Okoguard Is Okonite's registered trade name forits exclusive ethylene-propylene rubber (EPR)base, thermosetting compound, whose optimumbalance of electrical and physical properties isunequaled in other solid dielectrics. Okoguardinsulation, with the distinctive red color and atotally integrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free service.
Type MV-105 conductors are assembled withfillers, three bare stranded grounding conductorsand a binder tape into a round core. A continu-ously corrugated welded aluminum sheath(C-L-X) encases the cable core. The C-L-Xsheath is protected with a low temperatureyellow Okoseal® jacket. The impervious, con-tinuous, corrugated aluminum C-L-X sheathprovides complete protection against moisture,liquids and gases in addition to its excellent me-chanical strength. In addition, the aluminumsheath has adequate ampacity capability to beused as a grounding conductor in non HL areas.The Okoseal jacket allows the cable to be directburied in the ground, embedded in concrete orareas subjected to corrosive atmospheres.
C-L-Xpower cables are recommended as aneconomical alternate to a wire in conduit system.They are designed specifically for use as feed-ers or branch circuits in industrial and utilitypower distribution systems. C-L-Xpower cablesmay be installed in both exposed and concealedwork, wet and dry locations, directly buried in theearth, or embedded in concrete. They may beinstalled on metal racks, troughs, in cable traysor secured to supports not greater than 6 feetapart.C-L-X Type MC-HL cables are also approved forClasses I, II, and III, Division 1 and 2 and ClassI, Zones 1 and 2 hazardous locations - NEC Ar-ticles 501, 502, 503 and 505.
Uncoated copper compactstranded per ASTM B-496.
Extruded semiconducting EPRstrand screen meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMAWC74 and UL 1072.
Okoguard meets or exceeds theelectrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072. The insu-lated conductors are tested in accordance withAEIC CS8.
Extruded semiconduct-ing EPR insulation screen per ICEAS-93-639/NEMA WC74, AEIC CS8 and UL1072.
5 mil uncoated copper tape with12.5% nominal overlap.
Color coded (black,red, blue) polyester ribbon laid longitudinallyunder the copper shield tape.
Three uncoatedcopper in accordance with UL 1072.
Cabled with fillers and groundwires in the interstices, binder tape overall.
Close fitting, impervious, continu-ous, corrugated aluminum C-L-Xper UL1072, and UL listing E-60545; C-L-X is rec-ognized as a grounding conductor by NEC.
A low temperature, sunlight resis-tant, yellow PVC jacket in accordance withUL 1072. Other color jackets are available.UL Listed as type MV-105 or MC-HL, sun-light resistant for use in cable tray, and fordirect burial in accordance with UL 1072 &2225. Conforms to applicable requirementsof IEC 60502, 60332-3 and IEEE 1580. CSAListed to C68.3.
• Triple tandem extruded, all EPR system.• Complete prepackaged, color coded, factorytested wiring system.• Okoguard C-L-X cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).• Passes the vertical tray flame test require-ments of IEEE 383 and 1202, UL 1072,ICEA T-29-520 (210,000 BTU/hr.).• Complies with NEC Sections 310.7 and300.50 for direct burial.• Complies with NEC Articles 501, 502, 503 and505 for hazardous locations.• Continuous sheath provides grounding safety.• Excellent corona resistance.• Screens are clean stripping.• Exceptional resistance to “treeing”.• Minimum installation temperature of -40°C.• Improved Temperature Rating.• Three symmetrical grounding conductorsfor PWM/VFD and other modern ACdrive/motor applications.• ABS listed as CWCMC Type MC-HL.• CSA listed as FT4 and LTGG (-40°C).
C-L-X® Type MV-105 or MC-HL5/8kV Okoguard
®Shielded Power Cable-Aluminum Sheath
3 Okopact (Compact Stranded) Copper Conductors/105°C Rating5kV-133% or 8kV-100% Insulation Level
Uncoated (Compact Stranded)Copper ConductorsExtruded Semiconducting EPRStrand ScreenOkoguard Insulation (EPR)Extruded Semiconducting EPRInsulation ScreenPhase Identification TapeThree Copper GroundingConductorsUncoated Copper ShieldFillers and Binder TapeImpervious, continuous,Corrugated Aluminum C-L-X SheathJacket-Yellow Okoseal
ULR
C-L-X Type MV-105 or MC-HL3 Okopact (Compact Stranded) Copper Conductors/105°C Rating100% and 133% Insulation Level
571-22-3694571-22-3696571-22-3698
864
8.413.321.2
0.400.440.48
3x123x103x10
1.041.121.21
26.428.430.7
1.291.371.51
505060
1.271.271.52
1.401.481.65
35.637.641.9
90710901398
105612591556
6688
115
5877
100
90115150
� 571-22-3706571-22-3708571-22-3710
21
1/0
33.642.453.5
0.540.580.61
3x103x83x8
1.341.401.48
34.035.637.6
1.641.691.78
606060
1.521.521.52
1.781.821.91
45.246.248.5
173219922273
189021373012
154180205
135155185
190215245
� 571-22-3717� 571-22-3725
571-22-3727
2/04/0
250
67.4107.0127.0
0.650.750.80
3x83x73x6
1.571.781.90
39.945.248.3
1.872.152.28
606060
1.521.521.52
2.002.292.44
50.858.262.0
261636134175
417139804390
240320355
210285315
280360395
� 571-22-3838� 571-22-3846
571-22-3748571-22-3751
350500750
1000
177.0253.0380.0507.0
0.891.011.191.34
3x63x53x43x4
2.102.352.733.06
53.357.669.377.7
2.452.763.243.64
75758585
1.911.912.162.16
2.612.913.423.81
66.371.386.996.8
53287095
1013412966
54357603
1102114596
440545685790
390475585660
475570700785
Visit Okonite's web site, www.okonite.com for the most up to date dimensions.
F/11050222
� Available from our Customer Service Centers.
Optional jacket types available - consult local sales office.
Aluminum conductors are available on special order.
Ampacities are in accordance with Table 310.60(C)(71) of the NEC for aninsulated three conductor cable, isolated in air, with a conductor operating tem-perature of 105°C and an ambient air temperature of 40°C.
Ampacities are in accordance with Table 310.60(C)(75) of the NEC for athree conductor Type MV-105 or MC cable installed in uncovered cable tray in
accordance with Section 392.80(B) of the NEC with a conductor operating tem-perature of 105°C and ambient air temperature of 40°C. Where the cable tray iscovered for more than six feet with solid unventilated covers, the ampacitiesshall not be more than 95% of the values shown above.
Ampacities are in accordance with Table 310.60(B)(83) of the NEC for an in-sulated three conductor cable directly buried in the earth with a conductoroperating temperature of 105°C, ambient earth temperature of 20°C, 100% loadfactor and thermal resistance (RHO) of 90.Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacity Tables, or the Ok-onite Engineering Data Bulletin for installation in duct banks, other ambienttemperatures, circuit configurations or installation requirements.C-L-X® The Okonite Company
ULR
THE OKONITE COMPANYRamsey, New Jersey 07446