Asset: P.S. 114 - QUEENS, 134-01 CRONSTON AVE, New York, 11694 Inspection Id Inspection Type Time In Last Edited SA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment 1st Floor Locker and Shower Room (no key) Principal(s) Information Principal Name Elizabeth Welsome Organization P.S. 114 - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. The playground equipment is deteriorated and damaged presenting a hazard. 2. Student toilet flush valves are too difficult to operate by younger students. 3. Auditorium seating operates poorly. Custodian James Kennedy Fireman John Bobby Building Square Footage 62000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 34 Comments on the Year Built 1926 Student Population 687 Staff Population 86 Weather Fair Facade Photo Corner of Cronston Avenue and Beach 135th Street - Southeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q114 PB/A&W Print Date: 6/20/2019 Page 1 of 39

Upload: others

Post on 21-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Asset: P.S. 114 - QUEENS, 134-01 CRONSTON AVE, New York, 11694

Inspection Id Inspection Type Time In Last Edited

SA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM

AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment 1st Floor Locker and Shower Room (no key)

Principal(s) Information

Principal Name Elizabeth Welsome

Organization P.S. 114 - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows:1. The playground equipment is deteriorated and damaged presenting ahazard.2. Student toilet flush valves are too difficult to operate by youngerstudents.3. Auditorium seating operates poorly.

Custodian James Kennedy

Fireman John Bobby

Building Square Footage 62000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Number of Classrooms 34

Comments on the Year Built 1926

Student Population 687

Staff Population 86

Weather Fair

Facade Photo

Corner of Cronston Avenue and Beach135th Street - Southeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 1 of 39

Page 2: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Main Entrance Photo

Facade A - Beach 135th Street

Roof Photo

Roof 1 - View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Complete Exterior Doors replacement

Year: 2018

Systems: Auditorium upgrade including new Curtains and StageFlooring

Year: 2013

Systems: Exterior Modernization Project including: new PerimeterRoofing, Flashing, Parapets, Coping, Cornice,Leaders/Gutters, Skylight, Roof Hatch, Roof Barriers,Door and Window Lintels, and Exterior Guards; ExteriorMasonry repointing

Year: 2010

Systems: New Science Lab (Room 313)

Year: 2009

Systems: New Elevator; Student Toilet Rooms upgraded at 1st and3rd Floors

Year: 2007

Systems: New Roofing, Windows, and Exterior Guards

Year: 1998

Have there been any New Building Additions? Yes

Comments on New Building Additions 1953 (+30,000sf)

Tandem Schools? No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 2 of 39

Page 3: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No Potential FallingDebris

A steel beam hascracked andspallingconcretefireproofingpresenting ahazard.

INTERIOR |STRUCTURAL|COLUMNS/BEAMS/BEARING WALLS

BasementCrawlspace (atVacuum Pump)

James Kennedy Custodian

No ProtrudingElements

Severelydamaged playequipment withsharp edge is apotential safetyhazard.

SITE |PLAYGROUNDS | PlayEquipment

PlaygroundNear Beach134th Street

James Kennedy Custodian

Yes Potential FallingDebris

Deterioratedconcrete floorstructure is apotential fallingdebris hazard.

INTERIOR |STRUCTURAL| FLOORSTRUCTURE

Boiler Room James Kennedy Custodian

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? No

Is there at least one Boys and Girls or Unisex toilet accessible in the building? Yes

If the following spaces exist, are SOME accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts Yes Yes

Interior Corridor Doors and Hardware Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 3 of 39

Page 4: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Interior Routes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps Yes Yes

Rooms & Spaces

Art Rooms Room 104 Yes Yes

Auditorium 1st Floor Yes Yes Yes Yes

Cafeteria 1st Floor Yes Yes Yes Yes

Classrooms 1st Floor Yes Yes

Computer Rooms Room 103 Yes Yes

Gymnasium 1st Floor Yes Yes Yes Yes

Library Room 307 Yes Yes

Main Office Room 160 Yes Yes

Multi-purpose Room No

Nurse's Room Room 154 Yes Yes

Pool No

Science Lab Room 313 Yes Yes

Toilet Rooms (Boys) 1st-3rd Floors Yes Yes

Toilet Rooms (Girls) 1st Floor Yes Yes

Toilet Rooms (Staff) 1st Floor Yes Yes

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 4 of 39

Page 5: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Chimney

Violations No violations recorded.

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

DOOR HARDWARE Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 5 - Poor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 5 of 39

Page 6: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

DOORS

TRANSOM/SIDE LIGHT

Deficiency WOOD: EXCESSIVELY WEATHERED

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency METAL: BROKEN GLASS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 6 of 39

Page 7: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

DOORS

TRANSOM/SIDE LIGHT

Deficiency Photo1

Facade B

Violations No violations recorded.

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 38,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 38,000

Instance Quantity Uom S.F.

Deficiency No deficiencies recorded

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 14,000

Replacement Uom C.F.

InspectedInstance on All Roofs

Instance Condition 2 - Between Good and Fair

Instance Quantity 14,000

Instance Quantity Uom C.F.

Deficiency No deficiencies recorded

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 34,800

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 7 of 39

Page 8: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

ROOF

Roofing

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Deficiency No deficiencies recorded

ROOF BARRIER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: All Roofs

Instance Condition 3 - Fair

Instance Quantity 34,800

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1998

Source of Installation Custodial Staff

Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Built-Up: All Roofs

Deficiency Quantity 34,800

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 3 - Fair

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 8 of 39

Page 9: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: WATERINFILTRATION

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

BH2

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Inspected

Material Type(s) Glass

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 9 of 39

Page 10: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

RAILINGS Inspected

Condition 4 - Between Fair and Poor

Deficiency RUST - MAJOR

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

STAIRS/RAMPS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 10 of 39

Page 11: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Condition 3 - Fair

Deficiency STONE: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 30

Quantity Uom L.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 8,500

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency DETERIORATED/TORN-OUT/MISSING

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 11 of 39

Page 12: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Elevation

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 5 - Room 215

Violations No violations recorded.

Deficiency RUST - MINOR

Roof Plan reference

Elevation

Deficiency Quantity 180

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 12 of 39

Page 13: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 3 - Fair

Instance Quantity 8,500

Instance Quantity Uom S.F.

Installation Year 1998

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 4 - Between Fair and Poor

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED/MISSINGPLASTER FIREPROOFING

Deficiency Location/Instance Boiler Room Entry Stair

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Boiler Room Entry Stair

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING

Deficiency Location/Instance Gas Meter Room

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPAIR AND REPAINT

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 13 of 39

Page 14: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Purpose of Action LEVEL 5

Deficiency Photo1

Gas Meter Room

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED/MISSINGSPRAY-ON FIREPROOFING

Deficiency Location/Instance Basement Crawlspace

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement Crawlspace

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement Crawlspace (similar throughout Basement)

Deficiency Quantity 370

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 14 of 39

Page 15: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Basement Crawlspace

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement Crawlspace (at Vacuum Pump)

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Basement Crawlspace

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 4 - Between Fair and Poor

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Boiler Room

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement Corridor

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 15 of 39

Page 16: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Purpose of Action LEVEL 5

Deficiency Photo1

Basement Corridor

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Boiler Room

Deficiency Quantity 220

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS

Deficiency Location/Instance Boiler Room

Deficiency Quantity 170

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 16 of 39

Page 17: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE Inspected

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Auditorium Fan Room

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Auditorium Fan Room

Violations No violations recorded.

VAULTS-BUNKERS Does not Exist

AUDITORIUM Inspected

InspectedInstance on 1st Floor (388 Seats)

Ceiling

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Seating

InspectedInstance on 1st Floor (388 Seats)

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor (388 Seats)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 17 of 39

Page 18: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

AUDITORIUM

Floor Finish

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor (388 Seats)

Stage

InspectedInstance on 1st Floor (388 Seats)

Stage Inspected

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

InspectedInstance on 1st Floor (388 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Right Side

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 18 of 39

Page 19: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

CAFETERIA

Ceiling

Right Side

Violations No violations recorded.

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Entrance Near Stair D

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Entrance Near Stair D

Violations No violations recorded.

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Near Windows, Center

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Sliding-folding Partition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 19 of 39

Page 20: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

CAFETERIA

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 310, Corridor near Room 316

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 310

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 103, 112, 162, 213, 308, and others

Deficiency Quantity 7

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 20 of 39

Page 21: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s) Inspected

Deficiency Photo1

Room 308

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency WOOD: DAMAGED/DETERIORATED

Deficiency Location/Instance Rooms 208, 209

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 208

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Corridor near Room 256, Room 204

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 21 of 39

Page 22: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish Inspected

Corridor near Room 256

Violations No violations recorded.

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Corridor near Room 148

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 148

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Room 206, Corridor near Rooms 211, 263, 312, 360, and others

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 360

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 22 of 39

Page 23: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

GYMNASIUM

Ceiling

Condition 3 - Fair

Deficiency METAL PAN: DAMAGED/MISSING

Deficiency Location/Instance Right Side, Left Side, Center

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Right Side

Violations No violations recorded.

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Seating

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency DAMAGED FIXED SEATING

Deficiency Location/Instance Center

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 23 of 39

Page 24: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

GYMNASIUM

Seating

Deficiency Photo1

Center

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Store Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 24 of 39

Page 25: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

KITCHEN

Door(s)

Deficiency Photo1

Store Room

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 307

Built-in Furnishing

InspectedInstance on Room 307

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Ceiling

InspectedInstance on Room 307

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 307

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 307

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Near Entrance

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 25 of 39

Page 26: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

LIBRARY

Floor Finish

Deficiency Photo1

Near Entrance

Violations No violations recorded.

Walls

InspectedInstance on Room 307

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Inspected

InaccessibleInstance on 1st Floor

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Inspected

InspectedInstance on Room 313

Alternative use No

Fixed Equipment

InspectedInstance on Room 313

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Inspected

InaccessibleInstance on 1st Floor

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Stair D/1 Vestibule

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 26 of 39

Page 27: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Deficiency Photo1

Stair D/1 Vestibule

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stair B/1

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/1

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 3 - Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Stair B/1

Deficiency Quantity 45

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 27 of 39

Page 28: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Deficiency Photo1

Stair B/1

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Stairs C/1,2,3, D/1,2,3

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair D/3

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Stair A/Bulkhead

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair A/Bulkhead

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 28 of 39

Page 29: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR Inspected

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 148

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 148

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 257, 357

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 357

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 29 of 39

Page 30: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

TOILET ROOMS - STAFF Inspected

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Rooms 257, 357

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 357

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Rooms 262, 263

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 263

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: MISSING DOOR

Deficiency Location/Instance Rooms 262, 263, 362, 364

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 30 of 39

Page 31: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s)

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 362

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Room 255, Near Room 102

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 255

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room 256, Inside Room 166

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 31 of 39

Page 32: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish

Deficiency Photo1

Room 256

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Rooms 255, 256, 362, 264

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 256

Violations No violations recorded.

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance Near Beach 134th Street

Deficiency Quantity 3

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 32 of 39

Page 33: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

CONTAINERIZATION

Deficiency Photo1

Near Beach 134th Street

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 3 - Fair

Deficiency DAMAGED COVER

Deficiency Location/Instance Schoolyard Near Beach 134th Street

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Schoolyard Near Beach 134th Street

Violations No violations recorded.

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Does not Exist

Drainage System for Soil Inspected

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Does not Exist

DRINKING FOUNTAINS Inspected

Condition 5 - Poor

Deficiency INOPERABLE

Deficiency Location/Instance Schoolyard

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 33 of 39

Page 34: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

DRINKING FOUNTAINS Inspected

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

FENCES Inspected

Condition 3 - Fair

Deficiency CHAIN LINK: MISSING SECTIONS

Deficiency Location/Instance Along Beach 134th Street

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Along Beach 134th Street

Violations No violations recorded.

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance Along Beach 135th Street, Along Cronston Avenue

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Along Beach 135th Street

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 3 - Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 34 of 39

Page 35: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

PAVING

Student Non-Use

Asphalt

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Near Beach 134th Street

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Beach 134th Street

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 4 - Between Fair and Poor

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 600

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 35 of 39

Page 36: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

PAVING

Student Use

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Near Beach 135th Street

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Beach 135th Street

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 36 of 39

Page 37: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

PAVING

DOT Sidewalk

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Beach 135th Street, Beach 134th Street

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 135th Street

Violations No violations recorded.

Deficiency DAMAGED CURBS

Deficiency Location/Instance Beach 135th Street, Beach 134th Street

Deficiency Quantity 95

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 135th Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Along Beach 135th Street

InspectedInstance on Along Beach 134th Street

Benches

InspectedInstance on Along Beach 135th Street

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 37 of 39

Page 38: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

PLAYGROUNDS

Benches

InspectedInstance on Along Beach 134th Street

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fence

InspectedInstance on Along Beach 134th Street

Condition 3 - Fair

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance North Side

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North Side

Violations No violations recorded.

Pavement

InspectedInstance on Along Beach 135th Street

Condition 4 - Between Fair and Poor

Deficiency ASPHALT: CRACKS - MAJOR

Deficiency Location/Instance South Side, North Side

Deficiency Quantity 400

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South Side

Violations No violations recorded.

Play Equipment

InspectedInstance on Along Beach 134th Street

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 38 of 39

Page 39: NYC Department of Education - NYCSCASA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM

Question Response

SITE

PLAYGROUNDS

Play Equipment

Condition 5 - Poor

Deficiency BROKEN/DETERIORATED/MISSING

Deficiency Location/Instance Playground Near Beach 134th Street

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Playground Near Beach 134th Street

Violations No violations recorded.

Safety Surfacing

InspectedInstance on Along Beach 134th Street

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Along Beach 135th Street

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Unpaved Area

InspectedInstance on Along Beach 135th Street

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Does not ExistInstance on Along Beach 134th Street

PLAYING SURFACE Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q114

PB/A&W Print Date: 6/20/2019Page 39 of 39