nuisance tripping - true rms measurements

12
European Copper Institute APPLICATION NOTE NUISANCE TRIPPING (TRUE RMS MEASUREMENTS) David Chapman, European Copper Institute October 2011 ECI Publication No Cu0110 Available from www.leonardo-energy.org/drupal/node/3942

Upload: european-copper-institute

Post on 26-Jun-2015

780 views

Category:

Business


2 download

DESCRIPTION

Nuisance tripping of circuit breakers is a common problem in many commercial and industrial installations. This Application Note explains the need to use ‘True RMS’ measurement instruments when troubleshooting and analyzing the performance of a power system. Nuisance tripping is often caused by the load current being distorted by the presence of harmonic currents drawn by non-linear loads. Harmonic currents distort the current waveform and increase the load current required to deliver energy to the load. Many measurement instruments, even quite modern ones, use an averaging measurement technique that does not measure harmonic currents correctly. ‘True RMS’ meters take the complete distorted waveform into account. If averaging meters are used to measure distorted current, the readings may be as much as 40% too low. Circuit breakers and cable sizes may be underrated as a result.

TRANSCRIPT

Page 1: Nuisance Tripping - True RMS Measurements

European Copper Institute

APPLICATION NOTE NUISANCE TRIPPING

(TRUE RMS MEASUREMENTS)

David Chapman, European Copper Institute

October 2011

ECI Publication No Cu0110

Available from www.leonardo-energy.org/drupal/node/3942

Page 2: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page i

Document Issue Control Sheet

Document Title: Application Note – Nuisance Tripping (formerly called ‘True RMS’)

Publication No: Cu0110

Issue: 02

Release: October 2011

Author(s): David Chapman

Reviewer(s): /

Document History

Issue Date Purpose

1 March

2001

Part of the Power Quality Application Guide, published under the name ‘True RMS –

the only true measurement’

2 October

2011

Reworked by the author for adoption in the Good Practice Guide

3

Disclaimer

While this publication has been prepared with care, European Copper Institute and other contributors provide

no warranty with regards to the content and shall not be liable for any direct, incidental or consequential

damages that may result from the use of the information or the data contained.

Copyright© European Copper Institute.

Reproduction is authorised providing the material is unabridged and the source is acknowledged.

Page 3: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page ii

CONTENTS

Summary ........................................................................................................................................................ 1

Nuisance tripping ............................................................................................................................................ 2

Inrush Currents ....................................................................................................................................................... 2

Case study ................................................................................................................................................ 2

True RMS – The Only True Measurement .............................................................................................................. 5

What is RMS? ........................................................................................................................................... 6

The consequences of under measurement .............................................................................................. 8

Conclusion ...................................................................................................................................................... 9

Page 4: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 1

SUMMARY Nuisance tripping of circuit breakers is a common problem in many commercial and industrial installations.

This Application Note explains the need to use ‘True RMS’ measurement instruments when troubleshooting

and analyzing the performance of a power system.

Nuisance tripping is often caused by the load current being distorted by the presence of harmonic currents

drawn by non-linear loads. Harmonic currents distort the current waveform and increase the load current

required to deliver energy to the load. Many measurement instruments, even quite modern ones, use an

averaging measurement technique that does not measure harmonic currents correctly.

‘True RMS’ meters take the complete distorted waveform into account. If averaging meters are used to

measure distorted current, the readings may be as much as 40% too low. Circuit breakers and cable sizes may

be underrated as a result.

Page 5: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 2

NUISANCE TRIPPING Many commercial and industrial installations suffer from persistent so-called ‘nuisance tripping’ of circuit

breakers. The term refers to the apparently random and inexplicable nature of these events which, although

there is no apparent fault, can cause significant disruption and financial loss. Of course, there is always a

reason for the nuisance tripping of a breaker and there are two common causes. The first possible cause is the

inrush currents that occur when some loads, particularly personal computers and other electronic devices, are

switched on. The second possible cause is that the true RMS current flowing in the circuit has been under-

measured – in other words, the true current really is too high and the trips are valid.

INRUSH CURRENTS

Modern electronic equipment, such as personal computers, monitors, television sets and office equipment,

uses a type of power supply that converts mains electricity to the low voltage direct current without a low

frequency transformer. This type of supply is known as a switched mode power supply (SMPS) and works by

rectifying mains current directly and storing the direct voltage on a large capacitor which charges to the peak

of the supply voltage. Conversion circuits draw current from the capacitor and generate the required low

voltage, usually via a high frequency transformer to provide galvanic isolation. SMPS is very cheap, but it

causes problems in installations because it produces large harmonic currents and draws very large inrush

currents to initially charge the storage capacitor.

Many PCs are never actually ‘turned off’ – in the sense of being electrically isolated from the supply - but

remain powered in standby mode and can be ‘woken up’ by user input, modem activity, or by a network

message. On wake up, they draw a starting current very similar to that drawn when starting from cold.

CASE STUDY In a small computer room at the University of Sheffield (UK) circuit breakers were being tripped apparently at

random but particularly during the night. Groups of 16 computers were connected to standard final circuits,

each protected by a 32 A miniature circuit breaker. A preliminary investigation revealed nothing – the

installation was apparently correctly installed and functioning correctly. As the problem persisted, further tests

revealed that the trips occurred at the start of the nightly maintenance procedure as the computers turned

back on and it was realized that the inrush current was responsible. Further inspection revealed that the MCBs

were type B devices so they were replaced with type D devices of the same rating – this will be discussed in

detail later. Although this change resolved the problem, a measurement exercise was undertaken to verify the

conclusion.

A logic controlled switch was interposed at the load side of one of the breakers together with a transient

recorder to measure the applied voltage and current. The switch was capable of applying the supply voltage at

a defined point on the voltage waveform.

A number of startup cycles were conducted and the inrush currents recorded. Figure 1 shows the inrush

current for a typical personal computer and (CRT) monitor set with the supply voltage applied close to the

positive voltage peak. At 155 A, this was the worst case – i.e. the maximum – inrush current recorded during

the testing for this configuration. The voltage waveform is shown only for clarity but it is interesting to note

the resulting distortion of the supply waveform, especially on the first half cycle. The steady state current

consumption was 0.75 A. The current and time resolutions of the measurements are 0.28 A and 0.8 mS

respectively.

Page 6: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 3

Figure 1 – Inrush current for one computer/monitor pairs fed by a normal final circuit.

Figure 2 shows the result with 16 computer/monitor pairs connected, the worst case peak current being 583 A.

The current and time resolutions of the measurements in this case are 1.12 A and 0.8 mS respectively.

Figure 2 – Inrush current for 16 computer/monitor pairs fed by a normal final circuit.

Page 7: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 4

MCB CHARACTERISTICS

Although the case study relates to personal computers, the principle applies to most modern electronic

equipment so it is prudent to design installations to survive large inrush currents.

Figure 3 shows the envelope of the characteristic curves for type B, C and D MCBs. The so-called ‘inverse time’

part of the characteristic is designed to protect against over-current. It allows for substantial short-term

overload without tripping, taking advantage of the inherent short time over-current tolerance of the cable. As

the over-current level increases, the time to respond reduces rapidly to restrict the rise in temperature and

reduce the risk of damage. The instantaneous characteristic is intended to respond very rapidly to fault current

to reduce the risk of damage to load circuits.

Types B, C and D MCBs are differentiated by their instantaneous tripping current, shown as Bmin, Bmax, etc. in

Figure 3.

Figure 3 – Characteristics of type B, C and D MCBs.

Taking the example of a type B MCB, Figure 3 shows that the breaker will not trip ‘instantaneously’ at any

current below 3 times nominal rating but must trip at or above 5 times nominal. In the case of a nominal 32 A

device, instantaneous tripping will occur between 96 A and 160 A with a type B device, and between 320 A and

640 A for a type D device. The minimum duration required to trip is not well defined.

Page 8: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 5

From the case study results, it is clear that a type B MCB could trip due to the inrush current from one

computer/monitor pair while selecting a type D device would provide a degree of protection against nuisance

tripping. Changing the MCB type means that the potential fault current is increased so the loop impedance of

the final circuit should be carefully checked to ensure compliance with the applicable regulations. In cases

where the inrush is too high for any available breaker, problem loads should be distributed among more final

circuits.

TRUE RMS – THE ONLY TRUE MEASUREMENT

Why do under-measurements occur frequently in modern installations even though digital test instruments

are so accurate and reliable? The answer is that many instruments are not suitable for measuring distorted

currents - and most currents these days are distorted. Since currents are being under-measured, the real

current is much closer to the nominal breaker current than believed, leading to genuine trips that are

misinterpreted as nuisance trips.

This distortion is due to harmonic currents drawn by non-linear loads, especially electronic equipment such as

personal computers, electronically ballasted fluorescent lamps and variable speed drives. Figure 6 shows the

typical current waveform drawn by a personal computer. Obviously, this is not a sine wave and all the usual

sine wave measurement tools and calculation techniques no longer work. This means that, when

troubleshooting or analyzing the performance of a power system, it is essential to use the correct tools for the

job – tools that can deal with non-sinusoidal currents and voltages.

Figure 4 shows two clamp-meters on the same branch circuit. Both the instruments are functioning correctly

and both are calibrated to the manufacturer’s specification. The key difference is in the way the instruments

measure.

Figure 4 - One current, two readings. Which do you trust? The circuit feeds a non-linear load with distorted

current. The True RMS clamp (left) reads correctly but the average responding clamp (right) reads low by 32%.

Page 9: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 6

The left-hand meter is a true RMS instrument and the right-hand one is an averaging reading RMS calibrated

instrument. Appreciating the difference requires an understanding of what RMS really means.

WHAT IS RMS? The ‘Root Mean Square’ magnitude of an alternating current is the value of equivalent direct current that

would produce the same amount of heat in a fixed resistive load. The amount of heat produced in a resistor by

an alternating current is proportional to the square of the current averaged over a full cycle of the waveform.

In other words, the heat produced is proportional to the mean of the square of the current, so the equivalent

current value is proportional to the root of the mean of the square or RMS. (The polarity is irrelevant since the

square is always positive.)

For a perfect sine wave, such as that seen in Figure 5, the RMS value is 0.707 times the peak value (or the peak

value is 2, or 1.414, times the RMS value). In other words the peak value of 1 amp RMS pure sine wave

current will be 1.414 amps. If the magnitude of the waveform is simply averaged (inverting the negative half

cycle), the mean value is 0.636 times the peak, or 0.9 times the RMS value. There are two important ratios

shown in Figure 5:

And

Figure 5 - A pure sine wave.

When measuring a pure sine wave – but only for a pure sine wave – it is quite correct to make a simple

measurement of the mean value (0.636 x peak) and multiply the result by the form factor 1.111 (making 0.707

times peak) and call it the RMS value. This is the approach taken in all analogue meters (where the averaging is

performed by the inertia and damping of the coil movement) and in all older and many currently available

digital multimeters. This technique is described as ‘mean reading, RMS calibrated’ measurement.

The problem is that the technique only works for pure sine waves and pure sine waves do not exist in the real

world of an electrical installation. The waveform in Figure 6 is typical of the current waveform drawn by a

Page 10: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 7

personal computer. The true RMS value is still 1 amp, but the peak value is much higher, at 2.6 amps, and the

average value is much lower, at 0.55 amps.

Figure 6 - Typical waveform of current drawn by a personal computer.

If this waveform is measured with a mean reading, RMS calibrated meter it would read 0.61 amps, rather than

the true value of 1 amp, nearly 40% too low. Figure 7 below gives some examples of the way the two different

types of meters respond to different wave shapes.

Figure 7 – Response of mean reading and true RMS meters to various waveshapes.

A true RMS meter works by taking the square of the instantaneous value of the input current, averaging over

time and then displaying the square root of this average. Perfectly implemented, this is absolutely accurate

whatever the waveform. Implementation is, of course, never perfect and there are two limiting factors to be

taken into account: frequency response and crest factor.

For power systems work it is usually sufficient to measure up to the 50th

harmonic, i.e. up to a frequency of

about 2500 Hz. The crest factor, the ratio between the peak value and the RMS value, is important; a higher

crest factor requires a meter with a greater dynamic range and therefore higher precision in the conversion

circuitry. A crest factor capability of at least three is required for accurate measurement in power installations.

It is worth noting that, despite giving different readings when used to measure distorted waveforms, meters of

both types would agree if used to measure a perfect sine wave. This is the condition under which they are

calibrated, so each meter could be certified as calibrated – but only for use on sine waves.

True RMS meters have been available for at least the past 30 years, but they used to be specialized and

expensive instruments. Advances in electronics have now resulted in true RMS measurement capability being

Page 11: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 8

built into many handheld multimeters. Unfortunately, this feature is generally found only towards the top end

of most manufacturers’ ranges, but they are still cheap enough to buy as ordinary instruments for everyone

and every day.

THE CONSEQUENCES OF UNDER MEASUREMENT The limiting rating for most electrical circuit elements is determined by the amount of heat that can be

dissipated so that the element or component does not overheat.

Cable ratings, for example, are given for particular installation conditions (which determine how fast heat can

escape) and a maximum working temperature. Since harmonic polluted currents have a higher RMS value than

that measured by an averaging meter, cables may have been under-rated and will run hotter than expected;

the result is degradation of the insulation, premature failure and the risk of fire.

Busbars are sized by calculating the rate of heat loss from the bars by convection and radiation and the rate of

heat gain due to resistive losses. The temperature at which these rates are equal is the working temperature

of the busbar, and it is designed so that the working temperature is low enough so that premature ageing of

insulation and support materials does not result. As with cables, errors measuring the true RMS value will lead

to higher running temperatures. Since busbars are usually physically large, skin effect is more apparent than

for smaller conductors, leading to a further increase in temperature.

Other electrical power system components such as fuses and the thermal elements of circuit breakers are

rated in RMS current because their characteristics are related to heat dissipation. This is the root cause of

nuisance tripping – the current is higher than expected so the circuit breaker is operating in an area where

prolonged use will lead to tripping. The response of a breaker in this region is temperature sensitive and may

appear to be unpredictable. As with any supply interruption, the cost of failure due to nuisance tripping can be

high, causing loss of data in computer systems, disruption of process control systems, etc.

Page 12: Nuisance Tripping - True RMS Measurements

Publication No Cu0110

Issue Date: October 2011

Page 9

CONCLUSION This paper has described two common causes of nuisance tripping. In each case there are some simple

preventive steps. Avoiding tripping due to inrush currents simply requires selection of the correct type of

breaker and sensible distribution of loads among circuits.

Under-measurement is easily avoided by ensuring that true RMS meters are used routinely. Knowledge of the

real current in a circuit allows corrective action to be taken, for example, redistributing loads across final

circuits.