palomino valley gid water sources truckee meadows fire protection district

14
PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

Upload: johana-thruston

Post on 01-Apr-2015

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

PALOMINO VALLEY GID WATER SOURCES

Truckee Meadows Fire Protection District

Page 2: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

Suppression Water Sources

2 Locations authorized for TMFPD use: SR445 (Pyramid Hwy) and Ironwood Road

Located across the Horse Corral. 5105 Wayside Drive (PVGID yard)

Take Whiskey Springs road about two miles from SR445 to Grass Valley road (just past the BLM Station). Turn left on Grass Valley road and Wayside drive is about ¼ mile on the right.

Page 3: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

Suppression Water Sources

SR445 and Ironwood Road

Page 4: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

Suppression Water Sources

5105 Wayside Drive

Page 5: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District
Page 6: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

SR445 and Ironwood Road Water Source

Gates are equipped with TMFPD combination locks intermingled with PVGID pad locks

Operation Overview:

Caution: make sure that you have the correct valves on the fill pipes at this location open and/or closed or you could get VERY wet. If you are filling a Water Tender that has a top fill hatch and have a spotter to help getting under the overhead fill, you may consider using the overhead fill pipe. This location makes about 390 GPM. There are two gate valves on the fill tower. The upper valve controls the overhead fill and the lower controls the 2.5” hose connection. To fill by hose you must make sure the upper valve is off and lower valve to hose connection is at least partially open before starting the well. Mounted on the block wall by the fill pipe is a controller switch that starts the generator which in turn powers the well. Approximately 1 minute after the generator starts the well will turn on. Once filled, turn the electric switch back to off. The well will shut down but the generator will run for a cool down cycle then will automatically shut down.

Page 7: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

SR445 and Ironwood Road Water Source

This site has two gates; one for entry and one for exiting.

Enter Ironwood road fill site from the East gate so your control panel is close to the fill valves.

Page 8: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

SR445 and Ironwood Road Water Source

Connect fill hose to the LOWER valve and to your apparatus. Open intake valve on apparatus.

Make sure upper valve is off and lower valve is partially open.

Page 9: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

SR445 and Ironwood Road Water Source

Turn control switch to “on” and push the “reset” button. This turns the generator on and the well pump will come on within

about 1 minute.

Page 10: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

SR445 and Ironwood Road Water Source

Regulate the fill valve as required for filling. This well produces 390 GPM. It is OK to create some back pressure on the well to regulate your water flow but try to avoid deadheading the water flow completely.

Once your apparatus is filled turn the control switch to the “off” position. The well will shut off and generator will shut down automatically after a cool down period.

Disconnect hoses.

Page 11: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

SR445 and Ironwood Road Water Source

Other Well equipment at the Ironwood site.

Do not do anything with any of this other equipment at the site.

Page 12: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

5105 Wayside Drive Water Source

This water supply to the tank is controlled automatically and all you

need to do is hook up to the 2.5” connection and open/close the ball

valve

Page 13: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

Helo Dip Sites

Helo dip sites could also be established at both fill locations, but the Wayside Dr. location should be considered first because it is away

from public roads and the water system is controlled automatically. Hose lines could be stretched from the water fill connections at each site to a remote dip site if there are personnel to stay at the sites to

keep the tanks filled.

Page 14: PALOMINO VALLEY GID WATER SOURCES Truckee Meadows Fire Protection District

Questions

Please direct any questions to Wayne Cirone.

Thank you