Asset: P.S. 124 - BROOKLYN, 515 4TH AVENUE, New York, 11215 Inspection Id Inspection Type Time In Last Edited SA : K124 Architectural - Senior 2020-07-13 11:03 AM 2020-07-13 3:48 PM AA : K124 Architectural - Associate 2020-07-13 11:41 AM 2020-07-13 2:47 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Grounding System (No Key) Principal(s) Information Principal Name Maria Interlandi Organization P.S. 124 - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. Water penetration from roof in Room 304A 2. Water penetration from roof at Exit Stairs 6E (C/D). 3. Water penetration from Foundation Walls at Exit Stair 7F (A/B) Basement Staff Toilet Room, Multipurpose Room, Cafeteria. 4. Climate control system is not functioning properly. 5. Window balances throughout the building are defective. Custodian Scott Rittenhouse Fireman Desmond Hylegar (Handyman) Building Square Footage 33,000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 20 Comments on the Year Built 1900 Student Population 276 Staff Population 60 Weather Fair Facade Photo Corner of 4th Avenue and 13th Street - South View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 K124 PB/A&W Print Date: 9/13/2020 Page 1 of 50

Upload: others

Post on 31-Jan-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • Asset: P.S. 124 - BROOKLYN, 515 4TH AVENUE, New York, 11215

    Inspection Id Inspection Type Time In Last Edited

    SA : K124 Architectural - Senior 2020-07-13 11:03 AM 2020-07-13 3:48 PM

    AA : K124 Architectural - Associate 2020-07-13 11:41 AM 2020-07-13 2:47 PM

    Asset Data

    Question Answer

    Was the building fully accessible for inspection No

    Inspection Access Comment Grounding System (No Key)

    Principal(s) Information

    Principal Name Maria Interlandi

    Organization P.S. 124 - Brooklyn

    Did you meet with this Principal? Yes

    Did this Principal provide feedback? Yes

    Summary of Principal's Feedback The Principal's comments are as follows: 1. Water penetration fromroof in Room 304A2. Water penetration from roof at Exit Stairs 6E (C/D).3. Water penetration from Foundation Walls at Exit Stair 7F (A/B)Basement Staff Toilet Room, Multipurpose Room, Cafeteria.4. Climate control system is not functioning properly.5. Window balances throughout the building are defective.

    Custodian Scott Rittenhouse

    Fireman Desmond Hylegar (Handyman)

    Building Square Footage 33,000

    Comments on the Area None

    Comments on the Stories (Floors) plus Basements 3+B

    Comments on the Number of Classrooms 20

    Comments on the Year Built 1900

    Student Population 276

    Staff Population 60

    Weather Fair

    Facade Photo

    Corner of 4th Avenue and 13th Street -South View

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 1 of 50

  • Main Entrance Photo

    Facade A - 4th Avenue

    Roof Photo

    Roof 1 - South View

    Have any Systems/Major Building Components been upgraded? Yes

    Systems: Flood Elimination Program including All RoofReplacement , Parapets Repairs and Facade C ExteriorWalls Repairs and Repointing. Bulkhead Repairs. NewRoof Guardrails. Boiler Room Foundation WallWaterproofing. New Canopy at Facade B. (Original FoyerRemoved). Partial Exterior Doors Replacement. SidewalkElevator Removed and opening closed.

    Year: 2019

    Systems: Partial Exterior Doors replacement; Ash Hoist Vault DoorsReplacement

    Year: 2016

    Systems: Basement Boys and Girls Toilet Rooms upgraded;Bulkhead Plaster Repairs; Exterior Stair Railings Repairs

    Year: 2014

    Systems: 1st Floor Boys and Girls Toilet Rooms upgraded

    Year: 2013

    Systems: Exterior Stairs and Partial Concrete PavementReplacement

    Year: 2010

    Systems: Roof 1 - Perimeter Roofing and Flashing Replacement;Parapets and Coping Replacement

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 2 of 50

  • Year: 2008

    Systems: Window and Window Guards replacement; Twoclassrooms converted to a Library and a Music Room

    Year: 1999

    Have there been any New Building Additions? No

    Tandem Schools? No

    Leased Space? No

    Priority Condition

    PriorityCondition ExistLast Year?

    PriorityCategory

    ConditionDescription

    ComponentAffected

    LocationDescription

    Person(s)Notified

    Person(s) Title PhotoImage

    No ProtrudingElements

    DamagedRailing is apotential safetyhazard.

    INTERIOR |STAIRS/RAMPS: INTERIOR |Railings

    StairAB/Bulkhead

    ScottRittenhouse

    Custodian

    Yes Tripping Hazard Damaged draincover is apotentialtripping hazard.

    INTERIOR |MULTI-PURPOSEROOM | FloorFinish

    Near DrinkingFountain

    ScottRittenhouse

    Custodian

    Structural Engineer Required

    StructuralCondition Type

    ConditionDescription

    ComponentAffected

    LocationDescription

    Person(s)Notified

    Person(s) Title PhotoImage

    No condition recorded

    Accessibility

    Accessibility Status Question Response

    Is the primary or secondary entrance on an accessible route? No

    Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

    FireAlarmStrobe

    FUNCTIONAL ACCESSIBILITY

    Exterior Routes

    Exterior Entrances & Exits Yes

    Exterior H/C Lifts No No

    Exterior Ramps and Railings No Yes

    Interior Routes

    Corridor and Lobby H/C Lifts No Yes

    Interior Corridor Doors and Hardware Yes Yes

    Interior Corridors and Lobbies No Change in Elevation

    Interior Elevators No

    Interior Lobby Doors and Hardware Yes

    Interior Ramps No

    Rooms & Spaces

    Art Rooms Room 208 Yes No Not on Accessible Route

    Auditorium No

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 3 of 50

  • Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

    FireAlarmStrobe

    Rooms & Spaces

    Cafeteria Basement Yes No Not on Accessible Route Yes No

    Classrooms Basement Yes No Not on Accessible Route

    Computer Rooms No

    Gymnasium No

    Library Room 305 Yes No Not on Accessible Route

    Main Office Room 106 Yes No Not on Accessible Route

    Multi-purpose Room Basement Yes No Not on Accessible Route Yes No

    Nurse's Room Room 104A Yes No Not on Accessible Route

    Pool No

    Science Lab No

    Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

    Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

    Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

    Building Template

    Inspection

    Question Response

    Architectural

    EXTERIOR Inspected

    AREAWAY Inspected

    InspectedInstance on AW1 - AW6

    Instance Condition 4 - Between Fair and Poor

    Instance Quantity 6

    Instance Quantity Uom EACH

    Deficiency AREAWAY GRATINGS: MAJOR RUSTING AND / OR BROKENSUPPORTS

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 4 of 50

  • Question Response

    EXTERIOR

    AREAWAY

    Roof Plan reference

    Deficiency Quantity 180

    Quantity Uom L.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    AW2

    Violations No violations recorded.

    Deficiency AREAWAY WALLS: CRACKS AND SPALLING

    Roof Plan reference

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 5 of 50

  • Question Response

    EXTERIOR

    AREAWAY

    Deficiency Photo1

    AW5

    Violations No violations recorded.

    AWNINGS AND CANOPIES Inspected

    Condition 3 - Fair

    Deficiency METAL: WATER PENETRATION

    Roof Plan reference

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    CHIMNEY Inspected

    Material Type(s) Masonry

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    COPING Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    CORNICE Inspected

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 6 of 50

  • Question Response

    EXTERIOR

    CORNICE

    Condition 2 - Between Good and Fair

    Deficiency STONE: MINOR CRACKS, SPALLING

    Roof Plan reference

    Deficiency Quantity 60

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    DOORS Inspected

    DOORS AND FRAMES Inspected

    Condition 5 - Poor

    Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION

    Roof Plan reference

    Deficiency Quantity 2

    Quantity Uom EACH

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 7 of 50

  • Question Response

    EXTERIOR

    DOORS

    DOORS AND FRAMES

    Deficiency Photo1

    Facade D

    Violations No violations recorded.

    Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

    Roof Plan reference

    Deficiency Quantity 3

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1 No photo recorded

    Violations No violations recorded.

    DOOR HARDWARE Inspected

    Condition 3 - Fair

    Deficiency No deficiencies recorded

    LINTELS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    TRANSOM/SIDE LIGHT Inspected

    Condition 5 - Poor

    Deficiency WOOD: EXCESSIVELY WEATHERED

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 8 of 50

  • Question Response

    EXTERIOR

    DOORS

    TRANSOM/SIDE LIGHT

    Roof Plan reference

    Deficiency Quantity 60

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A

    Violations No violations recorded.

    EXTERIOR WALLS Inspected

    Material Type(s) Masonry, Concrete

    Replacement Quantity 18,000

    Replacement Uom S.F.

    InspectedInstance on All Facades

    Instance Condition 4 - Between Fair and Poor

    Instance Quantity 18,000

    Instance Quantity Uom S.F.

    Deficiency STONE: CRACKS AT BUILDING CORNERS

    Roof Plan reference

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 9 of 50

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Elevation

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade D

    Violations No violations recorded.

    Deficiency BRICK: WATER INFILTRATION IN NON-INSTRUCTIONALSPACE

    Roof Plan reference

    Elevation

    Deficiency Quantity 50

    Quantity Uom S.F.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 10 of 50

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Potential Action REPAIR

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A - MDF Room 302A

    Violations No violations recorded.

    Deficiency BRICK: OPEN JOINTS

    Roof Plan reference

    Elevation

    Deficiency Quantity 1,800

    Quantity Uom S.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 11 of 50

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Facade A

    Violations No violations recorded.

    Deficiency BRICK: DETERIORATED MASONRY SILLS

    Roof Plan reference

    Elevation

    Deficiency Quantity 80

    Quantity Uom L.F.

    Potential Action REMOVE AND REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A

    Violations No violations recorded.

    Deficiency BRICK: MINOR CRACKS AND SPALLING

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 12 of 50

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Roof Plan reference

    Elevation

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action RESTITCH

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A

    Violations No violations recorded.

    Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES

    Roof Plan reference

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 13 of 50

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Elevation

    Deficiency Quantity 60

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A

    Violations No violations recorded.

    Deficiency STONE: OPEN JOINTS

    Roof Plan reference

    Elevation

    Deficiency Quantity 20

    Quantity Uom L.F.

    Potential Action REPOINT

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 14 of 50

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1 No photo recorded

    Violations No violations recorded.

    EXTERIOR SOFFITS Does not Exist

    LOADING DOCK Does not Exist

    LOUVER Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    PARAPETS Inspected

    Material Type(s) Masonry

    Replacement Quantity 2,500

    Replacement Uom C.F.

    InspectedInstance on All Facades

    Instance Condition 2 - Between Good and Fair

    Instance Quantity 2,500

    Instance Quantity Uom C.F.

    Deficiency BRICK: OPEN JOINTS

    Roof Plan reference

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 1 - Facade D

    Violations No violations recorded.

    PLAZA DECK Does not Exist

    ROOF Inspected

    Roofing Inspected

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 15 of 50

  • Question Response

    EXTERIOR

    ROOF

    Roofing

    Replacement Quantity 9,000

    Replacement Uom S.F.

    ROOF HATCH/SMOKE HATCH Does not Exist

    LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

    Condition 1 - Good

    Deficiency No deficiencies recorded

    ROOF BARRIER Inspected

    Condition 1 - Good

    Deficiency No deficiencies recorded

    ROOF CAGE Does not Exist

    ROOF FENCE Does not Exist

    ROOFING Inspected

    InspectedInstance on Modified Bitumen: All Roofs

    Instance Condition 4 - Between Fair and Poor

    Instance Quantity 9,000

    Instance Quantity Uom S.F.

    Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

    No

    Installation Year 2020

    Source of Installation Custodial Staff

    Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION

    Roof Plan reference

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 1 (Above Room 304A)

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 16 of 50

  • Question Response

    EXTERIOR

    ROOF

    Roofing

    ROOFING

    Violations No violations recorded.

    Deficiency MODIFIED BITUMEN: ROOFING: MAJOR ACTIVE ROOFLEAKS IN INSTRUCTIONAL SPACE

    Roof Plan reference

    Deficiency Quantity 200

    Quantity Uom S.F.

    Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 1 - Room 304A (Picture Taken) Roof 2 - Exit Stair 6E (C/D)Similar.

    Violations No violations recorded.

    ROOFING DRAINS Does not Exist

    Specialties Inspected

    BULKHEAD/PENTHOUSE Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    CUPOLA/ SPIRES/ TOWERS Does not Exist

    DORMER Does not Exist

    DUNNAGE STEEL Does not Exist

    SKYLIGHT/ROOF VENT Does not Exist

    ROOF/GRAVITY TANK Does not Exist

    STAIRS/RAMPS: EXTERIOR Inspected

    BUILDING CHEEK/FLANK WALLS Inspected

    Condition 5 - Poor

    Deficiency STONE: DETERIORATED COPING STONE

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 17 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    BUILDING CHEEK/FLANK WALLS

    Roof Plan reference

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade D

    Violations No violations recorded.

    Deficiency STONE: OPEN JOINTS

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 18 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    BUILDING CHEEK/FLANK WALLS

    Deficiency Photo1

    Facade D

    Violations No violations recorded.

    Deficiency STONE: CRACKS/SPALLING - MAJOR

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade D

    Violations No violations recorded.

    Deficiency STONE: BULGING/DISPLACED

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 19 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    BUILDING CHEEK/FLANK WALLS

    Roof Plan reference

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade D

    Violations No violations recorded.

    Deficiency BRICK: DETERIORATED COPING STONE

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 20 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    BUILDING CHEEK/FLANK WALLS

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    Deficiency BRICK: CRACKS/SPALLING - MAJOR

    Roof Plan reference

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    Deficiency STONE: DETERIORATED JOINTS AT COPING STONES

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 21 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    BUILDING CHEEK/FLANK WALLS

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom L.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

    Roof Plan reference

    Deficiency Quantity 40

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 22 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    BUILDING CHEEK/FLANK WALLS

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    RAILINGS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    STAIRS/RAMPS Inspected

    Condition 5 - Poor

    Deficiency STONE: OPEN JOINTS

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom L.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 23 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    STAIRS/RAMPS

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade C

    Violations No violations recorded.

    Deficiency STONE: WORN-OUT TREAD/RISER/NOSING

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 24 of 50

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    STAIRS/RAMPS

    Deficiency Photo1

    Facade A

    Violations No violations recorded.

    WINDOWS Inspected

    Replacement Quantity 5,000

    Replacement Uom S.F.

    EXTERIOR GUARDS Inspected

    Condition 3 - Fair

    Deficiency DETERIORATED/TORN-OUT/MISSING

    Roof Plan reference

    Elevation

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 25 of 50

  • Question Response

    EXTERIOR

    WINDOWS

    EXTERIOR GUARDS

    Deficiency Photo1

    Facade A - Near AW5

    Violations No violations recorded.

    LINTELS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    WINDOWS Inspected

    Material Type(s) Aluminum

    InspectedInstance on Aluminum - Double Hung: All Facades

    Instance Condition 3 - Fair

    Instance Quantity 5,000

    Instance Quantity Uom S.F.

    Installation Year 1999

    Source of Installation Custodial Staff

    Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE

    Roof Plan reference

    Elevation

    Deficiency Quantity 80

    Quantity Uom EACH

    Potential Action REPLACE BALANCES

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 26 of 50

  • Question Response

    EXTERIOR Inspected

    WINDOWS Inspected

    WINDOWS

    Deficiency Photo1 No photo recorded

    Violations No violations recorded.

    INTERIOR Inspected

    POOLS Does not Exist

    STRUCTURAL Inspected

    COLUMNS/BEAMS/BEARING WALLS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    FLOOR STRUCTURE Inspected

    Condition 3 - Fair

    Deficiency CINDER CONCRETE ARCH: METAL PAN DETERIORATED,SPALLED

    Deficiency Location/Instance Basement - Electrical Panel Room, Boiler Room

    Deficiency Quantity 80

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Basement - Electrical Panel Room

    Violations No violations recorded.

    Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

    Deficiency Location/Instance Basement - Electrical Panel Room, Boiler Room

    Deficiency Quantity 40

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Basement - Electrical Panel Room

    Violations No violations recorded.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 27 of 50

  • Question Response

    INTERIOR Inspected

    STRUCTURAL

    FOUNDATION WALLS Inspected

    Material Type(s) Concrete, Masonry

    Condition 5 - Poor

    Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE

    Deficiency Location/Instance Basement - Boiler Room

    Deficiency Quantity 100

    Quantity Uom S.F.

    Potential Action INSTALL WATERPROOFING

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Basement - Boiler Room

    Violations No violations recorded.

    Deficiency BRICK: OPEN JOINTS

    Deficiency Location/Instance Basement - Electrical Panel Room, Boiler Room

    Deficiency Quantity 120

    Quantity Uom S.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Basement - Electrical Panel Room

    Violations No violations recorded.

    Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE

    Deficiency Location/Instance Basement - Staff Toilet Room, Exit Stair 7F (A/B) to Courtyard,Cafeteria, Multipurpose Room

    Deficiency Quantity 400

    Quantity Uom S.F.

    Potential Action INSTALL WATERPROOFING

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 5

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 28 of 50

  • Question Response

    INTERIOR

    STRUCTURAL

    FOUNDATION WALLS

    Deficiency Photo1

    Basement - Staff Toilet Rooms

    Violations No violations recorded.

    Deficiency BRICK: CRACKED/SPALLED

    Deficiency Location/Instance Basement - Electrical Panel Room, Custodian Storage/Toilet Room

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action RESTITCH

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Basement - Electrical Panel Room

    Violations No violations recorded.

    ROOF STRUCTURE Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    VAULTS-BUNKERS Inspected

    Foundation Walls Inspected

    Condition 3 - Fair

    Deficiency OPEN JOINTS

    Deficiency Location/Instance Basement - Ash Hoist Vault

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 5

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 29 of 50

  • Question Response

    INTERIOR

    STRUCTURAL

    VAULTS-BUNKERS

    Foundation Walls

    Deficiency Photo1

    Basement - Ash Hoist Vault

    Violations No violations recorded.

    Slab Structure Inspected

    Condition 3 - Fair

    Deficiency CINDER CONCRETE ARCH: METAL PAN DETERIORATED,SPALLED

    Deficiency Location/Instance Basement - Ash Hoist Vault

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Basement - Ash Hoist Vault

    Violations No violations recorded.

    Vault/Ash Hoist Doors and Framing Inspected

    Condition 5 - Poor

    Deficiency WATER INFILTRATION

    Deficiency Location/Instance Basement - Ash Hoist Vault

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 30 of 50

  • Question Response

    INTERIOR

    STRUCTURAL

    VAULTS-BUNKERS

    Vault/Ash Hoist Doors and Framing

    Deficiency Photo1

    Basement - Ash Hoist Vault

    Violations No violations recorded.

    AUDITORIUM Does not Exist

    CAFETERIA Inspected

    InspectedInstance on Basement (1500 SF)

    Ceiling

    InspectedInstance on Basement (1500 SF)

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s)

    Not RequiredInstance on Basement (1500 SF)

    Fixed Equipment

    Does not ExistInstance on Basement (1500 SF)

    Floor Finish

    InspectedInstance on Basement (1500 SF)

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Sliding-folding Partition

    Does not ExistInstance on Basement (1500 SF)

    Stage

    Does not ExistInstance on Basement (1500 SF)

    Walls

    InspectedInstance on Basement (1500 SF)

    Condition 3 - Fair

    Deficiency WALL PADDING: DETERIORATED

    Deficiency Location/Instance Center columns

    Deficiency Quantity 40

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 31 of 50

  • Question Response

    INTERIOR

    CAFETERIA

    Walls

    Deficiency Photo1

    Center columns

    Violations No violations recorded.

    Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

    Deficiency Location/Instance Near Stair CD

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Near Stair CD

    Violations No violations recorded.

    Window Curtains/Shades/Blinds

    Does not ExistInstance on Basement (1500 SF)

    CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

    Deficiency Location/Instance Room 304A

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 32 of 50

  • Question Response

    INTERIOR

    CLASSROOMS/CORRIDORS/ADMIN SPACES

    Ceiling

    Deficiency Photo1

    Room 304A

    Violations No violations recorded.

    Door(s) Inspected

    Condition 5 - Poor

    Deficiency WOOD: DETERIORATED DOOR

    Deficiency Location/Instance Rooms 202,304A, Main Entrance Lobby

    Deficiency Quantity 4

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Room 202

    Violations No violations recorded.

    Floor Finish Inspected

    Condition 2 - Between Good and Fair

    Deficiency VINYL TILES: DETERIORATED SUBSTRATE

    Deficiency Location/Instance Rooms 204,304,306A, Corridor near Rooms 302,303, and others

    Deficiency Quantity 400

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 33 of 50

  • Question Response

    INTERIOR

    CLASSROOMS/CORRIDORS/ADMIN SPACES

    Floor Finish

    Deficiency Photo1

    Room 306A

    Violations No violations recorded.

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency PLASTER: CRACKS/SPALLING

    Deficiency Location/Instance Corridor near Room 307

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Corridor near Room 307

    Violations No violations recorded.

    Deficiency CERAMIC TILE: BROKEN/ MISSING

    Deficiency Location/Instance Main Entrance Vestibule

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 34 of 50

  • Question Response

    INTERIOR

    CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

    Walls Inspected

    Main Entrance Vestibule

    Violations No violations recorded.

    Specialties Does not Exist

    GYMNASIUM Does not Exist

    INTERIOR DOOR HARDWARE Inspected

    Condition 3 - Fair

    Deficiency No deficiencies recorded

    INTERIOR GUARDS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    KITCHEN Inspected

    InspectedInstance on Basement (500 SF)

    Ceiling

    InspectedInstance on Basement (500 SF)

    Condition 4 - Between Fair and Poor

    Deficiency METAL PAN: DAMAGED/MISSING

    Deficiency Location/Instance Near entrance

    Deficiency Quantity 40

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Near entrance

    Violations No violations recorded.

    Door(s)

    InspectedInstance on Basement (500 SF)

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Floor Finish

    InspectedInstance on Basement (500 SF)

    Condition 5 - Poor

    Deficiency CONCRETE: CRACKS

    Deficiency Location/Instance Storage Room

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 35 of 50

  • Question Response

    INTERIOR

    KITCHEN

    Floor Finish

    Deficiency Photo1

    Storage Room

    Violations No violations recorded.

    Deficiency CERAMIC TILE: BROKEN/MISSING TILES

    Deficiency Location/Instance Near entrance

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Near entrance

    Violations No violations recorded.

    Walls

    InspectedInstance on Basement (500 SF)

    Condition 2 - Between Good and Fair

    Deficiency CERAMIC TILE: BROKEN/ MISSING

    Deficiency Location/Instance Near entrance

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 36 of 50

  • Question Response

    INTERIOR

    KITCHEN Inspected

    Walls

    Deficiency Photo1

    Near entrance

    Violations No violations recorded.

    LIBRARY Inspected

    InspectedInstance on Room 305

    Built-in Furnishing

    Does not ExistInstance on Room 305

    Ceiling

    InspectedInstance on Room 305

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s)

    InspectedInstance on Room 305

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Floor Finish

    InspectedInstance on Room 305

    Condition 2 - Between Good and Fair

    Deficiency VINYL TILES: DETERIORATED SUBSTRATE

    Deficiency Location/Instance Near Circulation Desk

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Near Circulation Desk

    Violations No violations recorded.

    Walls

    InspectedInstance on Room 305

    Condition 2 - Between Good and Fair

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 37 of 50

  • Question Response

    INTERIOR

    LIBRARY Inspected

    Walls

    Deficiency No deficiencies recorded

    LOCKER ROOM Does not Exist

    MULTI-PURPOSE ROOM Inspected

    InspectedInstance on Basement (1600 SF)

    Ceiling

    InspectedInstance on Basement (1600 SF)

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s)

    Not RequiredInstance on Basement (1600 SF)

    Fixed Equipment

    InspectedInstance on Basement (1600 SF)

    Condition 3 - Fair

    Deficiency DAMAGED/MISSING

    Deficiency Location/Instance Near entrance

    Deficiency Quantity 1

    Quantity Uom EACH

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1 No photo recorded

    Violations No violations recorded.

    Floor Finish

    InspectedInstance on Basement (1600 SF)

    Condition 2 - Between Good and Fair

    Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

    Deficiency Location/Instance Near Drinking Fountain

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 6

    Deficiency Photo1

    Near Drinking Fountain

    Violations No violations recorded.

    Sliding-folding Partition

    Does not ExistInstance on Basement (1600 SF)

    Stage

    Does not ExistInstance on Basement (1600 SF)

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 38 of 50

  • Question Response

    INTERIOR

    MULTI-PURPOSE ROOM Inspected

    Walls

    InspectedInstance on Basement (1600 SF)

    Condition 2 - Between Good and Fair

    Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

    Deficiency Location/Instance Near windows

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Near windows

    Violations No violations recorded.

    Window Curtains/Shades/Blinds

    Does not ExistInstance on Basement (1600 SF)

    SCIENCE DEMO ROOM Does not Exist

    SCIENCE LAB Does not Exist

    SCIENCE PREP ROOM Does not Exist

    SHOWER ROOM Does not Exist

    STAIRS/RAMPS: INTERIOR Inspected

    Do Letter Stair Signs Exist? Yes

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s) Inspected

    Condition 5 - Poor

    Deficiency METAL: DETERIORATED DOOR

    Deficiency Location/Instance Stair AB/Basement

    Deficiency Quantity 2

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 39 of 50

  • Question Response

    INTERIOR

    STAIRS/RAMPS: INTERIOR

    Door(s)

    Deficiency Photo1

    Stair AB/Basement

    Violations No violations recorded.

    Partition Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Railings Inspected

    Condition 3 - Fair

    Deficiency METAL: DAMAGED

    Deficiency Location/Instance Stair AB/Bulkhead

    Deficiency Quantity 10

    Quantity Uom L.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 6

    Deficiency Photo1

    Stair AB/Bulkhead

    Violations No violations recorded.

    Stairs and Landings Inspected

    Condition 2 - Between Good and Fair

    Deficiency CONCRETE: CRACKS/SPALLING - MAJOR

    Deficiency Location/Instance Stair CD/Basement

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 40 of 50

  • Question Response

    INTERIOR

    STAIRS/RAMPS: INTERIOR

    Stairs and Landings

    Deficiency Photo1

    Stair CD/Basement

    Violations No violations recorded.

    Deficiency VINYL TILES: DETERIORATED SUBSTRATE

    Deficiency Location/Instance Stair CD/2

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Stair CD/2

    Violations No violations recorded.

    Deficiency STONE: BROKEN/MISSING

    Deficiency Location/Instance Stair AB/Basement

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Stair AB/Basement

    Violations No violations recorded.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 41 of 50

  • Question Response

    INTERIOR

    STAIRS/RAMPS: INTERIOR

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency PLASTER: CRACKS/SPALLING

    Deficiency Location/Instance Stair CD/Basement

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Stair CD/Basement

    Violations No violations recorded.

    Deficiency METAL CLADDING: DETERIORATED

    Deficiency Location/Instance Stair AB/Basement

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Stair AB/Basement

    Violations No violations recorded.

    Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

    Deficiency Location/Instance Stair AB/Basement,CD/Basement

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 42 of 50

  • Question Response

    INTERIOR

    STAIRS/RAMPS: INTERIOR

    Walls

    Deficiency Photo1

    Stair AB/Basement

    Violations No violations recorded.

    TOILET ROOMS - STAFF Inspected

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s) Inspected

    Condition 5 - Poor

    Deficiency WOOD: DETERIORATED DOOR

    Deficiency Location/Instance In Room 306A

    Deficiency Quantity 1

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    In Room 306A

    Violations No violations recorded.

    Floor Finish Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stalls Inspected

    Condition 5 - Poor

    Deficiency RUST - MAJOR

    Deficiency Location/Instance Basement

    Deficiency Quantity 1

    Quantity Uom EACH

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 43 of 50

  • Question Response

    INTERIOR

    TOILET ROOMS - STAFF

    Stalls

    Deficiency Photo1

    Basement

    Violations No violations recorded.

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency BRICK: CRACKS/SPALLING - ACTIVE LEAK

    Deficiency Location/Instance Basement

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Basement

    Violations No violations recorded.

    TOILET ROOMS - STUDENTS Inspected

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency PLASTER: CRACKS/SPALLING

    Deficiency Location/Instance 1st Floor - Boys

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 44 of 50

  • Question Response

    INTERIOR

    TOILET ROOMS - STUDENTS

    Ceiling

    Deficiency Photo1

    1st Floor - Boys

    Violations No violations recorded.

    Door(s) Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Floor Finish Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stalls Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LIFE SAFETY Inspected

    F.D. HOLDING AREA Does not Exist

    STEEL STAIRS Does not Exist

    SITE Inspected

    CONTAINERIZATION Does not Exist

    Drainage System for Asphalt Inspected

    Catch Basins/Manhole - Surrounded by asphalt Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Culverts - Asphalt Covering Does not Exist

    Drainage System for Concrete Does not Exist

    Drainage System for Soil Does not Exist

    DRINKING FOUNTAINS Does not Exist

    FENCES Inspected

    Condition 3 - Fair

    Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

    Deficiency Location/Instance 4th Avenue

    Deficiency Quantity 40

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 45 of 50

  • Question Response

    SITE

    FENCES

    Deficiency Photo1

    4th Avenue

    Violations No violations recorded.

    Deficiency WROUGHT IRON: RUST - MAJOR

    Deficiency Location/Instance 4th Avenue

    Deficiency Quantity 200

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    4th Avenue

    Violations No violations recorded.

    Deficiency CHAIN LINK: DAMAGED/DETERIORATED

    Deficiency Location/Instance 13th Street, 14th Street

    Deficiency Quantity 100

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    14th Street

    Violations No violations recorded.

    IRRIGATION SYSTEM Does not Exist

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 46 of 50

  • Question Response

    SITE

    IRRIGATION SYSTEM Does not Exist

    PAVING Inspected

    Student Non-Use Inspected

    Gravel Exists? No

    Asphalt Does not Exist

    Concrete Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Pavers Does not Exist

    Student Use Inspected

    Gravel Exists? Yes

    Asphalt Inspected

    Condition 4 - Between Fair and Poor

    Deficiency CRACKS - MAJOR

    Deficiency Location/Instance Schoolyard

    Deficiency Quantity 500

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Schoolyard

    Violations No violations recorded.

    Concrete Does not Exist

    Pavers Does not Exist

    Site Sidewalks & Walkways Inspected

    Asphalt Does not Exist

    Concrete Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Pavers Does not Exist

    DOT Sidewalk Inspected

    Asphalt Does not Exist

    Concrete Inspected

    Condition 3 - Fair

    Deficiency HEAVING

    Deficiency Location/Instance 13th Street

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action REPLACE

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 47 of 50

  • Question Response

    SITE

    PAVING Inspected

    DOT Sidewalk

    Concrete

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    13th Street

    Violations No violations recorded.

    Deficiency DAMAGED CURBS

    Deficiency Location/Instance 13th Street, 14th Street

    Deficiency Quantity 50

    Quantity Uom L.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    14th Street

    Violations No violations recorded.

    Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

    Deficiency Location/Instance 4th Avenue, 13th Street, 14th Street

    Deficiency Quantity 250

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 48 of 50

  • Question Response

    SITE

    PAVING

    DOT Sidewalk

    Concrete Inspected

    Deficiency Photo1

    4th Avenue

    Violations No violations recorded.

    Pavers Does not Exist

    PLAYGROUNDS Inspected

    InspectedInstance on Schoolyard - West

    Benches

    Does not ExistInstance on Schoolyard - West

    Fence

    Does not ExistInstance on Schoolyard - West

    Pavement

    Does not ExistInstance on Schoolyard - West

    Play Equipment

    InspectedInstance on Schoolyard - West

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Safety Surfacing

    InspectedInstance on Schoolyard - West

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Unpaved Area

    Does not ExistInstance on Schoolyard - West

    PLAYING SURFACE Does not Exist

    RETAINING WALLS Inspected

    Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

    No

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    SEATING Inspected

    Benches Inspected

    Concrete Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Metal/Wood/Plastic Does not Exist

    Bleachers Does not Exist

    SITE WALLS (NOT RETAINING WALLS) Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 49 of 50

  • Question Response

    SITE

    STAIRS/RAMPS: EXTERIOR Inspected

    Railings Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Site Cheek/flank Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

    Deficiency Location/Instance 14th Street

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    14th Street

    Violations No violations recorded.

    Stairs/ramps Inspected

    Condition 2 - Between Good and Fair

    Deficiency CAST IN PLACE CONCRETE: WORN-OUTTREAD/RISER/NOSERS

    Deficiency Location/Instance 13th Street

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    13th Street

    Violations No violations recorded.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K124

    PB/A&W Print Date: 9/13/2020Page 50 of 50