okken - eurosic · okken complies with international standards concerning type tested assemblies...

26
Okken Get more with the worlds Power & Control specialist for and high dependability switchboard power distribution up to 6300A motor control

Upload: vudang

Post on 11-Feb-2019

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken

Get more with the world�s Power & Control specialist

for and

high dependability switchboardpower distribution up to 6300Amotor control

Page 2: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric1

page

General 2

n Presentation 2n Technical data 3n The strong points 4

Description 6

n Cubicle architecture 6n Connections 7n Frameworks, cover panels 8n Busbars 10n Fonctional units 12

Choice of equipment 18

n Modularity charts 18

Dimensions 20

n Ground fastening 20n Cable entry 21n Civil engineering 22

Additional technical information 24

n Service rating 24

Okken Contents

Page 3: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric2

General Presentation

Okken complies with international standards concerning Type TestedAssemblies (TTA), in particular :n IEC 60439-1, concerning construction of LV assembliesn IEC 60529, defining the degrees of protection of enclosures and theequivalent national standards.The announced performances have undergone natural size type tests.

Reference standards

Applications Okken is a low voltage switchboard with modular structure for electricaldistribution and motor control applications in large sites of industrial,tertiary and infrastructures.

Its characteristics guarantee a high level of dependability, a perfectadaptation to the needs of the application and a high degree ofupgradeability.Its ergonomic design simplifies switchboard installation on site, as wellas operation and maintenance.Innovating, patented solutions provide an answer to the demandingdeadline and continuity of supply requirements : delayed differentiationand live reconfiguration*.

An homogeneous system of frameworks and busbars means thatequipment with front or rear connection can be produced in optimumaccessibility conditions.The various feeder types chosen according to service rating (IS)required by the applications can be combined in the same column or inthe same switchboard. Likewise, distribution feeders and motor controlfeeders can be combined.

A switchboard with an international vocation, Okken is designed tosatisfy most local habits.

* Live work must be carried out by authorised personnel.

Page 4: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric3

General Technical data

mechanical datacable entry top/bottomaccess front/rearIP 31/42 IP54: consult usIK 10form 2b/3b/4a/4bwithdrawability FFF/WFD/WFW/WWW

dimensionsheight 2200/2350width 650/900/1000/1100/1150/1300depth 600/1000/1200/1400average weight per section 650 kgcoating epoxy/polyester powder (SP03) polymerised > 50 µframework colour RAL 7016panelling colour RAL 1000

electrical datarated insulation voltage (Ui) 1000 Vrated operational voltage (Ue) 690 V ACrated frequency (F) 50/60 Hzrated impulse voltage (Uimp) 12 kVrated auxiliary circuit voltage 230 V AC max.overvoltage category IVpollution degree 3rated current (ln) 6300 Ahorizontal busbar rating 6300 Avertical busbar rating 4000, 2100 et 1500 Arated short-time current (lcw)1s horizontal busbar (rated peak current lpk) 50/80/100/150 kA rms

(110/176/2200/330 kA)rated short-time current (lcw)1s vertical busbar (rated peak current lpk) 50/80/100 kA rms (110/176/220 kA)rated conditional short-circuit current (lsc) up to 150 kAprotection of persons againstinternal arcs IEC 61641 100 kA rms 0.3 searthing system TT-IT-TNS-TNCpower incomer and feeder limits up to 6300 Amotor control feeder limits up to 250 kW 400 V

general dataapplications distribution

motor controlIS (service rating) 211 to 333reference standards IEC 60439-1IEC 60529climatic resistance damp heat withstand as per IEC 60068-2-30

dry heat withstand as per IEC 60068-2-2low temperature resistance as per IEC 60068-2-1salt spray resistance as per IEC 60068-2-11

installation indoorenvironment (EMC) type 2

Data

Page 5: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric4

General The strong points

Adaptability

n Equipment is chosen according to operating, maintenance,upgrading, layout and budget requirements which can be contradictory.The wide range of solutions offered by Okken in terms of dimensions,connection type, installation mode, service rating, combinationpossibilities, delayed differentiation, equipping reserve space at a laterstage, including for fixed feeders, enables it to meet projectrequirements and needs as closely as possible.n Management of modifications during the project is simplified byinterchangeability of FUs and the fact that they can be cabled outside theswitchboard.n Upgrades made exactly when required, without having to anticipatereserve space equipment, limit investments to what is strictlynecessary while at the same time keeping intact the capacity toadapt and change the installation.

Ease of installation

n One of the key moments in the success of a project is that ofinstallation and connection on site. Breaking times are normallyshort, mistakes unforgivable and working conditions uncomfortable.n Okken provides new answers that simplify and ensure the reliability ofthis phase.o built-in handling plinth, allowing movement by pallet truck or liftingdeviceo removable cross-pieces and cross-members allowing access toconnection compartments (patented system) for carrying out of cable-end lugs outside the switchboard.o wide choice of front or rear connection compartmentso pre-mounted sliding fishplates, easily accessible thanks to theremovable cross-memberso standardised connection for busbar trunking including phaseinversion and dimensional compensation devices.

Page 6: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric5

General The strong points

n OKKEN is a Large Site switchboard. Considerable stress is exertedon these switchboards during operation by a hostile environment, rapidintervention and modification needs. In view of the demandingrequirements for continuity of supply, interventions are frequentlyperformed in urgent, stressful conditions.n Safety of operators and installations is thus a decisive criterion inOkken�s design.n In addition to a wide choice of partitioning forms, Okken ischaracterised by :q red insulators for clamps in contact with the busbarq a red IP XXB busbar protection gridq self-compensated double clamps for the FU/busbar connectionq a draw-out safety device on plug-in and disconnectable FUs (>80A)q disabled drawer operation when the device is closed (for drawersequipped with Compact circuit-breakers or fuse-switches).q mechanical indexing and front panel indication of drawer positions.q ergonomic grippers for plug-in and disconnectable FUsq intuitive layout of drawer operating, control and signalling devicesq design allowing, in addition to lifting using slings, positioning of eachcolumn by pallet truckq standardised and tested connections with busbar trunking.

Safety

Ease of maintenance

n Operations of maintenance, as well as upgrading, are easier, fasterand safer, thanks to the Polyfast system (patented system). Withdrawalof a moving part, replacement or addition of a fixed part, and even totalreconfiguration are possible without switching off the section*. Theseadvantages, previously reserved to withdrawable technologies, arenow applicable to plug-in and disconnectable functional units.n As their connection to the busbar are made by means of clamps, thesame advantages apply to fixed and plug-in on base units. In this caseload interruption is necessary but limited to the mounting plate fitting.n The use of a double-clamp connection system simplifies the workof maintenance of the switchboard on a critical element : thedistribution busbar. The constraints it suffers are reduced, theclamps can be easily inspected or changed.

* Live work must be carried out by authorised personnel.

Page 7: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric6

Description Cubicle architecture

The cubicle houses the power devices and the busbars and is dividedinto 4 fully partitioned zones. The auxiliaries and connections are placedin specific compartments located at the rear or on the side of thecubicle. This design protects auxiliaries from undesirable effects(temperature rise, electromagnetic radiation) generated by the powercircuits. Okken�s minimum form is 2b. Moreover, the degree ofprotection IP2X is guaranteed when the switchgear zone doors are openand the functional units are in the �test, draw-out or withdrawn� position.

n main busbar : a single sizePlaced at the top of the switchboard, the main busbar is installed in avolume whose height does not vary whatever the connection andincoming configuration, and with a depth of 600 mm up to 4000 A.

n switchgearThe zone intended for switchgear is defined vertically in 25 mm highmodules. Installation of the FU includes the volume required for properoperation, for the safety perimeter, for connections and for protectionagainst direct contact.

n distribution busbar : always at the rear of the power devicesThe vertical busbar leaves the zone intended for switchgear and itsconnections completely free.

n the plinth: for column handling and switchboard ventilationThe plinth is used to fix the switchboard to the ground and includes ahandling space for pallet truck or fork-lift truck.Anti-intrusion grids allow cool air to enter the column. Natural convectionmaintains a normal operating temperature.

Distribution of zones in a cubicle

Page 8: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric7

ConnectionsDescription

SCside connection

RCrear connection

BDCbottom directconnection

TDCtop direct

connection

n Connections can be made traditionally from the front or rear, from thetop and/or the bottom. The layout and position of busbars allowsconsiderable space for cable entry from the top, including in frontconnection, without penalising heat loss characteristics or fishplateaccess. In front connection, the connection compartment is located tothe right of the switchgear cubicle.n Furthermore, Okken allows direct connection configurations on apower device in a 600 mm deep cubicle, from the top or from thebottom. This option is particularly advantageous for reducingswitchboard ground surface area without compromising connectionease.n Connection to the power circuit-breakers is possible by cables or bybusbar trunking system.Should busbar trunking be used, the transformer/busbar trunking/switchboard assembly is tested (Type Tested Assembly).This assembly includes standardised connection interfaces, a phaseinversion device and a compensation element for dimensionalcompensation.n The power cables are clamped on cable tie-bars and rails.n The auxiliary cables are fastened on a metal trunking.

Connection types

Page 9: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric8

Description Frameworks, cover panels

The framework receives various types of panels for equipmentprotection :n Front panel:q Plain doorq Transparent doorq Dedicated partial door

for Masterpactfor Compact

q Drawer front panelq Reserve space front plateq IP 31 ventilation gridq IP 42 cover platesn Rear panel:q Screwed-on rear panels, if the switchboard is connected from thefrontq Doors if the switchboard is connected from the rearn Side panels:q Screwed-on plain panels, in 2 superposed parts.n Top partq Roofn Bottom partq Gland plates

Inter-column and front-rear separations (for 250 mm wide auxiliarycompartments) complete the partitioning of each column.

Cover panels

The framework of an Okken cubicle consists of vertical frames andhorizontal cross-pieces supported by a transport plinth, forming ashock-resistant and rigid assembly that cannot be deformed. Thecross-pieces and cross-members can be disassembled from theoutside while preserving overall rigidity to allow carrying out of cable-end lugs outside the switchboard and simplify fishplating (patentedsystem). A variety of width and depth combinations allow assembly ofswitchgear cubicles and auxiliary or connection compartments.The switchgear cubicles have a single size up to 4000 A.

Frameworks

Page 10: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric9

Description Frameworks, cover panels

Associations

n Likewise for front connection, compartments from 350 to 650 mmoffer an excellent cabling comfort whatever the cross-section of thecables to be connected.

650

600

650 650

600

450

650

600

350

400

1150

600

400

1150

600

400

Note : for NW40b to NW63, the basic cubicle is 1150 x 1000 mm.

650

n The basic switchgear cubicle is always 650 x 600 mm, for allswitchgear up to Masterpact NW40. A variety of depths are feasible forrear connections according to the configuration.

650

600

600400

650

600600

650

400

600

400

n A 250 mm wide compartment is dedicated to implementation ofauxiliaries. It is installed:q to the left of a switchgear cubicle equipped with Masterpact in front orrear connectionq to the right of a switchgear cubicle in the other configurations withrear connectionIn front connection apart from Masterpact, auxiliaries are installed in theconnection compartment.According to the switchgear to be installed, wider compartments, up to650 mm, can be used.

600

650250 450

600

650 250

600

600

650250

600

Masterpact frontconnection

Masterpact rearconnection

Other rearconnection

Page 11: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric10

Description Busbars

The protective conductor ensures equipotential bonding of frames. It ismade up in each cubicle of a horizontal conductor connecting columnframes to one another and of a vertical conductor accommodating thepower cables protective conductors and the earthing connections whendevices so require.Cross-section : 40 x 5 for lcw < or = 50 kA

40 x 10 for 50 kA < lcw < 100 kA80 x 10 for lcw > 100 kA

Protection conductor

Auxiliary busducts ensure distribution of auxiliary supplies andreference voltages of monitoring circuits, as well as of somecommunication buses. They are installed in the connectioncompartments throughout the useful height of the cubicle.

Auxiliary busducts

Installed in a partitioned compartment to the rear of the switchgear zone,it consists of 10 mm thick bars whose cross-section and/or numberdepend on the current to be distributed in the cubicle. Functional unitsup to 630 A are connected without drilling by means of clampconnections. Access to the busbar is protected at the front by IP2Xinsulating grids. Power circuit-breaker connections are screwed on. Theslots for the Masterpact NW are standardised and bars are punched inthe workshop, thus allowing addition on the site.

Distribution busbars

Placed horizontally in a partitioned compartment at the top of theswitchboard, it consists of copper bars with a single cross-section (40 x10), whose number varies according to rated current, ambienttemperature and degree of protection of the enclosure. The connectionsto the distribution busbars and fishplates are made without drilling, thussimplifying site extensions. The original square type layout of the barsoffers 3 advantages :q the best layout in terms of limitation of electromagnetic radiationq it frees the surface necessary for cable penetration from the top infront connection, while at the same time preserving a favourable thermalexchange at busbar levelq It increases electrodynamic withstand of the busbar.

Note: Beyond 4000 A, the busbar is double and requires a minimumdepth of 1000 mm.

Main busbar

Page 12: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric11

Page 13: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric12

Description Fonctional units

The range of Okken functional units covers all needs, whether they areexpressed in terms of installation mode, withdrawability, form or ServiceRating (IS).Dimensions are standardised for each type of device installed andexpressed in 25 mm high modules. FUs normally take up all the usefulwidth of the cubicle. For drawers, a half-width version for < 37 kWpowers increases installation capacity in the switchboard.Switchgear up to 630 A is installed on mounting plates or interfaces, thewhole forming complete independent and interchangeable functionalunits.These functional units give priority to delayed customisation, in theplant and on site, as each one can be prepared outside theswitchboard.

General

Page 14: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric13

Description Fonctional units

These blocks with 6 sliding contacts accommodate the cabling of theauxiliary circuits and perform the �test� function of the drawers :power disconnected, auxiliaries connected.The moving part is protected mechanically when the FU is removed. Thefixed part is installed on the right-hand side plate of the fixed part of theFU and houses the �customer� cables in front connection. Cablingbetween the fixed part and the output terminal block is only necessary inrear connection.

Equipment capacity :Drawers as from 6 modules : 4 blocks (24 contacts)3-module drawers : 2 blocks (12 contacts)Plug-in Polyfast : 2 blocks (12 contacts)Disconnectable Polyfast : 2 blocks (12 contacts)

Withdrawable auxiliary blocks

Up to 630 A, all functional units are connected to the distribution busbarby a double-clamp connection, allowing interchangeability and quickadditions, while also preventing wear and damage to the busbar duringplug-in/plug-out operations. These clamps (patented system) are self-compensated without limit value so that clamping force increases withshort-circuit current.There is thus no risk of repulsion of a drawer or FU whatever the short-circuit current.For feeders on mounting plate, mountable and removable with poweroff, clamps are fastened to the support assembly.For other FU types, they are accessible when the functional unit iswithdrawn and can be installed or removed with power on*, without risk,thanks to the IP2X protection of the busbars and clamps. In order toimmediately identify the parts in contact with live parts, the insulator ofthe clamps connected to the busbar is red.As clamps form a vital component for functional features,performance and reliability of the switchboard, they benefit fromindividual manufacturing inspections and total traceability.

Clamps

Polyfast interfaces (patented system) are dedicated to Compact NS100to NS630 and GV7 circuit-breakers. They are made of an insulatingmoulded material. Acting as a base for disconnectable, plug-in,withdrawable in drawer units, they ensure dependability of a device/installation system assembly, standardised and tested. The built-in,insulated power connections provide effective protection against internalarcing risks. Plug-in and plug-out on load is impossible in allconfigurations thanks to the safety mechanism tripping the device.Auxiliary wiring is made secure in a dedicated zone and connected tothe sliding contact connectors attached to the interface : switchboardlegibility is facilitated, maintenance simplified and interference betweenpower circuits and auxiliaries reduced.Polyfast also ensures prompt intervention, interchangeability, easyaddition with power on* and flexibility.

Polyfast

* Live work must be carried out by authorised personnel.

Page 15: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric14

Description Functional units

Disconnectable solutions offer an economic alternative to plug-insolutions, if the skills of maintenance personnel and operatingrequirements allow intervention on downstream connections.Okken increases the safety level of the disconnectable FU by means ofa draw-out safety device and use of double-clamps for the busbarconnection.The description is the same as the Polyfast plug-in FU, except for thedownstream clamps : the downstream cables are directly connected tothe downstream terminals of the device.The auxiliaries are cabled to sliding withdrawable auxiliary blocks. Theoperating mechanisms are accessible behind the door.

Disconnectable Polyfast FU

This solution simplifies maintenance of high power devices (Masterpactand Compact NS 630b to NS1600). The devices are installed on achassis allowing the �plug-in / test / draw-out / withdrawn� positions withacknowledgement by mechanical action from the front when changingfrom one position to another. In all positions, the IP 2X degree ofprotection is maintained. Form 4b is recommended on all incomingunits (form 3b minimum by design).

Withdrawable on chassis FU

This solution offers, for distribution, the highest possible level offlexibility and safety :q free addition and reconfiguration,q easy modification of rating,q non-propagation of arc inside the FU,q draw-out safety,q identification of risk zones,q cabling of power and auxiliaries circuits outside the switchboard,q easy gripping.The functional unit is made up of a fixed part, installable and removablewith power on*, equipped with upstream and downstream plug-inclamps and with a moving interface, Polyfast, supporting the circuit-breaker, of the fixed type. Ergonomic handles simplify gripping of themoving part. The downstream connections are made in the fixed part onconnection bars in the side or rear compartment, and the auxiliaries onsliding withdrawable auxiliary blocks. The operating mechanisms areaccessible behind the door.

Plug-in Polyfast FU

* Live work must be carried out by authorised personnel.

Page 16: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric15

Description Functional units

The drawer is used to make up a FU consisting of several mechanicallyattached devices, that can assume the �plug-in / test / draw-out /withdrawn� positions, allowing the padlocking procedures andincorporating the man/switchboard interface elements on the frontpanel.

These functions are particularly important in motor control. Indistribution, the need to indicate and control on the front panel of the FUand the necessity to padlock are the main choice criteria for thissolution.The fixed part can be installed and removed with power on and supportsthe upstream and downstream plug-in clamps.The moving part supports the switchgear by means of an interface or amounting plate. It is guided in its movement and positioning, and ballbearings minimise the operating effort.The �plug-in / test / draw-out� positions are mechanically marked by anindexing device associated with a mechanical indicator on the frontpanel.

The front panel of the drawer gives priority to ergonomics and intuition ofoperations by the arrangement of the locking facilities and operatingmechanisms.Access to the inside of the drawer may be necessary during operation,to make settings or carry out a thermographic check. A deliberateopening by swivelling the front panel is possible using a tool.

Operating safety is guaranteed by a mechanical device disablingworking when the protection device is closed (for drawers equipped withCompact NS80, NS100 to NS630, GV7, and GS1 fuse-switches). An IP2X degree of protection is maintained in the test and draw-out positions.Locking is possible in all positions by a padlock (3 padlocks notsupplied), as is also padlocking of empty compartments.

Downstream connections are made in the fixed part on connection bars.The auxiliaries are connected to sliding blocks attached to the fixed andmoving parts which considerably reduce cabling.

Test position : power circuits are isolated upstream and downstream,while the control circuits remain connected in order to check off-loadoperation of the auxiliary circuits and automation systems.

Polyfast drawerThe switchgear is mounted on a Polyfast interface. This solution is usedfor distribution feeders by Compact NS100 to NS630 circuit-breaker. It isalso chosen in motor control for feeders of the �line starter� type,protection of which is ensured by a Compact NS100 to NS630 or GV7circuit-breaker.

Versatile drawerMounting plates adapted to the devices support the various componentsof the Functional Unit. This very open solution is applied in all othercases (for example : motor control feeder with GV2 or �line starter�equipped with an NS80 circuit-breaker) and is available in full-width andhalf-width drawers.

Withdrawable FU

* Live work must be carried out by authorised personnel.

Page 17: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric16

Description Functional units

This type of functional unit combines the savings of a fixed solution withthe flexibility provided by plugging in on busbar. The devices, of the fixedor plug-in on base type, are mounted on a support assembly equippedwith clamps allowing addition of a feeder with reduced breaking time.This assembly is completely assembled and cabled on table, includingany current transformers required. A mechanical device preventsuntimely removal of the FU, removal of which requires section switchingoff . Two devices (up to 250A) can be installed on the same mountingplate. The downstream cables are connected on connection bars orterminals in the side or rear compartment. The operating mechanismsare accessible on the front panel through an individual door.This solution combining total separation of FUs from one another andan individual door allows assembly of completely partitionedswitchboards (3b form minimum).

Choice of plug-in devices means they can be extracted for maintenanceor modification of rating without interrupting the power supply.

FU on mounting plate, fixeddevice or plug-in on base device

The disconnectable mounting plate FU is used in small distribution andfor low rating motor feeders with direct starting (which represent themajority of feeder units).This solution, for front connection, optimises cost and installationcapacity while giving priority to interchangeability and flexibility of livereconfiguration*. It requires intervention on downstream connections onextraction. This FU consists of a fixed part, that can be installed andremoved with power on*, equipped with upstream plug-in clamps(double-clamps) and of a moving part supporting the devices, of fixedtype. The downstream cables are connected to the device terminals andthe auxiliaries to connectors. The operating mechanisms areaccessible behind the door.

Disconnectable mountingplate FU

Protection of distribution feeders by horizontal fuse-switch 160A(size 00) to 630A (size 3) in front connection, satisfies the habits ofcertain countries. Okken allows functional, tested integration of suchunits, complying with the specifications of the fuse-switch manufacturerin order to guarantee the heat loss level required. All the accessoriesequipping these devices can be implemented. The downstreamconnections are made on terminals built into the device. Access tofuses is interlocked with the switch.

Jean Müller fuse-switchdisconnectable FU

* Live work must be carried out by authorised personnel.

Page 18: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric17

Description Functional units

Summary of functional units installation mode applications connections IS forms

IEC 60439-1 IEC 60439-1withdrawable on chassis DF WWW 332 3b-4bfixed on mounting plate DF FFF 211 3b-4bplug-in on base,on mounting plate DF WWW 232 3b-4bJean Müller fuse-switchdisconnectable DF WFD 223 3b-4bdisconnectable mounting plate DF MCF WFD 223 2bdisconnectable Polyfast DF WFW 223 4aplug-in Polyfast DF WWW 233 3b-4bwithdrawable in Polyfast drawer DF MCF WWW 333 3b-4bwithdrawable in versatile drawer MCF WWW 333 3b-4bwithdrawable in 1/2 width drawer DF MCF WWW 333 3b-4b

D f : distribution feedermcf : moteur control feeder:

1, 2 or 3 devices for 1 starter. Type 2 co-ordination, IEC 60947-4.

n Masterpact NW and NT high power circuit-breakers withdrawable onchassis, manual operating mechanism or motor mechanism throughdoorn Fixed or plug-in Compact NS moulded case circuit-breaker, toggle,rotary handle or motor mechanism, through door, behind door, or indrawer.n Contactors and thermal relaysn Fuse switchesn Disconnectable fuse-switchesn Measuring and metering devicesn LV/LV transformersn Relaysn Automation systemsn etc.

Switchgear installed

Summary of the installation andcontrol types

installation mode Masterpact Compact GV7 GV2/Integral sectionneur- Multi 9NW/NT NS400/630 NS400/630 NS80 + fusibleCompact NS100/250 NS100/250 + discontactor Jean MüllerNS1600 discontactor

withdrawable on chassis M/E through doorfixed on mounting plate M/R/E through doorplug-in on base, on mounting plate M/R through doorfuse-switch disconnectable M/E directdisconnectable mounting plate M behind door M behind doordisconnectable Polyfast M/R/E behind doorplug-in Polyfast M/R/E behind doorwithdrawable in drawer Polyfast R on front plate

E behind front plate R on front platewithdrawable in versatile drawer R on front plate R on front plate

M : manual control with toggle or energy storageR : direct rotary or extended handle (in drawer)E : electrical (motor mechanism)

Page 19: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric18

Choice of equipment Modularity charts

moteur control feeders power (kW) installation mode coil

400 V

drawer disconnectable

mounting plate ~ =with GV2P (without thermal relay) 11 3 mod 1/2 W 2 mod x xwith GV2L without fault signal contact 11 6 mod 1/2 W 2 mod x xwith GV2L with fault signal contact 11 6 mod 1/2 W 4 mod x xwith Integral 18 without aux. contact 9 3 mod 1/2 W 2 mod x xwith Integral 18 with aux. contact 9 6 mod 1/2 W 4 mod x xavec Intégral 32 15 6 mod 1/2 W 4 mod x xwith Integral 63 without aux. contact 33 6 mod 4 mod x xwith Integral 63 with aux. contact 33 6 mod x xwith NS80 7,5 6 mod 1/2 W xwith NS80 22 6 mod 1/2 W xwith NS80 30 4 mod x xwith NS80 37 6 mod x xwith NS100 37 6 mod x xwith NS160 75 6 mod x xwith NS250 110 12 mod x xwith NS400 160 18 mod x xwith NS630 250 18 mod x xwith GS1 15 6 mod 1/2 W xwith GS1 22 6 mod 1/2 W xwith GS1 37 6 mod x xwith GS1 110 12 mod x xwith GS1 220 24 mod x x

distribution incomers connection installation mode

and feeder units type

withdrawable disconnect. drawer fixed and disconnect. fuse-switch

on chassis plug-in plug-in on mounting disconnect.

Polyfast mounting plate

plateNW40b-NW63 BDC-RC H2350 72 modNW40b-NW63 BDC-RC H2200 66 modNW08-40/NT16/NS1600 RAR-SC-TDC 19 modNW08-40/NT16/NS1600 BDC H2350 38 modNW08-40/NT16/NS1600 BDC H2200 32 modNT16/NS1600mixed with FU<=630A RC 18 modNT16/NS1600mixed with FU<=630A SC-TDC-BDC 30 modNS250 3P all 5 to 6 mod 6 mod 6 modNS250 3P VIGI all 6 mod2 NS250 3P without VIGI all 6 modNS250 4P all 7 mod 8 mod 8 modNS250 4P VIGI all 8 mod2 NS250 4P without VIGI all 8 modNS630 3P all 8 mod 12 mod 8 modNS630 3P VIGI all 8 modNS630 4P all 9 mod 12 mod 10 modNS630 4P VIGI all 10 modmulti 9 all 6 mod 1/2 W 2 to 4 modSASIL 00 160 A SC 2 modSASIL 1 250 A SC 3 modSASIL 2 400 A SC 6 modSASIL 3 630 A SC 6 mod

TDC : top direct connectionBDC : bottom direct connectionSC : side connectionRC : rear connection

Page 20: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric19

Page 21: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric20

Ground fasteningDimensions

A B C D E F G H I J650 600 565 262.5 262.5 42.5 42.5 37.5 37.5650 400 565 325 42.5 42.5 37.5 37.5450 600 365 262.5 262.5 42.5 42.5 37.5 37.5450 400 365 325 42.5 42.5 37.5 37.5350 600 265 262.5 262.5 42.5 42.5 37.5 37.5350 400 265 325 42.5 42.5 37.5 37.5250 600 165 262.5 262.5 42.5 42.5 37.5 37.5250 400 165 325 42.5 42.5 37.5 37.5

Ground fastening$

* +&,

'

(

)

-

,

-

B

Page 22: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric21

Cable entryDimensions

A B C D E F G H

cubicle 115650 600 460 210 120 70 335 55

cubicle 70650 600 290 200 110 250 360 40

compartment650 600 570 260 40 40 320 20450 600 370 260 40 40 320 20350 600 270 260 40 40 320 20250 600 170 260 40 40 320 20

Cable entry from the top withbusbar

%

$( )&

*

'

+

A B C D E F G H

cubicle 115650 600 450 170 140 60 355 75

cubicle 70650 600 530 240 60 60 340 20

compartment650 600 530 560 60 60 20 20650 400 530 360 60 60 20 20450 600 330 560 60 60 20 20450 400 330 360 60 60 20 20350 600 230 560 60 60 20 20350 400 230 360 60 60 20 20250 600 130 560 60 60 20 20250 400 130 360 60 60 20 20

Cable entry from the bottom

%

$( )&

*

'

+

A B C D E F G H

compartment650 600 570 560 40 40 20 20650 400 570 360 40 40 20 20450 600 370 560 40 40 20 20450 400 370 360 40 40 20 20350 600 270 560 40 40 20 20350 400 270 360 40 40 20 20250 600 170 560 40 40 20 20250 400 170 360 40 40 20 20

Cable entry from the top withoutbusbar

%

$( )&

*

'

+

Page 23: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric22

Dimensions Spatial requirements

Top connection

Frontconnection

Cubicle seen from the side : clearance under ceiling

Front connection cubicle £ 4000 A : minimum space at thefront and rear

Front connection cubicle NW40b/50/63 3 poles :minimum space at the front and rear

Front connection cubicle NW40b/50/63 4 poles :minimum space at the front and rear

���

����

����

��

���

��

���

����

����

����

����

����

��

���

����

�����

���

�����

��

����������

Page 24: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric23

Civil engineeringDimensions

Rearconnection

Rear connection cubicle, depth 600 :minimum space at the front and rear

Rear connection cubicle, depth 1000 :minimum space at the front and rear

Rear connection cubicle, depth 1200 :minimum space at the front and rear

Rear connection cubicle, depth 1400 :minimum space at the front and rear

���

����

����

��

����

����

����

����

��

����

����

����

����

��

����

����

��

����

����

����

Page 25: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Okken Schneider Electric24

The service rating is a characterisation tool for LV switchboards set upby the French manufacturers of electrical switchgear.It allows the users to express their needs as answers to therequirements of their site. It doesn�t need any specific knowledge of theapplicable standards.It is made of three digits : one per criterion from 1 to 3.The minimum index is 111, the maximum 333

With Okken the service rating can be stated considering each functionalunit.Thanks to the functional units combination the selection can be donefor each application and the investment reduced to the barenecessities.

Service ratingAdditional technicalinformation

21

3

1

123

123

123

Operation- Setting- Locking- Padlocking

Shutting down the wholeswitchboard

Shutting down only theFU concerned(Power + auxiliaries)

Shutting down only thepower of the FUconcerned (Aux powermaintained / stable testposition)

Maintenance- Checking- Cleaning- Repairing

Shutting down the wholeswitchboard

Shutting down the FUconcerned / re-installingrequires handling theconnexion

Shutting down the FUconcerned / connexionhandling not required

Evolution- Addition- Modification- Extension

Shutting down thewhole switchboard

Shutting down the FUconcerned / Reserveslot previously defined& equipped

Shutting down the FUconcerned / Freeevolution

Page 26: Okken - EUROSIC · Okken complies with international standards concerning Type Tested Assemblies (TTA), in particular : n IEC 60439-1, concerning construction of LV assemblies n IEC

Schneider Electric IndustriesPostal addressMerlin Gerin AlpesBP 18F-73804 Montmélian CedexFranceTél : +33 (0)4 79 75 48 00Fax : +33 (0)4 79 84 28 36

Published by : Schneider Electric IndustriesDesigned by : Schneider Electric IndustriesPrinted by :

SBSED101020ENART.027391D 06/2001

As standards, specifications and designs develop from time totime, always ask for confirmation of the information given inthis publication.