periodic inspection · a periodic inspection on 45 glan y gors, prestatyn, denbighshire ll19 7rl....
TRANSCRIPT
Periodic inspectionPeriodic inspection45 Glan Y Gors
Inspected byInspected by:: OffaltdDate of InspectionDate of Inspection:: 4th May 2016Prepared ByPrepared By:: Offa LtdPrepared forPrepared for:: Jay LiptrotTenantTenant::Junior Buchanon & Catherine FrenchRefers toRefers to::45 Glan Y Gors, Prestatyn, DenbighshireLL19 7RLDate PublishedDate Published:: 10th May 2016
GENERAL INSPECTION NOTESGENERAL INSPECTION NOTESA periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by propertymanager, Lucy Knight. Present at the inspection were the tenants, Junior Buchanon & Catherine French. The property wasclean and tidy and in a good decorative condition. Any maintenance issues have been highlighted for your attention.
CERTIFICATESCERTIFICATESSPACESSPACES
Property Front ExteriorProperty Front Exterior
04/05/2016 10:47 (UTC) at 53.33486217079063 ° ,-3.417643401774967 °
Notes:Notes:The front of the property is in good condition.
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 1 of 12
Front GardenFront Garden
04/05/2016 10:55 (UTC) at 53.33484184467544 ° ,-3.417696123945916 °
04/05/2016 10:55 (UTC) at 53.33484678999831 ° ,-3.417650777849758 °
Notes:Notes:The tenant has advised that the landlord did agree to replacing the gravel in the front garden, if this correct please advisewhether you are happy to provide this.
Living RoomLiving Room
04/05/2016 10:54 (UTC) at 53.33488136534889 ° ,-3.417633008215034 °
04/05/2016 10:54 (UTC) at 53.33488044333954 ° ,-3.417701823640072 °
Notes:Notes:The living room is clean and tidy and is in good decorative condition.
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 2 of 12
KitchenKitchen
04/05/2016 10:50 (UTC) at 53.33486155843625 ° ,-3.417814341463165 °
04/05/2016 10:51 (UTC) at 53.33486844052312 ° ,-3.41779528793329 °
04/05/2016 10:51 (UTC) at 53.33486667271292 ° ,-3.417742876181535 °
Notes:Notes:The kitchen is clean and tidy and is in good decorative condition.
ItemItem DescriptionDescriptionFloors UsedUsed
The flooring is non slip vinyl and is in good condition.
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 3 of 12
KitchenKitchen (continued)(continued)
ItemItem DescriptionDescription
04/05/2016 10:51 (UTC) at 53.3348587907882 ° ,-3.417818891485341 °
Walls UsedUsedThe walls are wallpapered and are in a good condition.
04/05/2016 10:51 (UTC) at 53.33482453604539 ° ,-3.417741386223042 °
Cabinets FlaggedFlagged
The tenant complained that some of her work tops have chipped and also that the gap where thecooker is hasn't enough space to get out easily and asked if it could be considered to increase thisgap.
Floors(continued)
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 4 of 12
KitchenKitchen (continued)(continued)
ItemItem DescriptionDescription
04/05/2016 10:50 (UTC) at 53.33484536870088 ° ,-3.417740890088031 °
04/05/2016 10:50 (UTC) at 53.33487347709884 ° ,-3.417884285325066 °
BedroomBedroom
04/05/2016 10:52 (UTC) at 53.33493358460565 ° ,-3.417767705399001 °
04/05/2016 10:52 (UTC) at 53.33494448107977 ° ,-3.417799472812021 °
Cabinets(continued)
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 5 of 12
04/05/2016 10:52 (UTC) at 53.33493127958228 ° ,-3.417814224961603 °
04/05/2016 10:52 (UTC) at 53.33492407114555 ° ,-3.417815649885142 °
Notes:Notes:The bedroom is clean and tidy and is in good decorative condition.
ItemItem DescriptionDescriptionFloors UsedUsed
The flooring is carpeted in brown and is in good condition, no marks present.
04/05/2016 10:52 (UTC) at 53.33493111194421 ° ,-3.417767873037064 °
Walls UsedUsedThe walls are plastered and painted pink and are in a good condition.
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 6 of 12
BedroomBedroom (continued)(continued)
ItemItem DescriptionDescription
04/05/2016 10:52 (UTC) at 53.33492482551684 ° ,-3.417770806703174 °
Bedroom 2Bedroom 2
04/05/2016 10:53 (UTC) at 53.33489138172318 ° ,-3.417782373729551 °
Notes:Notes:The bedroom is clean and tidy and is in good decorative condition.
Walls(continued)
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 7 of 12
ItemItem DescriptionDescriptionFloors UsedUsed
The flooring is carpeted in brown and is in good condition, no marks present.
04/05/2016 10:53 (UTC) at 53.33488647830983 ° ,-3.41778622940501 °
Walls UsedUsedThe walls are wallpapered and are in a good condition.
04/05/2016 10:53 (UTC) at 53.33487185188879 ° ,-3.417799472812021 °
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 8 of 12
Bedroom 3Bedroom 3
04/05/2016 10:53 (UTC) at 53.33486971450348 ° ,-3.417803077030384 °
04/05/2016 10:53 (UTC) at 53.33486971450348 ° ,-3.417803077030384 °
Notes:Notes:The bedroom is clean and tidy and is in good decorative condition.
ItemItem DescriptionDescriptionWalls UsedUsed
The walls are wallpapered and are in a good condition.
04/05/2016 10:53 (UTC) at 53.33489775196959 ° ,-3.417827468368614 °
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 9 of 12
BathroomBathroom
04/05/2016 10:51 (UTC) at 53.33489008252819 ° ,-3.417753539982641 °
Notes:Notes:The bathroom is clean and tidy and is in good decorative condition.
ItemItem DescriptionDescriptionFloors UsedUsed
The flooring is red no slip vinyl and is in a good condition.
04/05/2016 10:52 (UTC) at 53.33489008252819 ° ,-3.417753539982641 °
Walls UsedUsedThe walls are wallpapered and in a good condition.
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 10 of 12
BathroomBathroom (continued)(continued)
ItemItem DescriptionDescription
04/05/2016 10:52 (UTC) at 53.33487109751751 ° ,-3.417757563296163 °
Walls(continued)
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 11 of 12
FLAGGED ADDENDUMFLAGGED ADDENDUMItemItem DescriptionDescriptionKitchen:Cabinets
FlaggedFlagged
The tenant complained that some of her work tops have chipped and also that the gap where thecooker is hasn't enough space to get out easily and asked if it could be considered to increase thisgap.
04/05/2016 10:50 (UTC) at 53.33484536870088 ° ,-3.417740890088031 °
04/05/2016 10:50 (UTC) at 53.33487347709884 ° ,-3.417884285325066 °
Periodic inspectionPeriodic inspection45 Glan Y Gors
Page 12 of 12
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
ELECTRICAL INSTALLATIONCONDITION REPORT
Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor orConforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX
Contractor's Reference Number
A. DETAILS OF THE CLIENT
Client: Address:OFFA Ffordd william morganSt Asaph
Postcode:
B. PURPOSE OF THE REPORT This report must be used only for reporting on the condition of an existing installation.
Purpose for whichthis report is required:
Landlords Request
Date(s) on which inspection and testing were carried out: 10/09/2015
C. DETAILS OF THE INSTALLATION
Occupier N/A Address 45 glan y gorsPrestatyn
Postcode:
Estimated age of theelectrical installation: 25 years Description of premises:
domestic, commercial,industrial, other(Please state)
DomesticEvidence of alterations
or additions á If yes,estimatedage
5 years
Date of previousinspection:
Unknown Electrical Installation Certificate No or previousPeriodic Inspection or Condition Report No:
UNKNOWN
Records of installation available: á Records held by: NWHA
D. EXTENT OF THE INSTALLATION AND LIMITATIONS ON THE INSPECTION AND TESTING
Extent of the electrical installation covered by this report:
Atleast 10% of each circuit has been inspected during this inspection and test, no floor boards or fixed furniture have been removed to get to electrical equipment, where there are gascookers the cooker supply has only been inspected to the isolator.Only fixed wiring has been inspected and tested .Insulation resistance and R1+R2 test only where shown.
Agreed limitations (including the reasons), if any, on the inspection and testing:
Due to sensitive equipment such as fluorescents and boilers ect the insulation resistance test is only carried out at 250 volts.Tests in most cases have been carried out up to isolators, no fans, central heating systems fixed or portable appliances ect are included within the scope of the test.
Agreed with:
Operational limitations including the reasons (see page No. )
N/A
The inspection and testing have been carried out in accordance with BS 7671, as amended. Cables concealed within trunking and conduits, or cables and conduitsconcealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, have not been visually inspected unlessspecifically agreed between the client and inspector prior to the inspection.
E. SUMMARY OF THE CONDITION OF THE INSTALLATION
General condition of the installation (in terms of electrical safety):
Unsatisfactory.
Summary of the condition of the installation continued on additional pages? No Yes Specify page No(s):áOverall assessmentof the installation: SATISFACTORY / UNSATISFACTORY
An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentiallydangerous (CODE C2) conditions have been identified, or that Further investigation withoutdelay (FI) is required
This report should have been reviewed and confirmed by the registered Qualified Supervisorof the Approved Contractor responsible for issuing it. (See declaration on page 2)
This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
Page 1 of 8
Please see the 'Notes for Recipients'
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
ELECTRICAL INSTALLATIONCONDITION REPORT
Please see the 'Guidance for Recipients on theclassification codes' in the 'Notes for Recipients'
F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN
Referring to the attached schedules of inspection and test results, and subject to the limitations at D:
Item No Code Ú
There are no items adversely affecting electrical safety. N/A or The following observations and recommendations forare made
á
Additional Pages? No Yesá Specify page
ÚOne of the following codes, as appropriate, has been allocated to each of theobservations made above to indicate to the person(s) responsible for the installationthe degree of urgency for remedial action:
Code C1 "Danger Present". Risk of injury. Immediate remedial action required.
Code C2 "Potentially dangerous". Urgent remedial action required.
Code C3 "Improvement recommended".
Code FI "Further investigation required without delay".
Please see the notes for recipient for guidance regarding the Classification codes.
1 Main earth is only 10mm C2
2 Main equipotential bonding conductors are only 6mm C2
3 Kitchen light had no defuser C3
4 There is no RCD protection C2
Immediate remedial actionrequired for items:
Urgent remedial actionrequired for items: 4, 1, 2
Further investigation requiredwithout delay for items:
Improvementrecommended for items: 3
G. DECLARATION
I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of whichare described in page 1 (see C), having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the informationin this report, including the observations (see F) and the attached schedules (see H), provides an accurate assessment of the condition of the electricalins ta l la t ion tak ing into account the stated extent of the ins ta l la t ion and the l im i tat ions of the inspect ion and tes t ing (see D ) .I/We further declare that in my/our judgement, the overall assessment of the installation in terms of its suitability for continued use is
SATISFACTORY / UNSATISFACTORY* (see F) at the time the inspection was carried out, and that it should be further inspected as recommended (see I).
*An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentially dangerous (CODE C2) conditions have been identified, or that Further investigationwithout delay (FI) is required.
INSPECTION, TESTING AND ASSESSMENT BY:
Signature
Name(CAPITALS) JONATHON BENBOW
Position QS
Date: 10/09/2015
REPORT REVIEWED AND CONFIRMED BY:
Signature
Name(CAPITALS) JONATHON BENBOW
(Registered Qualified Supervisor for the Approved Contractor at J)
Date: 10/09/2015
Page 2 of 8
This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
ELECTRICAL INSTALLATIONCONDITION REPORT
Page 3 of 8
H. SCHEDULES AND ADDITIONAL PAGES
Inspection Schedule: Page(s) No 4,5,6 Additional pages, including additionalsource(s) data sheets: Page No(s)
Schedule of Test Results for the Installation: Page No(s) 8Schedule of Circuit Details for the Installation: Page No(s) 7
The pages identified are an essential part of this report. The report is valid only if accompanied by all the schedules and additional pages identified above.
I. NEXT INSPECTION
I/We recommend that this installation is furtherinspected and tested after an interval of not more than 5 Years (Enter interval in terms of
years, months or weeks, as appropriate)
provided that any items at F which have been attributed a Classification code C1 (danger present) are remedied immediately and that any itemswhich have been attributed a code C2 (potentially dangerous) or FI (further investigation required without delay) are remedied or investigatedrespectively as a matter of urgency. Items which have been attributed a Classification code C3 should be improved as soon aspracticable (see F).
J. DETAILS OF NICEIC APPROVED CONTRACTOR
Trading Title: 1st Class Electrical
Address: 2 Allt-y-graigDyserth
Postcode:LL18 6DE
Telephone number: 01745 571162
Email Address: [email protected]
Enrolment number:(Essential information)
600502
Branch number:(if applicable)
000
K. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
System Type(s) Number and Type of Live Conductors Nature of Supply Parameters
Characteristics of Primary SupplyOvercurrent Protective Device(s)
TN-S N/A
TN-C-S á
TN-C N/A
TT N/A
IT N/A
1-phase(2 wire) á2-phase(3 wire) N/A
3-phase(3 wire) N/A
1-phase(3 wire) N/A
3-phase(4 wire) N/A
a.c. á d.c. N/A
2 pole N/A
3 pole N/A
other
Other
NominalVoltage(s): Uþ 400
V230
UÒþ V
Nominalfrequency, fþ
50Hz
Prospective faultcurrent, IÙÄÅ
1.03kA
External earth faultloop impendance, Ñ Å Ç
0.22É
1Number ofsources
Notes:(1) by enquiry
(2) by enquiry or bymeasurement
(3) where more thanone supply, recordthe higher or highestvalues
(4) by measurement
BS(EN) 1361
Type 2b
Rated current 80 A
33 kAShort-circuitcapacity
Confirmation ofsupply polarity á (á)
L. PARTICULARS OF INSTALLATION AT THE ORIGINMeans of Earthing Details of Installation Earth Electrode (where applicable)
Main Switch/Switch-Fuse/Circuit-Breaker/RCD
Distributor'sfacility: á
Installationearth electrode: N/A
Type:(eg rod(s),tape(s))
Electroderesistance, RÕ: (É)
Location:
Method ofmeasurement:
* (applicable only where an RCD is suitable and is used as a main circuit-breaker)
60497-3Type:BS(EN)
2No ofPoles
CopperPrimary supplyconductorsmaterial
16Primary supplyconductorscsa
mmâ
Voltagerating
230
Ratedcurrent,IÐ
100
RCD operatingcurrent, IÜ *
N/A
Rated timedelay*
N/A
RCD operatingtime (at IÜ )*
N/A
V
A
mA
ms
ms
Earthing conductor Main protective bonding conductors Bonding of extraneous-conductive-parts (á)
Earthing and protective bonding conductors
Conductormaterial
Copper Conductormaterial
Copper
Conductorcsa
16 mmâConductor
csa10 mmâ
Connection/ ácontinuityverified
Connection/continuityverified
(á) (á)
Waterinstallation pipes á
Oilinstallation pipes N/A
Gasinstallation pipes á
Lightningprotection N/A
Structuralsteel N/A
Other
This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
Please see the 'Notes for Recipients'
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
ELECTRICAL INSTALLATION CONDITION REPORT
This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable
Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)
OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.
Page 4 of 8
1.0 Condition/adequacy of distributor's/supply intake equipmentÚ
1.1 Service cable á1.2 Service head á1.3 Distributor's earthing arrangement(s) á1.4 Meter tails - Distributor/ Consumer á1.5 Metering equipment á1.6 Means of main isolation (where present) á
2.0 Presence of adequate arrangements for parallel or switched alternative sources
2.1 Adequate arrangements where a generating set operates as a switched alternative to the public supply N/A
2.2 Adequate arrangements where a generating set operates in parallel with the public supply N/A
3.0 Automatic disconnection of supply
3.1 Main earthing and bonding arrangements
Presence and condition of distributor's earthing arrangement áPresence and condition of earth electrode arrangement N/A
Adequacy of earthing conductor size C2 1
Adequacy of earthing conductor connections áAccessibility of earthing conductor connections áAdequacy of main protective bonding conductor size(s) C2 2
Adequacy of main protective bonding conductor connections áAccessibility of main protective bonding connections áAccessibility and condition of other protective bonding connections áProvision of earthing/bonding labels at all appropriate locations á
3.2 FELV
Source providing at least simple separation N/A
Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A
3.3 Reduced low voltage
Adequacy of source N/A
Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A
4.0 Other methods of protection (where the methods of protection listed below are employed, details should be provided on separate sheets)
4.1 Double insulation á4.2 Reinforced insulation N/A
4.3 Use of obstacles á4.4 Placing out of reach N/A
4.5 Non-conducting location N/A
4.6 Earth-free local equipotential bonding N/A
4.7 Electrical separation for more than one item of equipment á
5.0 Distribution equipment
5.1 Adequacy of working space/accessibility of equipment á5.2 Security of fixing á5.3 Condition of insulation of live parts á5.4 Adequacy/security of barriers á5.5 Condition of enclosure(s) in terms of IP rating á5.6 Condition of enclosure(s) in terms of fire rating á5.7 Enclosure not damaged/deteriorated so as to impair safety á5.8 Presence of main switch(es), linked where required á5.9 Operation of main switch(es) (functional check) á5.10 Correct identification of circuit protective devices á5.11 Adequacy of protective devices for prospective fault current á5.12 RCD(s) provided for fault protection - includes RCBOs C2 4
5.13 RCD(s) provided for additional protection - includes RCBOs C2 4
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
ELECTRICAL INSTALLATION CONDITION REPORT
This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable
Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)
OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.
Page 5 of 8
5.14 RCD(s) provided for protection against fire - includes RCBOs C2 4
5.15 Manual operation of circuit-breakers and RCDs to prove disconnection C2 4
5.16 Presence of RCD retest notice at or near equipment where required á5.17 Presence of diagrams, charts or schedules at or near equipment, where required á5.18 Presence of non-standard (mixed) cable colour warning notice at or near equipment where required á5.19 Presence of alternative/additional supply arrangement warning notice(s) at or near equipment where required á5.20 Presence of replacement next inspection recommendation label á5.21 Presence of other required labelling (specify) á5.22 Examination of protective device(s) and base(s); correct type and rating (no signs of unacceptable thermal damage,
arcing or overheating)á
5.23 Single-pole switching or protective devices in line conductors only á5.24 Protection against mechanical damage where cables enter equipment á5.25 Protection against electromagnetic effects where cables enter metallic enclosures N/A
6.0 Distribution/final circuits
6.1 Identification of conductors á6.2 Cables correctly supported throughout their length á6.3 Condition of insulation of live parts á6.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking á6.5 Suitability of containment systems for continued use (including flexible conduit) á6.6 Cables correctly terminated in enclosures (indicate extent of sampling in Section D of report) á6.7 Confirmation of indication that SPD(s) are functional á6.8 Confirmation that ALL conductor connections, including connections to busbars are correctly located in terminals and
are tight and secureá
6.9 Examination of cables for signs of unacceptable thermal and mechanical damage/deterioration á6.10 Adequacy of cables for current-carrying capacity with regard to the type and nature of installation á6.11 Adequacy of protective devices; type and rated current for fault protection á6.12 Presence and adequacy of circuit protective conductors á6.13 Co-ordination between conductors and overload protective devices á6.14 Cable installation methods/practices appropriate to the type and nature of installation and external influences á6.15 Cables where exposed to direct sunlight, of a suitable type á6.16 Cables installed under floors, above ceilings, in walls / partitions, adequately protected against damage
installed in prescribed zones (see Section D. Extent and limitations) áincorporating earthed armour or sheath, or installed within earthed wiring system, or otherwise protected against mechanical damage by nails, screws and the like (see Section D. Extent and limitations)
N/A
6.17 Provision of additional protection by 30 mA RCD
Ú for mobile equipment not exceeding a rating of 32 A for use outdoors C2 4
Ú for all socket-outlets of rating 20 A or less, unless exempt C2 4
Ú for cables installed in walls / partitions at a depth of less than 50 mm C2 4
Ú for cables installed in walls / partitions containing metal parts regardless of depth C2 4
6.18 Provision of fire barriers, sealing arrangements and protection against thermal effects á6.19 Band II cables segregated/separated from Band I cables á6.20 Cables segregated/separated from non-electrical services á6.21 Termination of cables at enclosures (identify numbers and locations of items inspected in Section D)
Connections under no undue strain áNo basic insulation of a conductor visible outside an enclosure áConnections of live conductors adequately enclosed áAdequacy of connection at point of entry to enclosure (gland, bush or similar) á
6.22 General condition of wiring systems á6.23 Temperature rating of cable insulation á6.24 Condition of accessories including socket-outlets, switches and joint boxes á6.25 Suitability of accessories for external influences á6.26 Single-pole switching or protective devices in line conductors only á6.27 Adequacy of connections, including cpcs, within accessories and to fixed and stationary equipment - identify /record
numbers and locations of items inspectedá
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
ELECTRICAL INSTALLATION CONDITION REPORT
This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS
Item Description Outcome* Location reference
* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable
Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)
OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.
Page 6 of 8
7.0 Isolation and switching
7.1 Isolators
presence and condition of appropriate devices áacceptable location (state if local or remote) ácapable of being secured in the OFF position ácorrect operation verified áclearly identified by position and/or durable marking(s) áWarning label posted in situations where live parts cannot be isolated by the operation of a single device á
7.2 Switching off for mechanical maintenance
presence and condition of appropriate devices áacceptable location ácapable of being secured in the OFF position ácorrect operation verified áclearly identified by position and/or durable marking(s) á
7.3 Emergency switching/stopping
presence and condition of appropriate devices áreadily accessible for operation where danger might occur ácorrect operation verified áclearly identified by position and/or durable marking(s) á
7.4 Functional switching
presence and condition of appropriate devices ácorrect operation verified á
8.0 Current-using equipment (permanently connected)
8.1 Condition of equipment in terms of IP rating á8.2 Equipment does not constitute a fire hazard á8.3 Enclosure not damaged/deteriorated so as to impair safety á8.4 Suitability for the environment and external influences á8.5 Security of fixing á8.6 Cable entry holes in ceiling above luminaires, sized or sealed so as to restrict the spread of fire (indicate extent of
sampling in Section D of report)8.7 Recessed luminaires (e.g. downlighters)
correct type of lamps fitted N/A
installed to minimise build-up of heat by use of "fire rated" fittings, insulation displacement box or similar N/A
no signs of overheating to surrounding building fabric N/A
no signs of overheating to conductors/terminations N/A
9.0 Location(s) containing a bath or shower
9.1 Additional protection by RCD not exceeding 30 mA
for low voltage circuits serving the location C2 4
for low voltage circuits passing through Zone 1 and Zone 2 not serving the location C2 4
9.2 Where used as a protective measure, requirements for SELV or PELV are met N/A
9.3 Shaver sockets comply with BS EN 61558-2-5 or BS 3535 N/A
9.4 Presence of supplementary bonding conductors unless not required by BS 7671: 2008 á9.5 Low voltage (e.g. 230 volts) socket-outlets sited at least 3 m from zone 1 á9.6 Suitability of equipment for external influences for installed location in terms of IP rating á9.7 Suitability of equipment for installation in a particular zone á9.8 Suitability of current-using equipment for a particular position within the location á
10.0 Other special installations or locations
List special locations present, if any. List the results of particular inspections applied (a separate page is required for each location). N/A
N/A
N/A
N/A
N/A
N/A
Page 7 of 8
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*
Location ofdistribution board:
Hallway
Distributionboard designation: DB001---
Supply to distributionboard is from:
No ofphases:
Nominalvoltage: V
Overcurrent protective device for the distribution circuit:Associated
RCD (if any): BS(EN)
Type:BS(EN) Rating: A RCD No
of poles: IÜ mA
Þ See Table 4A2 of Appendix 4 of BS 7671
CODES FOR TYPE OF WIRINGA B C D E F G H
Thermoplasticinsulated/
sheathed cables
Thermoplasticcables in
metallic conduit
Thermoplasticcables in non
metallic conduit
Thermoplasticcables in
metallic trunking
Thermoplasticcables in non
metallic trunking
Thermoplastic/SWA cables
Thermosetting/SWA cables
Mineral-insulated
cables
O (Other - please state)
* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.
See next page for
Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
CIRCUIT DETAILS
Cir
cuit
num
ber
and
line
Circuit designationT
ype
of w
irin
g(s
ee c
ode
belo
w)
Ref
eren
ce
Þ
met
hod
Num
ber
ofpo
ints
ser
ved Live
(mmâ)
Circuitconductors: csa
cpc
(mmâ)
Max
. dis
conn
ecti
onti
me
perm
itte
dby
BS
767
1
(s)
BS (EN)
Typ
e
Rat
ing
(A)
Overcurrent protective devices
Sho
rt-c
ircu
itca
paci
ty
(kA)
RCD
Ope
rati
ngcu
rren
t, IÜ
(mA)
Max
imum
Öpe
rmit
ted
by B
S 7
671
(É)
1 Shower A B 2 6 2.5 0.4 60898 B 40 6 0.92
2 Cooker A B 2 6 2.5 0.4 60898 B 32 6 1.15
3 Sockets A B 14 2.5 1.5 0.4 60898 B 32 6 1.15
4 Immersion A B 2 4 2.5 0.4 60898 B 16 6 2.3
5 Lights A B 7 1 1 0.4 60898 B 6 6 6.13
Page 8 of 8
Ori
gin
al
(To
the
pers
on o
rder
ing
the
wor
k)
This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081
SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD
TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION
Characteristics at this distribution board
Confirmation of supply polarity* See note below
Ö É
IÙ kA
*
*
At IÜ ms
At 5IÜ ms
Operating timesof associated
RCD (if any)
Phase sequence confirmed (where appropriate) N/A
Test instruments (serial numbers) used:
Earth fault loopimpedance 5988
Insulationresistance 5988
Continuity 5988
RCD 5988
Multifunction
Other
* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.
TESTED BY
Signature:
Date oftesting: 10/09/2015Name:
(CAPITALS) JONATHON BENBOW
Position: QS
See previous page for
Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©
TEST RESULTS
Cir
cuit
num
ber
and
line
rã(Line)
rÐ(Neutral)
Ring final circuits only(measured end to end)
rå(cpc) Rã + Rå
Circuit impedances(É)
All circuits(At least one column
to be completed)
Rå
Line/Line Ú
(MÉ)
Line/Neutral Ú
(MÉ)
Line/Earth Ú
(MÉ)
Insulation resistance
Neutral/Earth
(MÉ)
Polarity
(á)
Maximummeasured earth
fault loopimpedance, Ö
(É)
at IÜ
(ms)
RCD operatingtimes
at 5IÜ
(if applicable)
(ms)
Testbutton
operation
(á)
1 N/A N/A N/A 999 999 999 á 0.36
2 N/A N/A N/A 999 999 999 á N/A
3 0.44 0.50 0.87 N/A N/A N/A 999 999 999 á 0.71
4 N/A N/A N/A 999 999 999 á 0.45
5 N/A N/A N/A 999 999 999 á 0.95