part b : price bid bid... · flexible / pvc conduits run concealed within walls / partition / work...
TRANSCRIPT
Page 1 of 17
Signature of Contractor with Seal
SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD.
STATE BANK OF INDIA.
LOCAL HEAD OFFICE,3rd FLOOR ,C-6,G- BLOCK,
SYNERGY BUILDING, BANDRA-KURLA COMPLEX,
BANDRA (EAST), MUMBAI-400 051.
PART – B : PRICE BID
TENDER FOR:
PROPOSED ELECTRICAL WORKS OF RETALL ASSETS CENTRALLSED
PROCESSING CENTER AT FIRST FLOOR, ASHOK SILK MILIS COMPOUND,
LBS MARG, GHATKOPAR (WEST),MUMBAI-400 086.
TENDER SUBMITTED BY : NAME : __________________________________ ADDRESS : __________________________________ __________________________________ __________________________________ DATE : __________________________________ ARCHITECT : KALA AREKHAN ARCHITECT & INTERIOR DESIGNER, 101, VINDHYCHAL CO-OP HOUSING SOC, PLOT NO. 204, SECTOR IV, CHARKOP, KANDIVLI (W), MUMBAI-400 067. TEL NO: 2868 2567. E MAIL: [email protected]
Page 2 of 17
Signature of Contractor with Seal
STATE BANK OF INDIA
TENDER FOR ELECTRICAL AND ALLIED WORK AT SBI RACPC OFFICE ,
GHATKOPAR.
Sr.No. Description Qty Unit Rate Total
SECTION - A
1 MAIN POWER SWITCH UNIT.
SITC of 250 Amps. SFU With HRC Fuse
Enclosure
1 Set
2 MAIN POWER PANEL
Providing & Fixing of fabricated main
power panel as follows: :Main Incomer
200A TPN MCCB
i) Thermal O/L Realease Range : 80-160A
ii) Instantaneous magnetic S/C Trip
iii) Rotary handle.
iv) Shunt Trip .
Digital Metering & Indications
Ammeter class 1.5 with selector switch-1
set Voltmeter class 1.5
with selector switch-1 set
250A 4 pole Tinned & sleeved copper bus
bars Indication lamps R,
Y, B-22.5 dia cluster LEDs
Outgoing: 3 Nos. 125A TPN MCCB
3 Nos. 125A TPN MCCB
6 Nos. 63A FP MCB
1 Set.
3 Auto PF Correction Panel 50.0Kvar with
Auto Manual Capacitor Banks, 3 Phase,
EPCOS, Siemens, Heavy Duty as follows:
i)15.0Kvar - 1 No.
ii)10.0Kvar - 2 No.
iii)7.5Kvar - 2 Nos.
iv) APFCR Relay 4 stage, Intelligent type
v)Contactors, Capacitor Duty : suitable for
above capacitor vi)TP MCB's :
40A-3 no., 25A 2 no.
vii) Timers & auxliary relays, control &
Power wiring.
The rate shall include all components,
Bus Bars, Wiring & accessories.
1 set.
Page 3 of 17
Signature of Contractor with Seal
4 AC DISTRIBUTION BOARD
TPN DB 6 WAY as follows : ACDB
Incommer 63A FP MCCB-- 1 No.
Outgoing 20/25/32 SP MCBs -18 Nos.
2 Set
5 LIGHTING / RAW MAIN
DISTRIBUTION BOARD
4 WAY TPN LDB IP42
Incomer:- 63 Amps.TPN MCB - 1 No.
3No.s 32A DP RCCB/ ELCB. Previous
100MA
10/16/20/25 Amps. SP MCB - 12 Nos.
( Make:- MDS Legtrant / Merlin Gerin /
Siemens/Hagger )
4 Set
6 UPS POWER DISTRIBUTION
BOARD 12
WAY SPN UPS IP42
Incomer:- 40 Amps.DP MCB - 1 No.
Outgoing:- 10/16/20 Amps. SP MCB - 10
Nos. ( Make:- MDS
Legtrant / Merlin Gerin /
Siemens/Hagger )
2 Set
7 UPS POWER DISTRIBUTION
BOARD 6
WAY SPN UPS IP42
a) Incomer:- 63 Amps.DP MCB - 1 No.
b) Outgoing:- 20/25/32 Amps. SP MCB - 4
Nos. ( Make:- MDS Legtrant / Merlin
Gerin / Siemens/Hagger )
1 Set
8 Supplying, Installation, Testing &
Commissioning of 63 Amps TPN MCB in
Waterproof IP55 Enclosure Box.
4 Set
9 Supplying, Installation, Testing &
Commissioning of 63 Amps FP MCB in
MS Enclosure Box.
2 Set
10- Supplying, Installation, Testing &
Commissioning of 63 Amps DP MCB in
MS Enclosure Box.
2 Set
TOTAL OF SECTION - A
Page 4 of 17
Signature of Contractor with Seal
SECTION - B
POWER CABLE & TERMINATION
1 Supplying, Installationm, Testing &
Commissionning of LT Cable rated for
600/1100 Volts AC as per IS Standard
with necessary accessories.
a 3.5 Core x 185 sq.mm. Al Armoured
Cable with 1 Nos. of 14 SWG GI earth
wire For Main Power Panel
70 Mtrs.
b 4 Core x 6 sq.mm. Copper Armoured
Cable with 1 Nos. of 14 SWG GI earth
wire for Lighting Raw Power & AC.
280 Mtrs.
c 3 Core x 4 Sq.mm. Copper Armoured
Cable with For AC.
150 Mtrs.
d 4 Core x 10 sq.mm. Copper Armoured
Cable with 1 Nos. of 14 SWG GI earth
wire for UPS Input.
55 Mtrs.
e 4 Core x 16 sq.mm. Copper Armoured
Cable with 1 Nos. of 14 SWG GI earth
wire for AC DB. GI earth wire for AC DB.
90 Mtrs.
f 4 Nos.x 10 Sq.mm. Copper Lead Wire
Copper Lead Wire in 32mm. PVC pipe for
UPS Input.
30 Mtrs.
2 S/I/T/Commissioning of LT Cable
Termination with Copper brass gland and
Termination of Each Core with necessary
required Copper Lugs etc.complete as per
instructions of the Architect /
a
3.5 Core x 185 Sq.mm. Al Armoured
cable. 2 Nos.
b
3 Core x 4 Sq.mm. Copper Armoured
cable. 10 Nos.
c
4 Core x 6 Sq.mm. Copper Armoured
cable. 16 Nos.
d
4 Core x 10 Sq.mm. Copper Armoured
cable. 2 Nos.
e
4 Core x 16 Sq.mm. Copper Armoured
cable. 4 Nos.
TOTAL OF SECTION -B
Page 5 of 17
Signature of Contractor with Seal
SECTION - C
LIGHT POINT WIRING
1 Supplying, Installation, Testing &
Commissioning of Light Point Wiring
using 650 / 1100 Volts grade 3 Nos. of 1.5
Sq.mm. PVC insulated Copper wire
including circuit wiring with 3 nos. 2.5
sq.mm. from DB to switch board and
switch board to switch board FR Grade
pulled through 20/25mm PVC conduit
MMS grade with requiredcapacity of wires
as per mentioned inTechnical Set.
. All the wiring below false celing or on
wall must be concealed with back filling of
the same upto finish level with sand,
cement etc. complete.
. All the drops from the junction box to the
light of the proposed light point must be
drop in PVC flexible pipe with BALL
socket, glant at the junction box.
. Rate quoted must include the cost of
Modular Switches,Modular Sockets, Metal
Concealed Box, Modular Switches,
Modular Plate with Cover & Required
Accessories etc.
a Primary Light Point. 105 Nos.
b Secondary Light Point Looped from above
Primary Light Point.
155 Nos.
c Half Socker Point on Lighting Board. 12 Nos.
d Fan Point With Fan Regulator. 6 Nos.
e Exhaust Fan Point. 6 Nos.
f Bell Point with Bell Indicator type with
Remote Bell.
6 Nos.
2 AC POWER POINT
a Supplying, Installation, Testing &
Commissioning of 20 Amps.Rey roll metal
Socket with plug top complete set. With
3x2.5Sq.mm.Cu wire from AC DB to point
AC
5 Nos.
b Supplying, Installation, Testing &
Commissioning of 6 Amps. Power Point
With 2.5 x 3 Wire Copper Wire Circuit as
Pramary point. For AC indoor Unit.
35 Nos.
TOTAL OF SECTION - C
Page 6 of 17
Signature of Contractor with Seal
SECTION - D
FLOOR RACEWAYS & CONDUITS
1 Supplying, Installation, Testing &
Commissioning of follwing raceways /
conduits in flooring. The rate shall be
inclusive of removing the flooring by
cutter & back filling the same with
required Sand, Cement etc.and giving the
finishing upto the floor level as per
Instruction of Architect / Engineer.
a 80mm x 40mm Aluminum Raceways. 180 Mtrs.
b 25mm Dia PVC conduit HMS Grade. 850 Mtrs.
2 FLOOR JUNCTION BOX
Supplying, Installation, Testing &
Commissioning of following GI junction
boxes in floor of 14 SWG thick duly
painted. The rate shall be inclusive of
providing Sand, Cement etc. and finishing
the same upto the floor level as per
instructions of the Architect / Engineer.
a 200mm x 200mm x14 SWG Junction Box
with Stainless Steel Cover Plate.
15 Nos.
b 250mm x 250mm x14 SWG Junction Box
with Stainless Steel Cover Plate.
15 Nos.
c 300mm x 300mm x14 SWG Junction Box
with Stainless Steel Cover Plate.
10 Nos.
d 350mm x 350mm x14 SWG Junction Box
with Stainless Steel Cover Plate.
10 Nos.
TOTAL OF SECTION - D
Page 7 of 17
Signature of Contractor with Seal
SECTION - E
RAW POWER POINT
1 Supplying, Installation, Testing &
Commissioning of raw power socket point
on Skirting, Walls, Tables using PVC
flexible / PVC conduits run concealed
within Walls / Partition / Work Station etc.
The rate shall be inclusive of MS
Concealed Box, Modular Surface Plate,
Modular Switch, Modular Socket, Pipe
from junction To Point & Required
Accessories etc. complete as per
instruction of the Architect / Consultant.
Including circuit wiring with 3 nos. 2.5
sq.mm.from DB to Raw/Ups point FR
Grade pulled through 20/25mm PVC
conduit MMS grade with required capacity
of wires.
1a 16 Amps Switch & 16 Amps Socket Point.
As Primary Point with 3x2.5Sq.mm.Cu
Wire.
5 Nos.
1b 16 Amps Switch & 16 Amps Socket Point.
As Secondary Point.
10 Nos.
2a 6 Amps Switch & 6 Amps Socket Point
For AC Power & Workstation. as Primary
Point.with 3x2.5Sq.mm.Cu Wire. 1 Max.
three counters/tables in One Circuit.
25 Nos.
2b 6 Amps Switch & 6 Amps Socket Point
For AC Power & Workstation. as Primary
Point. with 3x2.5Sq.mm.Cu Wire.1 Max.
three counters/tables in One Circuit.
35 Nos.
2 COMPUTER SOCKET POINT
Supplying, Installation, Testing &
Commissioning of computer socket point
on Skirting, Walls, Tables
a 3 Nos.of 6 Amps socket below work
station on 6 Module plate & 1 No.of 16
Amps SP switch on 1 Module Plate above
Work Station as (Primary) Point with
3x2.5Sq.mm.Cu Wire circuit put from
UPS DB 1 Max. three counters/tables
in1Circuit.
25 Nos.
Page 8 of 17
Signature of Contractor with Seal
b 3 Nos.of 6 Amps socket below work
station on 6 Module plate & 1 No.of 16
Amps SP switch on 1 Module Plate above
Work Station as (Secondary) Point.with
3x2.5Sq.mm.Cu Wire.1 Max. three
counters/tables in One Circuit.
45 Nos.
TOTAL OF SECTION - E
SECTION - F
1 LIGHT FIXTURE
a 2 x 2 x 36 Watts LED Light Fixture with
accessories such as Chain Link Support on
ceilling.
85 Nos.
b 15/ 18Watts LED down light Fixture. 135 Nos.
c 2/4 Feet LED Tubelight Fixture 10 Nos.
d Warmwhite LED Strip Light with Driver 150 Mtrs.
e 9" Exhaust Fan 6 Nos.
f 16" Wall Fan Fan 2 Nos.
g 48" Ceiling Fan. 6 Nos.
TOTAL OF SECTION -F
SECTION - G
TELEPHONE CABLING
1 S/I/T/C of 20 pair Jelyfild telephone
armoured cable in 25mm PVC pipe MMS
grade.
55 Mtrs.
2 S/I/T/Commissioning of 50 Pair telephone
tag block with 5 Nos. 10 pair crone
modulewith Termination & Crimping etc.
complete.
2 Nos.
3 S/I/T/Commissioning of Telephone point
with 1 No.of RJ 11 socket, 1 Module Plate,
Box etc.from Tag Block upto the Point.
Including 2 Pair telephone cable in already
laid pipes and raceways.
70 Nos.
4 Do as above ITEM NO.4, but with 2
Nos.of RJ 11 socket.
4 Nos.
TOTAL OF SECTION - G
Page 9 of 17
Signature of Contractor with Seal
SECTION - H
MISCELLANEOUS WORK
1 Supplying / Installation/ Testing &
Commissioning of Earthing station with
600 x 600 x 3mm thick CU plate as per IS
643.Rate shall be inclusive of supply
installation of CU Plate, 25mm dia GI pipe
with funnel for water and 450mm Cast
Iron cover with its frame. Necessary
digging of earth pit, excavation, back
filling of earth,electrode, charcoal, salt
layer & brick masonary work in proper
manner.
2 Nos.
2 S/I/T/Commissioning of 25mm x 3mm GI
Earthing Strip.
50 Mtrs.
3 S/I/T/Commissioning of 1 No.of
10sq.mm.single core PVC flexible copper
wire for UPS in 20mm PVC conduit with
all required accessories etc.
110 Mtrs.
4 provision of temporary lighting for work to
be carried out at site with necessary cables
/ wires / switch board / main switch etc
complete.
1 Job.
5 Electronic AC Timmer For 2 Nos. Acs. 1 Nos.
6 Electronic Cyclic Timmer For Sign Board. 1 Nos.
TOTAL OF SECTION - H
SECTION - I
I REMOVING & BUY- BACK
ITEMS
Removing Dismantling & Buy Back of
all removed Eelctrical Itemsincluding
existing wiring of all types, Light
fixtures, Fans,Switch Sockets, Data
Cables,IO etc. as per instructions given
& approved by the Client / Branch
Manager / Bank Engineer Consultant at
site. Contractor shall take approval &
official permission before dispatching
L.S.
Page 10 of 17
Signature of Contractor with Seal
the buy-back material from site.
SUMMARY
A Lighting Main Distribution Board
B Power Cable & Termination
C Light Point Wiring
D Floor Raceways & Conduits
E Raw Power Point
F Light Fixture
G Telephone Cabling
H Miscellaneous Work
TOTAL
I Less Removing & Buy back Items
TOTAL AMOUNT:
Add 9% CGST :
Add 9% SGST :
GRAND TOTAL:
Page 11 of 17
Signature of Contractor with Seal
Page 12 of 17
Signature of Contractor with Seal
Page 13 of 17
Signature of Contractor with Seal
Page 14 of 17
Signature of Contractor with Seal
LIST OF APPROVED MANUFACTURERS FOR LT ELECTRICAL WORKS
S.N. MATERIALS APPROVED MANUFACTURERS
1 Moulded Case Circuit Breaker (MCCB) i) Legrand
ii) Schneider
iii) Hager
iv) Siemens
v) Havells
2 Switch Fuse Unit (SFU) i) L & T
ii) Siemens
iii) ABB
3 Power Contactors i) L & T
ii) Siemens
iii) Schneider
4 Meters i) HPL
ii) IMP
iii) L & T
5 Armoured LT cable i) Polycab
ii) Finolex
iii) R R Kabel
iv) CCI
6 Cable Termination i) Dowells
ii) Comet
iii) Frontier Technologies
7 Cable Tray i) Profab
ii) Metalemms
iii) Asian Ancillary Corporation
8 PVC Conduit & Accessories i) Allied Conduits
ii) SRG
iii)New India Trading
Page 15 of 17
Signature of Contractor with Seal
9 Wires (FRLS only) i) RR Kabels
ii) Havells
iii) Finolex
iv) Polycab
10 MS Conduit & Accessories (ISI Mark). i) BEC
Medium - 1.6 mm thick. ii) AKG
Heavy - 2 mm thick. iii) NIC
10 Modular Switches & Sockets with PVC Box
i) Legrand - (Arteor model)
ii) MK - (Blenz model)
iii) Schneider - (Zencelo model)
iv) Elleys - (Fotolia model)
11 Distribution Board, MCB, RCCB & RCBO i) Legrand
ii) Schneider Hager
iii) Hager
12 Data/ Voice Cable & accessories i) D-Link
ii) AMP
13 Light Fixtures i) CG
ii) Philips
iii) CGL
iv) Osram
i) Bajaj
ii) Orient
iii) Havells
14 Tubes, PL's & CFL's i) Philips
ii) Osram
15 Ceiling Fan i) CG
ii) Havells
iii) Bajaj
16 Exhaust Fan i) CG
ii) Almonard
iii) Alstom
17 Speakers i) BOSCH
ii) Ahuja
18 Amplifier i) BOSCH
Page 16 of 17
Signature of Contractor with Seal
ii) Ahuja
19 Electrical LT Panel CPRI Approved Panel Manufacturer Only.
20 Capacitors i) Siemens
ii) L& T
iii) GE
iv) ABB
iii) Universal
21 CT'S / PT'S i) AE
ii) Kappa
iii) Ricco
iv) Rishabh
22 APFC Relay. i) HPL
ii) Emercon
iii) Alstom
iv) Beluk
v) L & T
23 Contactor / Timer i) Schneider
ii) Hager
iii) L & T
iv) Siemens
iv) Legrand
24 Energy Meters i) Trinity
ii) Schneider
iii) L & T
iv) Tecnic
v) AE
vi) HPL
NB. 1) The contractor should obtain prior approval from Employer / Consultants before
placing order for any specific materials. Employer may / delete any of the
makes or brands out of the above list.
2). All materials should conform to relevant standards and codes of BIS.
3) Materials with I.S.I. mark shall be used duly approved by the SBIIMS Engineer
/ Architect.
Note: - If any material is found to be not up to the mark, the contractor will have
to produce original bills/certificate from the manufacturer or his
authorised Distributor for authenticity and genuineness of the material
Page 17 of 17
Signature of Contractor with Seal
for consideration and as per make approved by the SBIIMS. The same