![Page 1: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/1.jpg)
CHUCK MOZINAConsultant – Beckwith Electric
WSU Hands-On Generator ProtectionTrack Overview
![Page 2: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/2.jpg)
Chuck Mozina -- is a Consultant, Protection and Protection Systems for Beckwith Electric and resides in Palm Harbor (near Tampa), Florida. His consulting practice involves projects relating to protective relay applications, protection system design and coordination. He specializes in generator and power plant protection.
Chuck is an active 20-year member of the IEEE Power System Relay Committee (PSRC) and is the past chairman of the Rotating Machinery Subcommittee. He is active in the IEEE IAS I&CPS, PCIC and PPIC committees, which address industrial system protection. He is a former U.S. representative to the CIGRE Study Committee 34 on System Protection and has chaired a CIGRE working group on generator protection. He also chaired the IEEE task force that produced the tutorial “The Protection of Synchronous Generators,” which won the PSRC’s 1997 Outstanding Working Group Award. Chuck is the 1993 recipient of the Power System Relay Committee’s Career Service Award and he recently received the 2002 IAS I&CPS Ralph Lee Prize Paper Award. His papers have been republished in the IAS Industrial Applications Magazine.
Chuck has a Bachelor of Science in Electrical Engineering from Purdue University and is a graduate of the eight month GE Power System Engineering Course. He has authored a number of papers and magazine articles on protective relaying. He has over 25 years of experience as a protection engineer at Centerior Energy, a major investor-owned utility in Cleveland, Ohio where he was the Manager of the System Protection Section. He is also a former instructor in the Graduate School of Electrical Engineering at Cleveland State University as well as a registered Professional Engineer in the state of Ohio.
![Page 3: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/3.jpg)
A major US manufacturer of :
Digital multifunction generator,interconnection and transformer protection
Generator synchronizing and bus transfer equipment
Voltage control devices for LTC transformer, regulators, and capacitor banks
Packaged systems using Beckwith products
![Page 4: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/4.jpg)
Introduction
Contrary to popular belief, generators do experience shorts and abnormal electrical conditionsProper protection can mitigate damage to the machine in many casesGenerator Protection Areas:
Short Circuits in the generator itselfAbnormal electrical conditions may be caused by the generator or the system
![Page 5: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/5.jpg)
Generator Protection
Internal FaultsStator PhaseStator and Field Ground
System Back Up for FaultsPhase and Ground
Abnormal Operating Conditions
OvervoltageOverexcitationLoad UnbalanceLoss of FieldLoss of SynchronismFrequencyLoss of prime moverInadvertent EnergizingCompromised potential source (blown fuse)Open trip circuit
![Page 6: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/6.jpg)
IEEE StandardsLatest developments reflected in:
Std. 242: IAS Buff BookC37.102: IEEE Guide for Generator ProtectionC37.101: IEEE Guide for AC Generator Ground ProtectionC37.106: IEEE Guide for Abnormal Frequency Protection for Power Generating Plants
These are created/maintained by the IEEE PSRC & IASThey are updated every 5 years
![Page 7: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/7.jpg)
C37.102-2006 Updated Version now available which has significant changes and additions.
![Page 8: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/8.jpg)
IEEE Generator Tutorial
![Page 9: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/9.jpg)
FUNDAMENTALS
![Page 10: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/10.jpg)
FundamentalsBasic Synchronous GeneratorsConnections to the systemShort CircuitsGenerator GroundingIEEE GuidelinesDevice Numbers
![Page 11: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/11.jpg)
Basic Synchronous Generator
![Page 12: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/12.jpg)
Generator Excitation & AVR Control
Gen.
AVR ExcitationTransformer
Generator Step-upTransformer
CT VTGenerator
Field
StaticExciter
![Page 13: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/13.jpg)
![Page 14: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/14.jpg)
Synchronous Generator Types
![Page 15: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/15.jpg)
![Page 16: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/16.jpg)
![Page 17: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/17.jpg)
![Page 18: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/18.jpg)
Direct Connected Generatorto Power System
![Page 19: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/19.jpg)
Unit Connected Generator to Power System
![Page 20: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/20.jpg)
GENERATOR CURRENT DECAY
![Page 21: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/21.jpg)
Symmetrical Trace of a Generator Short-Circuit Current
![Page 22: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/22.jpg)
Generator Short-Circuit Currents Phase
![Page 23: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/23.jpg)
Generator Terminal Fault Current
![Page 24: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/24.jpg)
Accumulation of damage over time:
Most of the damage occurs in the period after the generator breaker opens
0
2000
4000
6000
8000
time, sec0.01 0.1 1 10
watt seconds
Wat
t-sec
onds
Total
Generator
System
![Page 25: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/25.jpg)
High Side ofGeneratorBreakerCurrents
GeneratorNeutral
TerminalCurrents
Fault Inception
High Side Breaker Opens
Multi-Phase Generator Fault Oscillograph
![Page 26: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/26.jpg)
Low Impedance Grounding
![Page 27: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/27.jpg)
Types of Generator Grounds
Low ImpedanceUsually a good ground sourceGenerator still likely to be damaged on internal ground fault
Ground fault current typically 200-400 AThis Level of Ground Current Can Cause unacceptable damage
G System
![Page 28: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/28.jpg)
Low Impedance Grounding Generators Bussed Together
![Page 29: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/29.jpg)
High Impedance Grounding
![Page 30: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/30.jpg)
Oscillograph of STATOR Ground Fault
Generator NeutralVoltage
GeneratorPhase
Currents
Fault Inception
Breaker Opens
Trip Command
![Page 31: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/31.jpg)
Types of Generator Grounds
High ImpedanceModerately expensiveUsed when generators are unit connectedSystem ground source obtained from generator grounding transformer Generator damage minimized or mitigated from ground faultGround fault current typically <=10A
G System
![Page 32: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/32.jpg)
Stator Iron Burning
Pictures of stator damage after an internal ground faultThis generator was high impedance grounded, with the fault current less than 10ASome iron burning occurs, but the damage is repairable vs. low impedance grounded machines where the damage is typically severe.
![Page 33: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/33.jpg)
![Page 34: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/34.jpg)
![Page 35: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/35.jpg)
Dual (Hybrid) Grounding
�������������
����� �������������
��������� �
���� ����� ���������������
����� ���������! ������
![Page 36: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/36.jpg)
Hybrid GroundHYBRID GROUNDING
Converts from low to high Impedance Grounding if internal generator fault is detected.
G
51 51N
51 51N
51 51N
87GD
51G
59N
52B
52F1
52F2
52F3
52G
VS
TripExcitation,
PrimeMover
![Page 37: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/37.jpg)
Device Function Discussed in Tutorial Section
21 Distance Relay. Backup for system and generator zone phase faults.
11
24 Volts/Hz protection for generator overexcitation.
6
32 Reverse power relay. Anti-motoring protection. 14
40 Loss-of-field protection. 8
46 Negative sequence unbalance current protection for the generator.
10
![Page 38: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/38.jpg)
Device Function Discussed in Tutorial Section
49 Stator Thermal Protection. 14
51GN Time overcurrent ground relay. 4 & 11
51TN Backup for ground faults. 4 & 11
51V Voltage-controlled or voltage-restrained time overcurrent relay. Backup for system and generator phase faults.
11
59 Overvoltage protection. 6
59GN Overvoltage relay. Stator ground fault protection for a generator.
4
![Page 39: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/39.jpg)
Device Function Discussed in Tutorial Section
78 Loss-of-synchronism protection. 9
81 Frequency relay. Both underfrequency protection.
5
86 Hand-reset lockout auxiliary relay. 14
87G Differential relay. Primary phase-fault protection for the generator.
2
87N Stator ground fault differential . 4
87T Differential relay. Primary protection for the transformer.
2
87U Differential relay for overall generator and transformer protection.
2
![Page 40: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/40.jpg)
Large Machine
FROM IEEEC37.102
Unit Connected,High Z Grounded
![Page 41: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/41.jpg)
NERC PROTECTION SYSTEM
MAINTENANCE REQUIREMENTS
![Page 42: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/42.jpg)
NERC REGIONAL RELIABILITY ORGANIZATIONS (RROs)
![Page 43: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/43.jpg)
NERC RELIABILITY STANDARDS TRANSMISSION SYSTEM - GENERATOR
MAINTENANCE AND TESTING:PRC-005-1 TRANSMISSION AND GENERATION
PROTECTION SYSTEM MAINTENANCE AND TESTING
R1. Each Transmission Owner and any Distribution Provider thatowns a transmission Protection System and each GeneratorOwner that owns a generation Protection System shall havea Protection System maintenance and testing program forProtection Systems that affect the reliability of the BES. Theprogram shall include:R1.1 Maintenance and testing intervals and their basisR1.2 Summary of maintenance and testing procedures
![Page 44: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/44.jpg)
NERC RELIABILITY STANDARDS TRANSMISSION SYSTEM - GENERATOR
MAINTENANCE AND TESTING:PRC-005-1 EVIDENCE OF COMPLIANCE
R2.1 Evidence Protection System devices were maintained and tested within the defined intervals.
R2.2 Date each Protection System device was last tested/maintained.
![Page 45: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/45.jpg)
NERC RELIABILITY STANDARDS TRANSMISSION SYSTEM - GENERATOR
MAINTENANCE AND TESTING:
NERC PROTECTION SYSTEM DEFINED:
RELAY
DC
CT & VTTRIP
CONTROLLOGIC
GEN.SHUTDOWN
CIRCUITBREAKER
![Page 46: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/46.jpg)
NERC RELIABILITY STANDARDS TRANSMISSION SYSTEM - GENERATOR
MAINTENANCE AND TESTING:
CATEGORIES OF PROTECTION SYSTEMS:
UNMONITORED – -------------- Electromechanical and Solid State (no self-testing)
PARTIALLY MONITORED –- Digital Relays with Failure Alarms Send to a Manned Location (Relay Self-Testing)
THOROUGHLY MONITORED – Same as Above Monitoring, Plus Additional Monitoring of Alarms and Performance Measured Values
FULLY MONITORED - --------- Same as Above, Plus Continuous Monitoring of allComponents of the Protection System
![Page 47: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/47.jpg)
NERC RELIABILITY STANDARDS TRANSMISSION SYSTEM - GENERATOR MAINTENANCE AND TESTING:
![Page 48: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/48.jpg)
APPLICATION OF MULTIFUNCTION
DIGITAL GENERATOR PROTECTION
![Page 49: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/49.jpg)
Evolution of Technology in Generator Protection
Single Function Electromechanical
Single Function Static
Single Function Microprocessor-Based
Multifunction Digital Relays
Almost all new generating facilities use this technology
All generator protection functions in on hardware platform
![Page 50: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/50.jpg)
Multifunction Digital Relay
U t i l i t y S y s t e m
5 2U n i t
5 2G e n
8 1 R 8 1 5 9 2 7 2 4
M - 3 9 2 1+
-
V T
C T
R
C T
5 9 N2 7
3 2R
H ig h - im p e d a n c e G r o u n d in g w i t h T h i r dH a r m o n ic 1 0 0 % G r o u n d F a u l t P r o te c t io n
L o w - im p e d a n c e G r o u n d in g w i t hO v e r c u r r e n t S ta t o r G r o u n d F a u l t P r o t e c t io n
V T
V T
2 5
5 9 D
3 V o
C T
8 7G
6 7 N
*
*
T a r g e t s( O p t io n a l )
In t e g r a l H M I( O p t io n a l )
M e t e r in g
W a v e f o r m C a p t u r e
IR IG - B
F r o n t R S 2 3 2C o m m u n ic a t io n
M u l t i p le S e t t i n gG r o u p s
P r o g r a m m a b le I /O
S e l f D ia g n o s t ic s
D u a l P o w e r S u p p ly( O p t io n a l )
R e a r E t h e r n e tP o r t ( O p t i o n a l )
R e a r R S - 4 8 5C o m m u n ic a t io n
B r e a k e rM o n i t o r in g
T r i p C i r c u i tM o n i t o r in g
2 7T N
8 1 A
4 64 92 13 2 5 04 07 8 6 0 F L 5 1 V 5 0 / 2 7
2 76 4 F 6 4 B
8 7G D 5 0 N 5 1 N
T oT e r m n a l
C T s
5 0 N
![Page 51: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/51.jpg)
Multifunction Digital Relay
![Page 52: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/52.jpg)
I/O M-3425A
Standard
Expanded
![Page 53: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/53.jpg)
AdvantagesAdvance technology: reduced maintenanceReduced panel space: more economical, lower price per function, more complete protection on smaller generatorsFlexibilityCommunication capabilitySystem integrationSelf-diagnostics: reduced maintenanceOscillographic capabilitySystem Integration (Input to DCS Systems)
Multifunction Digital RelaysDigital Relays
![Page 54: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/54.jpg)
Va
Vb
Vc
Vn
iA
Hardware Block Diagram
Va
Vb
Vc
Vn
ia
ib
ic
iA
iB
iC
iN
Power Supply
ProgrammableGain Amplifier
MUX
Digital Signal Processor (DSP)
Dual-Ported RAM
Character Liquid Crystal Display
RAM
Flash-Programmable ROM
Host Processor
EEPROM
Clock with battery backup
MMI Module) Target ModuleRS232 and
RS485 Communi-cation
ports
IRIG-B Time Code input
Relay Outputs
Contact Inputs
Anti-Aliasing Low-Pass Filters (LPF)
Analog Multiplexer
VTs & CTs
Va
Vb
Vc
Vn
ia
ib
ic
iA
iB
iC
iN
RAM
Address/Data Bus
Analog-to-Digital Converter
![Page 55: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/55.jpg)
Single Relay
![Page 56: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/56.jpg)
Strategy #1Use a single multifunction relayIf you have a relay failure:
Rely on self-test features to detect failure (MTBF Typically 100 years)Remove generator from serviceInstall spare relayRecommissionReturn generator to service
Cost of Strategy #1No primary and backupProduction loss for generator during off periodModerately sized utility generators (150MW) can result in production losses of over $100,000/day or more.
Levels of Redundancy
![Page 57: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/57.jpg)
Dual Relay Approach
![Page 58: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/58.jpg)
Strategy #2Use duel relay approach
Have defined primary and backup systems
If you have a relay failure:Continue to run the generatorReplace the failed relayRecommissionPlace the new relay in service
Cost of Strategy #2Purchase and installation of a second relay
Levels of Redundancy
![Page 59: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/59.jpg)
Multifunction Generator Protection Application Considerations
Level of Redundancy
Most new generators are gas turbines or steam unit as part of a combined cycle plant
On these projects - generator protection is “pre-packaged” by generator manufactures
Standard offering by many generator manufactures is a single multifunction relay package
![Page 60: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/60.jpg)
Multifunction Generator Protection Application Considerations
Level of Redundancy
There is no remote backup protection for most generation fault/abnormal operation consideration
Utilities need to be aware that if more redundancy is desired - they need to ask for it before generator is ordered
![Page 61: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/61.jpg)
Generator VT Connections
These major VT generator connections are widely used
line to line voltage
line to ground
4-wire
3-wire
line to ground VT connections have unique application considerations
![Page 62: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/62.jpg)
Line to Line VT’s
Common open delta VT connection
Relay VT inputs connected line to line
![Page 63: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/63.jpg)
Line to Ground VT’s
Relay VT input connected line to ground
4 Wire Connection
![Page 64: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/64.jpg)
A ground fault will cause LG connected phase elements through a 3Y-3Y VT to have undervoltage or overvoltage (depending on faultedphase)
System
HighImpedanceGround
SLG
ABC
a
bc
a
bc
ground
Van=Vag
Vbn=VbgVbn=Vbg
n=gvag=0
n
Van= -Vng
Vcn Vbn
VbgVcg
Neutral Shift on Ground Fault:High Impedance Grounded Generator
Fault
Setting Calculations
![Page 65: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/65.jpg)
Line to Ground VT’s
Relay VT input connected line to groundFor stator ground fault neutral shift can result in false indication of overvoltage/overexcitationIdeal solution is to supply voltage functions with phase to phaseIf oscillograph monitors L-G voltage, it can be used to phase identify a stator and fault.
4 Wire Connection
![Page 66: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/66.jpg)
The “Line-Ground to Line-Line” selection shouldbe used when it is desired to provide the phasevoltage-based elements (27, 59, 24 functions)
with phase-to-phase voltages
They will not operate for neutral shifts that canoccur during stator ground faults on high
impedance grounded generators
The oscillograph in the relays will record line-ground voltage to provide stator ground faultphase identification
Voltage Inputs3Y-3Y VT, secondary wired L-G (L-G to L-L selection)Use of L-L Quantities for Phase Voltage-based elements
![Page 67: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/67.jpg)
Line to Ground VT’s
Relay VT input connected line to groundFor stator ground fault neutral shift can result in false indication of overvoltage/overexcitationIdeal solution is to supply voltage functions with phase to phaseIf oscillograph monitors L-G voltage, it can be used to phase identify a stator and faultNeed to coordinate 59N relay with VT secondary fuses to avoid unit trip for a VT secondary ground fault
4 Wire Connection
![Page 68: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/68.jpg)
Line to Ground VT
Relay VT inputs connected line to lineThis VT connection avoids the need to coordinate 59N with VT fusingCan not phase identify stator ground faults
3 Wire Connection
![Page 69: OPG GENERATION PROTECTION SEMINAR - etouches · PDF fileA major US manufacturer of : Digital multifunction generator,interconnection and transformer protection Generator synchronizing](https://reader034.vdocuments.mx/reader034/viewer/2022052213/5a9604f07f8b9ab6188c79b8/html5/thumbnails/69.jpg)
THE END
????QUESTION ????
WSU Hands- On Generator ProtectionTrack Overview