open mdc...open mdc roberto söderhäll, cbdo, swedish modules scott neal, product director,...

21

Upload: others

Post on 31-Dec-2019

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility
Page 2: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Open MDC

Roberto Söderhäll, CBDO, Swedish ModulesScott Neal, Product Director, Schneider Electric

Data Center Facility

Page 3: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

DATA CENTER FACILITY

Specifications

Background

Page 4: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Starting the processDATA CENTER

FACILITY

Specifications

Page 5: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Establishing the ProjectDATA CENTER

FACILITY

Specifications

Page 6: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Community Innovation startsDATA CENTER

FACILITY

Specifications

Page 7: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Merging the best ideas and experiencesDATA CENTER

FACILITY

Specifications

Page 8: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

DATA CENTER FACILITY

Specifications

Time to disclose

Page 9: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Standardizing the MDC Specification

DATA CENTER FACILITIES

The guidelines and specifications for Modular Data Centers optimized for - OCP HW

To meet the OCP´s criteria - Maintainability - Cost and energy efficiency - Openness- Scalability

Specifications

Page 10: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Product InfoScalable 300KW Modular Data Center

Standalone 90KW Modular Data Center 

Page 11: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Scalable 300KW Modular Data Center

Page 12: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

SpecificationsIT Load:• 300-500 kW with N+1 internal UPS redundacy

Floor Space:• Racks: 30/ 28 without UPS/with UPS (average density 10kW/Rack)• Racks: 28/26 without UPS/with UPS (average density up to 18kW/Rack)• Internal Space (L x W x H): 13.35m x 4.45m x 3.55m

Cooling System:• CW system with InRow Coolers @ N+1 Redundancy

Module Weight [kg]:• 20 350/57 350 Empty no racks or IT equipment/Fully equipped racks

DATA CENTER FACILITY

Specifications

Page 13: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Design

Page 14: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Scalability

Page 15: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

EfficiencyBy this design you are reaching good efficiency on these areas:

• Energy use

• Floor Space

• IT-load flexibility

• Foot print of the DC

Planning to deploy OCP HW?

Page 16: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Standalone 90KW Modular Data Center 

Page 17: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

SpecificationsIT Load: • Up to 90kW with N+1 internal UPS redundacy.   100kW with no UPS.

Floor Space:• Racks: 12-14  with UPS or without UPS (density 6.4-7.5kW/Rack)• Internal Space (L x W x H):  13.5m x 3.1m x 3.4m

Cooling System:• DX system with InRow Coolers @ N+1 Redundancy

Module Weight [kg]:• 25 000/44 636 Empty no racks or IT equipment/Fully equipped racks 

DATA CENTER FACILITY

Specifications

Page 18: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Design

12-14 42U racks

Entrance Lobby and Electrical roomIncludes: •400A Main Panel•Fire Suppression and control panel•Auxiliary electrical panel•ATS and controller•Optional EPO

Hot/Cold Aisle Containment

In-Row DX Close Coupled Cooling

Optional UPS & Batteries

Modular PDU or Overhead Busway

Site Works – Condensers, Gensets, Transformer

Page 19: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Repeatability, Flexibility, and SpeedSmaller solutions (less than 100kW) are not typically intended to scale

An All-In-One Modular Data Center dramatically simplifies design and construction

Often these units support single deployments, or multiple deployments in a repeatable design

Common applications include:

Retail warehousingUniversitiesTelco and IoTIndustrial

Page 20: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility

Call to ActionHow to get involved in the project Mailing list: https://ocp-all.groups.io/g/OCP-MDC

Link to Contribution on OCP websiteWhere to see: https://www.opencompute.org/contributions

Where to find additional information (URL links)Project Wiki: https://www.opencompute.org/wiki/Data_Center_Facility/MDC

DATA CENTER FACILITY

Specifications

Page 21: Open MDC...Open MDC Roberto Söderhäll, CBDO, Swedish Modules Scott Neal, Product Director, Schneider Electric Data Center Facility