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN - ANNEX2
KEYED NOTES - FIRE SAFETY PLAN
F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL
No. Description Date1 ADDENDUM 01 FOR PKG A 03/25/2019
1