orion on-line water analysis - neotec.cz · boiler water chemistry 3 power plant chemistry 4...

32
Orion On-Line Water Analysis products catalog pH / ISE / DISSOLVED OXYGEN / CONDUCTIVITY WASTEWATER / DRINKING WATER / POWER SEMICONDUCTOR / PAPER PULP / PURE WATER BOILER WATER / CHEMICAL / PETROCHEMICAL Analyze Detect Measure Control TM

Upload: truonghuong

Post on 06-Sep-2018

252 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Orion On-Line Water Analysis

p r o d u c t s c a t a l o g

pH / ISE / DISSOLVED OXYGEN / CONDUCTIVITY

WASTEWATER / DRINKING WATER / POWER

SEMICONDUCTOR / PAPER PULP / PURE WATER

BOILER WATER / CHEMICAL / PETROCHEMICAL

Analyze • Detect • Measure • ControlTM

Page 2: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Dear Valued Customer,

Welcome to the NEW Orion On-Line Water Analysis Catalog. This edition includes our wide range of

continuous monitors designed to measure concentrations of various chemical species in a On-Line

environment. On-Line measurements are becoming increasingly important for a number of reasons.

Improved detection limits are now possible and regulations are mandating lower levels of contaminants in

water. On-Line monitors are ready to meet all your critical measurement needs.

New product highlights of this edition include:

• New 1811EL Diisopropylamine Reagent for better lower-level stability and longer reagent life.

• The 1817LL Low-Level Chloride Monitor for detecting ppb levels of chloride in

power plant chemistry.

• The QC Sampler introduces samples and standards for rapid validation of analyses.

Products include:

• 2001 pH Monitoring System featuring exclusive ROSS™ pH Technology

• 2002 pH and Conductivity Systems

• 2030 Silica Analyzer for pure water measurements

• 1700 Series Analyzers for chlorine and fluoride measurements in final release wastewater

• 1800 Series Analyzers, for specific ion and dissolved oxygen analysis in pure and potable water

• On-Line electrodes for process applications

• Steam Conditioner to reduce the temperature and pressure of a steam sample for On-Line analysis

• Paperless data recorders

Also available are Applications Support, Technical Notes and information about Orion laboratory products.

For comprehensive information about other Orion’s products please request the latest copy of the

Laboratory Products Catalog or Titration Products Catalog. Our Technical EdgeSM Customer Service Program

is available at 800.225.1480 or by fax at 978-232-6015. Please visit us at www.thermo.com, for the very

latest product information.

Thank you for your support and we will continue to guarantee your success!

Sincerely,

Jim Barbookles

President & CEO

Water Analysis

Environmental Instruments 166 Cummings Center Beverly, MA (978) 232-6000 www.thermo.com

Water Analysis

01915-6199 USA (978) 232-6015 fax

(800) 225-1480 technical

Page 3: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

1

table of contentsanalyzer selection table

Monitors: Page(s):

Pure Water Analysis 2

Boiler Water Chemistry 3

Power Plant Chemistry 4

Drinking Water 5

Wastewater 6

Conductivity Analyzers & Sensors 7

ROSS™ pH 8, 9

pH Analyzers 10, 11

AquaPro - Industrial pH Electrodes 12, 13

Sodium 14, 15

Fluoride 16, 17

Chloride 18, 19

Ammonia 20

Dissolved Oxygen 21

Silica 22

Chlorine 23

Calcium 24

Oxygen Scavenger 25

Accessories: 26-27

• Paperless Recorders

• Steam Conditioner

• Dynamic Calibrator

• QC Sampler

Terms and Conditions, Warranty 28

Page 4: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Industries that manufacture and use DI/UPW are many.Some common ones are:

• The Power Industry, for steam generation to drive turbines.

• The Semiconductor Industry, for wafer production rinse water.

• The Pulp and Paper Industry, for steam generation usedto boil the wood pulp and also to drive turbinesgenerating power.

• The Pharmaceutical Industry, for products e.g. Water ForInjection (WFI), cleaning and rinsing, addition togranulates for tablet manufacturing and steamgeneration.

• The Petrochemical Industry, for steam generation usedto heat and boil products (better than naked flames!)and also for power generation.

The DI/UPW is generally manufactured using two methods, often a combination of both:

• Resin columns for stripping out cations (positivelycharged ions) and anions (negatively charged ions).

• Reverse Osmosis.

Resin columns are the most common and best way fordeionizing water. Good resins leave pure H2O. However, aresin column only has a limited life before the resins needto be regenerated. This regeneration process takes timeand is expensive. It involves washing resins with largequantities of sulfuric acid (for cation columns) or caustic(for anion columns). The more efficient the column is(until breakthrough occurs), the less expensive and moreenvironmentally safe it is for the user. Reverse Osmosisunits are often used ahead of demineralizers becausethey remove a good amount of the dissolved salts in theraw water. This extends the run time of the resin beds andlowers the frequency of regeneration.

Sodium

Water (usually city water or RO conditioned water) passesthrough a cation resin column first. This strips out cationssuch as sodium, potassium and calcium and exchangesthem for hydrogen ions. When the column is saturated,ions with the weakest bond to the resin escape. This iscalled "breakthrough" and when caught in time allows theuser to switch to a new resin column while regeneratingthe exhausted column. Sodium has the weakest bond ofall common cations and can be measured reliably at lowlevels. Sodium analyzer (Model 1811AO) is used to catchthis "breakthrough" as it is occurring.

Silica

The water leaving the cation column is now free of allcations, having replaced them with hydrogen ion, H+.Anions such as chloride and sulfate are still present. Theanion column strips these negatively charged ions andreplaces them with hydroxide ions, OH-, creating pureH2O. Although not an ion, silicate (SiO2) has a very weaknegative charge and bond and is the first measurableelement to "breakthrough" and indicate that anioncolumn regeneration is necessary. After the anion columna silica analyzer (Model 2030) is used to catch the firstsigns of this “breakthrough” occurring.

2

pure water analysisdeionized (DI)ultra pure water (UPW)

Cation Anion

H2O

Removes Cationssuch as Na+, K+

and Ca+2

Removes Anionssuch as Cl-, Br -

and SO4-2

“Don’t regenerateearly! Monitor silica

breakthrough!”

Page 5: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

3

Boiler

Softened or Demineralized Water

Condensate return

Steam for power generation

Process steam

Industries that use Ultra Pure Deionized Water for plantprocesses and/or power generation need to maintain theintegrity of this water in their downstream applications.

Minimization of trace salt contamination is critical toprevent serious corrosion problems that can causeexpensive damage to turbines and other plantcomponents. Control of dissolved gases such as oxygenand ammonia, in proper low concentration ranges, isrequired to prevent corrosion. pH ranges must bemaintained in a narrow window for the same reasons.Proper chemistry control in these plant processes will notonly prevent costly and unscheduled outages, but willalso greatly extend the useful lifetime of the plant.

A typical plant schematic is outlined on thefollowing page, power plant chemistry.

Industries concerned with boiler water chemistry include:

• The Power Industry, See schematic for specificapplications - page 4

• The Pulp and Paper Industry, steam carryover andcontamination by sodium, sodium in condensate,deaerator outlet for oxygen concentration, sodium andsilica breakthrough on demineralizers or calciumhardness breakthrough on softeners, pH andconductivity at various points.

• The Petrochemical Industry, same applications as Pulpand Paper

Softened orDemineralizedMake Up water

• Model 1820Calcium hardnessmonitor for softenereffluent analysis

• Model 1811ELSodium & Model2030 Silica fordemineralized wateranalysis

Boiler Feed Water

• Model 1816AODissolved Oxygenfor deaerator outlet

• Model 2001 pH & 2002 pH andConductivity

• Model 1811ELSodium

• Model 1818AOOxygen Scavenger

Boiler Water

• Model 2001 and2002 pH

• ROSS™ pHElectrode

• Model 1817LL and1817HL Chloride

• Model 1811ELSodium

Steam

• Model 1811ELSodium for boilercarryover analysis

• Model 2001 pH& 2002 pH andConductivity

• ROSS pH Electrode

Condensate Return

• Model 1811ELSodium

• Model 1816AODissolved Oxygen

boiler water chemistryboiler feed water, steam, and condensate

“Only the best

sensors measure to

critical levels”

Page 6: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Condensate/Boiler Field Water

Cooling Water

Steam Analysis

Pure WaterProduction

Boiler Water/Blowdown

Make upDemineralizer(polisher)

Anion Bed

Cation Bed

City Water

Turbine

BoilerFeed Pump Condensate

Pump

Economizer(preheatsboiler feed

water)

Deaerator CondensatePolisher

(not used in all plants)

BoilerSteam

Generator

SuperHeaters

CoolingTower

StorageTank

Generator

Condenser

Pure Water Production• Model 1811EL Low Level Sodium Monitor for

Demineralization Mixed Bed Analysis• Model 1811AO Cation Sodium Monitor for

Demineralization Cation Exchange Analysis• Model 2030 Low Level Silica Monitor for

Demineralization Anion / Mixed Bed Analysis• Model 1820 Calcium Hardness Monitor for Softener

Effluent Analysis• Model 2001 pH/2002 pH and Conductivity Monitors

Boiler Feed Water• Model 1818 Oxygen Scavenger Monitor • Model 1810

Ammonia Monitor• Model 1811EL Low Level Sodium Monitor• Model 1816 Dissolved Oxygen Monitor• Model 2001 pH/2002 pH and Conductivity Monitors

Condensate• Model 1811EL Low Level Sodium Monitor• Model 1816 Dissolved Oxygen Monitor• Model 2001 pH/2002 pH and Conductivity MonitorsDeaerator• Model 1816 Dissolved Oxygen Monitor• Model 1818 Oxygen Scavenger Monitor• Model 2001 pH/2002 pH and Conductivity Monitors

Boiler Water / Blowdown• Model 2030 Low Level Silica Monitor• Model 1811EL Sodium Monitor• Model 1817HL and 1817LL (Equilibrium Phosphate

Treatment) Chloride Monitors• Model 2001 pH/2002 pH and Conductivity Monitors

Cooling Water Effluent• Model 1770 Total Residual Chlorine Monitor• Model 2001 pH/2002 pH and Conductivity Monitors

4

power plant chemistrywith On-Line monitors

“Corrosion in

your system is like

having termites.

CONTROL

CORROSION

with good water

chemistry”

Page 7: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

5

Raw WaterPumping Station

2001 & 2002 pHAquaPro pH electrodes

Model 1809Fluoride

2001 pH & 2002 pHand Conductivity

ROSS pH electrodes

Mixing FlocculationSettling

Filtration ClearwellFinished Water

Distribution/Bottling

Drinking water

is subject to regulations set forth by the U.S. EPA, the state, the city, town or county and vary across national and stateborders. Bottled drinking water is controlled, so that measured values and concentrations may be listed. Manymeasurements are made in the lab on benchtop instruments, however pH, conductivity and fluoride are also measuredOn-Line. These On-Line measurements detect changes as they occur and raise warning flags if limits are exceeded.

Model: Description: Application:2001 series pH analyzer (dual channel) Inlet and outlet of drinking water plant2002 series pH and conductivity analyzers (single channel) Inlet and outlet of drinking water plant1809 Fluoride analyzer Fluoride is commonly added to drinking water and

must be controlled at approximately 1 ppm.AQUA10 Industrial pH electrode AquaPro Series best for raw water,

and pre-filtration steps of processAQUA20 Twistlock industrial pH electrode For pipe insertion applicationsAQUA30 & 3H Flat surface pH electrode module and holder For pipe insertion applications2001SC ROSS™ pH electrode For high accuracy finished water applications

drinking watermunicipal and bottled

“Save lab time,monitor fluoride levels

‘On-Line’for accurate results

24 hours a day.”

Page 8: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Model 2001& 2002 pH

AquaPro pH Electrodes

Model 2001 pH & 2002 pHand Conductivity

AquaPro pH Electrodes

Model 1709 Fluoride forsemi conductor andmicro electronicsindustries using HF

1770 chlorine for industrial and municipal wastewater

Model 2001 pH & 2002 pHand Conductivity

AquaPro pH Electrodes

Model 1770 Chlorine

Model 1709 Fluoride

Influent TreatmentProcess

FinalEffluent

Wastewatercan be either municipal wastewater or industrial wastewater. The chemical composition of the wastewater is measured asis enters treatment and it is also measured before release into public waters such as rivers, lakes or the ocean. Analyzersused to measure wastewater On-Line are:

Model: Description: Application:2001 series pH analyzer (dual channel) Inlet and outlet2002 series pH analyzer (single channel) Inlet and outlet1770 Total residual chlorine analyzer Final release – the 1770 measures down to 1 ppb. No

other On-Line analyzer can read this low.1709 Fluoride analyzer Hydrofluoric acid (HF) is used in the etching process

in the semiconductor and microelectronics industry.Measuring fluoride indicates HF in the wastewaterwhich has not been removed. There are also some applications in refineries which use HFalkylation units.

6

wastewatermunicipal and industrial

"Are Chlorine

levels too high in

your effluent?"

Page 9: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

7

µS/cm (sample) mS/cm (sample)0.1 1.0 10 100 10 100 1000

2 Cell Stainless Steel Cell Electrode

D.I. water

K = 0.1

drinking water

wastewater

surface water

seawaterprocess water

conc. acids and lyes

K = 0.475

4 Cell Carbon Cell Electrode

boiler feedwater

conductivitymodel 2002CD

Features: • Panel, surface or pipe mounting

• NEMA 4X, IP65, FM Class 1,Division 2

• Automatic temperature compensation

• Timer for wash down cycle• Automated USP Function• StatFace™ Sensor Diagnostics

2002CD Monitor Specifications:Measuring Range: 0.01 µS/cm to 1000 mS/cmOperating/EnvironmentTemperature Range: -20 to 55°C (-4 to 131°F)ATC Selection: Pt 100, Pt 1000, NTC 30 kohm or NTC

100 kohmChannels: 1 channelCell Constant Range: 0.0050 to 1.999 cm-1

Signal Output: 4-20 mA or 0-20 mACalibration Mode: Cell Constant AdjustmentElectrical 20 to 253 V AC @ 45 to 65 HzRequirements: 2VAProtection Rating: NEMA 4X/IP65, Class I, Div.2Housing: Thermoplastic polyester 1/2 DIN

144x144mm bezelShipping: Dimension: (LxWxD)

16x16x14 cm (6.3x6.3x5.5 in) Weight: 1 kg (2.2 Lbs)

2002SS 2-Cell Specifications:Measuring Range: 0.01 µS/cm to 300 µS/cmNominal Cell Constant: 0.1 cm-1

Application: Boiler feedwater, ultrapure waterTemperature Range: -5 to 100°C (23 to 212°F)Maximum Pressure: 100 psi (6.9 bar)Cable Length: 5 meters (16.4 ft)Electrode Material: stainless steel

2002CC 4-Cell Specifications:Measuring Range: 10 µS/cm to 200 mS/cmNominal Cell Constant: 0.475 cm-1

Application: Drinking water, waste or process waterTemperature Range: -5 to 100°C (23 to 212°F)Maximum Pressure: 100 psi (6.9 bar)Cable Length: 5 meters (16.4 ft)Electrode Material: Epoxy/graphite

2002CD: Model 2002 conductivity monitor2002BK: Bracket kit for pipe mounting2002PK: Panel mounting kit2002SH: Protective stainless steel housing2002SS: Stainless steel conductivity 2-cell with 100

µS/cm standard (2 oz. bottle)2002CC: Carbon conductivity 4-cell with 4-pack of

standards (one each: 100 µS/cm, 1413 µS/cm,12.9 mS/cm and 111.9 mS/cm, 2 oz. bottles)

2002FC: Flowcell and adapters

2002AD: Adapter for 2002CC011005: 111.9 mS/cm conductivity standard five pack,

2 oz. bottles011006: 12.9 mS/cm conductivity standard five pack,

2 oz. bottles011007: 1413 µS/cm conductivity standard five pack,

2 oz. bottles011008: 100 µS/cm conductivity standard five pack,

2 oz. bottles

Ordering Information:

Page 10: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

8

ROSS™ pHsuperior technology

ROSS technology is widely used in laboratory and field pH measurements.

ROSS pH technology is also available for measuring ultrapure, pure or potable water On-Line, where the highestaccuracy is needed.

Pure water samples have relatively low ionic strength andare therefore poor conductors.

If you are measuring On-Line samples that have low ionicstrength or that fluctuate in temperature, the ROSSelectrode’s patented internal reference system provides:

• superior measurement stability

• faster response

• greater accuracy

• more reproducible results than conventionalOn-Line pH electrodes

The silver-free ROSS reference system has NO dissolvedmetals. In conventional silver-chloride based referencesystems, dissolved metals precipitate. The result inclogged junctions, causing a slow, sluggish response. TheROSS internal reference system features a unique liquid-to-liquid double junction design. This avoids long-termdrift or inaccurate readings. The graph below showstypical results of how ROSS electrodes respond versusconventional pH electrodes. The ROSS electrode respondsalmost immediately to the correct buffer pH value with thechange in temperature.

Temperature Response ofROSS Electrode vs. Conventional Electrode.

4.19 100

4.13 75

4.07 50

4.01

Minutes

Conventional Electrode

ROSS Electrode

Theoretical Response

1 2 3 4 5

pH Temp (°C)

Page 11: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

2001SC and Filling Solution

9

ROSS™ pHmodel 2001SC

Features: • Patented ROSS technology

• Platinum reference system• Superior stability• Faster response• No long-term drift• Unique silver chloride-free

reference system• Specially designed flow

cell for low conductivity samples

Markets: • Semiconductor• Power• Pharmaceutical• Drinking water

Applications: • Ultra pure water• Potable water• Aqueous solutions

2001SC SpecificationsMeasuring Range: 0.01 to 14.00 pHTemperature Range: 0 to 100°C (32 to 212°F)Drift: < 0.5 pH units for 30 daysSlope: 92-102% (54.4-60.3 mV/dec)Isopotential Point: pH 7Diameter: 12 mm (0.5 in)Length: 125 mm (5.0 in)Electrolyte: ROSS

2001SC: ROSS combination screw-cap pH electrode,complete with reference electrolyte

2001EC: Electrode cable, 1 meter20015M: Electrode cable, 5 meter2001XM: Electrode cable, 10 meter2001FC: Stainless steel flow cell with mounting bracket2001TP: ATC probe, stainless steel, 30 kohm,

1 meter cable2001XT: ATC probe, stainless steel, 30 kohm,

10 meter cable2001LN: ATC probe, stainless steel, 8.5 kohm,

5 meter cable2001TM: ATC probe, stainless steel, 1 kohm,

5 meter cable

New! ROSS 5 meter electrode kit, (1) 2001SC ROSS2001EK: electrode, (1) 2001FC, (1) 2001XT, (1) 20015M2001PA: Pre-amp, for 2001 pH monitor2001BH: Calibration beakers (2) and holder2001B2: Spare calibration beakers (2)2001CP: Consumables pack, contains 5 bottles of ROSS

reference electrolyte, buffers 4, 7, and 10 (1 pint each), for 6 months

2001FS: 5 pack fill solution, contains five 2 oz. bottles ofROSS reference electrolyte

2001F4: 4 pack fill solution, contains four 4 oz. bottles ofROSS reference electrolyte

Ordering Information:

Page 12: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

2001 Pre-Amplifier

10

pH On-Linemodel 2001pH

Features: • 2 measurement channels

• Large, easy-to-read LED display• Backlit LCD user prompts• Automatic temperature

compensation• Solution Compensation• 4 alarms, 4 relays• Rugged aluminum housing /

NEMA 4X• Panel or surface mounting

Markets: • Power• Pulp and paper• Semiconductor• Pharmaceutical• Drinking water• Wastewater

Applications: • Rugged industrial environments• Variety of application-specific

electrodes

2001pH Monitor Specifications:Measuring Range: 0.00-14.00 pHDisplay: Red LED: pH and temperature

Backlit LCD: 2 line, alphanumeric, userinterface prompts, display mV, E0,slope, channel information

Operating/EnvironmentTemperature Range: 0 to 45°C (32 to 113°F)ATC Probe Input: 30 kohm thermistorChannels: 2 channelsSignal Output: 4-20 mA or 0-20 mA

0-5V, RS2322 analog outputs (1 per channel)

Calibration: 1 or 2 point calibration Auto buffer recognition (4, 7, 10)

Electrical 110/115V AC @ 60 Hz 10 VARequirements: 220/240V AC @ 50 Hz 10 VAProtection Rating: NEMA 4X/IP66Housing: Aluminum, 1/2 DIN 144x144 mm

bezelShipping: Dimensions: (LxWxD)

25.4x25.4x25.4 cm (10x10x10 in)Weight: 2 kg (4.5 lbs)

200100: Model 2001 On-Line pH monitor200101: Model 2001 monitor 1 channel kit, complete

with (1) 2001SC ROSS electrode, (1) 2001FCflowcell, (1) 2001TP temperature probe, (1)2001EC electrode cable, 1 meter and buffers

200102: Model 2001 monitor 2 channel kit, completewith (2) 2001SC ROSS electrodes, (2) 2001FCflowcells, (2) 2001TP temperature probes, (2)2001EC electrode cable, 1 meter and buffers

2001PA: Pre-amp for 2001pH monitor (pictured above)New! Battery operated preamp for use with ModelsPHAMP1: 2001 and 2002 pH monitors910104: 4 buffer, 475mL (1 pint bottle)910107: 7 buffer, 475mL (1 pint bottle)910110: 10 buffer, 475mL (1 pint bottle)

Ordering Information:

Page 13: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

pH Buffers 4, 7 and 10

11

pH On-Linemodel 2002pH

Features: • Panel, surface or pipe mounting

• NEMA 4X, IP65, FM Class 1,Division 2

• Automatic temperature compensation

• Temperature probe calibration• Timer for Activating Wash Cycle• StatFace™ Sensor Diagnostics

Markets: • Power• Pulp and paper• Semiconductor• Pharmaceutical• Drinking Water• Wastewater

2002pH Monitor Specifications:Measuring Range: 0.00 - 14.00 pHOperating/EnvironmentTemperature Range: -20 to 55 °C (-4 to 131 °F)ATC Selection: Pt 100, Pt 1000, NTC 30 kohmChannels: 1 channelSignal Output: 4-20 mA or 0-20 mACalibration: 1 or 2 point calibration

Auto buffer recognition (4, 7, 10)Electrical 20 to 253 V AC @ 45 to 65 HzRequirements: 2VAProtection Rating: NEMA 4X/IP65, Class I, Div.2Housing: Thermoplastic polyester

1/2 DIN 144 x 144 mm bezelShipping: Dimension: (LxWxD)

16x16x14 cm (6.3 x 6.3 x 5.5 in)Weight: 1 kg (2.2 Lbs)

2002PH: Model 2002 pH monitor2002BK: Bracket kit for pipe mounting2002PK: Panel mounting kit2002SH: Protective stainless steel housingNew! Battery operated preamp for use with ModelsPHAMP1: 2001 and 2002 pH monitors

910104: pH 4 buffer, 475mL (1 pint bottle)910107: pH 7 buffer, 475mL (1 pint bottle)910110: pH 10 buffer, 475mL (1 pint bottle)

Ordering Information:

Page 14: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

12

AquaPro pHmodel AQUA10model AQUA40

AQUA10 Features: • Ideal general-purpose electrode

for all your On-Line pH needs• Rugged industrial housings for

On-Line, pipe insertion orsubmersion (dip system)applications

• Built in thermistor and solution ground

• Suitable for the harshest On-Lineor wastewater samples

• Stainless steel bulb guards to protect glass pH sensing bulb from breakage and damage

AQUA40Features: • Glass body electrode for flowcell

measurements• Ideal general-purpose electrode

for all your On-Line pH needs• Screw-cap connector for various

cable lengths

AQUA10 and AQUA40 Specifications:Measuring Range: 0.01 to 14.00 pHTemperature Range: -5 to 60°CThermistor (built in): 30 kohm (AQUA10)Isopotential Point: pH 7Pressure Range: 0 to 100 psi (6.9 bar)AQUA10 Dimensions: Length: 170 mm (6.7 in) Diameter:

30 mm (1.2 in), 3/4 in NPT ThreadingAQUA40 Dimensions: Length: 120 mm (4.7 in)

Diameter: 12 mm (0.5 in)Cable Length AQUA10: 5 meters (16 ft) AQUA40 screwcap electrode does not come with cable, may be used with 2001EC and 2001XM

AQUA10: Combination pH electrode w/ATC, 5 meter cableAQUA40: Combination pH electrode w/screwcap2001TP: ATC probe, stainless steel, 30 kohm, 1 meter2001XT: ATC probe, stainless steel, 30 kohm, 10 meters2001EC: Electrode cable, 1 meter (3 ft)2001XM: Electrode cable, 10 meters (32 ft)2001FC: Stainless steel flow cell w/mounting

bracket (AQUA40)

900023: pH Electrode cleaning solution (for generalcleaning, includes four 1 oz. bottles)

900024: pH Electrode cleaning solution (for removing oiland grease contaminant’s, includes four 1 oz.bottles)

see page 10 for pH buffer ordering information

Ordering Information:

CONTACT Reference SystemThe AQUA10 and AQUA40 On-Line pH electrodes featurethe unique CONTACT Reference System. This referencesystem utilizes a polymer reference electrolyte. Thispolymer electrolyte does not hydrolyze or break down andis extremely stable. The polymer reference electrolytemakes direct CONTACT with the sample, through an open-hole junction. Problems associated with clogged junctionsare eliminated! These electrodes are Ag/AgCl double-junction combinationpH electrodes, which do not have any silver (Ag+) in theelectrolyte contacting the sample. Samples andtemperatures that precipitate silver are not a problem. • Internal reference system held under constant

conditions for high stability, low drift• Polymer matrix acts as protective barrier from

sample contamination• Long life, low maintenance electrodes which

don’t need refilling• Designed for use with models 2001 and

2002 pH Monitors

Page 15: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

13

AquaPro pHmodel AQUA20model AQUA30

AQUA20Features: • Ideal for quick insertion and

removal applications• AQUA20 pH electrode inserts

and locks into AQUA2A adapter• Rugged industrial housings for

On-Line, pipe insertion orsubmersion (dip system)applications

• Built in thermistor and solution ground

• Bulb guards to protect glass pHsensing bulb from breakage and damage

AQUA30 Features: • Flat surface sensor helps prevent

breakage and damage• Ideal for samples containing oil,

grease or particulates• AQUA30 pH electrode screws into

AQUA3H electrode housing foreasy cleaning or replacement

• AQUA3A adapter slides ontoAQUA3H for On-Line insertion

• Built in thermistor and solution ground

AQUA20 and AQUA30 Specifications:Measuring Range: 0.01 to 14.00 pHDrift: < 0.5 pH units for 30 daysTemperature Range: -5 to 100°CThermistor (built in): 30 kohmIsopotential Point: pH 7AQUA20 Dimensions: Length: 144 mm (5.7 in)

Diameter: 25 mm (1.0 in) 3/4 in NPTon AQUA20, 1 in NPT on AQUA2A

AQUA3H Dimensions: Length: 185 mm (7.3 in)Diameter: 28 mm (1.1 in) 3/4 in NPTon AQUA3H, 1 1/2 in NPT on AQUA3A

Pressure Range: 0 to 100 psi (6.9 bar)Cable Length: 5 meters (16 ft)

AQUA20: Combination pH electrode/thermistorAQUA2A: Twistlock adapter for AQUA20AQUA30: Combination pH electrode module

(needs AQUA3H)AQUA3H: Bulkhead assembly and thermistor

for AQUA30 module, AQUA3A included

900023: pH electrode cleaning solution (for generalcleaning, includes four 1 oz. bottles)

900024: pH electrode cleaning solution (for removing oil and grease contaminant’s, includes (4) 1 oz. bottles)

see page 10 for pH buffer ordering information

Ordering Information:

HYDRAPERM Reference SystemThe AQUA20 and AQUA30 On-Line pH electrodes are idealfor the harshest samples and environments. TheHYDRAPERM Reference System is a polymer basedreference electrolyte, which hydrates and expands when itcomes in contact with an aqueous sample. Theseelectrodes have a large, rugged reference junction, suitablefor harsh On-Line samples that fluctuate in temperatureand pressure. • Long life double junction combination

Ag/AgCl electrodes

• Designed for use with models 2001 and 2002 pH Monitors

Page 16: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Sodium Reagent, Electrodes and Solutions

14

sodium monitormodel 1811EL

Features: • 0.01 ppb - low detection range

• No moving parts - little maintenance required

• Automatic calibration

Markets: • Power• Semiconductor• Chem / Petrochemical• Pulp and Paper

Applications: • Ultra pure water analysis• Boiler feed water• Ion exchange breakthrough• Steam analysis• R/O systems• Drum boiler water

1811EL Specifications:Measuring Range: 0.01-1000 ppb sodium,

higher levels on requestAccuracy: 0.01 ppb or 2.5%, whichever is greater

Standard deviation ± 2.5%Response Time: 50% within 2 minSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Sample Temperature: 5 to 40°C (41 to 104°F) Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 40 mL/min, minimumTotal acidity: < 50 ppm CaCO3

Calibration: Automatic - double known additionElectrical 100/110/115/220/240V ACRequirements: 50/60 Hz 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1811EL: Low-level sodium monitor, complete with sodiumelectrode, reference electrode, temperaturesensor, standard solutions kit, signaloutput module

181101: Electrode kit complete with (1) 100048 sodiumelectrode, (1) 100058 reference electrode and (2) cables

100058: Reference electrode, with 2 oz. bottle of referencefilling solution

150072: Reference electrode internal filling solution, five 2 oz. bottles

181140: Sodium Standard Solutions Kit, (2) 2 oz. BottlesStandard “1” – 19.1 ppm Na, Standard “2” – 192ppm Na, and one 2 oz. rinse solution

181148: Calibration kit, with carrying case, includesincludes 0.1 mL pipet, box pipet tips, washbottle, 4-ft. diffusion tubing, bottle adapter

18LL53: Consumables kit, for 1 year, consists of (6) 1 literbottles of monoethylamine reagent, diffusiontubing, adapter, standards, sodium and referenceelectrode, filling solution, O-rings, check valve,pipet tips, restriction tubing, and inlet filters.

151111: Monoethylamine reagent, with tubing, for 1 year181111: Monoethylamine reagent, with tubing,

for 2 months100048: Sodium electrode, screw cap

180011: Alarm module, with 2 separate adjustable alarms

181127: Temperature sensor181113: Sodium electrode rinse solution*New! Diisopropylamine Reagent (DIPA) (0.8 L bottle) 181190: with diffusion tubing kit*New! Diisopropylamine Reagent (6 x 0.8 L bottle) with181191: six diffusion tubing kits*New! Sodium Consumables DIPA Kit (Includes181192: Diisopropylamine Reagents). Consists of 6x0.8L

reagent with diffusion tubing kit, diffusion bottleadapter/cap, (1) standard solutions kit, (1) sodium electrode, one reference electrode, (5) 2 oz. bottles reference filling solution, one O-ring kit, one check valve, (1) set pipet tips, (1) restriction tube assembly, (2) 60 micron inlet filters, and (1) filter gasket.

*New! Diffusion Bottle Adapter/Cap Assembly for use181193: with DIPA reagent. *New! Diffusion Tubing Kit, (for use with DIPA reagent):181194: 2 x 4-inch lengths and O-rings.*New! Retro Fit Kit for DIPA: including bottle adapter/cap181195: and bottle shelf.New! 1800 series shelf/clamp for 181196: glass reagent bottles

*Must purchase retro fit kit to use DIPA reagent

Ordering Information:

Page 17: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Calibration Kit

15

sodium monitormodel 1811AO

Features: • 1 ppb detection limit

• Simple operation and calibration• Low maintenance requirements• Digital LCD• Automatic calibration

Markets: • Power• Semiconductor• Chem / Petrochemical

Applications: • Cation exchange breakthrough• For high acid samples• Increase the effective run time on

cation exchangers• Drum boiler water

1811AO Specifications:Measuring Range: 1 ppb-200 ppm sodiumAccuracy: ± 2 ppb up to 10 ppb 5% of

reading up to 200 ppmResponse Time: 50% within 2 minSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Sample Temperature: 5 to 45°C (41 to 112°F)Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 25 mL/min minimumTotal acidity: < 250 ppm CaCO3

Calibration: Automatic - double known additionElectrical 110/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1811AO: Cation sodium monitor, complete with sodiumelectrode, reference electrode, temperaturesensor, signal output module, standard solution kit

181102: Electrode kit complete with (1) 100045 sodiumelectrode, (1) 100056 reference electrode and(2) cables

100045: Sodium electrode100056: Reference electrode, with 2 oz. bottle of

filling solution181073: Reference electrode internal filling solution,

five 2 oz. bottles181149: Calibration kit, with carrying case, includes 0.5

mL pipet, pipet tips, diffusion bottle adapter,wash bottle, tubing, rinse solution (shown above)

181150: Consumables kit, for 1 year, consists of (12) 2liter bottles reagent, diffusion tubing, standardsolutions kit, sodium electrode, referenceelectrode, filling solution, O-ring kit, check valve,pipet tips, restriction tube assembly and inlet filters

181130: Acid Reagent, 2 liter bottle, for 30 days(181160 diffusion tubing not included)

181160: Diffusion tubing, (3) 5’ 8” lengths with O-rings180011: Alarm module, with 2 separate adjustable alarms181127: Temperature sensor181113: Sodium electrode rinse solution181140: Sodium standard solution kit181141: High level sodium standard solution kit

Ordering Information:

Page 18: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Fluoride Reagent and Electrodes

16

fluoride monitormodel 1809AO

Features: • 0.01 to 100 ppm

• Solid state electrode• Simple operation• No moving parts• Simple calibration• Correlates well with lab

measurements• Designed to measure clean water

Markets: • Potable water• Bottled water• Municipal drinking water

Applications: • Fluoridation control• Fluoride level monitoring

1809AO Specifications:Measuring Range: 0.01-100 ppm fluorideAccuracy: 0.1 ppm or 10% of reading,

whichever is greaterResponse Time: 90% within 2 min function of flowSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Sample Temperature: 5 to 35°C (41 to 95°F)Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 40 mL/minTotal alkalinity: < 200 ppm CaCO3

Calibration: Automatic - double known additionElectrical 110/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1809AO: Low-level fluoride monitor, complete withfluoride electrode, reference electrode,temperature sensor, standard solutions (100and 1000 ppm), signal output module

100029: Fluoride electrode, screw cap100056: Reference electrode, screw cap181073: Reference electrode internal filling solution, five

2 oz. bottles940907: Fluoride standard solution, 100 ppm,

475mL (1 pint bottle)110902: Fluoride standard solution, 1000 ppm,

475mL (1 pint bottle)182011: Reagent, acid, for 60 days

180949: Calibration kit, with carrying case, includes 0.5ml pipet, pipet tips, fluoride standards (100 and1000 ppm), inlet filter, wash bottle and diffusionbottle adapter, tubing, solutions

180950: Consumables kit, for 1 year, consists of six 1 literbottles of reagent, diffusion tubing, standards,fluoride electrode, reference electrode, fillingsolution, O-ring kit, check valve, pipet tips,restriction tube assembly and inlet filters.

181170: Inlet filters, stainless steel, 60 micron filters with gaskets, pack of 2, for 6 months

181125: Restriction Tube Assembly204847-001: Calibration pipet, 0.5 mL204846-001: Pipet tips, set of 100

Ordering Information:

Page 19: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Fluoride Standard and Electrodes

17

fluoride monitormodel 1709

Features: • 0.01 to 1000 ppm

• Solid state electrode• Choice of measuring range• Measures unfiltered wastewater• Reagent buffers up to 500 ppm

acidity / alkalinity• Reliable chemistry• Low cost of operation

Markets: • Semiconductor• Industrial wastewater• Municipal wastewater

Applications: • Compliance monitoring

1709 Specifications:Measuring Range: 0.01-1000 ppm fluoride. User to

select 2, 3, or 4 decades within thisrange. Higher ranges available

Accuracy: ± 10 ppb or ± 10% of readingwhichever is greater

Response Time: 1 minSignal Output: 0-5V DC

4-20 mAOutputs to drive recorder

Sample Temperature: 0 to 40°C (32 to 104°F)Requirements: Pressure: (0.1 - 1.4 bar) (2-20 psi)

Flow: 2-20 L/min (0.5-5 gal/min)Total alkalinity: 0-500 ppm CaCO3

Calibration: 2 point calibrationElectrical 115V AC (170901) 50/60 HzRequirements: 220V AC (170903) 50/60 Hz

100 wattsShipping: Dimensions: (LxWxD)

154x64x33 cm (60x25x13 in)Weight: 102 kg (225 lbs)

170901: Fluoride monitor, 115V, complete with fluoride electrode (100029), and reference electrode(100031)

170903: Fluoride monitor, 220V, complete with fluoride electrode(100029), and reference electrode(100031)

100029: Fluoride electrode, screw cap100031: Reference electrode, with 2 oz. bottle of internal

filling solution150071: Reference electrode internal filling solution, for

use with 100031 reference electrode, (5) 2 oz. bottles

170950: Consumables kit, for 1 year, contains fluoridereagent and standard

170930: Fluoride reagent, for 30 days170959: Spare parts kit, consists of fluoride electrode,

reference electrode, filling solutions, inletscreens, pump seals, fuses, O-ring kit, checkvalves and carbon filter.

940907: Fluoride standard solution, 100 ppm, 475mL (1 pint bottle)

110902: Fluoride standard solution, 1000 ppm, 475mL (1 pint bottle)

170013: Tubing kit150084: Signal linearizer207303-A01: Cable, screw cap to SHV connector

Ordering Information:

Page 20: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Chloride Reagent and Electrodes

chloride monitormodel 1817HL

Features: • 0.1 ppm detection limit

• Simple operation and calibration• No moving parts• Wide range of detection• Digital LCD• Chloride specific measurement

Markets: • Power• Semiconductor• RO systems

Applications: • Detects condenser leaks inseawater cooled power plants

• Boiler water monitoring• RO feedwater monitoring

1817HL Specifications:Measuring Range: 0.1-100 ppm chloride Higher

ranges availableAccuracy: ± 0.1 ppm or 10%, whichever

is greaterResponse Time: 90% within 2 minSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Sample Temperature: 5 to 35°C (41 to 95°F)Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 40 mL/minTotal alkalinity: < 50 ppm CaCO3Sulfite cannot be present in sample

Calibration: Automatic - double known additionElectrical 110/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1817HL: Chloride monitor, complete with chloride andreference electrodes, standard solutions kit, andsignal output module

100025: Chloride electrode, screwcap100057: Reference electrode, screwcap181140: Standard solutions kit181141: High level standard solutions kit

182011: Reagent, Acid, with tubing, for 60 days180011: Alarm module, 2 adjustable alarms181060: Diffusion tubing (thin-walled), (4) 2 foot lengths

with O-rings181125: Restrictor Tube Assembly204847-001: Calibration pipet, 0.5 mL204846-001: Pipet tips, set of 100

Ordering Information:

18

Page 21: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

1817LL Sample Cooler

chloride monitormodel 1817LL (Low-Level)

New!

Features: • Measures down to 5 ppb chloride• Low cost of operation• QC Sampling Capability:

- Validation using standards- Grab samples- Alternative to lab analyses

• Integrated sample temperaturecontrol for lower levels of detection

• Low maintenance• Ease of calibration

Markets: • Power Generation• Reverse Osmosis

Applications: • Boiler water chloridemeasurements

• Equilibrium Phosphate Treatment (EPT) chloridemeasurements

• RO Effluent

1817LL Specifications:Measuring Range: 5ppb to 10ppm chlorideSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Precision: 10% of reading or ± 5 ppb, whicheveris greater, within ± 5˚ C of calibrationtemperature.

Drift: 0.1 ppm per month or 10% of readingwhichever is greater.

Sample Temperature: 5 to 45 ˚C (40 to 113 ˚F)Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 40 mL/minTotal alkalinity: < 50 ppm CaCO3

Sulfite must not be present. Cooled Sample Temp: 5-12 ˚CCalibration: 1 - 3 - point calibration using dynamic

calibrator (see page 27)Electrical 100/115/220 or 240V AC, ± 10%, Requirements: 50/60 Hz, 100 watts.Shipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1817LL: Low-Level Chloride monitor with cooler, 110V1817LL100: 1817LL, 100V1817LL230: 1817LL, 230V100025: Chloride electrode, screwcap100057: Reference electrode, screwcap941707: 100 ppm Chloride standard,

475mL (1 pint bottle)

1817CAL: Includes Dynamic calibrator (Cat. No. 15DC15),and 100ppm Chloride standard (Cat. No.941707) in an easy-to-use kit.

*182011: Acid Reagent for 60 days operation (one literbottle) with one 2 foot length thin-walled tubingand O-rings

*Contains hazardous material.

Ordering Information:

19

Page 22: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Ammonia Reagents, Electrodes and Solutions

20

ammonia monitormodel 1810AO

Features: • 10 ppb detection limit

• Direct measure of ammonia• Continuous readings• Simple operation and

automatic calibration• Digital LCD

Markets: • Power• Pulp and Paper• Chem / Petrochemical

Applications: • Boiler feed water

1810AO Specifications:Measuring Range: 10 ppb-10 ppm ammoniaAccuracy: ± 0.03 ppm

Standard deviation ± 5%Response Time: 90% response within 1.5 minSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Sample Temperature: 15 to 35°C (59 to 95°F)Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 40 mL/min Total alkalinity: < 250 ppm CaCO3

Calibration: Automatic - double known additionElectrical 110/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1810AO: Ammonia monitor, complete with sensingelectrode, reference electrode, temperatureprobe, standard solution kit, signal outputmodule

181049: Calibration kit, with carrying case, includesstandards, electrodes, bottles, tubing, solutions

180011: Alarm module, 2 adjustable alarms

181050: Consumables kit, for 1 year181030: Reagent, 2 liter bottle181040: Ammonia standard solutions kit100047: Ammonium electrode100056: Reference electrode, with 2 oz. bottle of

filling solution181127: Temperature sensor

Ordering Information:

Page 23: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Dissolved Oxygen Probe and Filling Solution

21

dissolved oxygenmodel 1816AO

Features: • Low-level detection - 0.1 ppb

• Galvanic cell with low-levelguard ring

• 316 stainless steel flow cell• Digital LCD readout• Built in alarms and relays• Pre-assembled teflon membrane

module for easy replacement

Markets: • Power• Pulp and Paper• Chem / Petrochemical

Applications: • Boiler feed water• Ultra pure water• Process steam• Deaerator outlet• Condensate• Oxygen feed control for plants

using oxygen treatment chemistry

1816AO Specifications:Measuring Range: 0.1 ppb-300 ppb dissolved oxygenCalibration Range: 0-10 ppm oxygen in water

saturated airAccuracy: 0.1 ppb ± 2%, whichever is greaterResponse Time: 1 min, from high to low levelsSignal Output: 4-20 mA or 0-20 mA

0-5V or 1-5V DCBi-directional RS232, 2 relays

Sample Temperature: 2 to 45°C (35 to 113°F)Requirements: Flow: 50-200 mL/min pH: > 4

Pressure: < 4 bar (60 psi)Calibration: Automatic in water saturated airProtection Rating: NEMA 4X/IP65Electrical 115/230V AC 50/60 HzRequirements: 50 wattsShipping: Dimensions: (LxWxD)

16x26x9 cm (6.3x10.24x3.54 in) Weight: 4.9 kg (10.8 lbs)

1816AO: Low-level dissolved oxygen monitor, completewith flow cell, maintenance kit and electrodewith 10 foot shielded cable, 115/230V

1816A2: Low-level dissolved oxygen monitor, 115/230V(without electrode)

181621: Low-level dissolved oxygen probe, with 10 footshielded cable

181621X: Low-level dissolved oxygen probe, customlength shielded cable (30 foot max)

181622: Maintenance kit, with membrane module, o-ring, and fill solution

1816FP: Portable fluidics panel, with needle valve andbypass, quick connect fitting, for easy hook up(shown above with monitor and electrodeattached)

223115-S01: Flow cell assembly

Ordering Information:

Page 24: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Silica Reagent and StandardGrab Sampler

22

silica monitormodel 2030

Features: • 0.5 ppb detection limit

• 3 reagent addition CEGB method• 6 stream capability (1 standard)• Ease of use with digital

alphanumeric readout• Grab sample capability• Accurate reagent metering for

low and high levels• Fully programmable for individual

needs - 10 stored methods• Fully programmable AUTOCAL™• Analog and digital outputs• Stores last 25 calibrations and

last 120 measurements• Rugged NEMA 4X enclosure

Markets: • Power• Semiconductor• Pharmaceutical• Pulp and Paper• Chem / Petrochemical

Applications: • Demineralizer effluent• Boiler water

2030 Specifications:Measuring Range: 0-500 ppb SiO2

Method: Silica in water using the absorptionband at 810 nm with referencewavelength at 450 nm single beamdual wavelength using fiber-opticprobe in the transflection mode

Limit of Detection: 0.5 ppbResponse Time: 8-10 min, 0-100 ppb

15 min, 100-500 ppbSignal Output: 0-10 mV

0-100 mV0-1V4-20 mARS232 bi-directionalModem

Sample Temperature: 5 to 70°C (41 to 158°F)Requirements: Pressure: (0.2 - 3 bar) (2-50 psi)

Flow: 50-900 mL/minSample Streams: 1 standard, 2-6 optionalCalibration: Automatic - fully programmableEnclosure Rating: NEMA 4X, IP65Electrical 110/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

76x76x48 cm (30x30x19 in) Weight: 44 kg (96 lbs)

203000: Silica analyzer, single stream2030S2: Silica analyzer, 2 streams2030S3: Silica analyzer, 3 streams2030S4: Silica analyzer, 4 streams2030S5: Silica analyzer, 5 streams2030S6: Silica analyzer, 6 streams*2030RE: Reagent kit, 1 month*2030IR: International reagent kit, 1 month2030RT: Reagent holder shelf203002: 20 ppb silica standard, (4) 475 mL

(1 pint) bottles*Contains hazardous material

203010: 100 ppb silica standard, (4) 475 mL(1 pint) bottles

203020: 200 ppb silica standard, 5 liters (1.3 gallons),for automatic calibration

2030MK: Maintenance kit, 3 months, check valves forreagent tubing, pump seals, silicon oil, reactioncell O-ring kit, C-flex tubing

2030GS: Silica grab sample kit2030GP: Silica grab sample kit spare parts2030LA: Replacement tungsten lamp

Ordering Information:

Page 25: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Chlorine Electrode and Standards

177001: Total residual chlorine monitor, complete withchlorine electrode, and manual, 115V

177003: Total residual chlorine monitor, complete withchlorine electrode, and manual, 220V

100020: Chlorine electrode177015: Calibration equipment kit, for use with

Calibration refill kit (177013)177050: Chlorine consumables kit177013: Calibration refill kit, for use with calibration

equipment kit*177011: Reagent, 900 mL concentrated acid and 54

grams Iodide reagent powder, requires dilutionwith deionized water to 5 gallons, for 30 days

*Contains hazardous material

177012: Iodide powder reagent, four 54 gram bottles, 4 months

177014: Standards A and B, 4 bottle pack, requires177041 and 177042 reagents

177041: Iodide reagent, five 2 oz. bottles, for use with177014 standards

177042: Acid reagent, five 2 oz. bottles, for use with177014 standards

170013: Tubing kit948201: Electrode polishing strips, twenty-four,

6 inch strips150084: Signal linearizer

Ordering Information:

Features: • 1 ppb detection limit

• Provides lowest level of detection• Reliable• Low operating cost• Solid state electrode• U.S. EPA approved method• Measures unfiltered wastewater• Measures other oxidants

such as bromine

Markets: • Power• Desalination plants• Reverse osmosis• Wastewater treatment

Applications: • Cooling water• RO membrane protection• Effluent samples• Compliance monitoring

1770 Specifications:Measuring Range: 0.001-10 ppm total residual chlorine

4-decade scale standard. Other ranges available

Accuracy: ± 10% of readingResponse Time: 90% within 2 minSignal Output: 4-20 mA or 0-5VSample Temperature: 5 to 45°C (40 to 113°F)Requirements: Flow: 2-20 L/min

Total alkalinity: < 500 ppm CaCO3

Calibration: 2 point calibrationElectrical 115V AC (177001) 50/60 HzRequirements: 220V AC (177003) 50/60 Hz

230 wattsShipping: Dimensions: (LxWxD)

154x64x33 cm (60x25x13 in)Weight: 102 kg (225 lbs)

chlorine monitormodel 1770 total residual

23

Page 26: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Calcium Reagent, Electrodes and Solutions

24

1820AO Specifications:Measuring Range: 25 ppb-500 ppm calcium hardness

as CaCO3

Accuracy: ± 10% of reading or 10 ppb,whichever is greater within ± 10°C ofcalibration temperature

Response Time: 50% within 2 min function offlow and volume

Signal Output: 4-20 mA or 0-20 mA 0-5V or 0-10V DCLinear or log output

Sample Temperature: 5 to 40°C (41 to 104°F)Requirements: Pressure: (0.6 - 6.9 bar) (8-100 psi)

Flow: 40 mL/min, minimumTotal alkalinity: < 250 ppm,No filming amines; cannot contain

sulfite > 2 ppm chelants such as EDTAmust not be present

Calibration: Automatic - double known additionElectrical 100/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

Features: • 25 ppb up to 500 ppm

• Wide range• Simple operation• No moving parts

Markets: • Power• Pulp and Paper• Chem / Petrochemical• Drinking water

Applications: • Zeolite softener effluent monitoring

• Water softening• Blending applications

calcium monitormodel 1820AO

1820AO: Calcium hardness monitor, complete withcalcium electrode, reference electrode,temperature sensor, standard solutions kit,signal output module

182049: Calibration kit, with carrying case, includesstandards, tubing, solutions, 0.5 mL pipet, pipettips, standards, inlet filter, wash bottle,diffusion bottle adapter

*182011: Reagent, acid, for 60 days*182051: Consumables kit, for 1 year, consists of (6) 1

liter bottles reagent, diffusion tubing andadapter, standards, calcium electrode, referenceelectrode, filling solutions, O-ring kit, checkvalve, pipet tips, restriction tube assembly, andinlet filters.

*Contains hazardous material

180011: Alarm module, with 2 adjustable alarms182040: Calcium standard solutions kit181073: Reference electrode internal filling solution,

five 2 oz. bottles100049: Calcium electrode, screw cap100056: Reference electrode, screw cap, with 2 ounce

bottle of filling solution181120: Inlet filters, 4 pack, for 1 year181127: Temperature sensor

Ordering Information:

Page 27: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Reagent, Electrodes and Solutions

25

oxygen scavengermodel 1818AO

Features: • 1 ppb detection limit

• Simple operation• No moving parts• Alarm and control capability• Measures most oxygen scavengers• Solid state electrode• Unique chemistry

Markets: • Power• Pulp and Paper• Chem / Petrochemical

Applications: • Boiler feed water• Hydrazine• Elimin-Ox®†

• Carbohydrazide• DEHA and others

† Elimin-Ox is a registered trademark of NALCO Chemical Co.

1818AO Specifications:Measuring Range: Hydrazine: 0-200 ppb

Elimin-Ox Carbohydrazide: 0-1000 ppb

Accuracy: Hydrazine: 0-50 ppb ± 2 ppb or 10%0-200 ppb ± 2 ppb or 15% Elimin-Ox: ± 30 ppb or 10%

Response Time: 90% within 4 minSignal Output: 4-20 mA or 0-20 mA

0-5V or 0-10V DCLinear or log output

Sample Temperature: 15 to 40°C (59 to 104°F)Requirements: Pressure: (0.6 - 6.8 bar) (8-100 psi)

Flow: 40 mL/min, minimumCalibration: Hydrazine: 1 or 2 point calibration

using dynamic calibratorElimin-Ox: 2 point calibration usingdynamic calibrator (see page 27)

Electrical 110/115/220/240V AC 50/60 HzRequirements: 100 wattsShipping: Dimensions: (LxWxD)

65x45x27 cm (26x17x11 in)Weight: 31.4 kg (69 lbs)

1818AO: Oxygen scavenger monitor, complete withsensing electrode, reference electrode, signaloutput module (note: comes installed withHYDRAK, ELIMAK software and instructions forinstallation are included)

HYDRAK: Application kit, for measuring HydrazineELIMAK: Application kit, for measuring NALCO ELIMIN-OX

Carbohydrazide100022: Iodide Sensing electrode, screwcap100056: Reference electrode, screwcap180011: Alarm module, 2 adjustable alarms

*181850: Consumables kit, for 1 year, consists of (6) 1liter bottles reagent, diffusion tubing, iodidereagent, reference electrode, filling solution, O-ring kit, check valve, restriction tube assemblyand inlet filters.

*181811: Reagent, with tubing, for 6 months181127: Temperature sensor181170: 60 micron inlet filters, 2 pack, for 1 year151810: Hydrazine standardizing solution,

475mL (1 pint bottle)180096: Syringe kit, for use with 15DC15

dynamic calibrator181860: Diffusion tubing and O-rings*Contains hazardous material

Ordering Information:

Page 28: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

accessoriesfor On-Line products

26

Steam conditioning:The 1803 is designed to take a high pressure steam sample (e.g.the process steam used in power plants, paper mills, oil refineriesetc.) and reduce the temperature and pressure down to the levelsrequired by our On-Line analyzers. Process steam is used in manyindustries; it is the analysis of this steam that has made On-Lineanalyzers so important in the power, paper, petrochemical andother industries.• The 1803 can handle pressures of up to 20,897 K Pa (3030 psi).

The usual average pressure of process steam is approximately6,896 K Pa (1000 psi)

• The 1803 can reduce the temperature of the sample from 538°C(1000°F) to under 38°C (100°F)

• No electrical requirements - the 1803 is purely mechanical,requiring no electrical hook up. This means that it can be used inmultiple countries regardless of the voltage requirements. The1803 can also be used in hazardous locations without anydanger of explosion

• The 1803 has a mechanical temperature shut off valve which willtrip if the temperature exceeds 40°C (104°F). This can happenwhen a cooler fails or the cooling water becomes too hot. Thevalve diverts the hot sample away from the On-Line monitor,avoiding costly damage

Features:• Thermal shut off valve• Sample cooler• Pressure reduction element• Temperature indicator• Back pressure relief valve

Markets:• Power• Pulp and Paper• Chem / Petrochemical

Applications:• Reduce temperature and pressure of steam samples for analysis

steam conditioner model 1803

Thermo Westronics SV100 Video Recorder

The SV100 takes touch screen technology to the next level withextensive use of intuitive Windows® style menus.

The SV100 comes standard with dual RS232 and RS485 interfaceswith MODBUS protocol support.

• Inputs: Accepts 6, 12 or 18 inputs and is designed with 3 cardslots to accommodate any combination of analog input cards andcontact output/digital input cards. Up to 30 calculated pointsincluding custom entry of algebraic equations. All pointsscanned at 125 mS.

• Display Options: Inputs and calculated points can be displayedin a wide variety of user-defined formats such as Vertical Trend,Horizontal Trend, Bargraph, Digital, Alarm Summary, Overviewand/or Bitmap Screens. “Thumbnails” of all configured screensare on one page eliminating need to scroll through numerousselections. Points can be programmed to flash or change coloron alarm. Intuitive touch screen and Windows style menus allowstraightforward programming and operation without requiring theuse of cumbersome function keys and keypads. Review ofhistorical data is flexible with the touch of the fast forward andrewind buttons.

• Storage Media: 8 MB Internal Flash Memory protectsconfiguration and data from power loss. 16MB Internal RAM

permits the operator to search through an extensive amount ofhistorical data effortlessly and without delay. RemovableStorage: 3.5” floppy disk, ATA flash memory card and Zip disks.User-selectable for Cyclical or Fill to End mode of storage.Measured values are saved to media as an average orinstantaneous value. No data is lost during media change.

• Networking: 10 Base-T Ethernet. RS232, RS485 with MODBUSRTU or ASCII as standard feature. Real time remote monitoring anddata backup.

• Additional Features: A standard parallel printer port supportsPrint Screen, Alarms and/or Time of Day or Interval Logs. EventMessage feature allows the operator to mark the trend screens withcustom messages. IP65 Front Panel. Modular Compact Design.

Note: Specially configured for each application, please call for ordering information.

†Windows is a registered trademark of Microsoft Corporation

New! paperless recorder

Sample requirements: Temperature: up to 538°C (1000°F)Pressure: 20,897 K Pa (3030 psi)Panel dimensions: 30.5x91.5x17 cm (12x36x6.5 in)Material: Stainless steel

180300: Steam sample conditioner

Specifications: Ordering Information:

Paperless Recorder

Steam Conditioner

Page 29: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

27

By using the QC Sampler, operators can temporarily interrupt theflow of water to 1800 Series monitors and substitute it withsamples coming from the QC Sampler. In this way, samples fromother parts of the plant, or validation and calibration standardscan be analyzed. The QC Sampler allows for rapid sampling whereno On-Line instrumentation is present, and providestroubleshooting to validate readings without disturbing On-Line operations.

Features:• Compatible with all 1800 series monitors• Portable design• Easy to install• Introduce standards or samples into the monitor for analysis

1800 Series QC Sampler

Dynamic Calibrator

Many analyzers claim to measure in the low ppb range but it can be difficult to verify that an On-Line instrument is accuratelyreading at this low-level. Part-per-billion standards are difficult tomake and maintain, and transporting grab samples for laboratoryanalysis is difficult.

The Low-Level Verification system uses On-Line dynamic dilution.The key component of this system is the Dynamic Syringe Pumpwhich can deliver a steady flow rate of solution or standard downto 0.1 mL/min. The low-level verification kit includes an injectionport, which is installed into the process downstream offlow regulation.

Calculation for the expected concentration of the standard:

The expected reading is the sample reading plus the expectedstandard concentration.

The Dynamic Calibrator can be used for Low-Level Verification of allmodel 1800 Series ISE Analyzers!

low-level verification system

accessoriesfor On-Line products

ElectricalRequirements: 9V DC, 9 wattsInput: 115VAC/60Hz Adapter, 230VAC/50Hz AdapterFlow Rate: 40 mL/min nominal set by pressure regulatorCompatibility: All 1800 Series MonitorsDimensions: 14.5 x 10 x 6 in (h.w.d.);

36.8 x 25.4 x 15.2 cm (h.w.d.)Weight: 10 pounds/4.5 kgTemperature: 5 to 45 °CApprovals: CE, CSA

18GRAB: 1800 Series QC Sampler, includes (1) 1-liter polypropylenesample bottle, tubing, fittings, power supplies and instruction sheet.

18GBTL: 1-Liter Polypropylene Bottle with Cover, case of 418GTBK: QC Sampler Replacement Tubing Kit224329-A01: Wall Adapter, 115V224330-A01: Wall Adapter, 230V

Specifications: Ordering Information:

X= Expected Standard

Concentration

Injected Standard

(Sample + Injected Standard)

Injected StandardConcentration

15DC15: Dynamic Calibrator, complete with syringe pump and syringekits (150096 and 180096) and mounting bracket, 115V.

15DC20: Dynamic Calibrator, 220V216970-AOI: Low-Level verification kit, includes T-fitting and tubing

Ordering Information:

Low-Level Verification System

QC Sampler

Page 30: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

terms and conditionswarranty informationFor products not listed in this warranty statement, please visit our website at www.thermo.com

28

Minimum order:

The minimum order requirement is $100 for Orion On-Lineproducts. An order is considered to be a purchase order forproducts to be shipped to a single location. International minimumorder requirements may vary. Contact your international coordinatorfor details.

Rush orders:

For customers in the U.S., rush orders received before 12 pmEastern Time will be shipped the same day. Rush orders receivedafter 12 Noon Eastern Time will be shipped the next business day.For customers and dealers in Canada, rush orders will be shippedwithin 2 business days. For customers and dealers outside the U.S.and Canada, contact your international coordinator for rush orderscheduling. All rush orders carry a $50 incremental charge perorder. FOB: Beverly. Freight charges are prepaid and added orfreight collect. All rush order processing is subject to stockavailability.

Returning goods:

Permission to return merchandise purchased from Thermo ElectronCorporation must be obtained prior to return. Contact within 30days of receipt of goods for a return authorization number:

Thermo Electron CorporationEnvironmental Instruments DivisionWater Analysis166 Cummings Center, Beverly, MA 01915. Phone 978-232-6000, fax 978-232-6015 (inside U.S. and Canada), fax 978-232-6031 (outside U.S. and Canada), or call toll free 800-225-1480.

Hazardous materials:

Some materials are designated corrosive/oxidizer by DOT and IATA.Some materials may require special labeling and handling. Carriersmay add additional freight charges for handling/transporting thesematerials. Consolidating such material with other products may beprohibited. Additional freight charges are billed to you per FOBterms. Advise Thermo Electron Corporation of shipping instructionsfor these hazardous materials to reduce your freight costs.

Restocking charge:

Permission to return new, excess inventory must be obtained priorto return. If any item is authorized to be returned for credit as aresult of an incorrect purchase without a reorder, a 25% restockingcharge of the price paid for the product will be made. Internationalcustomer’s restocking fee of 25% will be off the international price.Only new (in-the-box) goods may be returned within 30 days ofshipment from Thermo. Older items, 9-digit parts, anddiscontinued items cannot be returned for credit.

Short shipments:

Thermo must be notified within 30 days of receipt of invoice of anyitem or billing discrepancies. All substantiated claims will beremedied by a credit memo and a new order placed for shortshipment. Any shipment discrepancy claimed after 30 days of

invoice date will not be honored and credit will not be issued by Thermo.

Force majeure:

Thermo shall not be liable for failure to perform or for delay inperformance due to fire, flood, strike, or other labor difficulty, act ofGod, act of any governmental authority or of the purchaser, riot,embargo, fuel or energy shortage, wrecks or delays intransportation, inability to obtain necessary labor, materials, ormanufacturing facilities from usual sources, or due to any causebeyond its reasonable control. In the event of a delay inperformance due to any such cause, the date of delivery or time forcompletion of performance will be extended by a period of timereasonably necessary to overcome the effect of such delay.

Warranty:

Orion On-Line monitoring products are warranted to be free fromdefects in material and workmanship for a period of 12 monthsfrom date of installation or 18 months from date of shipment,whichever is earlier, when used under normal operating conditionsand in accordance with the operating limitations and maintenanceprocedures given in the instruction manual, and when not havingbeen subjected to accident, alteration, misuse, or abuse. Thiswarranty is also conditioned upon expendable and consumableitems (diffusion tubing, electrodes, and all solutions) being storedat temperatures between 5°C and 45°C (40°F and 110°F) in a non-corrosive atmosphere and within the shelf life printed on the product.

In the event of failure within the warranty period, Thermo, or itsauthorized dealer, will, at Thermo’s option, repair or replace theproduct nonconforming to the above warranty, or will refund thepurchase price of the unit.

The warranty described is exclusive and in lieu of all otherwarranties whether statutory, express, or implied including, but notlimited to, any implied warranty of merchantability or fitness for aparticular purpose and all warranties arising from the course ofdealing or usage of trade. The buyer’s sole and exclusive remedy isfor repair or replacement of the non-conforming part thereof, orrefund of the purchase price, but in no event shall Thermo (itscontractors and suppliers of any tier) be liable to the buyer or anyperson for any special indirect, incidental, or consequentialdamages whether the claims are used in contract, in tort (includingnegligence), or otherwise with respect to or arising out of theproduct furnished hereunder.

On-Line products used at overseas nuclear facilities are alsosubject to Thermo nuclear terms and conditions. Contact Thermo ifyou do not have a copy.

Representations and warranties made by any person, including itsauthorized dealers, distributors, representatives, and employees ofThermo, which are inconsistent or in addition to the terms of thiswarranty shall not be binding upon Thermo unless in writing andsigned by one of its officers.

Page 31: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

© Copyright 2003 Thermo Electron Corporation. All rightsreserved. Thermo Electron Corporation, question everything,Analyze. Detect. Measure. Control., AUTOCAL, Pure Water,ROSS and StatFace are trademarks of Thermo ElectronCorporation. Guaranteed Success and The Technical Edge areservice marks of Thermo Electron Corporation. PerpHecTROSS are protected by U.S. patent 4,495,050.

The specifications, descriptions, drawings, orderinginformation and part numbers within this document aresubject to change without notice. This publicationsupersedes all previous publications on this subject.

Be sure to log on to thermo.com for all thelatest information concerning all productsand new releases.

Page 32: Orion On-Line Water Analysis - neotec.cz · Boiler Water Chemistry 3 Power Plant Chemistry 4 Drinking Water 5 ... Boiler Water/ Blowdown Make up Demineralizer (polisher) Anion Bed

Thermo Electron CorporationEnvironmental Instruments DivisionWater Analysis166 Cummings CenterBeverly, MA 01915-6199 USATel: 978-232-6000Dom. Fax: 978-232-6015Int’l. Fax: 978-232-6031

Lit 242720-001 Rev. A 2/03

Customer SupportToll Free: 800-225-1480 www.thermo.com Dom. e-mail: [email protected]’l. e-mail: [email protected]

I S O9 0 0 1

RegisteredQuality System

www.thermo.com