Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory http://hightech.lbl.gov Data Center Energy Research and Demonstrations Critical Facilities Roundtable Meeting - March 25, 2005

Upload: dwain-dennis

Post on 27-Dec-2015

218 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

Page 1

Public Interest Energy Research (PIER)California Institute for Energy & Environment (CIEE)

Bill Tschudi Lawrence Berkeley National Laboratory

http://hightech.lbl.gov

Data Center Energy Research and Demonstrations

Critical Facilities Roundtable Meeting - March 25, 2005

Page 2: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

• Benchmarking and Best Practices identification• Research-directed benchmarking• Self-benchmarking protocol

• Improve uninterruptible power supplies (UPS)

• Develop performance metrics (Computing vs. Watts)

• Improve power supplies in IT equipment

• Adding demonstration projects

2

Current LBNL data center related activities

Page 3: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

Wide range of efficiencies:For example: data center HVAC

0102030405060708090

100

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Facility Identifier

W/S

q.F

t.

Current Computer Load Projected Computer Load

Average 39.3

Average ~25

HVAC (as a % of total load)

0%

10%

20%

30%

40%

50%

60%

1 2 3 4 5 6 7 8 9 10 11 12

Data Center Identifier

% o

f to

tal l

oad

3

HVAC effectiveness varies

Page 4: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

Load intensity is increasing in our supercomputing center

4

LBNL NERSC Facility Computer Power Density

0

10

20

30

40

50

60

70

80

90

100

25-Oct-2002 17-Aug-2004 14-Feb-2005

W/s

f

Page 5: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

5

Factory Measurements of UPS Efficiency

80%

85%

90%

95%

100%

0% 20% 40% 60% 80% 100%

Percent of Rated Active Power Load

Eff

icie

nc

y

Flywheel UPS

Double Conversion UPS

(tested using resistive loads)

Efficiency ranged from 86% to 97% at peak load, but efficiency under typical operating loads ranges from 81% to 97%

Measured UPS Efficiency

Typical operating range

Page 6: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

6

Data Centers – UPS measured vs mfg. efficiencyMeasured and Manufacturer-Reported UPS

Efficiency at Nominal Load

89%90%91%92%93%94%95%96%97%98%99%

1 2 3 4 5 6 7

UP

S E

ffic

ien

cy

Measured Efficiency

Manufacturer-reported efficiency

• Manufacturer’s reported efficiency in product literature consistently within 1% of measured performance

• Unfortunately, manufacturers often do not report efficiency in typical data center operating range (30% - 50%)

Page 7: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

Power Supply Findings:

7

Measured Server Power Supply Efficiencies

45%

50%

55%

60%

65%

70%

75%

80%

85%

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

% of Nameplate Power Output

% E

ffic

ien

cy

80 Plus

Non-PFC Power Supplies

PFC Power Supplies

Typical operating range

Page 8: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

Power Conversion Conclusions:

8

There is a wide range of efficiency for both UPS and power supplies and they have lower part load

efficiency (where most operate)

Server power supplies are less efficient than PC’s

Computer manufacturers caution that setting criteria for power supplies may lead to “gaming” of the rest of the power supply chain

Elimination of electric power conversion(s) could be a large impact on energy use

Page 9: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

• Heat removal from servers without fans

• DC powering rack of computers• IT/facilities design process for new

supercomputer center–

9

Data center demonstration projects

Page 10: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

• Start-up company – Nisvara has patented technology using carbon micro fiber to efficiently conduct heat in one direction to a point where it can be transferred to air or liquid.

• Seeking “industry partner(s)” to provide servers and rack systems to modify to

use this technology. Also seeking a demonstration site.

10

Heat removal without fans demonstration

Page 11: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

• Discussions with server manufacturers, processor and other component manufacturers

• www.nisvara.com

11

Heat removal without fans …

Page 12: Page 1 Public Interest Energy Research (PIER) California Institute for Energy & Environment (CIEE) Bill Tschudi Lawrence Berkeley National Laboratory

• Demonstrate energy savings using commercially available DC power at rack level to eliminate or consolidate a power conversion

• Various potential configurations and manufacturers

• Seeking “industry partner(s)” to provide servers to modify to use this technology. Also may involve a demonstration site.

• Potential overlap with heat removal demo–

12

DC powering demonstration