Page 1: PARSONS NORTH TERMINAL PROJECT … · LOUIS ARMSTRONG NEW ORLEANS INTERNATIONAL AIRPORT NEW ORLEANS, ... Note that the W30x90 beam has moment connection at each end so needs to be

PARSONS BRINCKERHOFF

NORTH TERMINAL PROJECT

LOUIS ARMSTRONG NEW ORLEANS INTERNATIONAL AIRPORT

NEW ORLEANS, LOUISIANA

TRANSMITTAL COVER

Date: 07/26/2016

To: Company: HGBM Person: Document Control

Submitted on Behalf of: NOAB

Document Title: OSI WPM-DSl-0031 (RFl-00679)

Number of Copies: One (1) Electronic

Action:

Transmittal #: 03862-006-0l

From: Company: PB Person: Jim Stievater

Delivered Via: Email

D No Cost/Time Impact. Proceed with the work indicated. Advise within 14 days if there is any Cost or Time Impact.

D Cost Decrease. Proceed with the work. Submit credit proposal for Review. D Cost Increase. Proceed with the work on a T&M Basis. Cost to be submitted when work is complete. ~ Cost Increase. Proceed with the work. Submit proposal. D Cost Increase. Do not proceed with work. Submit proposal. D VE/Conformed Documents Implementation

Comments: Additional clarifying detail provided for a few joist supports at concourses.

Attached: NT SG 5231 , CCAT WPM-DSl-0031 , RFI 00679

Construction Manager Approv~---=-~-=.._l._ ._.~ ....... --"'=CJL, ......,.,.k,"-=-..___ _______ 1..,./_u__,p,_,-=L'-James T. Stievater - Parsons Brinckerhoff Date

CC: File PB-Chris Spann Document Control @HGBM-JV.com [email protected]

Page 2: PARSONS NORTH TERMINAL PROJECT … · LOUIS ARMSTRONG NEW ORLEANS INTERNATIONAL AIRPORT NEW ORLEANS, ... Note that the W30x90 beam has moment connection at each end so needs to be

Attachments: Partial sheets:

None

Reissued full sheets:

NT SG 5231

By: Kiran Tamvada Engineer

DESIGNER SUPPLEMENTAL INSTRUCTIONS DSI NO. WPM-DSI-0031 DDAATTEE:: 0077//2255//22001166

PPRROOJJEECCTT NNAAMMEE:: NNOOAABB PPrroojjeecctt ## 88991100--0011223333

LLoouuiiss AArrmmssttrroonngg NNeeww OOrrlleeaannss IInntteerrnnaattiioonnaall AAiirrppoorrtt NNoorrtthh TTeerrmmiinnaall DDeevveellooppmmeenntt PPrrooggrraamm PPhhaassee 11

Note: if the following information is deemed to have an impact on GMP Price or time, submit a proposal for Owner approval before proceeding with this DSI. If approved by Owner, the resulting contract change will be incorporated in the next formal Change Order.

11.. Additional clarifying detail provided for a few joist supports at concourses

Page 3: PARSONS NORTH TERMINAL PROJECT … · LOUIS ARMSTRONG NEW ORLEANS INTERNATIONAL AIRPORT NEW ORLEANS, ... Note that the W30x90 beam has moment connection at each end so needs to be

From: Dean Schuerman To: Cedric Johnson CC: Daniel Taylor, David Daileda, Jason Levy, David Zelig, Sara Delahoussaye, Raymond Symanski, Kiran Tamvada, Bret Busse,

Kevin Anderson

RFI 00679 From Kiet Vo

To Dean Schuerman

CC Frans Labranche, Morris Wallace, Cedric Johnson, Cindy Shields, David Daileda, Sara Delahoussaye, Kiet Vo, Cinda Denoux, Daniel Taylor, Jason Levy, Raymond Symanski, Scott Rydin

Project North Terminal Project - NOLA (MSY) Construction Subject Volume 3.1/NT SC 1221A/Concourse B & C /Lower Roof - Special Joist to Beam Connection Required

Subject: Volume 3.1/NT SC 1221A/Concourse B & C /Lower Roof - Special Joist to Beam Connection Required Date Required: 2016-07-25 Cost Impact: Potentially Cost Amount: Question: At the concourse low roof the 'kinked' W30x90 beams and the 'skew' W24x55 beams highlighted on the attached plan are set at

underside of roof deck level. Note that the W30x90 beam has moment connection at each end so needs to be set at this underside of roof deck level. MBJ connection details are also based on these beam elevations. The incoming joists will need a special seating bracket added to the support beams to allow for the joist to bear on the seat and field weld. Please provide suitable details. Note that revising any beam levels in this roof area will create additional detailing rework hence it is preferred that a special detail is developed for the connection of the roof joists.

Suggestion: Answer: NOTE: An RFI response cannot change the requirements of the Contract Documents. Response By: Kiran Tamvada Date: 07/25/2016 CCAT Response: See attached WPM-DSI-0031 for the special detail requested at these joist locations.

Cost Impact: None Pursuant to paragraph 4.2.14 of the General Conditions of the Contract, the Engineer of Record provides the following response to the referenced RFI. This RFI response does not constitute a Construction Change Directive, and does not authorize changes in project scope, contract price or time. Refer also to Article 7 of the General Conditions and for AIP work to Article 50-16 of the FAA General Provisions. RFI’s are to be returned for reconsideration if there is a cost or schedule impact.

R E Q U E S T F O R I N T E R P R E T A T I O N

Page 4: PARSONS NORTH TERMINAL PROJECT … · LOUIS ARMSTRONG NEW ORLEANS INTERNATIONAL AIRPORT NEW ORLEANS, ... Note that the W30x90 beam has moment connection at each end so needs to be

AA BB

AA

AA

S

STEEL JOIST LL3x3x1/4 FOR S<= 4'-0"L5x3x1/4 (LLV) FOR4'-0" < S <= 6'-6"

L3x3x1/4 FOR L<= 4'-0"L5x3x1/4 (LLV) FOR4'-0" < L <= 6'-6"

PLAN

CL PANELPOINT

A

NOTE 2

STEEL ANGLES

SECTION A-A

PROVIDE BRACES WHERE "A"DIMENSION EXCEEDS 3",REFER TO DETAIL TITLED"TYPICAL STIFFENING OF JOISTFOR CONCENTRATED LOADS"

NOTES:1. REFER TO ENGINEER FOR OPENINGS LARGERTHAN 6'-6".2. THE OPENINGS IN THE STEEL DECK ARE NOT TOBE CUT AND REMOVED UNTIL THE OPENING ISNEEDED.

SECTION B-B

STEEL JOIST TOP CHORD

CUT AND CHIP VERTICAL LEG OFANGLE TO CLEAR TOP CHORD OFSTEEL JOIST

3/16

3/161/2" MAXIMUM

BOTTOM OF DECK

REFER TO PLAN

AND ASSOCIATES, INC.© COPYRIGHT WALTER P. MOORE

2010

05200-RF-SJST-06

SECTION B

STEEL JOIST TOP CHORD

L4x4x3/8 CUT AND CHIP VERTICAL LEG OFANGLE TO CLEAR TOP CHORD OF STEEL JOIST.ATTACH TO TOP CHORD OF STEEL JOIST ATPANEL POINTS

3/16

1/2" MAXIMUM

CL OF BEAM AND COLUMN

PANEL POINT

STEEL BEAM

STEEL COLUMN

CAP PLATE

3/8" STIFFENER PLATES

3/16TYPICAL

BRACE L2 1/2x2 1/2x1/4

PROVIDE BOLTEDCONNECTION ASREQUIRED STEEL COLUMN

CAP PLATE, AS REQUIRED(1/2" MINIMUM)

STIFFENEREACH SIDE OFBEAM

STEELJOIST

BRACE

CL OF COLUMN CL OF BEAM CONNECTION

NOTE 3

ELEVATION

REFER TO ARCHITECTURAL DRAWINGSAND GENERAL NOTES FOR ROOFCONSTRUCTION

STEEL ROOF DECKREFER TO PLAN

SECTION A

SECTION C

3/4"

MA

XIM

UM2" MINIMUM

SECTION C

SECTION B

3/16

3 SIDES,TYPICAL

BOTTOM OF DECK

REFER TO PLAN

NOTES:1. INSTALL ALL BRACES BEFORE STEEL DECK IS INSTALLED.2. REFER TO TYPICAL DETAILS FOR BRACE CONNECTIONS TO STEEL JOISTS.3. STEEL JOISTS BRIDGING AS REQUIRED BY STEEL JOIST INSTITUTE SPECIFICATIONS AND AS SHOWN ON PLAN.4. STEEL JOISTS BEARING DEPTH SHALL BE BASED ON STEEL JOIST INSTITUTE REQUIREMENTS.

PROVIDE BOLTEDCONNECTION, ASREQUIRED

WEB CONNECTION

PROVIDE WELDS,AS REQUIRED

AND ASSOCIATES, INC.© COPYRIGHT WALTER P. MOORE

2012

05200-RF-SJST-X15

NO

TE

4

0

6" MAXIMUMFROM JOISTTO BRACE

NOTES:1. REFER TO PLAN OR DETAILS FOR BEAMS

REQUIRING COLLECTORS.2. WT 2.5x8 FOR K SERIES JOIST WT 5x7.5 FOR LH

AND DLH JOIST. ADJUST AS NECESSARY FOROTHER JOIST SEAT DEPTHS.

3. ROTATE WT AS REQUIRED TO MATCH DECKCROSS SLOPE.

4. AT CONTRACTORS OPTION, PROVIDE BUILT UPPLATE SECTION IN LEIU OF WT. SECTION A-A

WT DECK SUPPORTWELD STEEL DECK TO WT, REFER TO GENERALNOTES FOR ATTACHMENT

3/16 3-12

3/16 3-12

2" CLEAR

NOTE 2ELEVATION

REFER TO PLAN

TOP OF ROOF DECK

AND ASSOCIATES, INC.© COPYRIGHT WALTER P. MOORE

2010

05200-FL-SJST-18

CONT LIGHT GAGE CLOSURE/RIDGE PLATEREF 9/SG 5231

NOTES:1. ATTACHMENT PATTERN AND FASTENERS SHALL BE PER GENERAL NOTES.2. RIDGE PLATE DECK ATTACHMENT TO DEVELOP FULL DIAPHRAGM STRENGTH OF DECK GAGE PER PLAN WITH A 5'-0" MAXIMUM SPAN.3. RIDGE PLATE GAGE SHALL BE NO LESS THAN THE DECK GAGE OF THE DECK BEING SPLICED.

AND ASSOCIATES, INC.© COPYRIGHT WALTER P. MOORE

2012

05200-RF-SJST-13

ROOF GIRDER

SLOPED JOISTSEAT

FASTENER CENTER TOCENTER DISTANCE NOT TOEXCEED RIB SPACING

CONTINUOUS LIGHTGAGE RIDGE PLATE

0

AND ASSOCIATES, INC.© COPYRIGHT WALTER P. MOORE

2011

05300-RF-STLDK-01

DETAIL A

CL BEAM OR GIRDER

REFERENCEELEVATION

USE FLAT BAR TOACHIEVE SLOPE

0

1/2"1/2"

000

1/2"1/2"

DETAIL A DETAIL AALTERNATE

1/8" BENT PLATECONTINUOUS

STEEL DECK

WELD STEEL DECK TOPLATE

1/8 1 1/2-12 1/8 1 1/2-12

NOTE: THIS DETAIL APPLIES WHEN THE DECK SLOPE EXCEEDS 5% .

BOT OF DECK

JOIST SEAT

1/2" SEAT PLATE TOACCOMMODATE THEJOIST SEAT

3/8" STIFFENERWITH 1/4" FILLETALL 3-SIDES NS & FS

DSI-0031

KEY PLAN

REVISIONS

FILE LOG

ACTIVITY

Draw

Design

Manager

Check

STAMP

© LEO A DALY Company 2014

PROJECT NO.

BY

A

B

C

D

1

A

B

C

D

2 3 4 5

THE NEW ORLEANSAVIATION BOARD

CRESCENT CITYAVIATION TEAM

1 GALLERIA BOULEVARD #1516METAIRIE, LA 70001T (504) 303.7535 / F (504) 841.2229

A JOINT VENTURE

1 2 3 4 5

CONFORMED SET 02-08-2016

7/2

5/2

016

12

:43:5

3 P

M

PROJECT ADDRESSKENNER, LOUISANA ZIP

CITY OF NEW ORLEANS

STEEL ROOF FRAMING TYPICALDETAILS

NT SG 5231

NORTH TERMINALLOUIS ARMSTRONGNEW ORLEANSINTERNATIONALAIRPORT

051-10250-000

02-08-2016

BB

RCW

GT

BH

THE NEW ORLEANS AVIATIONBOARD, 900 EAST AIRLINEDRIVE, KENNER, LA 70062

ISSUED FOR CONSTRUCTION

S01-12002-04

VOLUME 3.1

1" = 1'-0"2

TYPICAL ROOF OPENINGFOR JOIST CONSTRUCTION

NO SCALE4EXAMPLE CANTILEVERED BEAM WITH JOIST AT WIDE FLANGE COLUMN

NO SCALE8

TYPICAL DECK SUPPORT DETAILAT DECK DIRECTION TRANSITION

NO SCALE9

TYPICAL DECK RIDGE PLATE DETAILINTERIOR STEEL BEAM

NO SCALE7

TYPICAL SLOPING STEEL DECK SUPPORTON BEAM WITH VERTICAL WEB

Signature: Date:

NO. DESCRIPTION DATE

C ADDENDUM 3 07-24-2015

WPM-DSI-0031 07-25-2016

NO SCALE10

JOIST FRAMING AT KINKED BEAMAT CONCOURSES

WPM­DSI­0031DSI­0031 07­25­2016