oncor west texas dynamic line rating (dlr) project · line ratings terminology static rating –...
TRANSCRIPT
![Page 1: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/1.jpg)
OncorWest Texas Dynamic Line Rating
(DLR) Project
ERCOT RPG Overview
March 26th, 2013
![Page 2: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/2.jpg)
Transmission Line Ratings are governed by:
– Current flowing in the conductor
– Conductor size and resistance
– Conductor clearance to ground
– Ambient weather conditions:
• Temperature
• Wind speed and direction
• Solar radiation
Dynamic Line Rating
Ambient Temperature:3.6o F, 2oC change +/- 2%
Solar Radiation:Cloud shadowing +/- a few
Wind increase 3.2 ft/sec (2.2 mph): 45 angle + 35%90 angle + 44%
![Page 3: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/3.jpg)
Line Ratings Terminology
Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per second wind
Ambient Adjusted Rating (AAR) – adjusted for ambient temperature other than Static Rating base temperature
Dynamic Line Rating (DLR) – adjusted rating based on actual measured ambient conditions
![Page 4: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/4.jpg)
Integrated DLR System
SCADA/EMS Master
Existing SCADA protocolover substation RTU channel(RS232/485)
License freeSpread Spectrum Radio
IntelliCATTM
for WindowsICCP or MODBUS protocol
CAT-1™ and line load data from EMS
Substation
Control Center
Transmission Line
Operator’s Console’
CATMasterTM
Base Station
Line capacity and temperature to EMS
TGM & ERCOT Operations Telemetry
![Page 5: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/5.jpg)
DOE DLR Project Description
![Page 6: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/6.jpg)
LOCATION OF INSTRUMENTED CIRCUITS• Study Area in Critical Congestion Zone
– 42 Loadcell Tension Monitors– 8 Master Locations Feeding into SCADA
![Page 7: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/7.jpg)
1400
1900
2400
2900
3400
3900
4400
25-A
ug
25-A
ug
26-A
ug
27-A
ug
Ratin
g (A
mps
)
Time of Day
Dynamic Line Ratings and Ambient Adjusted RatingsTradinghouse-Temple Pecan Creek, August, 2011
Time Series
Ambient Adjusted Rating Dynamic Line Rating Static Rating
Example of Capacity ChartStatic, Ambient-Adjusted & DLR Ratings
![Page 8: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/8.jpg)
Example of Capacity ChartStatic, Ambient-Adjusted & DLR Ratings
1400
1900
2400
2900
3400
3900
4400
25-A
ug
26-A
ug
27-A
ug
Ratin
g (A
mps
)
Time of Day
Dynamic Line Ratings and Ambient Adjusted RatingsTradinghouse-Temple Pecan Creek, August, 2012
Time Series
Ambient Adjusted Rating Dynamic Line Rating Static Rating
![Page 9: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/9.jpg)
Percent Time Above Static
0.000%
10.000%
20.000%
30.000%
40.000%
50.000%
60.000%
70.000%
80.000%
90.000%
100.000%
110.000%
Aug
ust-1
1
Sep
tem
ber-1
1
Oct
ober
-11
Nov
embe
r-11
Dec
embe
r-11
Janu
ary-
12
Febr
uary
-12
Mar
ch-1
2
Apr
il-12
May
-12
June
-12
July
-12
Aug
ust-1
2
Sep
tem
ber-1
2
Oct
ober
-12
Nov
embe
r-12
Perc
ent
of T
ime
Lake Creek -Temple 345 kVDLR & AAR Percent of Time Above Static
DLR above static AAR above static
![Page 10: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/10.jpg)
Annual Probability Distribution
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
3400
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Ratin
g (A
mps
)
% of Time
Cumulative Probability DistributionAugust 2012 - December 2012
DLR AAR Static Rating No wind
Static Rating 1794 amps -DLR provided 99.2% of time
DLR exceeded AAR rating90% of time
![Page 11: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/11.jpg)
DLR Congestion Mitigation
• Target Lines – can significantly mitigate congestion toward $0; with +5 to +10% DLR;
• Peripheral Lines – radiate from one of the target endpoint substations – see additional relief
• Ripple effect – some additional congestion impacts distant from target lines– Some mitigation– Some increases – Grid flexibility – System awareness increased
![Page 12: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/12.jpg)
West Texas DLR Project
DLR Applied to 5 Target Lines:Odessa – Odessa North 138 kV (4)
Moss – Amoco Cowden North – Holt 138 kV (3)
Holt – Emma Tap 69 kV (1)
Moss – Odessa Southwest – Odessa EHV 138 kV (3)
Midland East – Winwood 138 kV (1)
() Number of DLR units on target line
![Page 13: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/13.jpg)
West Texas DLR Project
![Page 14: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/14.jpg)
West Texas DLR ProjectDLR Application in ERCOT Nodal System
• Ratings polled from Oncor server by ERCOT every 10 secs
• DLR Ratings updated every 10 minutes (remember time constant of conductor)
• Oncor posts DLR rating (if passes quality and availability check)
orAAR rating (default if DLR is not available)
• SCED operates on posted ratings every 5 minutes
![Page 15: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per](https://reader034.vdocuments.mx/reader034/viewer/2022051910/5fff2c87673b2e5ea17212d4/html5/thumbnails/15.jpg)
West Texas DLR Project
DLR Installation Milestones
• Schedule line outages to install DLR loadcells starting March 18th
• Calibrate DLR ratings completed May 17th
• Post DLR ratings to ERCOTcompleted May 31st