OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP) PART 4: SCHEDULES Table of Contents SCH.01 Schedule of Requirements.........................SH-1 SCH.01.1 Material Supply..................................SH-1 SCH.01.1A NHBS Material Supply.............................SH-1 SCH.01.1B HBBS Material Supply.............................SH-3 SCH.01.1C OHS Material Supply..............................SH-4 SCH.01.2 Electromechanical Works..........................SH-5 SCH.01.3 Civil Works......................................SH-6 SCH.02 Schedule of Prices...............................SH-7 SCH.02.1 Material Supply..................................SH-7 SCH.02.1A NHBS Material Supply.............................SH-7 SCH.02.1B HBBS Material Supply.............................SH-9 SCH.02.1C OHS Material Supply..............................SH-10 SCH.02.2 Electromechanical Works..........................SH-11 SCH.02.2A NHBS Electromechanical Works.....................SH-11 SCH.02.2B HBBS Electromechanical Works.....................SH-12 SCH.02.2C OHS Electromechanical Works......................SH-13 SCH.02.3 Civil Works......................................SH-14 SCH.02.3A NHBS Civil Works.................................SH-14 SCH.02.3B HBBS Civil Works.................................SH-15 SCH.02.3C OHS Civil Works..................................SH-16 SCH.02.4 Summary of Prices................................SH-17 SCH.02.5 Spare Parts and Tools............................SH-18 SCH.02.5.1 Protection Panels................................SH-18 SCH.02.5.2 GE D20MX RTU.....................................SH-19 SCH.02.5.3 Communication Equipment..........................SH-20 SCH.02.5.4 138kV Circuit Breakers...........................SH-21 SCH.02.5.5 69kV Circuit Breakers............................SH-22 SCH.02.5.6 Bus Work and Shield Wire.........................SH-23 SCH.02.5.7 80/100MVA 138/69kV Interbus Transformer..........SH-24 SCH.02.5.8 HV Disconnect Switches...........................SH-25 SCH.02.5.9 125 VDC Battery and Charger......................SH-26 SCH.02.5.10.................................................48VDC Battery & Charger SH-27 SCH.02.5.11.................................................Summary Spare Parts and Tools.............................................SH-28 SH- i

Upload: others

Post on 03-Mar-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

PART 4: SCHEDULES

Table of ContentsSCH.01 Schedule of Requirements.........................................................................SH-1SCH.01.1 Material Supply...........................................................................................SH-1SCH.01.1A NHBS Material Supply................................................................................SH-1SCH.01.1B HBBS Material Supply................................................................................SH-3SCH.01.1C OHS Material Supply..................................................................................SH-4SCH.01.2 Electromechanical Works............................................................................SH-5SCH.01.3 Civil Works..................................................................................................SH-6SCH.02 Schedule of Prices......................................................................................SH-7SCH.02.1 Material Supply...........................................................................................SH-7SCH.02.1A NHBS Material Supply................................................................................SH-7SCH.02.1B HBBS Material Supply................................................................................SH-9SCH.02.1C OHS Material Supply..................................................................................SH-10SCH.02.2 Electromechanical Works............................................................................SH-11SCH.02.2A NHBS Electromechanical Works................................................................SH-11SCH.02.2B HBBS Electromechanical Works................................................................SH-12SCH.02.2C OHS Electromechanical Works...................................................................SH-13SCH.02.3 Civil Works..................................................................................................SH-14SCH.02.3A NHBS Civil Works......................................................................................SH-14SCH.02.3B HBBS Civil Works......................................................................................SH-15SCH.02.3C OHS Civil Works.........................................................................................SH-16SCH.02.4 Summary of Prices.......................................................................................SH-17SCH.02.5 Spare Parts and Tools..................................................................................SH-18SCH.02.5.1 Protection Panels.........................................................................................SH-18SCH.02.5.2 GE D20MX RTU.........................................................................................SH-19SCH.02.5.3 Communication Equipment.........................................................................SH-20SCH.02.5.4 138kV Circuit Breakers...............................................................................SH-21SCH.02.5.5 69kV Circuit Breakers.................................................................................SH-22SCH.02.5.6 Bus Work and Shield Wire..........................................................................SH-23SCH.02.5.7 80/100MVA 138/69kV Interbus Transformer.............................................SH-24SCH.02.5.8 HV Disconnect Switches.............................................................................SH-25SCH.02.5.9 125 VDC Battery and Charger....................................................................SH-26SCH.02.5.10 48VDC Battery & Charger..........................................................................SH-27SCH.02.5.11 Summary Spare Parts and Tools..................................................................SH-28

SCH.03 Schedule of Technical Data Sheets...........................................................SH-29SCH.03.1 Surge Arresters............................................................................................SH-29SCH.03.1A 138kV Surge Arresters................................................................................SH-29SCH.03.1B 69kV Surge Arresters..................................................................................SH-31

SH- i

Page 2: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2 Protection & Control Equipment.............................................................SH-33SCH.03.2A 138kV and 69kV Bus Differential Protection Panels..............................SH-33SCH.03.2A.1 138kV Primary Bus Differential Protection Panel......................................SH-33SCH.03.2A.2 138kV Backup Bus Differential Protection Panel.......................................SH-34SCH.03.2A.3 69kV Primary Bus Differential Protection Panel........................................SH-35SCH.03.2A.4 69kV Backup Bus Differential Protection Panel.........................................SH-36SC.03.2B Breaker Fail Protection Panels.................................................................SH-37SCH.03.2B.1 138kV Breaker Fail Panel I.........................................................................SH-37SCH.03.2B.2 69kV Breaker Fail Panel..............................................................................SH-38SC.03.2C Line Protection Panels...............................................................................SH-39SCH.03.2C.1 NHBS 138kV Line 1 Protection Panel........................................................SH-39SCH.03.2C.2 NHBS 69kV Line 8 Protection Panel..........................................................SH-40SCH.03.2C.3 NHBS 69kV Line 10 Protection Panel .......................................................SH-41SCH.03.2C.4 HBBS 69kV Line L9 and L12 Protection Panels........................................SH-42SCH.03.2D Transformer Protection Panel..................................................................SH-43SCH.03.2D.1 Transformer T1 Protection Panel.................................................................SH-43SCH.03.2D.2 Transformer T2 Protection Panel.................................................................SH-44SCH.03.2E Station Control Panel...................................................................................SH-45SCH.03.2F RTU Interface Panel....................................................................................SH-46SCH.03.2G HBBS Loose Items – Protection & Control................................................SH-47SCH.03.2H Relay List.....................................................................................................SH-48SCH.03.3 SCADA RTU...............................................................................................SH-52SCH.03.3A NHBS RTU Panel........................................................................................SH-52SCH.03.3B HBBS Loose Items......................................................................................SH-53SCH.03.3C NHBS Communication Panel......................................................................SH-54SCH.03.3D NHBS Communication Rack.......................................................................SH-55SCH.03.3E HBBS Communication Equipment..............................................................SH-56SCH.03.3F OHS Communication Equipment................................................................SH-57SCH.03.4 HV Circuit Breakers....................................................................................SH-58SCH.03.4A 138kV SF6 Circuit Breaker.........................................................................SH-58SCH.03.4B 69kV SF6 Circuit Breaker...........................................................................SH-60SCH.03.5 Steel Structures............................................................................................SH-62SCH.03.6 Bus Work & Shield Wire.............................................................................SH-63SCH.03.6A Bus Conductors & Shield Wire...................................................................SH-63SCH.03.6B Insulators......................................................................................................SH-66SCH.03.7 VOLTAGE TRANSFORMERS...............................................................SH-70SCH.03.7A 138kV, 750VA Voltage Transformer..........................................................SH-70SCH.03.7B 69kV, 750VA Voltage Transformer............................................................SH-72SCH.03.7C 69kV, 100KVA Station Service Voltage Transformer................................SH-74SCH.03.8 138/69KV, 80/100MVA Interbus Transformer...........................................SH-76SCH.03.9 HV Disconnect Switches............................................................................SH-79SCH.03.9A 138kV Manual Group Operated Disconnect Switches ...............................SH-79SCH.03.9B 138kV Motor Operated Disconnect Switches ............................................SH-81

SH- ii

Page 3: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.9C 69kV Manual 2000A Group Operated Disconnect Switches .....................SH-83SCH.03.9D 69kV Motor Operated Disconnect Switches ..............................................SH-85SCH.03.9E 69kV 1- Phase 600A Manual Operated Disconnect Switches ....................SH-87SCH.03.10 AC & DC Distribution Panelboards........................................................SH-88SCH.03.10A 240VAC, 2-Phase 12-Way Main Panelboard..............................................SH-84SCH.03.10B 240VAC, 2-Phase 52-Way Sub Panelboard................................................SH-89SCH.03.10C 125 VDC Main Panelboard.........................................................................SH-90SCH.03.10D 125 VDC 54 Way Sub Panelboards.............................................................SH-91SCH.03.10E 48 VDC Distribution Panel..........................................................................SH-92SCH.03.11 Lighting Fixtures.......................................................................................SH-93SCH.03.11A Substation Lighting Fixtures........................................................................SH-93SCH.03.11B Area Lighting...............................................................................................SH-94SCH.03.12 Low Voltage Power, Control, and Instrument Cables.................................SH-95SCH.03.13 Substation Grounding..................................................................................SH-96SCH.03.14 125 VDC Battery Set...................................................................................SH-97SCH.03.15 240VAC, 2-Phase 125VDC Battery Charger..............................................SH-98SCH.03.16 48VDC Battery Set......................................................................................SH-100SCH.03.17 240VAC, 2-Phase, 48VDC Battery Charger...............................................SH-101SCH.03.18 Civil Works..................................................................................................SH-103SCH.03.19 Cable Laying, Cable Trenches, Ducts.........................................................SH-104SCH.03.20 Relay Building.............................................................................................SH-105SCH.03.21 High Voltage Power Cables.........................................................................SH-106SCH.03.22 Equipment Identification.............................................................................SH-107

SCH.04 Schedule of Delivery..................................................................................SH-108

SCH.05 Schedule of Tender Information..............................................................SH-109SCH.05.1 Addenda to Bid Documents.........................................................................SH-109SCH.05.2 Deviation from Specifications – Minor Modifications................................SH-110SCH.05.3 Deviation from Specifications – Major Modifications................................SH-111SCH.05.4 Legal Documentation...................................................................................SH-112SCH.05.5 Previous Experiences, Eligibility.................................................................SH-113SCH.05.6 Key Personnel..............................................................................................SH-114SCH.05.7 Sub-Contractors...........................................................................................SH-116SCH.05.8 Technical Capability....................................................................................SH-117SCH.05.9 Work Program.............................................................................................SH-118SCH.05.10 Day Work Rates...........................................................................................SH-119SCH.05.11 Equipment Rental Rates..............................................................................SH-120SCH.05.12 Material Unit Prices.....................................................................................SH-121SCH.05.13 Financial Capability.....................................................................................SH-122SCH.05.14 Civil Works Rates........................................................................................SH-123SCH.05.15 Details of Contractor’s Insurance Coverage................................................SH-124SCH.05.16 Technical Documentation............................................................................SH-125

SH- iii

Page 4: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.01 SCHEDULE OF REQUIREMENTS

The Supplier shall design, manufacture, supply (CIF to Kingston Port, Jamaica), and transport to site, all equipment, and materials for the OHCATNEP – Substation.

The Contractor shall design and construct all civil works, all pile works, ductwork, and relay building, install steel structures, equipment and facilities, test, and commission the substation into service.

SCH.01.1 MATERIAL SUPPLY

SCH.01.1A NHBS Material SupplyITEM QTY UNIT SPECS

NO. DESCRIPTIONNEW HUNTS BAY SUBSTATION

1 Surge Arresters TS.03.11.1 138kV Surge Arresters (Line) with counters and accessories 6 Ea.1.2 69kV Surge Arresters (Line) with counters and accessories 6 Ea.2 Protection & Control Equipment TS.03.2

2.1 Bus Differential Protection 4 Ea. TS.03.2.72.2 Breaker Failure Protection 2 Ea. TS.03.2.82.3 Line Protection Panels 3 Ea. TS.03.2.92.4 Transformer T1 & T2 Protection Panel 2 Ea. TS.03.2.102.5 Station Control Panel 1 Ea. TS.03.2.112.6 RTU Interface Panel (RTUIF) 1 Ea. TS.03.2.123 SCADA RTU and Communication Equipment TS.03.3

3.1 NHBS RTU 1 Ea. TS.03.3.1.23.2 NHBS Communication Panel 1 Ea. TS.03.3.2.13.3 Telephone 1 Ea. TS.03.3.2.1.43.4 NHBS Communication Rack 1 Ea. TS.03.3.2.13.5 80-foot tall communication tower (steel pole) for antenna 1 Ea. TS.03.3.2.1.84 HV Circuit Breakers TS.03.4

4.1 138kV,1200A, SF6 Circuit Breakers 5 Ea.4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea.5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.56 Bus Work & Insulators 1 Lot TS.03.67 Voltage Transformers TS.03.7

7.1 138kV, 750 VA Voltage Transformers 18 Ea.7.2 69kV, 750VA Voltage Transformers 18 Ea.7.3 69kV, 100KVA, Station Service Voltage Transformer 1 Ea.7.4 PT Marshalling Boxes 12 Ea.7.5 SSVT LV AC Distribution Panel 1 Ea.8 138/69kV, 80/100 MVA Interbus Power Transformer,

complete with surge arresters and accessories. Assembly supervised by Manufacturer’s representative.

2 Ea. TS.03.8

9 HV Disconnect Switches TS.03.99.1 138kV, 1200A Motor Operated Disconnect Switches 4 Ea.9.2 69kV, 1200A Motor Operated Disconnect Switches 4 Ea.9.3 138kV, 1200A, Manual Group Operated Disconnects 12 Ea.9.4 69kV, 2000A, Manual Group Operated Disconnects 12 Ea.9.5 69kV, 600A, Manual Op. 1-Pole Dis. Switch 1 Ea.10 AC & DC Distribution Panelboards TS.03.10

10.1 12-Way, 240 VAC, 400A Distribution Panel 1 Ea.10.2 60-Way, 240 VAC, 225A Distribution Panel 2 Ea.10.3 52-Way, 250 VDC, 400A Distribution Panel 1 Ea.10.4 60-Way 250 VDC, 225A Distribution Panels 2 Ea.10.5 48VDC Intelligent dual 150A, distribution panelboard 1 Ea.

SH- 1

Page 5: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.01.1A NHBS Material Supply ContinuedITEM QTY UNIT SPECS

NO. DESCRIPTION11 Lighting Fixtures TS.03.11

11.1 Structure Mounted S/S Lighting 1 Lot11.2 Area Lighting 1 Lot12 Low Voltage Power & Control Cable 1 Lot TS.03.1213 Substation Grounding 1 Lot TS.03.1314 125 VDC Battery Set 1 Ea. TS.03.1415 125 VDC Charger 1 Ea. TS.03.1516 48 VDC Battery 1 Ea. TS.03.1617 48 VDC EATON 48VDC Power System 1 Ea. TS.03.17

SH- 2

Page 6: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.01.1B HBBS Material Supply ITEM QTY UNIT SPECS

NO. DESCRIPTIONB HUNTS BAY B SUBSTATION1 69kV Surge Arresters 6 Ea. TS.03.12 Line Protection Panels 2 Ea. TS.03.2.93 69kV Voltage Transformers 6 Ea. TS.03.74 Loose items Protection and Control 1 Lot TS.03.2.155 HBBS SCADA Equipment 1 Lot TS.03.3.1.36 HBBS Communication Equipment 1 Lot TS.03.3.2.27 69kV, 1200A Motor Operated Disconnect Switches 2 Ea. TS.03.98 Grounding materials (for surge arresters) 1 Lot

SH- 3

Page 7: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.01.1C OHS Material SupplyITEM QTY UNIT SPECS

NO. DESCRIPTIONC OLD HARBOUR SUBSTATION1 138kV Surge Arresters 3 Ea. TS.03.12 Steel Structures 1 Lot TS.03.53 Bus Work & Insulators 1 Lot TS.03.64 138kV, 1200A Motor Operated Disconnect Switches 1 Ea. TS.03.95 138kV XLPE CABLE 1 Lot TS.03.216 OHS Communication Equipment 1 Lot TS.03.3.2.37 Grounding materials 1 Lot

SH- 4

Page 8: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.01.2 ELECTROMECHANICAL WORKSITEM SPECS

NO. DESCRIPTION1 Installation and testing of protection, control panels TS.03.2.212 Installation and testing of SCADA Equipment TS.03.3.13 Installation and testing of Communication Equipment TS.03.3.24 Equipment Installation (Surge Arresters, Breakers, PTS & SSVT,

Power Transformers, switches)TS.03.1.4TS.03.4.17TS.03.7.5TS.03.8.28TS.03.9.10

5 Installation of steel structures TS.03.5.116 Installation and testing of Buswork TS.03.6.5 & 67 Installation and testing of AC & DC Panels TS.03.10.68 Installation of Lighting Fixtures TS.03.11.69 Installation, termination and testing Low Voltage Cable TS.03.12.6 & 7

10 Grounding Installation (connection to ground grid), inspection and testing of equipment and structure grounding.

TS.03.13.5 & 6

11 125 VDC Battery & Charger12 48 VDC Battery & Charger13 Installation, termination and testing High Voltage Cable TS.03.21.8 & 9

SH- 5

Page 9: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.01.3 CIVIL WORKSITEM SPECS

NO. DESCRIPTION1 Design of all Civil and Piling Works TS.03.182 Construction of all Civil and Piling Works TS.03.183 Design of Ductwork TS.03.194 Construction of HV, LV, FOC Cable Trenches, Ducts, manholes

(HV and LV)TS.03.19

5 Relay Building design and construction- Building- Lighting and power- Fire protection (detection and suppression) system- Computer/raised floor- Eyewash station- Door entry alarm (two)- Substation Intrusion Alarm System- Lightning Protection System

TS.03.20

SH- 6

Page 10: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02 SCHEDULE OF PRICESSCH.02.1 Material Supply

SCH.02.1A NHBS Material SupplyNO. DESCRIPTION TS QTY UNITS PRICES CIF

Unit TotalA PACKAGE A – NHBS

1.1 138kV Surge Arresters with counters and accessories

TS.03.1 6 Ea.

1.2 69kV Surge Arresters with counters, accessories TS.03.1 6 Ea.2 Protection & Control Equipment TS.03.2

2.1 Bus Differential Panels TS.03.2.72.1.1 69kV Primary Bus Differential Panel 1 Ea.2.1.2 69kV Backup Bus Differential Panel 1 Ea.2.1.3 138kV Primary Bus Differential Panel 1 Ea.2.1.4 138kV Backup Bus Differential Panel 1 Ea.2.2 Breaker Fail Protection Panel TS.03.2.8

2.2.1 138kV Breaker Fail Panel I 1 Ea.2.2.2 69kV Breaker Fail Panel 1 Ea.2.3 Line Protection Panel TS.03.2.9

2.3.1 Line 1 Protection Panel 1 Ea.2.3.2 Line 8 Protection Panel 1 Ea.2.3.3 Line 10 Protection Panel 1 Ea.2.4 Transformer Protection Panel TS.03.2.10

2.4.1 Transformer T1 Panel 1 Ea.2.4.2 Transformer T2 Panel 1 Ea.2.5 Station Control Panel TS.03.2.11 1 Ea.2.6 RTU Interface Panel (RTUIF) TS.03.2.12 1 Ea.3 SCADA RTU and Communication Equipment TS.03.3

3.1 NHBS RTU TS.03.3.1.2 1 Ea.3.2 NHBS Communication Panel TS.03.3.2.1 1 Ea.3.3 Telephone TS.03.3.2.1.43.4 NHBS Communication Rack TS.03.3.2.1 1 Ea.3.5 80-foot tall communication tower (steel pole) TS.03.3.2.1.8 1 Ea.4 HV Circuit Breakers TS.03.4

4.1 138kV,1200A, SF6 Circuit Breakers 5 Ea.4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea.5 Steel Structures TS.03.5 1 Lot6 Bus Work & Insulators TS.03.6 1 Lot7 Voltage Transformers TS.03.7

7.1 138kV Voltage Transformers 18 Ea.7.2 169kV Voltage Transformers 18 Ea.7.3 69kV, 100KVA, Station Service Voltage Transformer 1 Ea.7.4 PT Marshalling Boxes 12 Ea.7.5 SSVT LV AC Distribution Panel 1 Ea.8 80/100 MVA Interbus Power Transformer TS.03.8 2 Ea.9 HV Disconnect Switches TS.03.9

9.1 138kV, 1200A Motor Operated Dis. Switches 4 Ea.9.2 69kV, 1200A Motor Operated Dis. Switches 4 Ea.9.3 138kV, 1200A, Manual Group Op. Disc. Sw. 12 Ea.9.4 69kV, 2000A, Manual Group Op. Disconnects 12 Ea.9.5 69kV, 600A, Manual Op. 1-Pole Dis. Switch 1 Ea.

SH- 7

Page 11: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.1A NHBS Material Supply ContinuedNO. DESCRIPTION TS QTY UNITS PRICES CIF

Unit TotalA PACKAGE A – NHBS Continued10 AC & DC Distribution Panel Boards TS.03.10

10.1 12-Way, 240 VAC, 400A Distribution Panel 1 Ea.10.2 60-Way, 240 VAC, 225A Distribution Panels 2 Ea.10.3 52-Way, 250 VDC, 400A Distribution Panel 1 Ea.10.4 60-Way 250 VDC, 225A Distribution Panels 2 Ea.10.5 48VDC Intelligent dual 150A, distribution Panel 1 Ea.11 Lighting Fixtures TS.03.11

11.1 Structure Mounted S/S Lighting 1 Lot11.2 Area Lighting 1 Lot12 Low Voltage Power & Control Cable TS.03.12 1 Lot13 Substation Grounding TS.03.13 1 Lot14 125 VDC Battery Set TS.03.14 1 Ea.15 125 VDC Charger TS.03.15 1 Ea.16 48 VDC Battery TS.03.16 1 Ea.17 48 VDC Battery Charger TS.03.17 1 Ea.

TOTAL PACKAGE A MS

SH- 8

Page 12: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.1B HBBS Material Supply NO. DESCRIPTION TS QTY UNITS PRICES CIF

Unit TotalB PACKAGE B – HBBS1 138kV Surge Arresters TS.03.1 6 Ea.2 69kV Line Protection Panels TS.03.2.9 2 Ea.3 69kV Voltage Transformers TS.03.7 6 Ea.4 Loose Items – Protection & Control TS.03.2.15 1 Lot5 SCADA RTU Equipment TS.03.3.1.3 1 Lot6 Communication Equipment (Loose) TS.03.3.2.2 1 Lot7 69kV, 1200A Motor Operated Dis. Switches TS.03.9 2 Ea.8 Grounding materials for surge arresters

TOTAL PACKAGE B MS

SH- 9

Page 13: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.1C OHS MATERIAL SUPPLY NO. DESCRIPTION TS QTY UNITS PRICES CIF

Unit Total

C PACKAGE C - OHS1 138kV Surge Arresters TS.03.1 3 Ea.2 Steel Structures TS.03.5 1 Lot3 Bus Work & Insulators TS.03.6 1 Lot4 138kV, 1200A Motor Operated Dis. Switches TS.03.9 1 Lot5 138kV, 1055A, 800 MMSQ XLPE CABLE TS.03.21 1 Lot6 OHS Communication Equipment (Loose) TS.03.3.2.3 1 Lot7 Grounding materials

TOTAL PACKAGE C MS

Name of Bidder

Currency in Bid

Signature of Bidder

SH- 10

Page 14: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.2 Electromechanical WorksSCH.02.2A NHBS Electromechanical Works

NO. DESCRIPTION TS UNITS QTY PRICESUnit Total

A PACKAGE A – NHBS1 Surge Arresters TS.03.1

1.1 69kV Surge Arresters 6 Ea.1.2 138kV Surge Arresters 6 Ea.2 Protection & Control Equipment TS.03.2

2.1 Bus Differential Panels 4 Ea.2.2 Breaker Fail Protection Panel 2 Ea.2.3 Line Protection Panel 3 Ea.2.4 Transformer Protection Panel 2 Ea.2.5 Station Control Panel 1 Ea.2.6 RTU Interface Panel (RTUIF) 1 Ea.3 SCADA AND COMMUNICATION EQUIPMENT TS.03.3

3.1 RTU Panel 1 Ea.3.2 NHBS Communication Panel 1 Ea.3.3 Telephone 1 Ea.3.4 NHBS Communication Rack 1 Ea.3.5 80-foot tall steel pole 1 Ea.4 HV Circuit Breakers TS.03.4.17

4.1 138kV,1200A, SF6 Circuit Breakers 5 Ea.4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea.5 Steel Structures TS.03.5.11 1 Lot6 Bus Work & Insulators TS.03.6.5 1 Lot7 Voltage Transformers TS.03.7.5

7.1 138kV Voltage Transformers 18 Ea.7.2 169kV Voltage Transformers 18 Ea.7.3 69kV, 100KVA, Station Service Voltage Transformer 1 Ea.7.4 PT Marshalling Boxes 12 Ea.7.5 SSVT LV Structure Mounted Distribution Panel 1 Ea.8 138/69kV, 80/100 MVA Power Transformer

Transportation, installation, and assemblyTS.03.8.28 2 Ea.

9 HV Disconnect Switches TS.03.9.109.1 138kV, 1200A Motor Operated Dis. Switches 4 Ea.9.2 69kV, 1200A Motor Operated Dis. Switches 4 Ea.9.3 138kV, 1200A, Manual Operated Disconnects 12 Ea.9.4 69kV, 2000A, Manual Operated Disconnects 12 Ea.9.5 69kV, 600A, Manual Op. 1-Pole Dis. Switch 1 Ea.10 AC & DC Distribution Panel Boards TS.03.10.6

10.1 12-Way, 240 VAC, 400A Distribution Panel 1 Ea.10.2 60-Way, 240 VAC, 225A Distribution Panel 2 Ea.10.3 52-Way, 250 VDC, 400A Distribution Panel 1 Ea.10.4 60-Way 250 VDC, 225A Distribution Panels 2 Ea.10.5 48VDC Intelligent dual 150A, distribution Panel 1 Ea.11 Lighting Fixtures TS.03.11.6

11.1 Structure Mounted S/S Lighting 1 Lot11.2 Area Lighting 1 Lot12 Low Voltage Power & Control Cable TS.03.12.6 1 Lot13 Substation Grounding (above ground connections) TS.03.03.13.5 1 Lot14 125 VDC Battery Set 1 Ea.15 125 VDC Charger 1 Ea.16 48 VDC Battery 1 Ea.17 48 VDC Battery Charger/Power System 1 Ea.18 Labels and signs TS.03.22 1 Lot19 TOTAL PACKAGE A EMW

SH- 11

Page 15: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.2B HBBS Electromechanical WorksNO. DESCRIPTION TS UNITS QTY PRICES

Unit TotalB PACKAGE B – HBBS1 138kV Surge Arresters TS.03.1.4 6 Ea.2 Line Protection Panels TS.03.2.21 2 Ea.3 69kV Voltage Transformers TS.03.7.5 6 Ea.4 Loose Items – Protection & Control 1 Lot5 SCADA RTU Equipment 1 Lot6 Communication Equipment 1 Lot7 69kV 1200A Motor Operated Dis. Switches TS.03.9.10 2 Ea.8 Grounding

TOTAL PACKAGE B EMW

SH- 12

Page 16: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.2C OHS Electromechanical WorksNO. DESCRIPTION TS UNITS QTY PRICES

Unit TotalC PACKAGE C OLD HARBOUR SUBSTATION1 138kV Surge Arresters TS.03.1.4 3 Ea.2 Steel Structures TS.03.5.11 1 Lot3 Bus Work & Insulators TS.03.6.5 1 Lot4 138kV, 1200A Motor Operated Dis. Switches TS.03.9.10 1 Lot5 138kV, 800A XLPE Cable installation &

Termination TS.03.21.8 1 Lot

6 Grounding

TOTAL PACKAGE C EMW

Name of Bidder

Currency in Bid

Signature of Bidder

SH- 13

Page 17: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.3 Civil Works

SCH.02.3A NHBS Civil WorksNO. DESCRIPTION TS QTY UNIT PRICES

Unit TotalA PACKAGE A – NHBS1 Preliminaries

1.1 Storage area preparation (clearing, levelling, marling, rolling, fencing, etc.)

1 Lot

1.2 Temporary Site Offices for Contractor & Engineer (Containerized buildings, portable toilets, security post, utilities, janitorial services)

1 Lot

1.3 Temporary Fencing for Substation Site 1 Lot2 Site Works TS.03.18.4

2.1 Site clearance, removal of topsoil, grading TS.03.18.4.1 1 Lot2.2 Backfilling and compaction TS.03.18.4.2 1 Lot2.3 Disposal of Surplus Materials TS.03.18.4.3 1 Lot2.4 Gravelling TS.03.18.4.4 1 Lot3 Drainage TS.03.18.5 1 Lot4 Piling Works (for current and future bases) TS.03.18.6

4.1 Designs & Calculations 1 Lot4.2 Setting Out 1 Lot4.3 Pile Installation (for current & future foundations) 1 Lot4.4 Pile reporting and testing 1 Lot5 Foundations TS.03.18.7&8

5.1 Two Interbus Transformers with oil containment pits and fire wall

1 Lot

5.2 138kV, 1200A Circuit Breaker 6 Ea.5.3 69kV, 2000A Circuit Breaker 6 Ea.5.4 138kV Type A Columns (C1-C6) 6 Ea.5.5 138kV Type B Columns (C9-C11) 3 Ea.5.6 69kV Column Gantries (C12-C36) 1 Lot5.7 138kV Bus Supports 24 Ea.5.8 138kV Switch Supports (Pie) 12 Ea.5.9 69kV Single Phase Switch Support Structure 1 Ea.

5.10 138kV PT (Pie) Support Structures 4 Ea.5.11 138kV Single PT Support Structure 6 EA.5.12 69kV SSVT Support Structure 1 Ea.

6 Road Works TS.03.18.14 1 Lot7 Design, Supply & Installation of Fence & Gate TS.03.18.158 Cable Ducts, Manholes and Trenches TS.03.19 1 Lot9 Relay Building

9.1 Relay Building (slab roof, raised floor, grounding, lighting, outlets, two air conditioning units, two pad-lockable doors, steps with rails, lightning protection system, door entry alarm, ladder, water tank)

TS.03.20 1 Lot

9.2 Sewerage Treatment Plant TS.03.20.6 1 Lot9.3 Fire Protection System TS.03.20.10 1 Lot9.4 Eye Wash Station TS.03.20.11 1 Lot9.5 Substation Intrusion Alarm System TS.03.20.13 1 Lot10 Installation of Main and Fence Ground Grid

(below surface with tails for connections to structures)TS.03.13.5 1 Lot

11 Switch Mats TS.03.13 32 Ea.12 Concrete testing (7-day and 28-day tests) TS.03.18.8.25 1 Lot13 Proctor Tests (Roadway) 1 Lot

TOTAL PACKAGE A CIVIL WORKS

SH 14

Page 18: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.3B HBBS Civil WorksNO. DESCRIPTION TS UNITS QTY PRICES

Unit TotalB PACKAGE B – HBBS

TOTAL PACKAGE B CIVIL WORKS

SH 15

Page 19: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.3C OHS CIVIL WorksNO. DESCRIPTION TS UNITS QTY PRICES

Unit TotalC PACKAGE C OLD HARBOUR SUBSTATION1 Column Gantry Foundations TS.03.18.7&8 1 Lot2 Cable Take-off Structures foundations TS.03.18.7&8 3 Ea.3 Duct Work – HV Cable TS.03.19 1 Lot4 Duct Work – LV Cable TS.03.19 1 Lot5 Ductwork - FOC TS.03.19 1 Lot

TOTAL PACKAGE C CIVIL WORKS

Name of Bidder

Currency in Bid

Signature of Bidder

SH 16

Page 20: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.4 Summary of Prices

ITEM CLAUSE PRICES

NO. DESCRIPTION

A Material Supply (CIF) SCH.02.1Package A MaterialsPackage B MaterialsPackage C Materials

B Clearance & Transportation of Materials to Site*

C Installation, testing, and commissioning of Substation Works

SCH.02.2

Package A EMWPackage B EMWPackage C EMW

D Construction of Civil Works SCH.02.3Package A Civil Works Package B Civil Works Package C Civil Works

E Equipment Field TestingF CommissioningG SecurityH InsuranceI Civil Designs (Foundations, grading,

roadworks, etc.)J Contractor’s Levy = 2% of Local WorksK TOTAL (A+B+C+D+E+F+G+H+I+J)

* JPS is responsible for payment of Duties and GCT. The Contractor shall be responsible for Port Charges (storage, etc.) clearance of goods and transportation to the site.

Name of Bidder

Currency in Bid

Signature of Bidder

SH 17

Page 21: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5 Spare Parts and Tools

SCH.02.5.1 Protection Panels

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.2.19

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 SEL 411L 1 Ea.2 SEL 3555 1 Ea.3 SEL 751 1 Ea.4 SEL 2440 1 Ea.5 SEL 3355 1 Ea.6 SEL 501-2 1 Ea.7 MICOM P442 1 Ea.8 MICOM P546 1 Ea.9 SEL587Z 1 Ea.10 SEL 352 1 Ea.11 MICOM P645 1 Ea.12 MICOM P747 1 Set13 Lockout Relay 2 Ea.14 Software for programming relays

included in Price for protection panels1 Ea. Incl. 0.00

15 TOTAL

SH 18

Page 22: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.2 GE D20MX RTU

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.31.2.25

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 D20MX Processor 1 Ea.2 WESDAC Modem 1 Ea.3 WESDAC D20 Termination Panel 1 Ea.4 D20 Power Supply 1 Ea.5 D20 Chassis Assembly VMU 3U 1 Ea.

TOTAL

SH 19

Page 23: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.3 COMMUNICATION EQUIPMENT

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.3.2.1.10

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

123456

TOTAL

SH 20

Page 24: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.4 138kV Circuit Breaker

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.4.14.

ITEM NO.

PART DESCRIPTION QTY PRICES CIFUnit Total

1 Bushing Current Transformer 12 138kV Bushing 13 Trip Coil 14 Close Coil 15 Set of gaskets and O Rings 16 Bottle SF6 Gas 178910 TOTAL

SH 21

Page 25: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.5 69kV Circuit Breaker

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.4.14.

ITEM NO.

PART DESCRIPTION QTY PRICES CIFUnit Total

1 Bushing Current Transformer 12 69kV Bushing 13 Trip Coil 14 Close Coil 15 Set of gaskets and O Rings 1678910 TOTAL

SH 22

Page 26: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.6 Bus-work and Shield Wire

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.6.4

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 138kV Post Insulator 1 Ea.2 138kV Strain Insulator 1 Ea.3 69kV Post Insulator 1 Ea.4 69kV Strain Insulator 1 Ea.5 Connectors (Attach List) 1 Lot6789 TOTAL BUSWORK

List of Connectors:

Item No

QTY Part Description

12345678910

Minimum one spare unit for each type of connector

SH 23

Page 27: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.7 80/100MVA 138/69kV Interbus Transformer

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.8.24

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 High Voltage Bushing complete with gaskets

1 Ea.

2 Low Voltage Bushing complete with gaskets

1 Ea.

3 High Voltage Neutral Bushing complete with gaskets

1 Ea.

4 One set of spare gaskets with cement 1 Ea.

5 One Pressure relief device 1 Ea.6 One set of indicators and detectors 1 Lot78910 TOTAL

SH 24

Page 28: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.8 Disconnect Switches

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.9.9

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 One pole center side break 138kV, 1200A disconnect switch

1 Ea.

2 One pole center side break 69kV, 2000A disconnect switch

3 One pole center side break 69kV, 1200A disconnect switch

TOTAL

SH 25

Page 29: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.9 125 VDC Battery & Charger

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.15.5 for Battery Charger Spares

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 Charger Alarm Board 1 Ea.2 Charger Control Board 1 Ea.3 Fuse 1 Ea.45678910 TOTAL

Include recommended 125 VDC Battery Spares

SH 26

Page 30: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.10 48 VDC Battery Charger

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation. See TS.03.17.5 for Battery Charger Spares

ITEMNO.

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 Rectifier 1 Ea.2 System Controller SC200 1 Ea.3 Fuse 1 Ea.4 Circuit Breakers 1 Ea.5 Input/Output Board 1 Ea.678910 TOTAL

Include recommended 48VDC Battery Spares

SH 27

Page 31: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.02.5.11 Summary Spare Parts and Tools

Bidder shall provide separate prices for recommended spare parts and tools required for continuous operation.

ITEM NO

PART DESCRIPTION QTY UNIT PRICES CIFUnit Total

1 Protection Panels 1 Lot2 RTU 1 Lot3 Communication Equipment4 138kV Circuit Breaker 1 Lot5 69kV Circuit Breaker 1 Lot6 Bus Work 1 Lot7 80/100MVA Inter-Bus Transf. 1 Lot8 Disconnect Switches 1 Lot9 125VDC Battery & Charger 1 Lot10 48VDC Battery & Charger 1 Lot11 Clearance & Transportation of

Spare Parts to Site*1 Lot

12 TOTAL

* JPS is responsible for payment of Duties and GCT. The Contractor shall be responsible for Port Charges (storage, etc.) clearance of goods and transportation to the site.

Name of Bidder

Signature of Bidder

SH 28

Page 32: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03 Schedule of Technical Data SheetsSCH.03.1 Surge Arresters (TS.03.1)SCH.03.1A 138kV Surge Arresters (TS.03.1.3)

Number Characteristics Specified Offered1 Manufacturer Required2 Maximum System Voltage, L-L 145kV3 Rated Voltage Ur 108kV4 Classification IEE Station Class; IEC Class 4

6 Nominal Discharge Current 20,000

7 BIL 650kV

8 Rated Frequency 50 Hz

9 Maximum Continuous Overvoltage 84kV

10 Temporary Overvoltage (10S) 118kV

11 Maximum 100% Impulse Spark over (1.2 x 50 µs) KV Crest

676kV

12 Maximum Discharge (Residual) Voltage with 8 x 20 µs current wave

302kV @ 20kA

13 Minimum Energy Discharge

(Capability per kV of MCOV)

11 kJ

14 Short Circuit/Pressure Relief Capability

65kA

15 Type of Insulator Polymer

16 Color of Insulator ANSI 70 Grey

17 Creepage Distance (Extra Creep) 4495mm

18 Surge Counter and leakage current monitor (one per phase)

Required

19 Dimensions (Height and weight) Required

20 Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 29

Page 33: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.1A 138kV Surge Arresters

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 30

Page 34: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.1B 69kV Surge Arresters (TS.03.1.3)

Number Characteristics Specified Offered1 Manufacturer Required2 Maximum System Voltage, L-L 69kV3 Rated Voltage Ur 72.5kV4 Classification IEE Station Class; IEC Class 4

6 Nominal Discharge Current 20,000A

7 BIL 350kV

8 Rated Frequency 50 Hz

9 Maximum Continuous Overvoltage 57kV

10 Temporary Overvoltage (10S) 79.5kV

11 Maximum 100% Impulse Spark over (1.2 x 50 µs) KV Crest

227kV

12 Maximum Discharge (Residual) Voltage with 8 x 20 µs current wave

193kV @ 20kA

13 Minimum Energy Discharge

(Capability per kV of MCOV)

11 kJ

14 Short Circuit/Pressure Relief Capability

65kA

15 Type of Insulator Porcelain or polymer

16 Color of Insulator ANSI 70 Grey

17 Creepage Distance (Extra Creep) 2248mm

18 Surge Counter and leakage current monitor (one per phase)

Required

19 Dimensions (Height and weight) Required

20 Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 31

Page 35: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.1B 69kV Surge Arresters

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 32

Page 36: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2 Protection & Control Equipment (TS.03.2)

SCH.03.2A 138kV and 69kV Bus Differential Protection Panels (TS.03.2.7)

SCH.03.2A.1 138kV Primary Bus Differential Protection Panel RP6 (TS.03.2.7.2.1)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Bus Differential Relays (QTY=2):

87BUS-HVN, HVSSEL 587Z

4 Lockout Relays – Bus (QTY=2) 86BUS-HVN, HVS

GE HEA61 or equivalent

5 Ethernet Security Gateway (QTY=1) SEL 36206 Discrete Programable Automation

Controller (QTY=1)SEL 2440

7 DC Supervision Relay (QTY=4) P&B, KPRA or equivalent8 FT Switches ABB or equivalent9 Panel Dimensions 2300X900X850

10 Each Protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2A.1 NHBS 138kV Primary Bus Differential Protection Panels

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 33

Page 37: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2A.2 138kV Backup Bus Differential Protection Panel RP7 (TS.03.2.7.2.2)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Bus Differential Relays (QTY=2 sets):

87BUS-HVN, HVSMICOM P747

4 Lockout Relays – Bus (QTY=2) 86BUS-HVN, HVS

GE HEA61 or equivalent

5 Ethernet Switch (QTY=1) SEL 2730M6 Discrete Programable Automation Controller SEL 24407 DC Supervision Relay (QTY=4) P&B, KPRA or equivalent8 FT Switches ABB or equivalent9 Panel Dimensions 2300X900X850

10 Each Protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2A.2 NHBS 138kV Backup Bus Differential Protection Panels

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 34

Page 38: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2A.3 69kV Primary Bus Differential Protection Panel RP16 (TS.03.2.7.2.3)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Bus Differential Relays Primary (QTY=2):

87BUS-LVN, LVSSEL 587Z

4 Lockout Relays – Bus (QTY=2) 86BUS-LVN, LVS

GE HEA61 or equivalent

5 Ethernet Security Gateway (QTY=1) SEL 36206 One IRIG B Distribution Board SEL 34007 Discrete Programable Automation

Controller (QTY=1)SEL 2440

8 DC Supervision Relay (QTY=5) P&B, KPRA or equivalent9 FT Switches ABB or equivalent

10 Panel Dimensions 2300X900X85011 Each Protection circuit on separate DC

circuit breakerRequired

Specification Compliance Summary – Exceptions to SCH.03.2A.3 NHBS 69kV Primary Bus Differential Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 35

Page 39: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2A.4 69kV Backup Bus Differential Protection Panel RP 17 (TS.03.2.7.2.4)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Bus Differential Relays Primary (QTY=2):

87BUS-LVN, LVSMICOM P747

4 Lockout Relays – Bus (QTY=2) 86BUS-LVN, LVS

GE HEA61 or equivalent

5 Ethernet Switch (QTY=1) SEL 2730M

6 Discrete Programable Automation Controller (QTY=1)

SEL 2440

7 DC Supervision Relay (QTY=4) P&B, KPRA or equivalent8 FT Switches ABB or equivalent9 Panel Dimensions 2300X900X850

10 Each Protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2A.4 NHBS 69kV Backup Bus Differential Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 36

Page 40: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2B Breaker Fail Protection Panels (TS.03.2.8)SCH.03.2B.1 138kV Breaker Fail Panel I, RP8 (TS.03.2.8.2.1)

NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Breaker Fail /Synchro-check Relay (QTY=2):

50BF/25-2, 5SEL 352

4 Breaker Fail relay (QTY=2)50BF-1, 3, 4, 6

SEL501-2One for two breakersCoils X & Y

5 Lockout Relays – Breaker Fail (QTY=6) 86BF-1, 2, 3, 4, 5, 6

GE HEA61 or equivalent

6 Ethernet Security Gateway (QTY=1) SEL 3620

7 Discrete Programable Automation Controller

SEL 2440

8 DC Supervision Relay (QTY=8) P&B, KPRA or equivalent9 FT Switches ABB or equivalent

10 Panel Dimensions 2300X900X85011 Each Protection circuit on separate DC

circuit breakerRequired

Specification Compliance Summary – Exceptions to SCH.03.2B.1 NHBS 138kV Bus Differential Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 37

Page 41: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2B.2 69kV Breaker Fail Panel RP18 (TS.03.2.8.2.2)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Breaker Fail /Synchro-check Relay (QTY=2):

50BF/25-11, 14SEL 352

4 Breaker Fail relay (QTY=2)50BF-10, 12 & 13, 15

SEL501-2One for two breakersCoils X & Y

5 Lockout Relays – Breaker Fail (QTY=6) 86BF-10, 11, 12, 13, 14, 15

GE HEA61 or equivalent

6 Ethernet Security Gateway (QTY=1) SEL 3620

7 Ethernet Switch (QTY=1) SEL2730M

8 Discrete Programable Automation Controller (QTY=1)

SEL 2440

9 DC Supervision Relay (QTY=7) P&B, KPRA or equivalent10 FT Switches ABB or equivalent11 Panel Dimensions 2300X900X85012 Each Protection circuit on separate DC

circuit breakerRequired

Specification Compliance Summary – Exceptions to SCH.03.2B.2 NHBS 69kV Bus Differential Protection Panels

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 38

Page 42: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2C Line Protection Panels (TS.03.2.9)SCH.03.2C.1 138kV Line 1 Protection Panel, RP5 (TS.03.2.9.2.1)

NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered

1 Manufacturer Required

2 Quantity of Panels One (1)3 Line Differential & Distance Protection

Relays 87+21/21NA-L1SEL 411L

4 Distance Relay Backup 21/21LNB-L1

MICOM P442

5 Directional Overcurrent Relay Backup67/67N- L1

SEL 751

6 Ethernet Switch SEL 2730M7 Discrete Programable Automation

Controller 30-L1SEL 2440

8 Auto Reclose Switch 79CO-L1

9 DC Supervision Relay (5) P&B, KPRA or equivalent

10 FT Switches ABB or equivalent11 Panel Dimensions 2300X900X850

12 Primary and backup protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2C.1 NHBS 138kV Transmission Line 1 Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 39

Page 43: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2C.2 69kV Line 8 Protection Panel RP12 (TS.03.2.9.2.2)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered

1 Manufacturer Required

2 Quantity of Panels One (1)3 Line Differential Primary A Protection

Relay 87LA-L8SEL 411L

4 Line Differential Primary B Protection Relay 87LB-L8

MICOM P546

5 Directional Overcurrent Relay 67/67N-L8

SEL 751

6 Ethernet Security Gateway SEL 36207 Discrete Programable Automation

Controller 30-L8SEL 2440

8 Auto Reclose Switch 79CO-L8

9 DC Supervision Relay (5) P&B, KPRA or equivalent

10 FT Switches ABB or equivalent11 Panel Dimensions 2300X900X850

12 Primary and backup protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2C.2 NHBS 69kV Line 8 Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 40

Page 44: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2C.3 69kV Line 10 Protection Panel RP13 (TS.03.2.9.2.3)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered

1 Manufacturer Required

2 Quantity of Panels One (1)3 Line Differential Primary A Protection

Relay 87LA-L10SEL 411L

4 Line Differential Primary B Protection Relay 87LB-L10

MICOM P546

5 Directional Overcurrent Relay 67/67N-L10

SEL 751

6 Discrete Programable Automation Controller 30-L10

SEL 2440

7 Auto Reclose Switch 79CO-L10

8 DC Supervision Relay (4) P&B, KPRA or equivalent

9 FT Switches ABB or equivalent10 Panel Dimensions 2300X900X850

11 Primary and backup protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2C.3 NHBS 69kV Line 10 Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 41

Page 45: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2C.4 69kV L 9 and L12 Protection Panels (TS.03.2.9.3)HUNTS BAY B SUBSTATION

No. Characteristics Specified Offered

1 Manufacturer Required

2 Quantity of Panels Two (2) – L9 and L123 Line Differential Primary B Protection

Relay 87LA-L9, L12SEL 411L

4 Line Differential Primary B Protection Relay 87LB-L9, L12

MICOM P442

5 Directional Overcurrent Relay 67/67N-L9, L12

SEL 751

6 Ethernet Switch SEL 2730M7 Discrete Programable Automation

Controller 30-L9, L12SEL 2440

8 Auto Reclose Switch 79CO-L9, L12 79CO-L9 and L129 TESLA 4000 Fault Recorder (QTY=1 in L9

Panel)TESLA 4000

10 DC Supervision Relay (5 per panel) P&B, KPRA or equivalent

11 Led Indicating Lights (5 per panel) GE ET-16 or equivalent

12 FT Switches ABB or equivalent13 Panel Dimensions 2300X900X850

14 Primary and backup protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2C.4 HBBS 69kV Line Protection Panels

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 42

Page 46: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SH 43

Page 47: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2D Transformer Protection Panels (TS.03.2.10)SCH.03.2D.1 Transformer T1 Protection Panel

NEW HUNTS BAY SUBSTATION

Number Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Differential Relay 87-T1A SEL 487E4 Differential Relay 87-T1B MICOM P6455 Directional Overcurrent Relay

67/67NHV-T1+25-3SEL 751

6 Directional Overcurrent Relay 67/67NLV-T1+25-10

SEL 751

7 Lockout Relays 86P-T1, 86BHV-T1, 86BLV-T1

GE HEA61 or equivalent

8 Discrete Programable Automation Controller 30-T1

SEL 2440

9 DC Supervision Relay (5) P&B, KPRA or equivalent10 FT Switches ABB or equivalent11 Panel Dimensions 2300X900X850

12 Primary and backup protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2D Transformer T1 Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 44

Page 48: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2D.2 Transformer T2 Protection PanelNEW HUNTS BAY SUBSTATION

Number Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 Differential Relay 87-T2A SEL 487E4 Differential Relay 87-T2B MICOM P6455 Directional Overcurrent Relay

67/67NHV-T2+25-5SEL 751

6 Directional Overcurrent Relay 67/67NLV-T2+25-14

SEL 751

7 Lockout Relays 86P-T2, 86BHV-T2, 86BLV-T2

GE HEA61 or equivalent

8 Discrete Programable Automation Controller 30-T2

SEL 2440

9 DC Supervision Relay (5) P&B, KPRA or equivalent10 FT Switches ABB or equivalent11 Panel Dimensions 2300X900X850

12 Primary and backup protection circuit on separate DC circuit breaker

Required

Specification Compliance Summary – Exceptions to SCH.03.2D.2 Transformer T2 Protection Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 45

Page 49: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2E Station Control Panel RP9 (TS.03.2.11)NEW HUNTS BAY SUBSTATION

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1) Panel3 GPS Clock SEL24884 Monitor5 Keyboard6 Mouse/Tracking Ball7 HMI SEL 33558 RTAC SEL35559 MIMIC Diagram on HMI NHBS Single Line Diagram

10 Ethernet Switch SW-CP2; Dual Power Supply

SEL2730M

11 Discrete Programable Automation Controller 30-T2

SEL 2440

12 Communication Protocol DNP3, HDMI, USB, Ethernet,IEC 61850

13 Power Supply 125 VDC & 48 VDC14 Panel Dimensions 2300X900X850

Specification Compliance Summary – Exceptions to SCH.03.2E NHBS Station Control Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 46

Page 50: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2F RTU Interface Panel RP10 (TS.03.2.12)

No. Characteristics Specified Offered1 Manufacturer Required

2 Quantity One (1) Panel3 TESLA 4000 Fault Recorder (QTY=3) TESLA 4000-1,2,34 Discrete Programable Automation

Controller 30-RTUIFSEL 2440

5 Station Control Remote/Standby Switch LOR

6 DC Supervision Relay (QTY=4) P&B, KPRA or equivalent

7 Panel Dimensions 2300X900X850

No. Characteristics Specified OfferedSpecification Compliance Summary – Exceptions to SCH.03.2F RTU Interface Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 47

Page 51: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2G Hunts Bay B Substation Loose Items – Protection & Control (TS.03.2.15)

No. Characteristics Specified Offered1 Instrument Cables2 Terminal Blocks3 Control Cables4 Fiber Optic Patch Cables56789

10

Specification Compliance Summary – Exceptions to SCH.03.2G Lose Items for HBBS Protection & Control

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 48

Page 52: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.2H Relay List – New Hunts Bay Substation

ID DESCRIPTION MANUFACTURER PART NUMBER

5 RP5 - 138KV LINE 1 PANEL

5.1 2730M SEL5.2 SEL 411L SEL5.3 MICOM P442 Schneider5.4 SEL 751 SEL5.5 SEL 2440 SEL

6 RP6 - 138KV PRIM BUS DIF PANEL

6.1 SEL 587Z-HVNP SEL6.2 SEL 587Z-HVSP SEL6.3 HEA or LOR-HVNP GE or ELECTRO SWITCH6.4 HEA or LOR-HVSP GE or ELECTRO SWITCH6.5 SEL 3620 SEL6.6 SEL 2440 SEL

7 RP7 - 138KV BACKUP BUS DIF PANEL

7.1 P747-HVNB Schneider7.2 P747-HVSB Schneider7.3 HEA or LOR-HVNP GE or ELECTRO SWITCH7.4 HEA or LOR-HVSP GE or ELECTRO SWITCH7.5 SEL 2730M SEL7.6 SEL 2440 SEL

8

8.1 SEL 352-2 SEL8.2 SEL352-5 SEL8.3 SEL501-1&3 SEL8.4 SEL501-4&6 SEL8.5 HEA or LOR GE or ELECTRO SWITCH8.6 HEA or LOR GE or ELECTRO SWITCH8.7 HEA or LOR GE or ELECTRO SWITCH8.8 HEA or LOR GE or ELECTRO SWITCH8.9 HEA or LOR GE or ELECTRO SWITCH

8.10 HEA or LOR GE or ELECTRO SWITCH8.11 SEL 3620 SEL8.12 SEL 2440 SEL

SH 49

Page 53: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

9 RP9 - STATION CONTROL PANEL

9.1 SEL 2448 SEL9.2 SEL3355 SEL9.3 SEL 3555 SEL9.4 MONITOR 9.5 KEYBOARD 9.6 43S-STANDBY/REMOTE 9.7 SEL 2440 SEL

10 RP10 - RTU INTERFACE PANEL (RTUIF)

10.1 TESLA 4000-1 TESLA10.2 TESLA 4000-2 TESLA10.3 TESLA 4000-3 TESLA10.4 SEL 2440 SEL

11 RP11 -RTU PANEL

11.1 D20MX GE11.2 SEL 2730M SEL11.3 SEL 3620 SEL

12 RP12 - 69KV LINE 8 PANEL

12.1 SEL 3620 SEL12.2 SEL 411L SEL12.3 MICOM P546 Schneider12.4 SEL 751 SEL12.5 SEL 2440 SEL

13 RP13 - 69KV LINE 10 PANEL

13.1 SEL 411L SEL13.2 MICOM P546 Schneider13.3 SEL 751 SEL13.4 SEL 2440 SEL

14 RP14 - TRANSFORMER T1 PANEL14.1 SEL 487E SEL14.2 MICOM P645 Schneider14.3 SEL 751 HV SEL14.4 SEL 751 LV SEL14.5 HEA or LOR GE or ELECTRO SWITCH14.6 HEA or LOR GE or ELECTRO SWITCH14.7 HEA or LOR GE or ELECTRO SWITCH14.8 SEL 2440 SEL

15 RP15 - TRANSFORMER T2 PANEL

15.1 SEL 487E SELSH 50

Page 54: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

15.2 MICOM P645 Schneider15.3 SEL 751 HV ED15.4 SEL 751 LV SEL15.5 HEA or LOR GE or ELECTRO SWITCH15.6 HEA or LOR GE or ELECTRO SWITCH15.7 HEA or LOR GE or ELECTRO SWITCH15.8 SEL 2440 SEL

16 RP16 - 69KV PRIMARY BUS DIF PANEL

16.1 SEL 587Z-LVNP SEL16.2 SEL 587Z-LVSP SEL16.3 HEA or LOR GE or ELECTRO SWITCH16.4 HEA or LOR GE or ELECTRO SWITCH16.5 SEL 3620 SEL16.6 SEL 3400 SEL16.7 SEL 2440 SEL

17 RP17- 69KV BACKUP BUS DIF PANEL

17.1 P747-LVNB (3 Relays) Schneider17.2 P747-LVSB (3 Relays) Schneider17.3 HEA or LOR GE or ELECTRO SWITCH17.4 HEA or LOR GE or ELECTRO SWITCH17.5 SEL 2730M SEL17.6 SEL 2440 SEL

18 RP18 - 69KV BF & SYNCHROCHECK PANEL

18.1 SEL 352-11 SEL18.2 SEL352-14 SEL18.3 SEL501-10&12 SEL18.4 SEL501-13&15 SEL18.5 HEA or LOR GE or ELECTRO SWITCH18.6 HEA or LOR GE or ELECTRO SWITCH18.7 HEA or LOR GE or ELECTRO SWITCH18.8 HEA or LOR GE or ELECTRO SWITCH18.9 HEA or LOR GE or ELECTRO SWITCH

18.10 HEA or LOR GE or ELECTRO SWITCH18.11 SEL 3620 SEL18.12 SEL 2730m SEL18.13 SEL 2440 SEL

SH 51

Page 55: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.2H Relay List

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 52

Page 56: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.03 SCADA RTUSCH.03.3A NHBS RTU Panel (TS.03.3.1.2)

No. Characteristics Specified Offered1 Manufacturer GE2 Quantity One (1)3 RTU Part Number D20MX-A-A-U-U-U-A-OV-A-U-U-U-U

3.1 Input Voltage 48 VDC3.2 Power Supply Part Number 580-20043.3 Number of Interposing Relays N/A3.4 Number of Master Station

Communication Ports3

3.5 Server for communication with HMI

1

3.6 Number of Status/Alarm Points See SCADA List (Current and future)3.7 Number of Analogue Points See SCADA List (Current and future)3.8 CPU Options D20MX Dual 10/100/1000 BASE -TX

Ethernet Ports (front access)

4 Ethernet Security Gateway SEL 3620

5 Ethernet Switch with dual voltage SEL 2730M

6 Panel Dimensions 2300X900X850

Specification Compliance Summary – Exceptions to SCH.03.3A NHBS RTU Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 53

Page 57: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.3B Hunts Bay B Substation Loose Items – SCADA (TS.03.3.1.3.8)

No. Characteristics Specified Offered1 Instrument Cables2 RS485 Signal Cables3 Ethernet Cables4 Four Interposing Relays 5 Fiber Optic Patch Cables6 Terminal Blocks7 Miscellaneous89

10

Specification Compliance Summary – Exceptions to SCH.03.3B Lose Items for HBBS SCADA

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 54

Page 58: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.3C NHBS Communication Panel (TS.03.3.2.1)

No. Characteristics Specified Offered1 Manufacturer2 Quantity One (1)3 Multiplexer EXMUX (QTY =2) EXMUX 35014 RUGGEDCOM Serial Server (QTY=1) RX15005 Intelligent Dual Distribution panel (QTY=1)6 Microwave Radio (One set) AVIAT WTM4100, 11GHZ 7

8 Panel Dimensions 2300X900X850

Specification Compliance Summary – Exceptions to SCH.03.3C NHBS Communication Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 55

Page 59: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.3D NHBS Communication Rack (TS.03.3.2.1)

No. Characteristics Specified Offered1 Manufacturer2 Quantity One (1)3 PATCH Panels (Four)

Panel Dimensions Required

Specification Compliance Summary – Exceptions to SCH.03.3D NMHS Communication Rack

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 56

Page 60: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.3E HBBS Communication Equipment – (TS.03.3.2.2)

No. Characteristics Specified OfferedHBBS

1 EXMUX C37.94 Ports (QTY=4)2 EXMUX 3501M (QTY=1)3 RX5000 Shelf (QTY=1)4 Patch Cables (1 Lot)5 Miscellaneous

Specification Compliance Summary – Exceptions to SCH.03.3E HBBS Communication Equipment (Loose Items)

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 57

Page 61: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.3F OHS Communication Equipment – (TS.03.3.2.3)

No. Characteristics Specified Offered

OHS1 EXMUX C37.94 Ports (QTY=2)2 Fiber Panel (QTY=1)3 Patch Cables (1 Lot)4 Miscellaneous

Panel Dimensions 2300X900X850

Specification Compliance Summary – Exceptions to SCH.03.3F HS Communication Equipment (Loose Items)

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 58

Page 62: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.4 HV Circuit Breakers (TS.03.4)

SCH.03.4A 138kV Circuit Breaker (TS.03.4.3)

Number Characteristics Specified Offered1 Manufacturer Required2 Model Number Required3 Nominal system voltage 138-kV4 Type of circuit breaker SF65 Number of Poles 36 Rated maximum voltage 145 kV7 Rated frequency 50 Hz8 Rated lightning impulse withstand level 650-kV9 Min. Continuous current 1200 A10 Rated Short Circuit Current (3 sec) 40 kA11 Symmetrical interrupting capability at

rated voltage40 kA

12 Maximum interrupting time 3 cycles13 Reclosing Duty Cycle CO - 15 sec - CO14 Rated control voltage (Trip & closing

coils and charging mechanism)125 VDC

15 Auxiliary Supply 110/240VAC,50Hz16 Bushing Creepage Distance (Extra

Creep)4495mm

17 Color of bushings and breaker) ANSI 70 Grey18 Current Transformer:

18.1 Ratio/Accuracy Class - Protection 1200:5/C40018.2 VA Rating Required18.3 Rating Factor @ 30 Deg. C 200%19 Grounding Connector

19.1 Frame (2 per breaker) Suitable for 4/0 Conductor19.2 Control Panel Suitable for 2/0 Conductor20 Terminal Connector (Type) 4-Hole NEMA Pad21 Supplied with support structures and

anchor boltsRequired

22 Number of spare auxiliary contacts 9 Normally Opened9 Normally Closed

23 Mechanical Key Interlock Kirk24 Dimensions & Weight (Outline

Drawing)Required

25 Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 59

Page 63: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.4A 138kV Circuit Breakers

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 60

Page 64: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.4B 69kV SF6 Circuit Breaker (TS.03.4.3)

Number Characteristics Specified Offered1 Manufacturer Required2 Model Number Required3 Nominal system voltage 69-kV4 Type of circuit breaker SF65 Number of Poles 36 Rated maximum voltage 145 kV7 Rated frequency 50 Hz8 Rated lightning impulse withstand level 350-kV9 Min. Continuous current 2000 A10 Rated Short Circuit Current (3 sec) 31.5 kA11 Symmetrical interrupting capability at

rated voltage31.5 kA

12 Maximum interrupting time 3 cycles13 Reclosing Duty Cycle CO - 15 sec - CO14 Rated control voltage (Trip & closing

coils and charging mechanism)125 VDC

15 Auxiliary Supply 110/240VAC,50Hz16 Bushing Creepage Distance (Extra

Creep)2248mm

17 Color of bushings and breaker) ANSI 70 Grey18 Current Transformer:

18.1 Ratio/Accuracy Class - Protection 2000:5/C40018.2 VA Rating Required18.3 Rating Factor @ 30 Deg. C 200%19 Grounding Connector

19.1 Frame (2 per breaker) Suitable for 4/0 Conductor19.2 Control Panel Suitable for 2/0 Conductor20 Terminal Connector (Type) 4-Hole NEMA Pad21 Supplied with support structures and

anchor boltsRequired

22 Number of spare auxiliary contacts 9 Normally Opened9 Normally Closed

23 Mechanical Key Interlock Kirk24 Dimensions & Weight (Outline

Drawing)Required

25 Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 61

Page 65: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.4B 69kV Circuit Breakers

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 62

Page 66: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.5 Steel Structures (TS.03.5)

No. Characteristics Specified Offered1 Manufacturer Required2 Type – Columns & Beams Lattice

3 Equipment and bus supports (Disconnect Switches, PTS, and tubular bus supports)

Hollow square

4 Galvanized coating (ASTM A123/ A123M) for steel structures

85 μM /600g/m2

5 Galvanized Anchor Bolts included Required6 Galvanized bolts, lock washers and flat washers included

(for assembly)Required

7 Galvanized coating (ASTM A123/ A123M) for bolts 55 μM /390g/m²8 Lightning masts Required9 List of structures (quantities and descriptions) - columns,

beams and bus, switch, surge arrester, PT, CT supportsRequired

10 Any other information specifically requested, or which may be useful to the Purchaser.

Required

Specification Compliance Summary – Exceptions to SCH.03.5 Steel Structures

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 63

Page 67: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6 Bus Work & Shield Wire (TS.03.6)SCH.03.6A Bus Conductors & Shield Wire (TS.03.6)

Number Characteristics Specified Offered

1 1590 kcmil Conductor

1.1 Manufacturer Required

1.2 Material Aluminum

1.3 Size 1590 kcmil, Coreopsis1.4 Number of Strands 61

1.5 Diameter of Individual Wire 4.1 mm

1.6 UTS 30,500 lb.

1.7 Electrical Resistance (DC @ 20˚C.) 0.0357Ω/kM

1.8 Current Rating (75˚C conductor temperature)

1330 A

2 927.2 MCM Conductor

2.1 Manufacturer Required

2.2 Material Aluminum

2.3 Size 927.1 MCM, Greely2.4 Number of Strands 372.5 Diameter of Individual Wire 4.02 mm2.6 UTS 30,500 lb.

2.7 Electrical Resistance (DC @ 20˚C.) 0.071Ω/kM

2.8 Current Rating (75˚C conductor temperature)

908 A

3 559.5 MCM Conductor

3.1 Manufacturer Required

3.2 Material Aluminum

3.3 Size 559.5 MCM, Darien3.4 Number of Strands 19

3.5 Diameter of Individual Wire 4.36 mm

3.6 UTS 18,80 lb.

3.7 Electrical Resistance (DC @ 20˚C.) 0.12Ω/kM

3.8 Current Rating (75˚C conductor temperature)

663 A

SH 64

Page 68: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6.A Bus Conductors & Shield Wire Continued

Number Characteristics Specified Offered

4 394.5 MCM Conductor

4.1 Manufacturer Required

4.2 Material Aluminum

4.3 Size 394.5 MCM, Darien4.4 Number of Strands 19

4.5 Diameter of Individual Wire 3.66 mm

4.6 UTS 13,300 lb.

4.7 Electrical Resistance (DC @ 20˚C.) 0.17Ω/kM

4.8 Current Rating (75˚C conductor temperature)

532A

5 2-1/2” Copper Tube Nominal Pipe Size (Main Bus)

5.1 Manufacturer Required

5.2 Material Copper

5.3 Type Hard Drawn (H.D.)

5.4 Schedule 80

5.5 Size 2.875 ins outer diameter

5.6 Thickness 0.280 ins.

5.7 Electrical Resistance DC (@ 20˚C) 3.69 Micro Ω per foot

5.8 AC Current Rating @ 70 ˚C, 50 Hz. 2100A

6 2” Copper Tube Nominal Pipe Size (Circuit Breakers & Discon. Switches)

6.1 Manufacturer Required

6.2 Material Copper

6.3 Type Hard Drawn (H.D.)

6.4 Schedule 80

6.5 Size 2.375 ins outer diameter

6.6 Thickness 0.221 ins.

6.7 Electrical Resistance DC (@ 20˚C) 5.64 Micro Ω per foot

6.8 AC Current Rating @ 70 ˚C, 50 Hz.

Emissivity =0.85

1921A

SH 65

Page 69: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6A Bus Conductors & Shield Wire Continued

Number Characteristics Specified Offered

7 Shield Wire

7.1 Manufacturer Required

7.2 Standard ASTM A383

7.3 Type EHS 5/16”

7.4 Size 7x2.64 mm sq.

7.5 Area 38.3 mm sq.

7.6 Diameter 7.92 mm

7.7 UTS 5085kG

7.8 Any other information specifically requested, or which may be useful to the Purchaser.

Required

Specification Compliance Summary – Exceptions to SCH.03.6A Bus Conductors & Shield Wire

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 66

Page 70: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6B Insulators (TS.03.6)

Number Characteristics Specified Offered1 138kV Post Type Porcelain

1.1 Manufacturer Required1.2 Material Porcelain1.3 Standard ASTM C29.91.4 Basic Impulse Level 900 kV1.5 Total Length 2032 mm1.6 Technical Reference Number TR3081.7 Leakage Distance 4191 mm1.8 Cantilever Strength 6.5kN1.9 Tensile Strength 111kN

1.10 Average Flashover Voltage- Low Frequency Dry- Low Frequency Wet 385kV

1.11 Critical Impulse Flashover Positive 1010 kV1.12 Bolt Circle (Top/Bottom) 5”/5”

2 138kV Post Type Polymer2.1 Manufacturer Required2.2 Material Polymer2.3 Standard IEEE 987-20012.4 Insulator Voltage Class 161 kV2.5 Total Length 1763 mm2.6 Technical Reference Number Required2.7 Leakage Distance 4315 mm2.8 Cantilever Strength (SCL) 10.2kN2.9 Tensile Strength (STL) 111kN

2.10 Average Flashover Voltage- Low Frequency Dry 595kV- Low Frequency Wet 510kV

2.11 Positive Critical Impulse Flashover 1010kV2.12 Bolt Circle (Top/Bottom) 5”/5”

SH 67

Page 71: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6B Insulators (TS.03.6) Continued

Number Characteristics Specified Offered3 69kV Post Type Porcelain

3.1 Manufacturer Required3.2 Material Porcelain3.3 Standard ASTM C29.93.4 Basic Impulse Level 550 kV3.5 Total Length 1143 mm3.6 Technical Reference Number TR2863.7 Leakage Distance 2515 mm3.8 Cantilever Strength 7.56kN3.9 Tensile Strength 89kN

3.10 Average Flashover Voltage- Low Frequency Dry- Low Frequency Wet 230kV

3.11 Critical Impulse Flashover Positive 610 kV3.12 Bolt Circle (Top/Bottom) 5”/5”

4 69kV Post Type Polymer4.1 Manufacturer Required4.2 Material Polymer4.3 Standard IEEE 987-20014.4 Insulator Voltage Class 69 kV4.5 Total Length 1763 mm4.6 Technical Reference Number Required4.7 Leakage Distance 4315 mm4.8 Cantilever Strength (SCL) 10.2kN4.9 Tensile Strength (STL) 111kN

4.10 Average Flashover Voltage- Low Frequency Dry 595kV- Low Frequency Wet 510kV

4.11 Positive Critical Impulse Flashover 1010kV

SH 68

Page 72: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6B Insulators (TS.03.6) Continued

Number Characteristics Specified Offered6 138kV Strain Type Polymer

6.1 Manufacturer Required6.2 Material Polymer6.3 Standard IEEE 987-20016.4 Insulator Voltage Class 161 kV6.5 Basic Impulse Level 900 kV6.6 Total Length 1590 mm6.7 Technical Reference Number TR2146.8 Leakage Distance 4458 mm6.9 SML Load 120kN

6.10 Average Flashover Voltage- Low Frequency Dry 560kV- Low Frequency Wet 460kV

6.11 Positive Critical Impulse Flashover 895kV

SH 69

Page 73: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.6B Insulators (TS.03.6) Continued

Number Characteristics Specified Offered7 69kV Strain Type Polymer

7.1 Manufacturer Required7.2 Material Polymer7.3 Standard IEEE 987-20017.4 Insulator Voltage Class 69 kV7.6 Total Length 867 mm7.7 Technical Reference Number Required7.8 Leakage Distance 2131 mm7.9 SML Load 120kN

7.10 Average Flashover Voltage- Low Frequency Dry 300kV- Low Frequency Wet 235kV

7.11 Positive Critical Impulse Flashover 485kV

7.12 Any other information specifically requested, or which may be useful to the Purchaser.

Required

Specification Compliance Summary – Exceptions to SCH.03.6B Insulators

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 70

Page 74: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.07 VOLTAGE TRANSFORMERS (TS.03.7)

SCH.03.7A 138kV Voltage Transformers – (TS.03.7.2)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Outdoor type oil filled induction

type suitable for Protection purposes.

3. Nominal operating Voltage 138kV4. Maximum Rated Voltage 145kV5. Frequency: 50Hz6. Number of phases: Single phase7. Primary connection: Phase-ground8. BIL: 650kV9. No. of secondary windings: Two (2)10. Voltage Rating10.1 Primary Voltage: 138/√3 kV10.2 Secondary voltage: 115/66.4V-115/66.4V11. Ratio:11.1 X1:X3 693:111.2 X2:X3 1200:112. Accuracy class 0.3 WXY Z (C57.13) or equal13. Thermal burden rating: 750 VA14 HV Connector 4-Hole NEMA Pad15 Secondary Connectors: Stud suitable for #2-#10 AWG

(6 sq.mm) copper stranded wire.16. Ground Connectors: 2-bolt clamp suitable for 2/0

AWG copperweld.17. Colour of finish paint: ANSI 70, light grey18. Bushing leakage length: Extra Creep, 3.1cm/kV19. Voltage factor: 1.2 continuous, 1.9 for 8 hrs.20. Temperature Rise 55C above ambient21. Standard: IEEE C57.1322. Mounting: Supply to include bolts for

mounting on steel structure23. Stainless steel PT Marshalling

BoxesOne per set of three PTS

24. Weight & Dimension (Outline Diagram)

Required

25. Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 71

Page 75: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.7A 138kV Potential Transformer (Protection)

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 72

Page 76: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.7B 69kV Potential Transformers – (TS.03.7.2)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Outdoor type oil filled induction

type suitable for Protection purposes.

3. Nominal operating Voltage 69kV4. Maximum Rated Voltage 72.5kV5. Frequency: 50Hz6. Number of phases: Single phase7. Primary connection: Phase-ground8. BIL: 350kV9. No. of secondary windings: Two (2)10. Voltage Rating10.1 Primary Voltage: 69/√3 kV10.2 Secondary voltage: 115/66.4V-115/66.4V11. Ratio:11.1 X1:X3 346:111.2 X2:X3 600:112. Accuracy class 0.3 WXY Z (C57.13) or equal13. Thermal burden rating: 750 VA14 HV Connector 4-Hole NEMA Pad15 Secondary Connectors: Stud suitable for #2-#10 AWG

(6 sq.mm) copper stranded wire.16. Ground Connectors: 2-bolt clamp suitable for 2/0

AWG copperweld.17. Colour of finish paint: ANSI 70, light grey18. Bushing leakage length: Extra Creep, 3.1cm/kV19. Voltage factor: 1.2 continuous, 1.9 for 8 hrs.20. Temperature Rise 55C above ambient21. Standard: IEEE C57.13.622. Mounting: Supply to include bolts for

mounting on steel structure23 Stainless steel PT Marshalling

BoxesOne per set of three PTS

24 Weight & Dimension (Outline Diagram)

Required

25 Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 73

Page 77: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.7B 69kV Potential Transformer

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 74

Page 78: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.7C 69kV Station Service Voltage Transformer – (TS.03.7.3)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Outdoor type oil filled induction

type.3. Nominal operating Voltage 69kV4. Maximum Rated Voltage 72.5kV5. Frequency: 50Hz6. Number of phases: Single phase7. Primary connection: Phase-ground8. BIL: 350kV9. No. of secondary windings: Two (2)10. Voltage Rating10.1 Primary Voltage: 69/√3 kV10.2 Secondary voltage: 240V/120V11. Ratio:11.1 X1:X2ǁX3-X4 332:111.2 X1:X4 166:112. Impedance 9%13. Thermal burden rating: 100 KVA14 HV Connector 4-Hole NEMA Pad15 Secondary Connectors: Stud suitable for 240 MMSQ

Stranded CU Wire16. Ground Connectors: 2-bolt clamp suitable for 2/0

AWG copperweld.17. Colour of finish paint: ANSI 70, light grey18. Bushing leakage length: Extra Creep, 3.1cm/kV19. Temperature Rise 55C above ambient20. Standard: IEEE C57.13.621. Mounting: Supply to include bolts for

mounting on steel structure22 Grade 304 Stainless steel

Distribution PanelNEMA 4

23 Weight & Dimension (Outline Diagram)

Required

24 Any other information specifically requested, or which may be useful to the Purchaser.

Required

SH 75

Page 79: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.7C 69kV Station Service Voltage Transformer

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 76

Page 80: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.8 138/69 KV, 80/100 MVA INTERBUS TRANSFORMER (TS.03.8)

Number Characteristics Specified Offered1 Manufacturer Required2 Type Outdoor Oil immersed,

with Conservator

3 Rated Capacity at 65˚C temperature rise:3.1 ONAN 80 MVA3.2 ONAF 100 MVA

4 Nominal Voltage Rating (Winding) Nominal/Maximum4.1 High Voltage 138kV4.2 Low Voltage 69kV5 Voltage Rating (Bushing)

5.1 High Voltage 138kV5.2 High Voltage Neutral 138kV5.3 Low Voltage 69 kV

6 BIL (Bushing & Winding)6.1 High Voltage (Bushing & Winding) 650kV6.2 High Voltage Neutral Bushing 110kV6.3 Low Voltage (Bushing & Winding) 350kV

7. Bus Connectors7.1 High Voltage (138kV) Required. For one 595.5

MCM Al Conductor7.2 High Voltage Neutral (H0) Required. For one 4/0 Cu

Conductor.7.3 Low Voltage (69kV) Required. For one 1590

MCM Al. Conductor8 Temperature rise 65˚C Over 40˚C Ambient9 Cooling ONAN/ONAF

10 Rated Frequency 50 Hz

11 Impedance11.1 On Base Rating ONAN (75MVA) 12%11.2 On ONAF Rating (100MVA) Required12 Vector Group YNd113 Number of Phases 314 Connections:

14.1 HV Windings Grounded Star14.3 LV Winding Delta15 Oil PCB Content Less than 2 ppm16 Material of winding Copper

SH 77

Page 81: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.8 138/69 KV, 80/100 MVA Transformer (TS.03.8) CONT

Number Characteristics Specified Offered17 Tap Changer

17.1 Type Off Load17.2 Winding Location High Voltage17.3 Voltage Range +10% -10%17.4 Voltage Change per Tap 2.5%17.5 Taps above rated Voltage 417.6 Taps below rated voltage 418 CT Accuracy Class C40019 CT Ratio & Quantity per Bushing

19.1 HV 2x1200:5A19.2 LV 2x1200:5A19.3 HV Neutral 1x1200:5A20 Bushing Leakage Length (3.1cm/kV)

20.1 HV (138kV) 4495 mm20.2 LV (69kV) 2248 mm20.3 HV (138kV) Neutral 3.1cm/kV

21 Weights21.1 Assembled Transformer in Service Required21.2 Shipping Weight of Heaviest Part Required21.3 Core and Coils (Un-tanking) Required21.4 Tank Required21.5 Oil Required

22 Guaranteed Noise Level22.1 With Fans (ONAF) Required22.2 Without Fans Required

23 Guaranteed Losses at rated voltage and at 65˚C temperature rise

23.1 No Load Loss Required23.2 Load Loss at Rated MVA (excluding no

load loss)Required

23.3 Total Losses (at rated MVA) Required24 Color of Bushing ANSI 70 Grey25 Provide Drawing showing assembled

dimensions of the transformer as well as shipping dimensions and lifting clearances for un-tanking and removal of bushings.

Required

26 Any other information specifically requested, or which may be useful to the Purchaser

Required

SH 78

Page 82: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.8 138/69 KV, 80/100 MVA Transformer

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 79

Page 83: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.9 HV DISCONNECT SWITCHES (TS.03.9)SCH.03.9A 138kV Manual Operated Disconnect Switch (TS.03.9.4)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Center Side Break air insulated3. Nominal Rated Voltage 138kV4. Rated Maximum Voltage 145 kV5. Rated Continuous Current, Amps 1200A6. Rated Frequency 50Hz7. BIL 650 kV8. Rated Short-time Current:

8.1 - Momentary, Amps 99000 A8.2 - 3 seconds 40000 A9 Dry 1 Min Power Frequency

withstand voltage335kV

10. Wet 10 s Power Frequency withstand voltage

275kV

11. Stack Spacing 3350mm12 Support Insulators:

12.1 -Type Porcelain12.2 - Creepage distance (3.1cm/kV) 449512.3 - Bolt Circle 5″12.4 - Colour ANSI Light Grey12.5 - Height 1500mm13. Operating Handle above Grade, M 1M14. Terminal Connection NEMA 4-Hole Pad15 Number of spare auxiliary contacts 16 (8 N/O and 8 N/C)16 Cantilever Strength (lbs) 2000 or better17 Mechanical Interlock Kirk18 Dimensions & Weight (Outline

Drawings)Required

19 Any other information specifically requested, or which may be useful to the Purchaser

Required

SH 80

Page 84: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.9A 138kV Manual Operated Disconnect Switch

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 81

Page 85: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.9B 138kV Motor Operated Disconnect Switch (TS.03.9.4)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Center Side Break air insulated3. Nominal Rated Voltage 138kV4. Rated Maximum Voltage 145 kV5. Rated Continuous Current, Amps 1200A6. Rated Frequency 50Hz7. BIL 650 kV8. Rated Short-time Current:

8.1 - Momentary, Amps 99000 A8.2 - 3 seconds 38000 A9 Dry 1 Min Power Frequency withstand 335 kV

10. Wet 10 s Power Frequency withstand 275 kV11. Stack Spacing 3350mm12. Support Insulators:

12.1 -Type Porcelain12.2 - Creepage distance (3.1cm/kV) 449512.3 - Bolt Circle Required12.4 - Colour ANSI Light Grey12.5 - Height 1500 mm13. Operating Handle above Grade, M 1M14. Terminal Connection NEMA 4-Hole Pad15 Number of spare auxiliary contacts 16 (8 N/O and 8 N/C)16 Cantilever Strength (lbs) 2000 or better17 Electrical Interlock Required18 Motor Operator

18.1 Voltage Rating 125 VDC18.2 Current Rating Required18.3 Heater Required18.4 Direction of Rotation Required18.5 Manual Handle Required18.6 Remote/Local Switch Required18.7 Open/Close Rotary Control Switch Required19 Dimensions & Weight (Outline Drawing) Required20 Any other information specifically

requested, or which may be useful to the Purchaser

Required

SH 82

Page 86: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.9B 138kV Motor Operated Disconnect Switch

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 83

Page 87: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.9C 69kV, 2000A Manual Operated Disconnect Switch (TS.03.9.4)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Center Side Break air insulated3. Nominal Rated Voltage 69kV4. Rated Maximum Voltage 72.5 kV5. Rated Continuous Current, Amps 2000A6. Rated Frequency 50Hz7. BIL 350 kV8. Rated Short-time Current:

8.1 - Momentary, Amps 164000 A8.2 - 3 seconds 44000 A9 Dry 1 Min Power Frequency

withstand voltage175kV

10. Wet 10 s Power Frequency withstand voltage

145kV

11. Stack Spacing 1830mm12 Support Insulators:

12.1 -Type Porcelain12.2 - Creepage distance (3.1cm/kV) 224812.3 - Bolt Circle Required12.4 - Colour ANSI Light Grey12.5 - Height Required13. Operating Handle above Grade, M 1M14. Terminal Connection NEMA 4-Hole Pad15 Number of spare auxiliary contacts 16 (8 N/O and 8 N/C)16 Cantilever Strength (lbs) 2000 or better17 Mechanical Interlock Kirk18 Dimensions & Weight (Outline

Drawings)Required

19 Any other information specifically requested, or which may be useful to the Purchaser

Required

SH 84

Page 88: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.9C 69kV Manual Operated Disconnect Switch

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 85

Page 89: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.9D 69kV, 1200A Motor Operated Disconnect Switch (TS.03.9.4)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Center Side Break air insulated3. Nominal Rated Voltage 69kV4. Rated Maximum Voltage 72.5 kV5. Rated Continuous Current, Amps 1200A6. Rated Frequency 50Hz7. BIL 350 kV8. Rated Short-time Current:

8.1 - Momentary, Amps 99000 A8.2 - 3 seconds 38000 A9 Dry 1 Min Power Frequency withstand 175 kV

10. Wet 10 s Power Frequency withstand 145 kV11. Stack Spacing 1830mm12. Support Insulators:

12.1 -Type Porcelain12.2 - Creepage distance (3.1cm/kV) 224812.3 - Bolt Circle Required12.4 - Colour ANSI Light Grey12.5 - Height Required13. Operating Handle above Grade, M 1M14. Terminal Connection NEMA 4-Hole Pad15 Number of spare auxiliary contacts 16 (8 N/O and 8 N/C)16 Cantilever Strength (lbs) 2000 or better17 Electrical Interlock Required18 Motor Operator

18.1 Voltage Rating 125 VDC18.2 Current Rating Required18.3 Heater Required18.4 Direction of Rotation Required18.5 Manual Handle Required18.6 Remote/Local Switch Required18.7 Open/Close Rotary Control Switch Required19 Dimensions & Weight (Outline Drawing) Required20 Any other information specifically

requested, or which may be useful to the Purchaser

Required

SH 86

Page 90: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.9D 69kV Motor Operated Disconnect Switch

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 87

Page 91: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.9E 69kV, 600A Single Phase Manual Operated Disconnect Switch (TS.03.9.4)

Number Characteristics Specified Offered1. Manufacturer Required2. Type: Vertical Break air insulated3. Nominal Rated Voltage 69kV4. Rated Maximum Voltage 72.5 kV5. Rated Continuous Current, Amps 600A6. Rated Frequency 50Hz7. BIL 350 kV8. Rated Short-time Current:

8.1 - Momentary, Amps 164000 A8.2 - 3 seconds 44000 A9 Dry 1 Min Power Frequency

withstand voltage175kV

10. Wet 10 s Power Frequency withstand voltage

145kV

11 Support Insulators:11.1 -Type Porcelain11.2 - Creepage distance (3.1cm/kV) 224811.3 - Bolt Circle Required11.4 - Colour ANSI Light Grey11.5 - Height Required12. Operating Handle above Grade, M 1M13. Terminal Connection NEMA 4-Hole Pad14 Number of spare auxiliary contacts 10 (5 N/O and 5 N/C)15 Cantilever Strength (lbs) 2000 or better16 Dimensions & Weight (Outline

Drawings)Required

17 Any other information Required

Specification Compliance Summary – Exceptions to SCH.03.9E 69kV, 600A Single Phase Manual Operated Disconnect Switch

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 88

Page 92: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.10 AC & DC DISTRIBUTION PANELBOARDS (TS.03.10)SCH.03.10A 240VAC, 2-Phase 12 Way Main Panelboard (TS.03.10.2)

No. Characteristics Specified Offered1 Manufacturer/Model Required2 Type NEMA, Type PRL3a or equal

480VAC, 400A Bus, 12 Way Panel3 Cooling Convection4 Number of Phases 25 Quantity One (1)

6 Mounting Wall mounted7 Voltage Rating 240VAC 8 Frequency 50Hz9 Current Rating – Main Breaker 400A

10 Short circuit current rating 10,000A11 Cabinet Dimensions Required12 Anti-seismic reinforcements Zone 413 Cable Entry Bottom and Top14 Outline Drawing Required

Specification Compliance Summary – Exceptions to SCH.03.10A 240VAC 2-Phase, 12-Way Main Panelboard

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 89

Page 93: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.10B 240VAC, 2-PHASE Sub Panelboard (TS.03.10.2)

No. Characteristics Specified Offered1 Manufacturer Required2 Type NEMA, Type PRL3e or equal

480VAC, 400A Bus, 52 Way Panel

3 Cooling Convection4 Number of Phases Two (2)5 Quantity Two (2)

6 Mounting Wall7 Voltage Rating 240 VAC 8 Frequency 50Hz9 Current Rating – Main bus 250A

10 Short circuit current rating 10,000A11 Cabinet Dimensions Required12 Anti-seismic reinforcements Zone 413 Cable Entry Bottom and Top14 Outline Drawing Required

Specification Compliance Summary – Exceptions to SCH.03.10B 240VAC 2-Phase Sub Panelboard

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 90

Page 94: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.10C 125VDC Main 52-Way Panelboard (TS.03.10.3)

No. Characteristics Specified Offered1 Manufacturer Required2 Type NEMA, Type PRL3a or equal

250 VDC, 400A, 48 Way Panel

3 Cooling Convection4 Quantity of Panels One (1)

5 Mounting Wall mounted6 Voltage Rating 125 VDC 7 Current Rating Main Breaker 400A8 Short circuit current rating 10,000A9 Cabinet Dimensions Required

10 Anti-seismic reinforcements Zone 411 Cable Entry Bottom and Top12 Outline Drawing Required

Specification Compliance Summary – Exceptions to SCH.03.10C 125 VDC Main 52-Way Distribution Panelboard

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 91

Page 95: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.10D 125VDC 60-Way, Sub Panelboards (TS.03.10.3)

No. Characteristics Specified Offered1 Manufacturer Required2 Type NEMA, Type PRL3E or equal

250 VDC, 400A Lugs, 60 Way Panel

3 Cooling Convection4 Quantity of Panels Three (3)

5 Mounting Wall mounted6 Voltage Rating 125 VDC 7 Current Rating Main Breaker 400A8 Short circuit current rating 10,000A9 Cabinet Dimensions Required

10 Anti-seismic reinforcements Zone 411 Cable Entry Bottom and Top12 Outline Drawing Required

Specification Compliance Summary – Exceptions to SCH.03.10D 125 VDC Distribution Panels

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 92

Page 96: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.10E 48VDC DISTRIBUTION PANEL (TS.03.10.4)

No. Characteristics Specified Offered1 Manufacturer Required2 Type Intelligent dual bus panel3 Cooling Convection4 Quantity of Panels One (1)

5 Mounting In Communication Panel6 Voltage Rating 48 VDC 7 Minimum Current Rating 150A8 Short circuit current rating 10,000A9 Cabinet Dimensions Required

10 Anti-seismic reinforcements Zone 411 Cable Entry Bottom and Top12 Outline Drawing Required

Specification Compliance Summary – Exceptions to SCH.03.10E 48VDC Distribution Panel

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 93

Page 97: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.11 LIGHTING FIXTURES (TS.03.11)SCH.03.11A Substation Lighting Fixtures (TS.03.11.3)

Number Characteristics Specified Offered1. Manufacturer Holophane2. Catalogue Number (Proposed) SU2A 400HP24TL3. Type: SU4. Wattage 400W5. Lamp High Pressure Sodium (HPS)6. Voltage 240 VAC7. Frequency 50Hz8. Mounting Height 9 - 12 feet9. Photo Electric Controller One per lamp

10. Ballast Required

Specification Compliance Summary – Exceptions to SCH.03.11A Substation Lighting

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 94

Page 98: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.11B Area Lighting (TS.03.11.4)

Number Characteristics Specified OfferedA Pole1. Manufacturer HAPCO or equal2. Pole Type: RTA3. Catalogue Number Required

B LAMP4. Catalogue Number (Proposed) 5. Type: M-4006. Wattage 250W7. Lamp Metal Halide or LED8. Voltage 240 VAC9. Frequency 50Hz

10. Mounting Height 9 - 12 feet11. Photo Electric Controller One per lamp12. Ballast 250 Watt Reactor Ballast

Specification Compliance Summary – Exceptions to SCH.03.11B Area Lighting

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 95

Page 99: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.12 LOW VOLTAGE POWER, CONTROL, AND INSTRUMENT CABLES (TS.03.12)

No. Characteristics Specified Offered1 Manufacturer Required2 Insulation voltage rating 600V/1000V3 Cable Type Armored or Shielded4 Insulation Type PVC or XLPE5 Flame retardant Yes6 Insulation Resistance Exceed 1000 M Ohms /kilometer7 Quantity Per Cable List

Specification Compliance Summary – Exceptions to SCH.03.12 Low Voltage Control, Power, and Instrument Cables

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 96

Page 100: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.13 SUBSTATION GROUNDING (TS.03.13)

No. Characteristics Specified Offered1. Drawings

1.1 Grounding Layout1.2 Grounding System Details – Equipment,

Structures, fencing and Lightning Protection System

2 Materials See Drawing OHS SH 42.1 7#5 Copperweld Conductor2.2 7#7 Copperweld Conductor2.3 Ground Rods2.4 CADWELD2.5 Connectors – Ground wire to structures

3 Calculations

Specification Compliance Summary – Exceptions to SCH.03.13 Grounding

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 97

Page 101: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.14 125 VDC BATTERY SET (TS.03.14)

No. Characteristics Specified Offered1 Manufacturer Required2 Quantity One (1)

3 Battery Type Nickel Cadmium, High PerformanceCell Type Clear, shock absorbing, leak proof,

plastic4 Connectors Acid resisting nuts, Nickel plated

copper inter-cell connectors (solid bar)

4 Nominal Voltage Rating 125 VDC5 Float Voltage, 104% of Nominal 129VDC6 Equalizing Voltage, 112% of

Nominal140 VDC

7 Minimum Voltage 84% of Nominal

105 VDC

8 Number of Cells 92/Required9 Ampere Hour Rating Capacity required; See OHS-016

10 Temperature Ratings10.1 Minimum Battery Temperature 25 Deg. C10.2 Nominal Battery Temperature 20 Deg. C10.3 Maximum Battery Temperature 30 Deg. C11 Spares Required (Provide List)12 Battery Rack Two-step galvanized, Zone 4

Earthquake Condition13 Outline Drawings Required

Specification Compliance Summary – Exceptions to SCH.03.14 125 VDC Battery Set

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 98

Page 102: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.15 240VAC, 2-PHASE 125 VDC BATTERY CHARGER (TS.03.15)

No. Characteristics Specified Offered1 Manufacturer Required2 Type Required3 Cooling Convection4 Control Fully automatic, silicon-controlled

rectifier5 Quantity One (1)

6 Current Rating Minimum 50A7 Voltage Rating 240 VAC Three Phase8 Frequency 50Hz9 Spares-Control & alarm board Required (Provide List)

10 Manual Required11 Alarms [(Local and remote (by

contacts)]:Required (Provide List)

11.1 Positive Ground Fault Required11.2 Negative Ground Fault Required11.3 AC Input Failure Required11.4 Rectifier Failure Required11.5 Maximum Output DC Voltage Required11.6 Minimum Output DC Voltage Required12 AC & DC Transient Voltage

Protection/Surge Protection13 Timer adjustment for equalize

switch automatic return to float0 – 72 Hours

14 Output voltage Required15 DC Voltmeter Required16 DC Ammeter Required17 Cabinet Dimensions Required18 Anti-seismic reinforcements Zone 419 Cable Entry Bottom20 Ethernet Gateway module;

DNP3Required for connection of ethernet cable – remote alarms

21 Outline Drawing Required

SH 99

Page 103: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.15 240VAC, 1-PHASE 125 VDC Battery Charger

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 100

Page 104: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.16 48 VDC BATTERY SET (TS.03.16)

No. Characteristics Specified Offered1 Manufacturer PIBAS or equivalent2 Quantity One (1)

3 Battery Type KGM-160 Nickel Cadmium, High Performance, Maintenance Free

Cell Type Clear, shock absorbing, leak proof, plastic

4 Connectors Acid resisting nuts, Nickel plated copper inter-cell connectors (solid bar)

4 Nominal Voltage Rating 48 VDC5 Float Voltage 53VDC6 Equalizing Voltage 57 VDC7 Minimum Voltage 84% of

Nominal43.2 VDC

8 Number of Cells Required9 Ampere Hour Rating 160AH

10 Temperature Ratings10.1 Minimum Battery Temperature 25 Deg. C10.2 Nominal Battery Temperature 20 Deg. C10.3 Maximum Battery Temperature 30 Deg. C11 Spares Required (Provide List)12 Battery Rack Two-step galvanized, Zone 4

Earthquake Condition13 Standard IEEE13 Outline Drawings Required

Specification Compliance Summary – Exceptions to SCH.03.16 48 VDC Battery

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 101

Page 105: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.17 240VAC, 2-PHASE, 48 VDC BATTERY CHARGER (TS.02.17)

No. Characteristics Specified Offered1 Manufacturer EATON2 Type APS3-321 DC Power Solution with

Single LVD3 Cooling Convection4 Control Fully automatic, silicon-controlled

rectifier5 Quantity One (1)

6 Rectifier Eaton 48V Rectifier, 2000W, Energy Saver (QTY = 3)

7 EATON 100A, 27MM Din Rail Load MCB (QTY = 2)

8 APS3-3G AC Kit and breaker for charger (QTY=1)

9 SC200 Controller (QTY=1)10 AC Voltage Rating 240 VAC Single Phase11 Frequency 50Hz12 Alarms Required (Provide List)

12.1 Ground Fault Required12.2 High DC Voltage Required12.3 Low DC Voltage Required12.4 AC Input Failure Required12.5 Rectifier Failure Required13 AC & DC Transient Voltage

Protection/Surge Protection14 Timer adjustment for equalize

switch automatic return to float0 – 48 Hours

15 AC Voltage Required16 DC Voltmeter Required17 DC Ammeter Required18 Cabinet Dimensions Required19 Anti-seismic reinforcements Zone 420 Cable Entry Bottom21 Spares Required (Provide List)22 Outline Drawing & Manual Required

SH 102

Page 106: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

Specification Compliance Summary – Exceptions to SCH.03.17: 240VAC 1-PHASE 48 VDC Battery Charger/DC Power System

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 103

Page 107: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.18 CIVIL WORKS (TS.03.18)

No. Characteristics Specified Offered1 Site Works

1.1 Removal of topsoil1.2 Backfilling1.3 Compaction2 Drainage3 Piling Works4 Foundations

4.1 Interbus Transformers (with oil pits and firewall)

4.2 HV Circuit Breakers4.3 Column Gantries4.4 Bus Supports4.5 138kV Disconnect Switches4.6 138kV VTS4.7 69kV SSVT4.8 Communication Tower (Steel Pole)5 Fence and Gate

5.1 Fence Posts Schedule 405.2 Chain Link Fabric Galvanized ASTM D392,

Class 2 or Aluminium5.36 Road Works7 Gravelling8 Relay Building (See SCH.03.20)9 Concrete Tests Indicate number of tests

Specification Compliance Summary – Exceptions to SCH.03.18 Civil Works

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 104

Page 108: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.19 CABLE LAYING, CABLE TRENCHES, DUCTS (TS.03.19)

No. Characteristics Specified Offered1 Cable Trenches2 Ductwork3 Manholes4 Handholes56789101112

12.112.212.312.4

Specification Compliance Summary – Exceptions to SCH.03.19 Duct Works

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 105

Page 109: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.20 RELAY BUILDING (TS.03.20)

No. Characteristics Specified Offered1 Foundations2 Building3 AC Power & Lighting4 Emergency Lighting5 Eye Wash Speakmans SE-4906 Toilet7 Sewerage Treatment8 Fire alarm and Suppression System

8.1 Fire Alarm Panel EST 66028.2 Smoke Detectors Edwards, Type EST6249C8.3 Fire Suppression FM-2009 Eye Wash Station SE-49010 Relay Panel Support11 Door Entry Alarm12 Substation Intrusion Alarm System

12.1 Infrared Camera/12.2 Motion Detectors12.3 Access Control12.4 Control Panel12.5 Communication Protocol12.6 Monitoring software12.7 Recording Software12.8 Management Software12.9 Drawings and catalogs/manuals Required13 Relay Building Access Floor

13.1 Manufacturer13.2 Construction Cement core in aluminium13.3 Height 18”13.4 Type Heavy Duty13.5 Panel 24”x24”13.6 Grounding Required13.7 Drawings and catalogs/manuals Required14 Cable Tray

Specification Compliance Summary – Exceptions to SCH.03.20 Relay Building

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 106

Page 110: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.21 HIGH VOLTAGE POWER CABLES (TS.03.21)

No. Characteristics Specified Offered1 Manufacturer Required2 Nominal Voltage Rating 138kV3 Maximum Voltage Rating 145kV4 Basic Impulse Level 650kV5 Continuous Current Rating 1055A6 Insulation Type XLPE7 Non-metallic outer sheath PVC8 Armour Single Wire Armour9 Maximum Temperature Rating @ IN 90 C⁰10 Max Temperature Rating @ ISC 200 C⁰11 Quantity Per Cable List12 Accessories

12.1 Voltage Limiters Required12.2 Link boxes Required12.3 Cable Terminations Required12.4 Insulators Composite or Porcelain

Specification Compliance Summary – Exceptions to SCH.03.21 High Voltage Power Cable

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 107

Page 111: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.03.22 EQUIPMENT IDENTIFICATION (TS.03.22)

No. Characteristics Specified Offered1 Substation Name On gate2 Substation Danger Sign On gate3 Substation Safety Sign On gate4 Substation Danger Sign Type 2 On fence5 Phase Labels On three outgoing lines6 Equipment Numbers Circuit Breakers and Switches7 Transformer Labels T1 and T28 Equipment Labels PTS

Specification Compliance Summary – Exceptions to SCH.03.22 Equipment Identification

COMPLIANCE LEVEL (MARK X) TOTAL ( ) PARTIAL ( )

If only PARTIAL Compliance, list below compliance exceptions

SH 108

Page 112: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.04 SCHEDULE OF DELIVERY

Purchaser Required Delivery 636 Calendar Days

Contractors Proposed Delivery

Name of Bidder

Signature of Bidder

SH 109

Page 113: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05 Schedule of Tender Information

SCH.05.1 Addenda to Bid Documents

The Bidder has received the following Addenda to the Bid Document prior to submission of this bid.

Addenda No Dated

For and on behalf of

(Contractor’s Name)

Title

SH 110

Page 114: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.2 Deviation from Specifications - Minor Modifications

The minor deviations from the specifications are as follows:

Minor changes and modifications to the solution outlined in the Specifications and Drawings.

If there are no deviations from the Technical Specifications, then “No Departure from Technical Specifications” shall be marked in the Schedule of Information.

For and on behalf of

(Contractor’s Name)

Title

SH 111

Page 115: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.3 Deviation from Specifications - Major Modifications

The major deviations from the specifications are as follows:

If a completely new solution or major modifications are proposed, then a separate set of Attachments shall be prepared and submitted in a separate envelope marked “Alternate Solution”.

If there are no deviations from the Technical Specifications, then “No Departure from Technical Specifications” shall be marked in the Schedule of Information.

For and on behalf of

(Contractor’s Name)

Title

SH 112

Page 116: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.4 Legal Documentation

For and on behalf of

(Contractor’s Name)

Title

SH 113

Page 117: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.5 Previous Experiences, Eligibility

For and on behalf of

(Contractor’s Name)

Title

SH 114

Page 118: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.6 KEY PERSONNEL

a) The names of the key personnel whom they would employ to direct the work on the site together with a brief resume of their qualifications and experience.

Duty Name Responsibility

Project Manager

Electrical Engineer

Civil Engineer

Geotechnical Engineer

Site Manager

Quality Controller

Civil Site Supervisor

EM Site Supervisor

Safety Officer

Commission Engineer

For and on behalf of

(Contractor’s Name)

Title

SH 115

Page 119: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

b) The estimated number and classification of workmen to be engaged on the work each month at the site:

Year Week Classification of Workman by TradeTotalEach Week

For and on behalf of

(Contractor’s Name)

Title

SH 116

Page 120: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.7 Sub-Contractors

Bidders shall submit the following list of all phases of the Work they propose to sublet with the names of all Sub- Contractors they propose to employ together with the other information specified:

Phase of Works Proposed Sub - Contractors

For and on behalf of

(Contractor’s Name)

Title

SH 117

Page 121: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.8 Technical Capability

Bidders shall submit the following statement of work which they have undertaken similar to that on which they are tendering over the past seven years. Full details of the location and ownership of any such work undertaken shall be supplied and the bidders shall also list the names and addresses of the Owner's representative(s) who were associated with said work for references:

Description and Value of

Works

Location Year Completed Owner Name & Address of Owners

Representative

For and on behalf of

(Contractor’s Name)

Title

SH 118

Page 122: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.9 Work Program

For and on behalf of

(Contractor’s Name)

Title

SH 119

Page 123: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.10 Day Work Rates

Include Rates for all personnel to be employed on the project.

Position/Personnel Charge RateProject ManagerElectrical EngineerGeotechnical EngineerCivil EngineerSite ManagerCivil Site SupervisorElectromechanical Site SupervisorCommissioning EngineerQuality Controller

For and on behalf of

(Contractor’s Name)

Title

SH 120

Page 124: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.11 Equipment Rental RatesList Equipment

Item Description Hourly Rate

Daily Rate Weekly rate

1 Excavator

2 Backhoe

3 10 Ton Roller

4

5

6

Include rate for equipment for excavation in rock.

For and on behalf of

(Contractor’s Name)

Title

SH 121

Page 125: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.12 Material Unit PricesBidder shall list items

Item Description Unit Rate

A Control Cables

B Grounding Materials

C Bus Work

For and on behalf of

(Contractor’s Name)

Title

SH 122

Page 126: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.13 Financial Capability

Bidder shall furnish the following statement as to their financial standing for reference:

Bank or reputable financial firm:

Name: ________________________________________

Address: ________________________________________

Other references of financial standing:

Name Address

For and on behalf of

(Contractor’s Name)

Title

SH 123

Page 127: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.14 Civil Work RatesBidder shall list items

Item Description1 Excavation in marl

2 Excavation in Rock

3 Road Works

4 Piling Works

5

6

7

8

9

10

For and on behalf of

(Contractor’s Name)

Title

SH 124

Page 128: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.15 Details of Contractor's Insurance Coverage

Insurance proposed by the Contractor in accordance with the Conditions of Contract:The premiums for all insurance shall be included in the Bid Price.

No. Type of Coverage Minimum Limit (US$)

For and on behalf of

(Contractor’s Name)

Title

SH 125

Page 129: PART · Web view138kV,1200A, SF6 Circuit Breakers 5 Ea. 4.2 69kV, 2000A, SF6 Circuit Breakers 6 Ea. 5 69kV and 138kV Substation Steel Structures 1 Lot TS.03.5 6 Bus Work & Insulators

OLD HARBOUR TO CORPORATE AREA TRANSMISSION NETWORK EXPANSION PROJECT (OHCATNEP)

SCH.05.16 Technical Documentation

For and on behalf of

(Contractor’s Name)