    To b e l e f t w i t h t h e u s e r

    Installation and Instructions for Use

    Outdoor

    Sensor

    www.glow-worm.co.uk

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    2/24

    www.glow-worm.co.uk2

    Customer Service: 01773 828100 Technical Helpline:01773 828300

    General and Sales enquiries: Tel. 01773 824639 Fax: 01773 820569

    Please read these instructions and follow them carefully for the safe and economical use

    your boiler. On completion of installation leave the instructions with the user.

    General

    Benchmark places responsibilities on both manufacturers and installers. The purpose is toensure that customers are provided with the correct equipment for their needs, that it is installed,commissioned and serviced in accordance with the manufacturers instructions by competentpersons and that it meets the requirements of the appropriate Building Regulations. The BenchmaChecklist can be used to demonstrate compliance with Building Regulations and should be provideto the customer for future reference.Installers are required to carry out installation, commissioning and servicing work in accordance withe Benchmark Code of Practice which is available from the Heating and Hot water Industry Counc

    who manage and promote the Scheme.Visit www.central heating.co.uk for more information.

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    3/24

    www.glow-worm.co.uk

    Contents

    Contents PageGeneral information 3Kit contents 5

    Section (A)Installer important information 6Outdoor sensor location 7Installation 9

    Section (B)Conguring the outdoor sensor 13

    Section (C)Conguring the outdoor sensor 22with external Glow-worm Climaproor Climastat controls

    General

    The outdoor sensorenables weathercompensation by providing an advanced

    level of modulation, achieving an additionlevel of efciency. This control compensafor the outside temperature by modulatinthe lower radiator temperatures in warmeweather and higher radiator temperaturescolder weather.

    The outdoor temperature compensation ieasily congured using either the boilersinterface controls or the interface of anexternal Glow-worm Climastat or Climaprroom control (if tted). Optimum comfortand efciency is achieved when used inconjunction with a Climastat or Climapro(in modulating mode). The outdoor senso

    can also be used with a conventional on/thermostat.

    General Information

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    4/24

    www.glow-worm.co.uk4

    The installation and the commissioning ofthe Outdoor sensor has to be carried out bya competent person in accordance with the

    current regulations.The maintenance and the repairing of theOutdoor sensor will also require the use of acompetent person.

    Documents

    Please keep these instructions as well as anydocuments enclosed, for future reference.

    We accept no liability in case of damage dueto the non-compliance of these instructions.

    General Information

    Application

    The outdoor sensorcontrols the heatingdemand for the appliance, which is

    dependant on the outdoor temperature.

    Any other use is considered as inappropriateand is forbidden.

    The user will be responsible for any damagecaused by any other use.

    Servicing

    Clean the case of the outdoor sensor withdamp soapy cloth, make sure that no watergoes inside the outdoor sensor.

    Do not use any abrasive cleaning productas they could damage the housing or plasticcase.

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    5/24

    www.glow-worm.co.uk

    General Information (A) Installer important informa

    Diagram 1

    Recycling

    The Outdoor Sensor comprises of manyrecyclable parts and should be disposed of

    according to the current WEEE regulations.

    The packaging should also disposed ofaccording to the current regulations.

    Kit contents Refer to diagram 1.Kit part number 0020040796.

    Safety instructions andregulations

    This outdoor sensor is tested and certica

    for safety and performance. It is, thereforimportant that no alteration is made tothe outdoor sensor, without permission, inwriting, from Glow-worm.

    Any alteration not approved by Glow-worcould invalidate the certication, appliancwarranty and may also infringe the currenissue of the statutory requirements.

    Safety instructions

    WARNING:

    Incorrect installation can cause electric shand damage to the outdoor sensor.

    13663

    www.glow-worm.co.uk

    Outdoorsensor

    INSTALLATION AND

    INSTRUCTIONS FOR

    USE LITERATURE.

    LABEL

    OUTDOOR

    SENSOR

    EDGE

    CONNECTOR

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    6/24

    www.glow-worm.co.uk6

    Regulations

    When installing and commissioning theoutdoor sensor, the regulations below shall

    be observed in their current version.

    Where no specic instructions are given,reference should be made to the relevantBritish Standard Code of Practice.

    Where no British Standard exists, materialsand equipment should be t for their purpose

    and of suitable quality and workmanship.The installation of this outdoor sensor mustbe carried out by a competent person inaccordance the rules in force in the countriesof destination. Manufacturers instructionsmust not be taken as overriding statutoryrequirements.

    Mandatory WARNING for EECcountries

    The CE mark on this appliance shows

    compliance with:

    Directive 89/336/EEC on the approximationof the Laws of the Member States relating toelectromagnetic compatibility.

    Directive 73/23/EEC on the harmonisationof the Laws of the Member States relating to

    electrical equipment designed for use withincertain voltage limits.

    (A) Installer important information

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    7/24

    www.glow-worm.co.uk

    Technical data

    Power supply 5V

    Power consumption

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    8/24

    www.glow-worm.co.uk8

    (A) Outdoor sensor location

    E

    W

    S

    N

    1m

    2/3

    1/3

    1m

    1m1m

    1

    2

    3

    4

    1

    2

    31/3

    OUTDOOR SENSOR POSITION

    (For buildings higher

    than three floors)

    OUTDOOR SENSOR POSITION(For buildings three floors or less)

    OUTDOOR SENSOR

    POSITION(For buildings three

    floors or less)

    2/3

    Diagram 2

    13662

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    9/24

    www.glow-worm.co.uk

    COVERSEAL

    ELECTRICAL SEALING

    GLAND

    BACK BOX

    (A) Installation

    Diagram 3 Diagram

    BACK BOX

    Refer to diagram 3. Remove the front cover,seal and electrical sealing gland.

    Choose the location of the outdoor sensorefer to page 6. Fit the back box to the wa

    see diagram 4.

    13

    666

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    10/24

    www.glow-worm.co.uk10

    ELECTRICAL

    CONNECTION

    ELECTRICAL

    SEALING

    GLAND

    (A) Installation

    WARNING:Isolate the boiler from theelectrical supply. A competant personshould make the electrical connections.

    Use a cable that complies with thespecications given in Technical data, page7. Route the cable from the outdoor sensorto the boiler electrical cartridge at the boiler,refer to the literature supplied with yourboiler for location and access.

    Refer to diagram 5, thread the cable through

    the electrical sealing gland. Connect thecable to the electrical connection, polarityis not important. Fit the sealing gland, thissecures the cable and gives a water tightseal. Connect the cable to OTC1 and OTC2connection in the electrical cartridge atthe boiler, polarity is not important, refer todiagram 6.

    Note:Ultracom hxi & Flexicom hx open ventsystem models only. The edge connector willneed to be tted, see diagram 7.

    Diagram 5

    13668

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    11/24

    www.glow-worm.co.uk

    OTC 1 and OTC 2

    (A) Installation

    Diagram

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    12/24

    www.glow-worm.co.uk12

    COVER

    SEAL

    (A) Installation

    Diagram 8

    13669

    Refer to diagram 8, t and secure the sealand cover.

    Diagram 7

    14819

    Connection at

    X41 on main PCB

    EDGECONNECTOR

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    13/24

    www.glow-worm.co.uk

    (B) Conguring the Outdoor Sensor

    NOTE: If a Glow-worm Climapro or Gloworm Climastat is tted, please refer to

    section C to congure the outdoor sensor

    Glow-worm Climapro

    Glow-worm Climastat

    Conguration of the outdoor sensor isachieved through the Appliance interfacecontrols on the boiler, see diagram below.

    Appliance interface controls

    (B) C i th O td S

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    14/24

    www.glow-worm.co.uk14

    Choosing and Setting SensorHeating Curve.

    A gradient must be chosen from the range

    shown on page 17, labelled 0-9.

    The decision as to which heating curveshould be used is based on two factors:

    1. The average minimum outside

    temperature of the region.

    2. The maximum temperature which the

    heating appliance can provide.

    NOTE: Consider the level of heat loss in

    comparison to typical UK heat loss e.g.

    (double glazing, loft insulation and cavity wall

    insulation).

    Method with example.

    The following example describes theprocess. The temperatures quoted should

    be substituted with real values to nd therequired heating curve.

    1. Select the average minimum outdoor

    temperature expected in your region where

    the sensor will be installed. For example at

    the peak of winter the temperature may dropto -5C. This would be the value selected

    from the Outdoor temperature C axis.

    2. Select the maximum output temperature

    of the heating appliance from the Heating

    ow temperature (C) axis. For example this

    could be 82C.

    (B) Conguring the Outdoor Sensor

    (B) C i th O td S

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    15/24

    www.glow-worm.co.uk

    Using the domestic hot water +/-

    button, scroll through to 35.Press mode button.

    (B) Conguring the Outdoor Sensor

    Running screen is displayed

    Press and hold the mode button. Whe

    the screen is lit orange and displays 0

    release the mode button.

    Plot these two points onto the chart.Theyintersect the gradient curve labelled 6. Thevalue 6 would be entered into the boiler viathe diagnostic menu d.45.

    Refer to the following diagrams and text todo this.

    (B) C i th O td S

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    16/24

    www.glow-worm.co.uk16

    On screen are two blocks of information,

    d0in the lower part of the screen in small

    text. In the top centre of the screen, where

    the pressure or temperature is normallyshown, is displayed the heating part

    loadfor the appliance (it will be different

    for various kW output boilers).

    For example this could be 18, 38.

    Using the domestic hot water +/- button,

    scroll through until d45is shown in small

    text. Press mode buttononce. The large

    number on the screen then starts ashing.Using the domestic hot water +/- button

    change the value to 6.

    Press mode buttononce.

    (B) Conguring the Outdoor Sensor

    (B) C i th O td S

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    17/24

    www.glow-worm.co.uk

    (B) Conguring the Outdoor Sensor

    50

    60

    70

    80

    90

    30

    40

    9

    0

    1

    3

    7

    4

    2

    568

    20

    Defaultcurve

    Heatingflow

    te

    mperature(C)

    Minimum outdoor

    temperature (C)Factory default room temperaturesetpoint, for weather compensation

    (B) Conguring the Outdoor Sensor

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    18/24

    www.glow-worm.co.uk18

    (B) Conguring the Outdoor Sensor

    Adjusting room temperature setpoint.

    By default the outdoor sensor aims to provide

    a room ambient temperature of 20C. Insome situations it may be necessary to have

    a lower or higher ambient room temperature

    the adjustment is made in terms of an offset

    value, which is entered into the appliance via

    diagnostic menu d.46. Refer to the

    following diagrams and text to do this.

    Method with example.

    Running screen is displayed

    Press and hold the mode button. When

    the screen is lit orange and displays 0,

    release the mode button.

    (B) Conguring the Outdoor Sensor

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    19/24

    www.glow-worm.co.uk

    Using the domestic hot water +/-

    button, scroll through to 35.

    Press mode button.

    On screen are two blocks of information

    d0in the lower part of the screen in sm

    text. In the top centre of the screen, wh

    the pressure or temperature is normallyshown, is displayed the heating part

    loadfor the appliance (it will be differen

    for various kW output boilers).

    For example this could be 18, 38.

    (B) Conguring the Outdoor Sensor

    (B) Conguring the Outdoor Sensor

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    20/24

    www.glow-worm.co.uk20

    If extra heating comfort is required, the roomtemperature setpoint can be increased viadiagnostic menu d.46. D.46 provides a

    means to offset from the default 20C roomset point. For example to increase the targetroom temperature to 22C set d.46 to thevalue 2.

    Range of value d.46: -10 to 10.

    (B) Conguring the Outdoor Sensor

    For example:

    10C = offset -10

    20C = offset 0

    30C = offset 10

    (C) Conguring the Outdoor Sensor with external

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    21/24

    www.glow-worm.co.uk

    ( ) g gGlow-worm Climapro or Climastat controls

    Choosing and Setting SensorHeating Curve.

    A gradient must be chosen from the range

    shown on page 17, labelled 0.2-4.The decision as to which heating curveshould be used is based on two factors:

    1. The average minimum outside

    temperature of the region.

    2. The maximum temperature which the

    heating appliance can provide.

    NOTE: Consider the level of heat loss in

    comparison to typical UK heat loss e.g.

    (double glazing, loft insulation and cavity wall

    insulation).

    Method with example.

    The following example describes theprocess. The temperatures quoted should

    be substituted with real values to nd therequired heating curve.

    1. Select the average minimum outdoortemperature expected in your region whethe sensor will be installed. For examplethe peak of winter the temperature may dto -5C. This would be the value selectedfrom the Outdoor temperature C axis.

    2. Select the maximum output temperatuof the heating appliance from the Heatingow temperature (C) axis. For example tcould be 82C.

    3. Plot these two points onto the chart.Thintersect the heating curve labelled 2.5. Tvalue 6 would be entered into the boiler v

    the diagnostic menu d.45.

    (C) Conguring the Outdoor Sensor with external

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    22/24

    www.glow-worm.co.uk22

    Making Adjustment on Climastat

    Refer to your Climastat instructions, section6 Commissioning. The heating curve is

    adjusted via Menu 2. Acess to this menuis achieved by following the steps stated inAdjustments.

    Making Adjustment onClimapro/ Climapro RF

    Refer to your Climapro/Climapro RF

    Commissioning Instructions. The heating

    curve is adjusted via menu COMP which is

    accessible by procedure stated in the table in

    the Commissioning section.

    Glow-worm Climapro or Climastat controls

    Adjusting Room Ambient

    With the heating curve correctly setup foryour specic region, the room temperature

    can be adjusted. This is achieved byincreasing or decreasing the setpointtemperature of your Climastat or Climapro/Climapro RF roomstat.

    For systems with a Glow-worm Climapro.To adjust the room ambient set pointtemperature, refer to sections, Setting the

    Comfort temperature or Central heatingtemporary override - central heating of theClimapro instructions for use, installation andservicing literature.

    For systems with a Glow-worm Climastat.To adjust the room ambient set pointtemperature, refer to section 2 instructions

    for use of the Climapro instructions for use,installation and servicing literature.

    (C) Conguring the Outdoor Sensor with externalGl Cli Cli l

  • 8/11/2019 Outdoor Sensor Installation and Instructions for Use

    23/24

    www.glow-worm.co.uk

    1 3 6 8 2

    Glow-worm Climapro or Climastat controls

    50

    60

    70

    80

    90

    30

    40

    4

    0.2

    0.6

    1.2

    3

    1.5

    1

    22.53.5

    20

    Outdoor temperature (C)

    Heatingflow

    temperature(C)

    Default

    curve

    Factory default room temperature

    setpoint, for weather compensation

    Recommended

    for UK