G P G 10 24 045 1 ABRAND Description EFFICIENCY NOMINAL CAPACITY HEATING INPUT VOLTAGE Revision

G = Goodman Packaged Gas 10 = 10 SEER 24=2 Tons 045=45 MBTUH (INPUT) 1 = 208-230/1/60 A = Initial 12 = 12 SEER 30=2 1/2 tons 070=70 MBTUH (INPUT) 3 = 208-230/3/60 B = Rev 1

36=3 Tons 090=90 MBTUH (INPUT) C = Rev 242=3 1/2 Tons 115=115 MBTUH (INPUT)48=4 Tons 140=140 MBTUH (INPUT)60=5 Tons

Model Number Chart

Page 4: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

SERIAL NUMBER

0409456678

04 is for the year it was built

09 is for the month it was built

Page 5: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

47” Wide

Fits in a standard size Pickup!

12 & 10 SEER Packaged Gas Electric

Page 6: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

12 & 10 SEER Packaged Gas Electric

• Convenient access panels to the compressor

• High-efficiency Scroll and Energy-efficient reciprocating compressor.

• Copper tube/aluminum fin coil.

• Liquid line filter drier.

• Fully charged R-22 system.

• Louvered Guard Protection

Cooling Features:

Page 7: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

10 & 12 SEER Packaged Gas Electric

• Convenient access panels to the Evaporator coil and control section.

• Direct spark ignition system, which includes a microprocessor based control for the entire ignition sequence, all blower operation and all safety circuits.

• Diagnostic Indicator provided for trouble shooting system faults.

Control Features:

Page 8: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Design Objectives• 2 – 5 ton Single Phase

• 3, 4 & 5 ton Three Phase

• 12 &10 SEER Cooling, 80% AFUE Heating

• Capable of expansion to higher SEER ratings

• Convertible

• Easy Access Service Panels

Architectural Gray

Page 9: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

12 & 10 SEER Packaged Gas Electric

Heating Features:• Convenient access panels to the heating section. • Redundant gas valve, natural gas and easy conversion to propane.• Power-assisted combustion.• L.P. Conversion Kit Available• 12 & 10 SEER units offer a durable, T-140 Aluminized Steel tubular heat exchanger.•California Low Nox Approved

Page 10: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Wrinkle-bend Process

• Manufacturing stress including wall-thinning is minimized

• Wrinkles are placed precisely where we want them

• Wrinkles promote turbulence to aid heat transfer and efficiency

We begin with T-140 Aluminized Steel tubes

Page 11: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Dual-diameter/Muffler-joint

• 1-3/4” diameter fits inside a 1-1/4” diameter

• Tubes are joined with a proprietary process

• Velocity of combustion products is optimized

• Efficiency is maximized

We apply a patented process to join tubes

Page 12: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

1,000°F

300°F

Tube can grow in length and diameter Growth is uniform at the cross-section No opportunity for stress-cracks

Non-uniform thermal growth Eyelets can pop Stress-cracks can form

Tubular Technology Renders Clamshell Obsolete

300°F300°F

1,000°F800°F

110°F300°F

Page 13: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

INSTALLATION

Page 14: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CLEARENCE FROM COMBUSTIBLE

MATERIALS

Page 15: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CURB INSTALLATION

Page 16: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

RIGGING

Page 17: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

PIPING

Page 18: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CONDENSATE DRAIN

Page 19: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

FLUE HOOD & BUG SCREEN

Page 20: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

12 & 10 SEER Packaged Gas Electric

McDaniel MetalsPart Number Description

PGC101/102 Roof Curb PGED101 Downflow Economizer 2 - 3 1/2 TonPGED102 Downflow Economizer 4 - 5 TonPGEH101 Horizontal Economizer 2 - 3 1/2 TonPGEH102 Horizontal Economizer 4 - 5 TonPGMDD101 Manual 25% Fresh Air Damper 2 - 3 1/2 Ton Downflow ApplicationPGMDD102 Manual 25% Fresh Air Damper 4 - 5 Ton Downflow ApplicationPGMDH101 Manual 25% Fresh Air Damper 2 - 3 1/2 Ton Horizontal ApplicationPGMDH102 Manual 25% Fresh Air Damper 3 - 3 1/2 Ton Horizontal ApplicationPGMDH103 Manual 25% Fresh Air Damper 4 - 5 Ton Horizontal ApplicationPGMDMD101 Motorized 25% Fresh Air Damper 2 - 3 1/2 Ton Downflow ApplicationPGMDMD102 Motorized 25% Fresh 4 - 5 Ton Downflow ApplicationPGMDMH101 Motorized 25% Fresh Air Damper 2 - 3 1/2 Ton Horizontal ApplicationPGMDMH102 Motorized 25% Fresh Air Damper 3 - 3 1/2 Ton Horizontal ApplicationPGMDMH103 Motorized 25% Fresh Air Damper 4 - 5 Ton Horizontal ApplicationSQRPG101 Square to Round Adapter w/ 16" Round Downflow Application 2 - 3 1/2 TonSQRPG102 Square to Round Adapter w/ 18" Round Downflow Application 4-5 TonPGFR101/102 Internal Filter Rack 2 - 5 Ton

Page 21: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

10 & 12 SEER Packaged Gas Electric

Blower Features:

• Convenient access panels to the blower section.

• Filter rack included on 12 SEER large (4 &5 ton) chassis.

• Easy removal of blower with two screws.

• Multi-speed evaporator blower.

• Fully insulated with blankets of fiberglass.

Page 22: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Shipped with four panels

Base Features:• 042 Aluminized Steel Bottom/Base Pan

• 2” High Base Rails

12 & 10 SEER Packaged Gas Electric

Page 23: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

DUST COVER INSTALLATION

Page 24: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

RECOMMENDED FILTER SIZES

Page 25: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Electrical

• 208/230 Volt Power connections and 460 Volt available in 5 Ton Cool only model

• Single Phase and Three phase models available

• Maximum Over current Protection determined by model

Page 26: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Wiring• All wiring should be made in accordance with

the National Electrical Code. • Wire sizes and over current protection should

be determined from the unit nameplate ampacity.

• Wire sizes should not be smaller than recommended by these two sources.

• All exterior wiring must be within approved weatherproof conduit.

• The unit must be permanently grounded in accordance with local codes.

Page 27: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

HIGH VOLTAGE WIRING

Page 28: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

LOW VOLTAGE WIRING

Page 29: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING THE COMPRESSOR

Page 30: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING CONTACTOR

Page 31: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING CAPACITOR

Page 32: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

COMPRESSOR NORMINCLATURE

Page 33: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

COMPRESSOR DIAGONSTICS

Page 34: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

TESTING FOR GROUNDED

COMPRESSOR

Page 35: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

FLOW RATER

Page 36: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

EVACUATION

Page 37: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

HEATING SIDE OF GPG

Page 38: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING GAS PRESSURE

Manifold Outlet Gas Pressure

Natural…. Min. 3.2” W.C., Max 3.8” W.C.

Propane….Min. 9.7” W.C., Max. 10.3” W.C.

Page 39: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING BURNERS

Page 40: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Burner

Page 41: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

BURNER BOX REMOVAL

Page 42: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING BURNERS

Page 43: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING LIMIT SWITCH

Page 44: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Pressure Switch Check

• Meter on AC Voltage Setting ; between Quick Connect on Pressure Switch and Ground

• Prior to Operation check for open side of Pressure Switch (No Voltage Present)

• When Pressure Switch Closes 24 Volts should be present on N/O side

• Issue: Watch for switch bounce on windy days

• Issue: Watch for P.S. drop-out for low pressure

Page 45: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING PRESSURE SWITCH

Page 46: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

CHECKING PRESSURE SWITCH

Page 47: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

PRESSURE SWITCH

Page 48: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

INDUCED DRAFT BLOWER

Page 49: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Understanding ECM Motors

Page 50: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Understanding ECM Motors

• What does ECM mean?• How does the ECM work?• Variable Speed vs

Constant Volume.• What is PWM• How does the ECM sense

static pressure?• Troubleshooting ECM

motors.

Page 51: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

BLOWER MOTOR & HOUSING

Page 52: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Electronic Controls

Page 53: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

B18099-18 Control

• B18099-21 Has Green Diagnostic LED

• B18099-21 Cannot be used alone; must be used with B18099-22 Control

• B18099-21 Control is set up for 50Hz Operation and for use in Europe (CE Mark)

Page 54: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Control Environment

• +80 to -40 Degrees Celsius (+176 to -40 F)

• 10% to 95% R.H. Non-Condensing• 98 to 132VAC Line Voltage• 18 to 30VAC Control Voltage• Frequency - 60Hz• UL & cUL Approved

Page 55: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

General Functions

• “W” Input On (Call for Heat)– Checks to see pressure switch open– Turns on Inducer– Pressure Switch Closes; 15 Second Pre-Purge– Starts Sparking & Gas Valve Turns On for 7 Seconds – Flame Sensed Anytime During Spark– Gas Valve Stays On– Blower Comes On after 30 Second Delay

• “W” Input Off (Call for Heat Satisfied)– Gas Valve De-Energizes Immediately– Inducer Remains on for 29 Second Post Purge– Indoor Blower De-Energizes after Selected Blower Off

Delay

Page 56: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

General Functions Continued....

• Single Compressor Mode (Tab is not Broken)– “Y” Input On (Call for Cooling)

• 3 Minute Anti-Short Cycle Timer from the time the compressor was last on.

• Cooling Speed Blower after a 7 second delay

– “Y” Input Off (Call for Cool Satisfied)• Cooling Speed Fan Off after 60 Second Delay

• Dual Compressor Mode (Tab is Broken)– 1st Stage Compressor is Energized Externally– “Y” Input On for 2nd Stage Cooling after 7 Second Delay– “Y” Input Off ; Cooling Speed Fan off after 60 Second Delay

Page 57: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

General Functions Continued....

• “G” Input On (Call For Fan)– Fan Immediately on Heat Speed

• “G” Input Off– Fan Immediately Shuts Off

• If “Y” input Occurs During “G”– Blower Switches to Cooling Speed

• If “W” Occurs During “G”– Blower off when Heat Blower On Delay Begins– Continuous Fan Operates while control is in Heat Mode

Lockout• Test/Speed-Up Bypasses Compressor Short-Cycle Timer

– If Shorted for Over 4 Minutes ; Control Ignores = Operates Normal

Page 58: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Diagnostic Codes• Steady On = Normal Operation in Standby• 1 Flash = Lockout for Ignition Failure or Flame Dropouts

– 3 Trials for Ignition or 5 Flame Losses • 2 Flashes = Pressure Switch Open with Inducer On• 3 Flashes = Pressure Switch Stuck Closed with Inducer Off• 4 Flashes = Limit Switch Open

– Heat Speed Blower and Inducer On Until Limit Closes– Blower Runs thru Off Delay; Inducer runs thru 29 Second Post-Purge

• 5 Flashes = Flame Detected with Gas Valve Off– Blower and Inducer Both On Until No Longer Sensed– Control Locks out But Senses Limit and Flame– Control is Reset By Removing Power or after 1 Hour Automatically

• 6 Flashes = Compressor Delayed for Short Cycle/Staging Timer• Status Light Off = Board Hardware Fault

Page 59: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Flame Sense Checking

• Digital Meter set for lowest uA Setting• Meter in series with Flame Sense Rod Wire• Control must read a minimum of .5uA during

flame sensing period• Average current reading is around 3-5uA.• Control constantly monitors Flame during

heating operation• Issue: Flame Sense Rod gets corroded ; Clean

w/ steel wool• Issue: Flame Rod not situated in Flame

Correctly

Page 60: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

Ground Check

• Meter set to Ohms or Resistance Setting• Place Meter from P1-6 or COM quick

connect to chassis ground• Reading should be near Zero ohms• Issue: COM Quick Connect Loose ;

causes board resetting when blower starts

• Issue: Flame Sensing problems if improper grounding in system

Page 61: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

GPG TROUBLESHOOTINGTHEORY OF OPERATION

Control of heating, cooling, and fan functions in response to a standard thermostat

Direct spark ignition using a microprocessor to control timing, flame sensing, and ignition

retries

Monitoring of system pressure switch and limit switch

Control of gas valve, indoor fan, and induced draft motor based on the thermostat demand

and status of safety inputs

Control of compressor contactor

Diagnostic indicator to provide information on power to the control and control status

Page 62: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

GPG TROUBLESHOOTINGSummary of Timing Functions (in

seconds)Function Signal Name Delay-On Delay-Off

Heat Speed MV (1) 30 120, 135,150 (2)

Cool Speed Y 7 60

Compressor Y 60 (3) 180 (4)

Induced Draft Induced Draft 15 (5) 29

1. Heat speed delay on and off occur only after flame has been sensed and main valve (MV) is energized

2. Selectable with jumpers

3. Indicates timing when “Two Stage Comp” tab is broken off, timer becomes delay on make

4. Indicates timing when “Two Stage comp”tab is not broken off, timer becomes compressor lock out between cycles(I.e. Minimum timing between compressor

cycles)

5. Prepurge timing (not delay on )

Page 63: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

GPG TROUBLESHOOTINGInputs

Limit Switch –The limit switch is connected to control pins 4 and 5. The limit switch is connected is electrically between fused 24 VAC and the

thermostat R

Pressure Switch-The pressure switch is connected on pins 6 and 8. The pressure switch “W and the gas valve relay contacts

Thermostat call for Heat “W”-24 VAC thermostat input. Connection via pin 10

Thermostat call for cool “Y”- 24 VAC thermostat input connections via pin 11

Thermostat call for fan “G”- 24 VAC thermostat inputs. Connection via pin 7

Flame Sense- Open circuit flame sense voltage shall be approximately 100 VAC . The control requires at least .5 microamperes DC flame current to

guarantee flame is sensed

Page 64: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630
Page 65: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630
Page 66: PACKAGE UNITS GPG 10 AND 12 SEER. TECHNICAL SUPPORT 888-593-9988 MARK STOKES 713-861-2500 EXT. 630

12 & 10 SEER Packaged Gas Electric Leading Warranties:

• 12 SEER offers an Aluminized Steel Heat Exchanger with a 20Year limited Warranty and10 Year Limited Warranty on the Compressor and Parts.

• 10 SEER offers an Aluminized Steel Heat Exchanger with a 20Year limited Warranty and 5 Year Limited Warranty on the Compressor and Parts.