November 21, 2016 ADDENDUM #1
BL003-17 Gwinnett County Corrections Complex Fire Alarm Replacement Project
This addendum is being issued to provide clarification. Q 1: Is it possible to publish the 2015 or 2016 Fire Alarm Inspection Reports, to provide more information about the system to be replaced? A 1: Reports are attached as requested and included in this addendum. Q 2: If these inspection & inventory reports are not available to be provided, will the County please publish an inventory of Booster Power Supplies and locations? A 2: Non Applicable Q 3: Will the graphical workstation PC to control the new fire alarm system be required to be UL-Listed? A 3: PC workstation required in Section 28311, paragraph 2.10 is deleted per this addendum. Q 4: If the proposed replacement system is EST, will it be required to replace the NAC Booster Power Supplies? A 4: Yes, all equipment associated with the fire alarm to be replaced. Q 5: Will proposals which do not include Graphic Annunciator Workstations (Spec 2.10 A) be disqualified? A 5: It is the contractor’s responsibility to include all necessary equipment as designed. Q 6: Will CAD (.dwg) files of the Detention Center be available to be provided to the winning bidder to establish the basis for the graphic annunciator computer? A 6: PC workstation required in Section 28311, paragraph 2.10 is deleted per this addendum. Q 7: Will the County consider value-engineering options for the current fire alarm system to minimize cost of full replacement? A 7: No. Project will be as designed. Q 8: We would like to request that Simplex be an allowable substitution for the fire alarm system at the jail since we are usually an approved equal. A 8: Please see specification section for substitution procedures. Q 9: The specifications note that ½” conduit is acceptable, but the prints identify that only ¾” shall be used. Please provide the acceptable minimum size. A 9: Conduit shall be 1/2 inch minimum. Q 10: The fiber is noted to be 62.5/125 MM. The newest standard for most FA systems are 50/125MM. It is blue, not orange which is specified color. Is the 50/125 acceptable substitute? A 10: Yes Q 11: Taking the existing system down completely is not permissible, which is understood. When adding new devices and using the same raceways and wire, is it permissible to cause troubles throughout the day while devices are switched? This would not compromise the system, it would still be fully functional. A 11: This is acceptable and anticipated.
BL003-17 Addendum #1 Page 2
Q 12: The specifications state that we should provide a complete inspection of the existing system prior to installing the new system to identify issues with the old system. How shall this be reported to GC? A 12: In writing. Q 13: Just for clarification, the system does not dial out or send signals anywhere? This is a standalone system. A 13: There is no outside monitoring. The system is monitored locally by Corrections Staff. Any call to 911 is handled by the Corrections Control Room. Q 14: Will the fiber optic network between FACPs be required to have single-mode or multi-mode transceivers? A 14: Fire alarm panels need to communicate over the multi-mode fiber cable indicated. Q 15: If factory-fabricated device guards are not available, will wire mesh protective guards from Space-Age Technologies be acceptable? A 15: Yes Q 16: Does the annunciation of points at the workstation PC need to have fully-programmed graphics, or is text-based reporting acceptable? A 16: PC workstation required in Section 28311, paragraph 2.10 is deleted per this addendum. Q 17: Can the County please provide information regarding the original contractor who installed the existing EST? A 17: This information is not available. This addendum should be signed in the space provided below and returned with your bid. Failure to do so may result in your bid being deemed non-responsive. Thank you Marlo Puckett Purchasing Associate II Company Name Authorized Representative
Entec Systems Inc.
Inspection and Testing CertificatePresented To
Gwinnett County-Police Semi
For
Correctional Institute750 Hi Hope Road
Lawrenceville GA 30043USA
CompletedThursday, October 01, 2015
ACCEPTED BY TESTED BY
Richard Turner Jared Coile
Gwinnett County-Police Semi Entec Systems Inc.
75 Langely DriveLawrenceville GA 30043USA
450 Satellite Blvd. NE, Suite PSuwanee GA 30024USA
This site has been inspected and tested in compliance with applicable standards.
Entec Systems Inc.
Inspection Summary
Building Information
PROPERTY Correctional Institute
ADDRESS 750 Hi Hope Road
CITY/STATE/ZIP Lawrenceville, GA 30043
COUNTRY USA
CONTACT Richard Turner
PHONE 0
MOBILE 0
Inspector Information
COMPANY Entec Systems Inc.
ADDRESS 450 Satellite Blvd. NE, Suite P
CITY/STATE/ZIP Suwanee, GA 30024
COUNTRY USA
CONTACT Jared Coile
PHONE (678) 858-4950
MOBILE
EMAIL [email protected]
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
Fire Control Panel 1 1(100 %) 1(100 %) 0(0 %)
Initiating Device 42 42(100 %) 42(100 %) 0(0 %)
Alarm Notification Appliance 1 1(100 %) 1(100 %) 0(0 %)
Certification
The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, withthe inspection completed on Thursday, October 01, 2015
ACCEPTED BY
10/1/2015
Richard Turner
Gwinnett County-Police Semi
TESTED BY
10/1/2015
Jared Coile
Technician
Entec Systems Inc.
Page 2 of 10
Entec Systems Inc.
System Details
Control Units
MANUFACTURER Edwards
MODEL EST3
SERIAL NUMBER
INSTALL DATE 10/1/2015
DESCRIPTION Main FACP
S/W VERSION
LAST UPDATE
S/W LOCATION
Page 3 of 10
Entec Systems Inc.
Corrective Action SummaryThe following 1 corrective action(s) were identified during the system inspection, testing or maintenance activities.
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor Notification
Corrective Action: A Dorm had no audio or visual notification during sound test. I dorm, J dorm, and Kdorm had no strobes during sound test, audio only.
Page 4 of 10
Entec Systems Inc.
Testing Details
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel Main FACP Manual 10/1/2015 10:49 AM
I I Manufacturer Edwards
I I Model EST3
I I Serial Number I
I I Visual Inspection True
I I Functional Inspection True
I I Ground Fault True
I I Disconnect Switches True
I I Alarm Verification Timer (s) I
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box A AREA B2105 Dayroom Officer A1061 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B2124 Waiting A1037 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B2129 Vestibule A1001 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B224 Concs Lab Exit Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B227 Dayroom Officer A1086 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B237 Dayroom Officer A1044 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B240 Concs Lab AES1 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B276 Dayroom Officer A1026 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
Page 5 of 10
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C10 Dayroom B1001 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C100 Dayroom Officer B1015 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C101 Waiting B1051 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C106 Search B1027 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C20 Dayroom Officer B1028 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C70 Dayroom Officer B1057 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA CC15 Corridor B1060 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA CC27 Staff Break B1095 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA CC8 Corridor B1060 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B2123 AA1043 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA 1stCORRIDOR
Outside Dining Hall Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I21 Kitchen C1008 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I33 Mechanical Room C1024 Manual 10/1/2015 10:51 AM
Page 6 of 10
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I35 Electrical Room C1023 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I70 Officer Station C1030 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I74 Corridor C1049 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I93 Corridor C1064 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC107 D1004 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC126 D1047 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC209 A1017 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC209 A1043 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC107 Nurse Station D1004 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC168 Corridor D1077 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC187 Release Lobby Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC70 Public Lobby Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC77 Visitor Waiting D1098 Manual 10/1/2015 10:51 AM
Page 7 of 10
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC84 Corridor D1038 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box I108 C1079 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W11 Vocational Classroom Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W12 Storage E1003 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W17 Equipment Room E1004 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W27 Warehouse E1010 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W35 Warehouse E1010 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
I I Alarm Verification Participation False
Manual Fire Box Warehouse W36 Vestibule E1001 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Alarm Notification Appliance
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Audible And Visible 1st Floor Notification Manual 10/1/2015 10:55 AM
I I Visual Inspection True
I I Functional Inspection True
Page 8 of 10
Entec Systems Inc.
Device/Equipment Details
Fire Control Panel
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Fire Alarm Panel
Main FACP Edwards EST3 10/1/2015
Initiating Device
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Manual Fire Box
A AREA B2105 Dayroom Officer A1061 Edwards 10/1/2015
A AREA B2124 Waiting A1037 Edwards 10/1/2015
A AREA B2129 Vestibule A1001 Edwards 10/1/2015
A AREA B224 Concs Lab Exit Edwards 10/1/2015
A AREA B227 Dayroom Officer A1086 Edwards 10/1/2015
A AREA B237 Dayroom Officer A1044 Edwards 10/1/2015
A AREA B240 Concs Lab AES1 Edwards 10/1/2015
A AREA B276 Dayroom Officer A1026 Edwards 10/1/2015
B AREA 1C10 Dayroom B1001 Edwards 10/1/2015
B AREA 1C100 Dayroom Officer B1015 Edwards 10/1/2015
B AREA 1C101 Waiting B1051 Edwards 10/1/2015
B AREA 1C106 Search B1027 Edwards 10/1/2015
B AREA 1C20 Dayroom Officer B1028 Edwards 10/1/2015
B AREA 1C70 Dayroom Officer B1057 Edwards 10/1/2015
B AREA CC15 Corridor B1060 Edwards 10/1/2015
B AREA CC27 Staff Break B1095 Edwards 10/1/2015
B AREA CC8 Corridor B1060 Edwards 10/1/2015
B2123 AA1043 Edwards 10/1/2015
C AREA 1stCORRIDOR
Outside Dining Hall Edwards 10/1/2015
C AREA I21 Kitchen C1008 Edwards 10/1/2015
C AREA I33 Mechanical Room C1024 Edwards 10/1/2015
C AREA I35 Electrical Room C1023 Edwards 10/1/2015
C AREA I70 Officer Station C1030 Edwards 10/1/2015
C AREA I74 Corridor C1049 Edwards 10/1/2015
C AREA I93 Corridor C1064 Edwards 10/1/2015
CC107 D1004 Edwards 10/1/2015
CC126 D1047 Edwards 10/1/2015
CC209 A1017 Edwards 10/1/2015
CC209 A1043 Edwards 10/1/2015
D AREA CC107 Nurse Station D1004 Edwards 10/1/2015
D AREA CC168 Corridor D1077 Edwards 10/1/2015
D AREA CC187 Release Lobby Edwards 10/1/2015
D AREA CC70 Public Lobby Edwards 10/1/2015
D AREA CC77 Visitor Waiting D1098 Edwards 10/1/2015
D AREA CC84 Corridor D1038 Edwards 10/1/2015
I108 C1079 Edwards 10/1/2015
Warehouse W11 Vocational Classroom Edwards 10/1/2015
Warehouse W12 Storage E1003 Edwards 10/1/2015
Warehouse W17 Equipment Room E1004 Edwards 10/1/2015
Page 9 of 10
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Warehouse W27 Warehouse E1010 Edwards 10/1/2015
Warehouse W35 Warehouse E1010 Edwards 10/1/2015
Warehouse W36 Vestibule E1001 Edwards 10/1/2015
Alarm Notification Appliance
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Audible And Visible
1st Floor Notification 10/1/2015
Page 10 of 10
Entec Systems Inc.
Inspection and Testing CertificatePresented To
Gwinnett County-Police
For
Correctional Institute750 Hi Hope Road
Lawrenceville GA 30044USA
This site has been inspected and tested in compliance with applicable standards.
CompletedThursday, February 25, 2016
Test Session: 2/25/16 Annual Fire Alarm Inspection Correctional Complex
ACCEPTED BY TESTED BY
Richard Turner Jared Coile
Gwinnett County-Police Entec Systems Inc.
75 Langely DriveLawrenceville GA 30043USA
450 Satellite Blvd. NE, Suite PSuwanee GA 30024USA
Entec Systems Inc.
Inspection Summary
Building Information
PROPERTY Correctional Institute
ADDRESS 750 Hi Hope Road
CITY/STATE/ZIP Lawrenceville, GA 30044
COUNTRY USA
CONTACT Richard Turner
PHONE
MOBILE
Inspector Information
COMPANY Entec Systems Inc.
ADDRESS 450 Satellite Blvd. NE, Suite P
CITY/STATE/ZIP Suwanee, GA 30024
COUNTRY USA
CONTACT Jared Coile
PHONE (678) 858-4950
MOBILE
EMAIL [email protected]
NAME INITIALS QUALIFICATION AND PROFICIENCIES
Jared Coile JC
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
Fire Control Panel 1 1(100 %) 1(100 %) 0(0 %)
Initiating Device 516 516(100 %) 516(100 %) 0(0 %)
Alarm Notification Appliance 1 1(100 %) 1(100 %) 0(0 %)
CertificationThe equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspectioncompleted on Thursday, February 25, 2016
ACCEPTED BY
3/1/2016
Richard Turner
Gwinnett County-Police
TESTED BY
3/1/2016
Jared Coile
Technician
Entec Systems Inc.
Page 2 of 70
Entec Systems Inc.
System Details
Control Units
MANUFACTURER EST
MODEL
SERIAL NUMBER
INSTALL DATE 2/29/2016
DESCRIPTION Main FACP
S/W VERSION
LAST UPDATE
S/W LOCATION
Monitoring Information
Page 3 of 70
Entec Systems Inc.
Open Corrective Action & Solution SummaryThe following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor Notification
Created By: Jared Coile
Creation Date: 3/1/2016
Corrective Action: K Dorm the strobe circuit is down.
Proposed Solution: Trouble shoot NAC circuit and/or relay.
Page 4 of 70
Entec Systems Inc.
Testing Details
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel Main FACP Manual 3/1/2016 11:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
I I
I I
I I
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralB AREA 1C681014
STORAGE B2035 Manual 2/25/2016 9:17 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C671013
DAYROOM B1057 Manual 2/25/2016 9:17 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C691003
DAYROOM B1057 Manual 2/25/2016 9:17 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C661012
DAYROOM B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C651011
DAYROOM B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C561009
DAYROOM MEZZ B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C631010
DAYROOM B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
Page 5 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C571008
DAYROOM MEZZ B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C581007
DAYROOM MEZZ B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1121001
CORRIDOR B1026 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C641006
DAYROOM B1057 Manual 2/25/2016 9:19 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C621005
DAYROOM B1057 Manual 2/25/2016 9:20 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C611004
DAYROOM B1057 Manual 2/25/2016 9:20 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C491016
CORRIDOR B1044 Manual 2/25/2016 9:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C521017
STORAGE B1041 Manual 2/25/2016 9:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C431018
CORRIDOR B1044 Manual 2/25/2016 9:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C481019
STORAGE B1042 Manual 2/25/2016 9:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I991498
VEST. ROOM D1114 Manual 2/25/2016 9:28 AM
I I Manufacturer EST
I I Visual Inspection True
Page 6 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C471020
STORAGE B1043 Manual 2/25/2016 9:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC771312
VISITOR WAITING D1098 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC831313
PUBLIC LOBBY D1117 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC671314
WAITING B1070 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2511507
ELECT. ROOM D1115 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C201033
DAYROOM OFFICER B1028 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC661315
WAITING B1070 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC651316
WAITING B1070 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC431317
CORRIDOR B1079 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC421320
MEETING ROOM B1077 Manual 2/25/2016 9:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC2801318
ADMIN ASSISTANTS B1080 Manual 2/25/2016 9:31 AM
I I Manufacturer EST
I I Visual Inspection True
Page 7 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C351029
DAYROOM B1028 Manual 2/25/2016 9:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C331030
DAYROOM B1028 Manual 2/25/2016 9:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C321031
DAYROOM B1028 Manual 2/25/2016 9:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C311032
DAYROOM B1028 Manual 2/25/2016 9:33 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C231026
CONC SLAB BES2 Manual 2/25/2016 9:35 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C341023
DAYROOM B1028 Manual 2/25/2016 9:36 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C361022
DAYROOM B1028 Manual 2/25/2016 9:37 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C371021
DAYROOM B1028 Manual 2/25/2016 9:38 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC401321
WORK ROOM B1086 Manual 2/25/2016 9:42 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC391322
SUPPLY ROOM B1085 Manual 2/25/2016 9:43 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC341324
BREAK ROOM B1089 Manual 2/25/2016 9:43 AM
I I Manufacturer EST
I I Visual Inspection True
Page 8 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Manual Fire BoxB AREA 1C701015
DAYROOM OFFICER B1057 Manual 2/25/2016 9:44 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1001069
DAYROOM OFFICER B1015 Manual 2/25/2016 9:46 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C891064
DAYROOM MEZZ B1015 Manual 2/25/2016 9:46 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C881063
DAYROOM MEZZ B1015 Manual 2/25/2016 9:47 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C871062
DAYROOM MEZZ B1015 Manual 2/25/2016 9:47 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C861061
DAYROOM MEZZ B1015 Manual 2/25/2016 9:48 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C931068
DAYROOM B1015 Manual 2/25/2016 9:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C951067
DAYROOM B1015 Manual 2/25/2016 9:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C961066
DAYROOM B1015 Manual 2/25/2016 9:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C981065
DAYROOM B1015 Manual 2/25/2016 9:51 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C971070
STORAGE B2034 Manual 2/25/2016 9:52 AM
I I Manufacturer EST
I I Visual Inspection True
Page 9 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C991058
DAYROOM B1015 Manual 2/25/2016 9:52 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C941059
DAYROOM B1015 Manual 2/25/2016 9:53 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C921060
DAYROOM B1015 Manual 2/25/2016 9:54 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C911057
DAYROOM B1015 Manual 2/25/2016 9:55 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C791055
CORRIDOR B1109 Manual 2/25/2016 9:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C811056
STORAGE B1055 Manual 2/25/2016 9:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C731052
CORRIDOR B1109 Manual 2/25/2016 9:59 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C781054
ELECTRICAL B1054 Manual 2/25/2016 9:59 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C771053
STORAGE B1053 Manual 2/25/2016 10:01 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C101051
DAYROOM B1001 Manual 2/25/2016 10:03 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C91043
DAYROOM MEZZ B1001 Manual 2/25/2016 10:04 AM
I I Manufacturer EST
I I Visual Inspection True
Page 10 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C71044
DAYROOM MEZZ B1001 Manual 2/25/2016 10:05 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C121040
DAYROOM B1001 Manual 2/25/2016 10:20 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C141041
DAYROOM B1001 Manual 2/25/2016 10:21 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C191042
DAYROOM B1001 Manual 2/25/2016 10:22 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C111039
DAYROOM B1001 Manual 2/25/2016 10:23 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1051036
SEARCH AREA B1027 Manual 2/25/2016 10:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1301035
SEARCH AREA B1027 Manual 2/25/2016 10:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C1061034
SEARCH B1027 Manual 2/25/2016 10:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1041037
CORRIDOR B1110 Manual 2/25/2016 10:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1031038
CORRIDOR B1051 Manual 2/25/2016 10:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C1011462
WAITING B1051 Manual 2/25/2016 10:32 AM
I I Manufacturer EST
I I Visual Inspection True
Page 11 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralD AREA 1STHALL1354
OUSIDE ROOM D1120 Manual 2/25/2016 10:43 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1021074
WAITING B1051 Manual 2/25/2016 10:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA RET1C1091461
WAITING B1051 RTU8 Manual 2/25/2016 10:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREASUP1C1081464
WAITING B1051 RTU8 Manual 2/25/2016 10:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1101072
CORRIDOR B1026 Manual 2/25/2016 10:52 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1111071
CORRIDOR B1026 Manual 2/25/2016 10:52 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC91365
CORRIDOR B1060 Manual 2/25/2016 10:53 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC71366
CORRIDOR B1060 Manual 2/25/2016 10:53 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC61367
CORRIDOR B1060 Manual 2/25/2016 10:54 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC51368
CORRIDOR B1060 Manual 2/25/2016 10:55 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21091077
EQUIPMENT ROOM A1042 Manual 2/25/2016 10:56 AM
Page 12 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B21051474
DAYROOM OFFICER A1061 Manual 2/25/2016 10:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2931236
DAYROOM MEZZ A1061 Manual 2/25/2016 11:01 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2921237
DAYROOM MEZZ A1061 Manual 2/25/2016 11:02 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2981239
DAYROOM A1061 Manual 2/25/2016 11:05 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21001241
DAYROOM A1061 Manual 2/25/2016 11:11 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21021242
DAYROOM A1061 Manual 2/25/2016 11:11 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA 1STDAYROOM A10611446
STORAGE A1058 Manual 2/25/2016 11:22 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C601002
STORAGE B 1066 Manual 2/25/2016 11:22 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2841447
ELECTRICAL ROOM A1056 Manual 2/25/2016 11:24 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2371107
DAYROOM OFFICER A1044 Manual 2/25/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General A AREA B241 DAYROOM A1044 Manual 2/25/2016 11:30 AM
Page 13 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1096
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2501101
DAYROOM A1044 Manual 2/25/2016 11:34 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2491094
DAYROOM A1044 Manual 2/25/2016 11:41 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2461093
DAYROOM A1044 Manual 2/25/2016 11:42 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2531091
DAYROOM A1044 Manual 2/25/2016 11:43 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2271105
DAYROOM OFFICER A1086 Manual 2/25/2016 11:45 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2241104
CONC SLAB EXIT Manual 2/25/2016 11:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2401106
CONC SLAB AES1 Manual 2/25/2016 11:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2281108
DAYROOM A1086 Manual 2/25/2016 11:56 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2351109
DAYROOM A1086 Manual 2/25/2016 11:56 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2311111
DAYROOM A1086 Manual 2/25/2016 11:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General A AREA B229 DAYROOM A1086 Manual 2/25/2016 11:58 AM
Page 14 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1110
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2151443
STORAGE A1090 Manual 2/25/2016 12:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2181468
STORAGE A1090 Manual 2/25/2016 12:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2171119
STORAGE A1090 Manual 2/25/2016 12:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2141442
ELECTRICAL A1030 Manual 2/25/2016 12:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2561118
STORAGE A1029 Manual 2/25/2016 12:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2571441
STORAGE A1029 Manual 2/25/2016 12:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2611467
STORAGE A1029 Manual 2/25/2016 12:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC961389
CORRIDOR D1030 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC951392
CORRIDOR D1030 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC941395
CORRIDOR D1030 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General D AREA CC205 CLASSROOM D1031 Manual 2/25/2016 2:29 PM
Page 15 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1385
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2061386
CLASSROOM D1031 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1221388
GED D1028 Manual 2/25/2016 2:30 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1191372
CORRIDOR C1025 Manual 2/25/2016 2:30 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I701408
OFFICER STATION C1030 Manual 2/25/2016 2:30 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I631404
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I671405
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I681406
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I621407
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1061402
WAITING D1001 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1051403
EXAM D1012 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General D AREA CC104 TREATMENT D1013 Manual 2/25/2016 2:31 PM
Page 16 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1375
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1081376
CORRIDOR D1011 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1091377
LAB D1014 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1101378
DENTAL SUITE D1015 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1151379
CORRIDOR D1011 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2171371
CORRIDOR D1011 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1191381
ISOLATION VESTIBULE Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1201369
ISOLATION D1018 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1181370
ISOLATION D1020 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I801298
DAYROOM C1041 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I861299
DAYROOM C1041 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General C AREA I72 CORRIDOR C1049 Manual 2/25/2016 2:33 PM
Page 17 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1300
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I731301
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I741302
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I751303
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I761304
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I921500
STORAGE C1042 Manual 2/25/2016 2:34 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC841244
CORRIDOR D1038 Manual 2/25/2016 2:34 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA 1STCORRIDOR1276
OUTSIDE DINING HALL Manual 2/25/2016 2:35 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA CCADD1247
CORRIDOR C1092 Manual 2/25/2016 2:35 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I961293
DAYROOM C1056 Manual 2/25/2016 2:35 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I871294
DAYROOM C1056 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 18 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - DuctC AREA I891454
DAYROOM C1056 RETURN Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I911295
CORRIDOR C1064 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I931296
CORRIDOR C1064 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I941297
CORRIDOR C1064 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1331281
CORRIDOR D1047 Manual 2/25/2016 2:39 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC901251
CORRIDOR D1038 Manual 2/25/2016 2:39 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1281282
CORRIDOR D1047 Manual 2/25/2016 2:40 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC1261283
CORRIDOR D1047 Manual 2/25/2016 2:40 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1311285
CORRIDOR D1047 Manual 2/25/2016 2:40 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC921253
CORRIDOR D1038 Manual 2/25/2016 2:41 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1571279
EQUIPMENT D1040 Manual 2/25/2016 2:42 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 19 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralD AREA CC1581272
DAYROOM D1054 Manual 2/25/2016 2:42 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1641273
DAYROOM D1054 Manual 2/25/2016 2:43 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1521274
CORRIDOR D1062 Manual 2/25/2016 2:44 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1501275
CORRIDOR D1062 Manual 2/25/2016 2:44 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box
1ST C AREACORRIDOROUTSIDE .11245
DINING HALL Manual 2/25/2016 2:45 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box
1ST C AREACORRIDOROUTSIDE .21246
DINING HALL Manual 2/25/2016 2:45 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1491277
CORRIDOR D1062 Manual 2/25/2016 2:45 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1531278
CORRIDOR D1062 Manual 2/25/2016 2:46 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC931254
CORRIDOR D1038 Manual 2/25/2016 2:47 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC941255
CORRIDOR D1038 Manual 2/25/2016 2:47 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC951256
CORRIDOR D1038 Manual 2/25/2016 2:48 PM
Page 20 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1801265
DAYROOM D1069 SUP Manual 2/25/2016 2:48 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1841266
DAYROOM D1069 Manual 2/25/2016 2:48 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1731271
CORRIDOR D1077 Manual 2/25/2016 2:49 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1711270
CORRIDOR D1077 Manual 2/25/2016 2:49 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC1681269
CORRIDOR D1077 Manual 2/25/2016 2:50 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1701268
CORRIDOR D1077 Manual 2/25/2016 2:50 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1741267
CORRIDOR D1077 Manual 2/25/2016 2:51 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC961257
CORRIDOR D1038 Manual 2/25/2016 2:52 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC971258
CORRIDOR D1038 Manual 2/25/2016 2:53 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC981259
CORRIDOR D1038 Manual 2/25/2016 2:54 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1881263
CORRIDOR D1084 Manual 2/25/2016 2:55 PM
Page 21 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1851260
INTERVIEW ROOM D1085 Manual 2/25/2016 2:55 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1891264
CORRIDOR D1084 Manual 2/25/2016 2:55 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1861261
RELEASE LOBBY D1085 Manual 2/25/2016 2:56 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC1871262
RELEASE LOBBY Manual 2/25/2016 2:56 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC471343
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC481340
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC461342
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC491341
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C801122
SUPSTORAGE B1055 RTU7 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C511124
STORAGE B1041 RTU10 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C461125
CORRIDOR B1044 Manual 2/25/2016 3:00 PM
Page 22 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C751123
CORRIDOR B1109 RTU6 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2811121
STORAGE A1055 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2851120
STORAGE A1056 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC541339
SEARCH AREA D1106 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA CC181126
M SHOWER B1093 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA CC221127
JANITOR ROOM B1098 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C541129
TOILET B1040 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA CC301128
W LOCKER B1092 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C551130
SHOWER B1039 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C711132
JANITOR ROOM B1103 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C841133
TOILET B1014 Manual 2/25/2016 3:01 PM
Page 23 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C411135
JANITOR ROOM B1047 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C851134
SHOWER B1013 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C391131
JANITOR B1048 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C271137
TOILET B1038 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC791344
STORAGE D1101 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC801345
VSP ROOM D1100 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C281136
JANITOR ROOM B1045 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C261138
SHOWER B1037 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C11139
JANITOR ROOM B1108 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C31140
SHOWER B1011 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2771142
JANITOR ROOM A1041 Manual 2/25/2016 3:02 PM
Page 24 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C21141
TOILET B1012 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2891143
TOILET A1059 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2901144
SHOWER A1060 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2581145
TOILET A1028 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2591146
SHOWER A1027 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2541147
JANITOR ROOM A1032 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B21151148
JANITOR ROOM A1033 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2201149
TOILET A1088 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2211150
SHOWER A1088 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2361151
JANITOR ROOM A1035 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2441153
TOILET A1064 Manual 2/25/2016 3:03 PM
Page 25 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2431152
SHOWER A1063 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2451154
JANITOR ROOM A1039 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I411155
LAUNDRY C1021 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I421156
LAUNDRY C1021 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I401157
LAUNDRY C1021 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I371158
DRY AREA C1022 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I31159
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I41160
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I21161
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I11163
DISH WASH C1087 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I111164
KITCHEN C1008 Manual 2/25/2016 3:04 PM
Page 26 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I171165
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I201166
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I181168
KITCHEN C1008 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I191167
KITCHEN C1008 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I231169
DRY STORAGE C1011 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I221170
DRY STORAGE C1011 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I71171
JANITOR ROOM C1012 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I531172
SERVERY C1003 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I541173
JANITOR ROOM C1006 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I551174
SERVERY C1005 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1121175
JANITOR ROOM Manual 2/25/2016 3:06 PM
Page 27 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I591176
JANITOR ROOM C1027 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I811177
LAUNDRY C1044 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I821178
JANITOR ROOM C1043 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I981179
JANITOR ROOM C1058 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I971180
LAUNDRY C1059 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I1041181
JANITOR ROOM C1073 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I1051182
LAUNDRY C1074 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1391183
JANITOR ROOM D1040 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1381184
LAUNDRY D1042 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1561185
JANITOR ROOM D1041 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1551186
LAUNDRY D1042 Manual 2/25/2016 3:06 PM
Page 28 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1771187
TOILET D1070 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1761188
LAUNDRY D1072 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC811189
JANITOR ROOM D1104 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC721190
JANITOR ROOM D1112 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW261194
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW241195
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW251196
SECURED STORAGE Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW231199
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW221200
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW321201
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
Page 29 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW331202
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW211203
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW201204
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW191205
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW341206
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW181207
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW151208
MAINTENANCE SHOP Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW141209
MAINTENANCE SHOP Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW101217
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W91218
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
Page 30 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W71219
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W81220
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W61221
VOCATIONAL CLASSROOM Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W51222
VOCATIONAL CLASSROOM Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW131223
STORAGE E1003 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW281226
EQUIPMENT STORAGE E1004 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I341228
MECHANICAL ROOM C1024 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I241229
MECHANICAL ROOM C1024 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2011398
MULTIPURPOSE D1037 Manual 2/25/2016 3:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2021397
MULTIPURPOSE D1037 Manual 2/25/2016 3:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 31 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralD AREA CC2161399
MULTIPURPOSE D1037 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1971396
MULTIPURPOSE D1037 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2081400
STORAGE D1036 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I571412
STAFF DINING C1005 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I561413
STAFF DINING C1005 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1071509
CORRIDOR C1016 Manual 2/25/2016 3:12 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I211418
KITCHEN C1008 Manual 2/25/2016 3:12 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I141162
KITCHEN C1008 Manual 2/25/2016 3:12 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I491415
DIVERSION DINING C1002 Manual 2/25/2016 3:13 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I501414
DIVERSION DINING C1002 Manual 2/25/2016 3:13 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I511417
DIVERSION DINING C1002 Manual 2/25/2016 3:14 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 32 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralC AREA I521416
DIVERSION DINING C1002 Manual 2/25/2016 3:17 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1201508
STORAGE C1017 Manual 2/25/2016 3:18 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I461419
JANITOR C1017 Manual 2/25/2016 3:18 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC1261494
A1017 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctI1081493
A1043 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC2091492
A1043 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC209.11491
D1004 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB21231490
DAYROOM C1041 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC1071489
DAYROOM D1039 SUPPLY Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctI781488
DAYROOM D1069 SUPPLY Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1351487
DAYROOM D1054 SUPPLY Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 33 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - DuctD AREA CC1821486
NEAR D 1075 SHOWER Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1601485
DAYROOM B1057 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC51RET1483
SHIFT SUPERVISOR D1121 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA R CC2001482
MULTIPURPOSE D1037 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA S CC1991481
MULTIPURPOSE D1037 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1001480
COMPUTER LAB D1027 SUP Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1021479
COMPUTER LAB D1027 RET Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I391475
LAUNDRY C1021 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B21131470
WAITING A1037 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C821459
RET STORAGE B1055 RTU7 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C451457
CORRIDOR B1042 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
Page 34 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C531456
STORAGE B1044 RTU10 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I791455
DAYROOM C1041 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I881453
DAYROOM A1056 SUPPLY Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I111.11452
DAYROOM C1071 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1361451
DAYROOM D1039 RETURN Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1831450
DAYROOM D1069 RETURN Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1611449
DAYROOM D1054 RETURN Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C211024
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C221025
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C251027
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C241028
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
Page 35 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C51045
DAYROOM MEZZ B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C41046
DAYROOM MEZZ B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C131047
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C151048
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C161049
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C181050
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1151073
EQUIPMENT ROOM B1104 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C721075
MULTIPURPOSE B1056 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA CC81076
CORRIDOR B1060 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2661078
EQUIPMENT ROOM A1016 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21101079
CORRIDOR A1015 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
Page 36 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21111080
CORRIDOR A1015 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21061081
EQUIPMENT ROOM A1042 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21181082
WAITING A1037 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21121083
COUNSELOR A1031 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21161084
SUPPLY ROOM A1034 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21251085
MULTIPURPOSE A1040 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21201086
CORRIDOR A1015 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21211087
CORRIDOR A1015 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21221088
SEARCH A1043 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21521089
SEARCH A1043 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21231090
SEARCH A1043 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
Page 37 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2521092
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2421095
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2391097
DAYROOM MEZZ A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2381098
DAYROOM MEZZ A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2471099
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2481100
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2331102
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2341103
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2261112
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2251113
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2231114
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
Page 38 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2221115
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2301116
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2321117
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I361191
ELECTRICAL C1023 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I351192
ELECTRICAL C1023 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW271193
WAREHOUSE E1010 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSEW28.11197
ELECTRICAL ROOM E1011 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSEW291198
OFFICE E1013 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW351210
WAREHOUSE E1010 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSE W21211
CORRIDOR E1006 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General WAREHOUSE W3 CORRIDOR E1006 Manual 3/1/2016 11:26 AM
Page 39 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1212
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSE W11213
OFFICE E1007 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSE W41214
VESTIBULE E1001 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW361215
VESTIBULE E1001 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW111216
VOCATIONAL CLASSROOM Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW121224
STORAGE E1003 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW171225
EQUIPMENT STORAGE E1004 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I331227
MECHANICAL ROOM C1024 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC45.11230
EQUIT D1119 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21041231
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21011232
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
Page 40 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2971233
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2961234
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2941235
DAYROOM MEZZ A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2911238
DAYROOM MEZZ A1061 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2991240
DAYROOM A1061 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21031243
DAYROOM A1061 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC871248
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC881249
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC891250
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC911252
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1431280
DAYROOM D1039 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
Page 41 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1291284
CORRIDOR D1047 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1021286
DAYROOM C1071 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1141287
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1101288
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1091289
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1081290
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1071291
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1061292
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B251305
VESTIBULE A1001 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B21291306
VESTIBULE A1001 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B231307
HOLDING CELL A1004 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
Page 42 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B221308
HOLDING CELL A1005 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B211309
HOLDING CELL A1006 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2121310
CORRIDOR A1012 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA CC151311
CORRIDOR B1060 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC441319
INMATE RECORDS D1083 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC311323
CORRIDOR OF ADMIN B1080 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC361325
STORAGE B1090 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC251326
CORRIDOR B1094 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC281327
STAFF BREAK B1095 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA CC271328
STAFF BREAK B1095 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC241329
TRAINING B1096 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
Page 43 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC261330
TRAINING B1096 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC231331
CORRIDOR B1094 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC201332
FITNESS B1099 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC171333
M LOCKER B1106 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC191334
CORRIDOR B1094 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC161335
CORRIDOR B1094 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC371336
UNIFORM STORAGE B1091 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC631337
MAIN VESTIBULE B1069 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC621338
MAIN VESTIBULE B1069 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC751346
VISITOR WAITING D1098 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC781347
VISITOR WAITING D1098 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 44 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC731348
STORAGE D1111 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC761349
VESTIBULE D1096 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC701350
PUBLIC LOBBY D1117 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC741351
CORRIDOR D1110 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC821352
OFFICE D1118 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC451353
EQUIPMENT D1119 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC591355
MASTER CONTROL D1129 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC531356
SHIFT SUPERVISOR D1121 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC551357
STORAGE D1122 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC561358
CORRIDOR D1125 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC611359
MAIL ROOM D1126 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 45 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC141360
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC131361
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC121362
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC111363
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC101364
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1131373
ELECTRICAL ROOM D1008 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I581374
VESTIBULE C1026 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1111380
STORAGE D1005 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC41382
CORRIDOR A1068 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC31383
CORRIDOR A1068 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC21384
CORRIDOR A1068 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 46 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2071387
STORAGE D1035 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC991390
COMPUTER LAB D1027 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1031391
BARBER D1026 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2031393
LIBRARY D1034 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2041394
LIBRARY D1034 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1211401
CORRIDOR C1025 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I611409
DAYROOM MEZZ C1030 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I691410
DAYROOM MEZZ C1030 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I601411
DAYROOM MEZZ C1030 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC2091420
VESITBULE A1017 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC11421
VESTIBULE A1017 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 47 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2101422
PROPERTY STORAGE A1014 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B271423
ISSUE A1073 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2131424
SEARCH AREA A1008 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B261425
INMATE WAITING A1002 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B241426
INTERVIEW A1003 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2751427
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2671428
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2681429
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2721430
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2621431
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2631432
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
Page 48 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2641433
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2651434
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2731435
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2741436
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2711437
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2701438
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2691439
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2161440
CORRIDOR A1074 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2781444
CORRIDOR A1057 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2791445
CORRIDOR A1057 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2831448
STORAGE A1055 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
Page 49 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA RET1C761458
CORRIDOR B1109 RTU6 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C381460
COUNSELOR B1049 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C421463
SUPPLY ROOM B1046 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C291465
COUNSELOR B1050 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C901466
EQUPIMENT B1024 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21191469
COUNSELOR A1036 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B21241471
WAITING A1037 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2761472
DAYROOM OFFICER A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA 1STDAYROOM A10611473
CORRIDOR A1057 B288 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I61476
IT TOILET C1013 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I51477
ST TOILET C1015 Manual 3/1/2016 11:29 AM
Page 50 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2951478
STORAGE A1070 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C591484
MAIN PANEL Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC691495
C1079 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC711496
D1047 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I831497
Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I951499
STORAGE D1113 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1371501
EQUIP. ROOM C1057 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC411502
CORRIDOR C1064 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC431503
CORRIDOR C1064 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC681504
DAYROOM D1039 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I471505
ADMIN. ASSISTS. B1080 Manual 3/1/2016 11:30 AM
Page 51 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I481506
CORRIDOR B1079 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1141510
DAYROOM A1044 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1171511
CORRIDOR C1025 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1161512
NURSE STATION D1004 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C301513
EMER. STORAGE D1007 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1111514
SOILED LINEN D1010 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC501515
CLEAN LINEN D1009 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21171516
DAYROOM B1028 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Alarm Notification Appliance
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Audible And Visible 1st Floor Notification Manual 3/1/2016 11:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 52 of 70
Entec Systems Inc.
Device/Equipment Details
Fire Control Panel
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Fire Alarm Panel
Main FACP EST 2/29/2016
Initiating Device
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Heat Detector - Restorable Spot
B AREA CC181126
M SHOWER B1093 EST 12/31/2011
B AREA CC221127
JANITOR ROOM B1098 EST 12/31/2011
B AREA CC301128
W LOCKER B1092 EST 12/31/2011
B AREA 1C541129
TOILET B1040 EST 12/31/2011
B AREA 1C551130
SHOWER B1039 EST 12/31/2011
B AREA 1C391131
JANITOR B1048 EST 12/31/2011
B AREA 1C711132
JANITOR ROOM B1103 EST 12/31/2011
B AREA 1C841133
TOILET B1014 EST 12/31/2011
B AREA 1C851134
SHOWER B1013 EST 12/31/2011
B AREA 1C411135
JANITOR ROOM B1047 EST 12/31/2011
B AREA 1C281136
JANITOR ROOM B1045 EST 12/31/2011
B AREA 1C271137
TOILET B1038 EST 12/31/2011
B AREA 1C261138
SHOWER B1037 EST 12/31/2011
B AREA 1C11139
JANITOR ROOM B1108 EST 12/31/2011
B AREA 1C31140
SHOWER B1011 EST 12/31/2011
B AREA 1C21141
TOILET B1012 EST 12/31/2011
A AREA B2771142
JANITOR ROOM A1041 EST 12/31/2011
A AREA B2891143
TOILET A1059 EST 12/31/2011
A AREA B2901144
SHOWER A1060 EST 12/31/2011
A AREA B2581145
TOILET A1028 EST 12/31/2011
A AREA B2591146
SHOWER A1027 EST 12/31/2011
A AREA B2541147
JANITOR ROOM A1032 EST 12/31/2011
A AREA B21151148
JANITOR ROOM A1033 EST 12/31/2011
A AREA B220 TOILET A1088 EST 12/31/2011
Page 53 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1149
A AREA B2211150
SHOWER A1088 EST 12/31/2011
A AREA B2361151
JANITOR ROOM A1035 EST 12/31/2011
A AREA B2431152
SHOWER A1063 EST 12/31/2011
A AREA B2441153
TOILET A1064 EST 12/31/2011
A AREA B2451154
JANITOR ROOM A1039 EST 12/31/2011
C AREA I411155
LAUNDRY C1021 EST 12/31/2011
C AREA I421156
LAUNDRY C1021 EST 12/31/2011
C AREA I401157
LAUNDRY C1021 EST 12/31/2011
C AREA I371158
DRY AREA C1022 EST 12/31/2011
C AREA I31159
KITCHEN C1008 EST 12/31/2011
C AREA I41160
KITCHEN C1008 EST 12/31/2011
C AREA I21161
KITCHEN C1008 EST 12/31/2011
C AREA I11163
DISH WASH C1087 EST 12/31/2011
C AREA I111164
KITCHEN C1008 EST 12/31/2011
C AREA I171165
KITCHEN C1008 EST 12/31/2011
C AREA I201166
KITCHEN C1008 EST 12/31/2011
C AREA I191167
KITCHEN C1008 EST 12/31/2011
C AREA I181168
KITCHEN C1008 EST 12/31/2011
C AREA I231169
DRY STORAGE C1011 EST 12/31/2011
C AREA I221170
DRY STORAGE C1011 EST 12/31/2011
C AREA I71171
JANITOR ROOM C1012 EST 12/31/2011
C AREA I531172
SERVERY C1003 EST 12/31/2011
C AREA I541173
JANITOR ROOM C1006 EST 12/31/2011
C AREA I551174
SERVERY C1005 EST 12/31/2011
D AREA CC1121175
JANITOR ROOM EST 12/31/2011
C AREA I591176
JANITOR ROOM C1027 EST 12/31/2011
C AREA I811177
LAUNDRY C1044 EST 12/31/2011
C AREA I821178
JANITOR ROOM C1043 EST 12/31/2011
C AREA I981179
JANITOR ROOM C1058 EST 12/31/2011
C AREA I971180
LAUNDRY C1059 EST 12/31/2011
Page 54 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I1041181
JANITOR ROOM C1073 EST 12/31/2011
C AREA I1051182
LAUNDRY C1074 EST 12/31/2011
D AREA CC1391183
JANITOR ROOM D1040 EST 12/31/2011
D AREA CC1381184
LAUNDRY D1042 EST 12/31/2011
D AREA CC1561185
JANITOR ROOM D1041 EST 12/31/2011
D AREA CC1551186
LAUNDRY D1042 EST 12/31/2011
D AREA CC1771187
TOILET D1070 EST 12/31/2011
D AREA CC1761188
LAUNDRY D1072 EST 12/31/2011
D AREA CC811189
JANITOR ROOM D1104 EST 12/31/2011
D AREA CC721190
JANITOR ROOM D1112 EST 12/31/2011
WAREHOUSEW261194
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW241195
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW251196
SECURED STORAGE EST 12/31/2011
WAREHOUSEW231199
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW221200
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW321201
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW331202
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW211203
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW201204
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW191205
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW341206
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW181207
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW151208
MAINTENANCE SHOP EST 12/31/2011
WAREHOUSEW141209
MAINTENANCE SHOP EST 12/31/2011
WAREHOUSEW10
VOCATIONAL CLASSROOM EST 12/31/2011
Page 55 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1217
WAREHOUSE W91218
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W71219
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W81220
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W61221
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W51222
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSEW131223
STORAGE E1003 EST 12/31/2011
WAREHOUSEW281226
EQUIPMENT STORAGE E1004 EST 12/31/2011
C AREA I341228
MECHANICAL ROOM C1024 EST 12/31/2011
C AREA I241229
MECHANICAL ROOM C1024 EST 12/31/2011
Manual Fire Box
B AREA CC81076
CORRIDOR B1060 EST 12/30/2011
C AREA I351192
ELECTRICAL C1023 EST 12/30/2011
WAREHOUSEW271193
WAREHOUSE E1010 EST 12/30/2011
WAREHOUSEW351210
WAREHOUSE E1010 EST 12/30/2011
WAREHOUSEW361215
VESTIBULE E1001 EST 12/30/2011
WAREHOUSEW111216
VOCATIONAL CLASSROOM EST 12/30/2011
WAREHOUSEW121224
STORAGE E1003 EST 12/30/2011
WAREHOUSEW171225
EQUIPMENT STORAGE E1004 EST 12/30/2011
C AREA I331227
MECHANICAL ROOM C1024 EST 12/30/2011
A AREA B21291306
VESTIBULE A1001 EST 12/30/2011
B AREA CC151311
CORRIDOR B1060 EST 12/30/2011
B AREA CC271328
STAFF BREAK B1095 EST 12/30/2011
D AREA CC701350
PUBLIC LOBBY D1117 EST 12/30/2011
A AREA B21241471
WAITING A1037 EST 12/30/2011
A AREA B2761472
DAYROOM OFFICER A1026 EST 12/30/2011
B AREA 1C701015
DAYROOM OFFICER B1057 EST 12/31/2011
B AREA 1C231026
CONC SLAB BES2 EST 12/31/2011
B AREA 1C20 DAYROOM OFFICER B1028 EST 12/31/2011
Page 56 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1033
B AREA 1C1061034
SEARCH B1027 EST 12/31/2011
A AREA B2241104
CONC SLAB EXIT EST 12/31/2011
A AREA B2271105
DAYROOM OFFICER A1086 EST 12/31/2011
A AREA B2401106
CONC SLAB AES1 EST 12/31/2011
A AREA B2371107
DAYROOM OFFICER A1044 EST 12/31/2011
D AREA CC841244
CORRIDOR D1038 EST 12/31/2011
1ST C AREACORRIDOROUTSIDE .11245
DINING HALL EST 12/31/2011
1ST C AREACORRIDOROUTSIDE .21246
DINING HALL EST 12/31/2011
D AREA CC1871262
RELEASE LOBBY EST 12/31/2011
D AREA CC1681269
CORRIDOR D1077 EST 12/31/2011
C AREA 1STCORRIDOR1276
OUTSIDE DINING HALL EST 12/31/2011
D AREA CC1261283
CORRIDOR D1047 EST 12/31/2011
C AREA I931296
CORRIDOR C1064 EST 12/31/2011
C AREA I741302
CORRIDOR C1049 EST 12/31/2011
D AREA CC771312
VISITOR WAITING D1098 EST 12/31/2011
C AREA I701408
OFFICER STATION C1030 EST 12/31/2011
C AREA I211418
KITCHEN C1008 EST 12/31/2011
B AREA 1C1011462
WAITING B1051 EST 12/31/2011
A AREA B21051474
DAYROOM OFFICER A1061 EST 12/31/2011
Smoke Detector - Duct
A AREA B2561118
STORAGE A1029 EST 12/31/2011
A AREA B2171119
STORAGE A1090 EST 12/31/2011
A AREA B2851120
STORAGE A1056 EST 12/31/2011
A AREA B2811121
STORAGE A1055 EST 12/31/2011
B AREA 1C801122
SUPSTORAGE B1055 RTU7 EST 12/31/2011
B AREA 1C751123
CORRIDOR B1109 RTU6 EST 12/31/2011
B AREA 1C511124
STORAGE B1041 RTU10 EST 12/31/2011
B AREA 1C461125
CORRIDOR B1044 EST 12/31/2011
D AREA CC161 DAYROOM D1054 RETURN EST 12/31/2011
Page 57 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1449
D AREA CC1831450
DAYROOM D1069 RETURN EST 12/31/2011
D AREA CC1361451
DAYROOM D1039 RETURN EST 12/31/2011
C AREA I111.11452
DAYROOM C1071 EST 12/31/2011
C AREA I881453
DAYROOM A1056 SUPPLY EST 12/31/2011
C AREA I891454
DAYROOM C1056 RETURN EST 12/31/2011
C AREA I791455
DAYROOM C1041 EST 12/31/2011
B AREA 1C531456
STORAGE B1044 RTU10 EST 12/31/2011
B AREA 1C451457
CORRIDOR B1042 EST 12/31/2011
B AREA 1C821459
RET STORAGE B1055 RTU7 EST 12/31/2011
A AREA B2611467
STORAGE A1029 EST 12/31/2011
A AREA B2181468
STORAGE A1090 EST 12/31/2011
A AREA B21131470
WAITING A1037 EST 12/31/2011
C AREA I391475
LAUNDRY C1021 EST 12/31/2011
D AREA CC1021479
COMPUTER LAB D1027 RET EST 12/31/2011
D AREA CC1001480
COMPUTER LAB D1027 SUP EST 12/31/2011
D AREA S CC1991481
MULTIPURPOSE D1037 EST 12/31/2011
D AREA R CC2001482
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC51RET1483
SHIFT SUPERVISOR D1121 EST 12/31/2011
D AREA CC1601485
DAYROOM B1057 EST 12/31/2011
D AREA CC1821486
NEAR D 1075 SHOWER EST 12/31/2011
D AREA CC1351487
DAYROOM D1054 SUPPLY EST 12/31/2011
I781488
DAYROOM D1069 SUPPLY EST 12/31/2011
CC1071489
DAYROOM D1039 SUPPLY EST 12/31/2011
B21231490
DAYROOM C1041 EST 12/31/2011
CC209.11491
D1004 EST 12/31/2011
CC2091492
A1043 EST 12/31/2011
I1081493
A1043 EST 12/31/2011
CC1261494
A1017 EST 12/31/2011
Smoke Detector - General
B AREA 1C211024
DAYROOM MEZZ B1028 EST 12/30/2011
Page 58 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C221025
DAYROOM MEZZ B1028 EST 12/30/2011
B AREA 1C251027
DAYROOM MEZZ B1028 EST 12/30/2011
B AREA 1C241028
DAYROOM MEZZ B1028 EST 12/30/2011
B AREA 1C51045
DAYROOM MEZZ B1001 EST 12/30/2011
B AREA 1C41046
DAYROOM MEZZ B1001 EST 12/30/2011
B AREA 1C131047
DAYROOM B1001 EST 12/30/2011
B AREA 1C151048
DAYROOM B1001 EST 12/30/2011
B AREA 1C161049
DAYROOM B1001 EST 12/30/2011
B AREA 1C181050
DAYROOM B1001 EST 12/30/2011
B AREA 1C1151073
EQUIPMENT ROOM B1104 EST 12/30/2011
B AREA 1C721075
MULTIPURPOSE B1056 EST 12/30/2011
A AREA B2661078
EQUIPMENT ROOM A1016 EST 12/30/2011
A AREA B21101079
CORRIDOR A1015 EST 12/30/2011
A AREA B21111080
CORRIDOR A1015 EST 12/30/2011
A AREA B21061081
EQUIPMENT ROOM A1042 EST 12/30/2011
A AREA B21181082
WAITING A1037 EST 12/30/2011
A AREA B21121083
COUNSELOR A1031 EST 12/30/2011
A AREA B21161084
SUPPLY ROOM A1034 EST 12/30/2011
A AREA B21251085
MULTIPURPOSE A1040 EST 12/30/2011
A AREA B21201086
CORRIDOR A1015 EST 12/30/2011
A AREA B21211087
CORRIDOR A1015 EST 12/30/2011
A AREA B21221088
SEARCH A1043 EST 12/30/2011
A AREA B21521089
SEARCH A1043 EST 12/30/2011
A AREA B21231090
SEARCH A1043 EST 12/30/2011
A AREA B2521092
DAYROOM A1044 EST 12/30/2011
A AREA B2421095
DAYROOM A1044 EST 12/30/2011
A AREA B2391097
DAYROOM MEZZ A1044 EST 12/30/2011
A AREA B2381098
DAYROOM MEZZ A1044 EST 12/30/2011
A AREA B2471099
DAYROOM A1044 EST 12/30/2011
A AREA B2481100
DAYROOM A1044 EST 12/30/2011
A AREA B2331102
DAYROOM A1086 EST 12/30/2011
Page 59 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
A AREA B2341103
DAYROOM A1086 EST 12/30/2011
A AREA B2261112
DAYROOM A1086 EST 12/30/2011
A AREA B2251113
DAYROOM A1086 EST 12/30/2011
A AREA B2231114
DAYROOM A1086 EST 12/30/2011
A AREA B2221115
DAYROOM A1086 EST 12/30/2011
A AREA B2301116
DAYROOM A1086 EST 12/30/2011
A AREA B2321117
DAYROOM A1086 EST 12/30/2011
C AREA I361191
ELECTRICAL C1023 EST 12/30/2011
WAREHOUSEW28.11197
ELECTRICAL ROOM E1011 EST 12/30/2011
WAREHOUSEW291198
OFFICE E1013 EST 12/30/2011
WAREHOUSE W21211
CORRIDOR E1006 EST 12/30/2011
WAREHOUSE W31212
CORRIDOR E1006 EST 12/30/2011
WAREHOUSE W11213
OFFICE E1007 EST 12/30/2011
WAREHOUSE W41214
VESTIBULE E1001 EST 12/30/2011
D AREA CC45.11230
EQUIT D1119 EST 12/30/2011
A AREA B21041231
DAYROOM A1061 EST 12/30/2011
A AREA B21011232
DAYROOM A1061 EST 12/30/2011
A AREA B2971233
DAYROOM A1061 EST 12/30/2011
A AREA B2961234
DAYROOM A1061 EST 12/30/2011
A AREA B2941235
DAYROOM MEZZ A1061 EST 12/30/2011
A AREA B2911238
DAYROOM MEZZ A1061 EST 12/30/2011
A AREA B2991240
DAYROOM A1061 EST 12/30/2011
A AREA B21031243
DAYROOM A1061 EST 12/30/2011
D AREA CC871248
CORRIDOR D1038 EST 12/30/2011
D AREA CC881249
CORRIDOR D1038 EST 12/30/2011
D AREA CC891250
CORRIDOR D1038 EST 12/30/2011
D AREA CC911252
CORRIDOR D1038 EST 12/30/2011
D AREA CC1431280
DAYROOM D1039 EST 12/30/2011
D AREA CC1291284
CORRIDOR D1047 EST 12/30/2011
C AREA I1021286
DAYROOM C1071 EST 12/30/2011
Page 60 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I1141287
CORRIDOR C1079 EST 12/30/2011
C AREA I1101288
CORRIDOR C1079 EST 12/30/2011
C AREA I1091289
CORRIDOR C1079 EST 12/30/2011
C AREA I1081290
CORRIDOR C1079 EST 12/30/2011
C AREA I1071291
CORRIDOR C1079 EST 12/30/2011
C AREA I1061292
CORRIDOR C1079 EST 12/30/2011
A AREA B251305
VESTIBULE A1001 EST 12/30/2011
A AREA B231307
HOLDING CELL A1004 EST 12/30/2011
A AREA B221308
HOLDING CELL A1005 EST 12/30/2011
A AREA B211309
HOLDING CELL A1006 EST 12/30/2011
A AREA B2121310
CORRIDOR A1012 EST 12/30/2011
B AREA CC441319
INMATE RECORDS D1083 EST 12/30/2011
B AREA CC311323
CORRIDOR OF ADMIN B1080 EST 12/30/2011
B AREA CC361325
STORAGE B1090 EST 12/30/2011
B AREA CC251326
CORRIDOR B1094 EST 12/30/2011
B AREA CC281327
STAFF BREAK B1095 EST 12/30/2011
B AREA CC241329
TRAINING B1096 EST 12/30/2011
B AREA CC261330
TRAINING B1096 EST 12/30/2011
B AREA CC231331
CORRIDOR B1094 EST 12/30/2011
B AREA CC201332
FITNESS B1099 EST 12/30/2011
B AREA CC171333
M LOCKER B1106 EST 12/30/2011
B AREA CC191334
CORRIDOR B1094 EST 12/30/2011
B AREA CC161335
CORRIDOR B1094 EST 12/30/2011
B AREA CC371336
UNIFORM STORAGE B1091 EST 12/30/2011
D AREA CC631337
MAIN VESTIBULE B1069 EST 12/30/2011
D AREA CC621338
MAIN VESTIBULE B1069 EST 12/30/2011
D AREA CC751346
VISITOR WAITING D1098 EST 12/30/2011
D AREA CC781347
VISITOR WAITING D1098 EST 12/30/2011
D AREA CC731348
STORAGE D1111 EST 12/30/2011
D AREA CC761349
VESTIBULE D1096 EST 12/30/2011
D AREA CC741351
CORRIDOR D1110 EST 12/30/2011
Page 61 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
D AREA CC821352
OFFICE D1118 EST 12/30/2011
D AREA CC451353
EQUIPMENT D1119 EST 12/30/2011
D AREA CC591355
MASTER CONTROL D1129 EST 12/30/2011
D AREA CC531356
SHIFT SUPERVISOR D1121 EST 12/30/2011
D AREA CC551357
STORAGE D1122 EST 12/30/2011
D AREA CC561358
CORRIDOR D1125 EST 12/30/2011
D AREA CC611359
MAIL ROOM D1126 EST 12/30/2011
B AREA CC141360
CORRIDOR B1060 EST 12/30/2011
B AREA CC131361
CORRIDOR B1060 EST 12/30/2011
B AREA CC121362
CORRIDOR B1060 EST 12/30/2011
B AREA CC111363
CORRIDOR B1060 EST 12/30/2011
B AREA CC101364
CORRIDOR B1060 EST 12/30/2011
D AREA CC1131373
ELECTRICAL ROOM D1008 EST 12/30/2011
C AREA I581374
VESTIBULE C1026 EST 12/30/2011
D AREA CC1111380
STORAGE D1005 EST 12/30/2011
A AREA CC41382
CORRIDOR A1068 EST 12/30/2011
A AREA CC31383
CORRIDOR A1068 EST 12/30/2011
A AREA CC21384
CORRIDOR A1068 EST 12/30/2011
D AREA CC2071387
STORAGE D1035 EST 12/30/2011
D AREA CC991390
COMPUTER LAB D1027 EST 12/30/2011
D AREA CC1031391
BARBER D1026 EST 12/30/2011
D AREA CC2031393
LIBRARY D1034 EST 12/30/2011
D AREA CC2041394
LIBRARY D1034 EST 12/30/2011
C AREA I1211401
CORRIDOR C1025 EST 12/30/2011
C AREA I611409
DAYROOM MEZZ C1030 EST 12/30/2011
C AREA I691410
DAYROOM MEZZ C1030 EST 12/30/2011
C AREA I601411
DAYROOM MEZZ C1030 EST 12/30/2011
A AREA CC2091420
VESITBULE A1017 EST 12/30/2011
A AREA CC11421
VESTIBULE A1017 EST 12/30/2011
A AREA B2101422
PROPERTY STORAGE A1014 EST 12/30/2011
A AREA B271423
ISSUE A1073 EST 12/30/2011
Page 62 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
A AREA B2131424
SEARCH AREA A1008 EST 12/30/2011
A AREA B261425
INMATE WAITING A1002 EST 12/30/2011
A AREA B241426
INTERVIEW A1003 EST 12/30/2011
A AREA B2751427
DAYROOM A1026 EST 12/30/2011
A AREA B2671428
DAYROOM A1026 EST 12/30/2011
A AREA B2681429
DAYROOM A1026 EST 12/30/2011
A AREA B2721430
DAYROOM A1026 EST 12/30/2011
A AREA B2621431
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2631432
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2641433
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2651434
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2731435
DAYROOM A1026 EST 12/30/2011
A AREA B2741436
DAYROOM A1026 EST 12/30/2011
A AREA B2711437
DAYROOM A1026 EST 12/30/2011
A AREA B2701438
DAYROOM A1026 EST 12/30/2011
A AREA B2691439
DAYROOM A1026 EST 12/30/2011
A AREA B2161440
CORRIDOR A1074 EST 12/30/2011
A AREA B2781444
CORRIDOR A1057 EST 12/30/2011
A AREA B2791445
CORRIDOR A1057 EST 12/30/2011
A AREA B2831448
STORAGE A1055 EST 12/30/2011
B AREA RET1C761458
CORRIDOR B1109 RTU6 EST 12/30/2011
B AREA 1C381460
COUNSELOR B1049 EST 12/30/2011
B AREA 1C421463
SUPPLY ROOM B1046 EST 12/30/2011
B AREA 1C291465
COUNSELOR B1050 EST 12/30/2011
B AREA 1C901466
EQUPIMENT B1024 EST 12/30/2011
A AREA B21191469
COUNSELOR A1036 EST 12/30/2011
A AREA 1STDAYROOM A10611473
CORRIDOR A1057 B288 EST 12/30/2011
C AREA I61476
IT TOILET C1013 EST 12/30/2011
C AREA I51477
ST TOILET C1015 EST 12/30/2011
A AREA B2951478
STORAGE A1070 EST 12/30/2011
Page 63 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C591484
MAIN PANEL EST 12/30/2011
D AREA CC691495
C1079 EST 12/30/2011
D AREA CC711496
D1047 EST 12/30/2011
C AREA I831497
EST 12/30/2011
C AREA I951499
STORAGE D1113 EST 12/30/2011
D AREA CC1371501
EQUIP. ROOM C1057 EST 12/30/2011
B AREA CC411502
CORRIDOR C1064 EST 12/30/2011
B AREA CC431503
CORRIDOR C1064 EST 12/30/2011
D AREA CC681504
DAYROOM D1039 EST 12/30/2011
C AREA I471505
ADMIN. ASSISTS. B1080 EST 12/30/2011
C AREA I481506
CORRIDOR B1079 EST 12/30/2011
D AREA CC1141510
DAYROOM A1044 EST 12/30/2011
D AREA CC1171511
CORRIDOR C1025 EST 12/30/2011
D AREA CC1161512
NURSE STATION D1004 EST 12/30/2011
B AREA 1C301513
EMER. STORAGE D1007 EST 12/30/2011
C AREA I1111514
SOILED LINEN D1010 EST 12/30/2011
D AREA CC501515
CLEAN LINEN D1009 EST 12/30/2011
A AREA B21171516
DAYROOM B1028 EST 12/30/2011
B AREA 1C1121001
CORRIDOR B1026 EST 12/31/2011
B AREA 1C601002
STORAGE B 1066 EST 12/31/2011
B AREA 1C691003
DAYROOM B1057 EST 12/31/2011
B AREA 1C611004
DAYROOM B1057 EST 12/31/2011
B AREA 1C621005
DAYROOM B1057 EST 12/31/2011
B AREA 1C641006
DAYROOM B1057 EST 12/31/2011
B AREA 1C581007
DAYROOM MEZZ B1057 EST 12/31/2011
B AREA 1C571008
DAYROOM MEZZ B1057 EST 12/31/2011
B AREA 1C561009
DAYROOM MEZZ B1057 EST 12/31/2011
B AREA 1C631010
DAYROOM B1057 EST 12/31/2011
B AREA 1C651011
DAYROOM B1057 EST 12/31/2011
B AREA 1C661012
DAYROOM B1057 EST 12/31/2011
B AREA 1C671013
DAYROOM B1057 EST 12/31/2011
Page 64 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C681014
STORAGE B2035 EST 12/31/2011
B AREA 1C491016
CORRIDOR B1044 EST 12/31/2011
B AREA 1C521017
STORAGE B1041 EST 12/31/2011
B AREA 1C431018
CORRIDOR B1044 EST 12/31/2011
B AREA 1C481019
STORAGE B1042 EST 12/31/2011
B AREA 1C471020
STORAGE B1043 EST 12/31/2011
B AREA 1C371021
DAYROOM B1028 EST 12/31/2011
B AREA 1C361022
DAYROOM B1028 EST 12/31/2011
B AREA 1C341023
DAYROOM B1028 EST 12/31/2011
B AREA 1C351029
DAYROOM B1028 EST 12/31/2011
B AREA 1C331030
DAYROOM B1028 EST 12/31/2011
B AREA 1C321031
DAYROOM B1028 EST 12/31/2011
B AREA 1C311032
DAYROOM B1028 EST 12/31/2011
B AREA 1C1301035
SEARCH AREA B1027 EST 12/31/2011
B AREA 1C1051036
SEARCH AREA B1027 EST 12/31/2011
B AREA 1C1041037
CORRIDOR B1110 EST 12/31/2011
B AREA 1C1031038
CORRIDOR B1051 EST 12/31/2011
B AREA 1C111039
DAYROOM B1001 EST 12/31/2011
B AREA 1C121040
DAYROOM B1001 EST 12/31/2011
B AREA 1C141041
DAYROOM B1001 EST 12/31/2011
B AREA 1C191042
DAYROOM B1001 EST 12/31/2011
B AREA 1C91043
DAYROOM MEZZ B1001 EST 12/31/2011
B AREA 1C71044
DAYROOM MEZZ B1001 EST 12/31/2011
B AREA 1C101051
DAYROOM B1001 EST 12/31/2011
B AREA 1C731052
CORRIDOR B1109 EST 12/31/2011
B AREA 1C771053
STORAGE B1053 EST 12/31/2011
B AREA 1C781054
ELECTRICAL B1054 EST 12/31/2011
B AREA 1C791055
CORRIDOR B1109 EST 12/31/2011
B AREA 1C811056
STORAGE B1055 EST 12/31/2011
B AREA 1C911057
DAYROOM B1015 EST 12/31/2011
B AREA 1C991058
DAYROOM B1015 EST 12/31/2011
Page 65 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C941059
DAYROOM B1015 EST 12/31/2011
B AREA 1C921060
DAYROOM B1015 EST 12/31/2011
B AREA 1C861061
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C871062
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C881063
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C891064
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C981065
DAYROOM B1015 EST 12/31/2011
B AREA 1C961066
DAYROOM B1015 EST 12/31/2011
B AREA 1C951067
DAYROOM B1015 EST 12/31/2011
B AREA 1C931068
DAYROOM B1015 EST 12/31/2011
B AREA 1C1001069
DAYROOM OFFICER B1015 EST 12/31/2011
B AREA 1C971070
STORAGE B2034 EST 12/31/2011
B AREA 1C1111071
CORRIDOR B1026 EST 12/31/2011
B AREA 1C1101072
CORRIDOR B1026 EST 12/31/2011
B AREA 1C1021074
WAITING B1051 EST 12/31/2011
A AREA B21091077
EQUIPMENT ROOM A1042 EST 12/31/2011
A AREA B2531091
DAYROOM A1044 EST 12/31/2011
A AREA B2461093
DAYROOM A1044 EST 12/31/2011
A AREA B2491094
DAYROOM A1044 EST 12/31/2011
A AREA B2411096
DAYROOM A1044 EST 12/31/2011
A AREA B2501101
DAYROOM A1044 EST 12/31/2011
A AREA B2281108
DAYROOM A1086 EST 12/31/2011
A AREA B2351109
DAYROOM A1086 EST 12/31/2011
A AREA B2291110
DAYROOM A1086 EST 12/31/2011
A AREA B2311111
DAYROOM A1086 EST 12/31/2011
C AREA I141162
KITCHEN C1008 EST 12/31/2011
A AREA B2931236
DAYROOM MEZZ A1061 EST 12/31/2011
A AREA B2921237
DAYROOM MEZZ A1061 EST 12/31/2011
A AREA B2981239
DAYROOM A1061 EST 12/31/2011
A AREA B21001241
DAYROOM A1061 EST 12/31/2011
A AREA B21021242
DAYROOM A1061 EST 12/31/2011
Page 66 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA CCADD1247
CORRIDOR C1092 EST 12/31/2011
D AREA CC901251
CORRIDOR D1038 EST 12/31/2011
D AREA CC921253
CORRIDOR D1038 EST 12/31/2011
D AREA CC931254
CORRIDOR D1038 EST 12/31/2011
D AREA CC941255
CORRIDOR D1038 EST 12/31/2011
D AREA CC951256
CORRIDOR D1038 EST 12/31/2011
D AREA CC961257
CORRIDOR D1038 EST 12/31/2011
D AREA CC971258
CORRIDOR D1038 EST 12/31/2011
D AREA CC981259
CORRIDOR D1038 EST 12/31/2011
D AREA CC1851260
INTERVIEW ROOM D1085 EST 12/31/2011
D AREA CC1861261
RELEASE LOBBY D1085 EST 12/31/2011
D AREA CC1881263
CORRIDOR D1084 EST 12/31/2011
D AREA CC1891264
CORRIDOR D1084 EST 12/31/2011
D AREA CC1801265
DAYROOM D1069 SUP EST 12/31/2011
D AREA CC1841266
DAYROOM D1069 EST 12/31/2011
D AREA CC1741267
CORRIDOR D1077 EST 12/31/2011
D AREA CC1701268
CORRIDOR D1077 EST 12/31/2011
D AREA CC1711270
CORRIDOR D1077 EST 12/31/2011
D AREA CC1731271
CORRIDOR D1077 EST 12/31/2011
D AREA CC1581272
DAYROOM D1054 EST 12/31/2011
D AREA CC1641273
DAYROOM D1054 EST 12/31/2011
D AREA CC1521274
CORRIDOR D1062 EST 12/31/2011
D AREA CC1501275
CORRIDOR D1062 EST 12/31/2011
D AREA CC1491277
CORRIDOR D1062 EST 12/31/2011
D AREA CC1531278
CORRIDOR D1062 EST 12/31/2011
D AREA CC1571279
EQUIPMENT D1040 EST 12/31/2011
D AREA CC1331281
CORRIDOR D1047 EST 12/31/2011
D AREA CC1281282
CORRIDOR D1047 EST 12/31/2011
D AREA CC1311285
CORRIDOR D1047 EST 12/31/2011
C AREA I961293
DAYROOM C1056 EST 12/31/2011
C AREA I871294
DAYROOM C1056 EST 12/31/2011
Page 67 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I911295
CORRIDOR C1064 EST 12/31/2011
C AREA I941297
CORRIDOR C1064 EST 12/31/2011
C AREA I801298
DAYROOM C1041 EST 12/31/2011
C AREA I861299
DAYROOM C1041 EST 12/31/2011
C AREA I721300
CORRIDOR C1049 EST 12/31/2011
C AREA I731301
CORRIDOR C1049 EST 12/31/2011
C AREA I751303
CORRIDOR C1049 EST 12/31/2011
C AREA I761304
CORRIDOR C1049 EST 12/31/2011
D AREA CC831313
PUBLIC LOBBY D1117 EST 12/31/2011
D AREA CC671314
WAITING B1070 EST 12/31/2011
D AREA CC661315
WAITING B1070 EST 12/31/2011
D AREA CC651316
WAITING B1070 EST 12/31/2011
D AREA CC431317
CORRIDOR B1079 EST 12/31/2011
B AREA CC2801318
ADMIN ASSISTANTS B1080 EST 12/31/2011
B AREA CC421320
MEETING ROOM B1077 EST 12/31/2011
B AREA CC401321
WORK ROOM B1086 EST 12/31/2011
B AREA CC391322
SUPPLY ROOM B1085 EST 12/31/2011
B AREA CC341324
BREAK ROOM B1089 EST 12/31/2011
D AREA CC541339
SEARCH AREA D1106 EST 12/31/2011
D AREA CC481340
VISITING ROOM D1105 EST 12/31/2011
D AREA CC491341
VISITING ROOM D1105 EST 12/31/2011
D AREA CC461342
VISITING ROOM D1105 EST 12/31/2011
D AREA CC471343
VISITING ROOM D1105 EST 12/31/2011
D AREA CC791344
STORAGE D1101 EST 12/31/2011
D AREA CC801345
VSP ROOM D1100 EST 12/31/2011
D AREA 1STHALL1354
OUSIDE ROOM D1120 EST 12/31/2011
B AREA CC91365
CORRIDOR B1060 EST 12/31/2011
B AREA CC71366
CORRIDOR B1060 EST 12/31/2011
B AREA CC61367
CORRIDOR B1060 EST 12/31/2011
B AREA CC51368
CORRIDOR B1060 EST 12/31/2011
D AREA CC120 ISOLATION D1018 EST 12/31/2011
Page 68 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1369
D AREA CC1181370
ISOLATION D1020 EST 12/31/2011
D AREA CC2171371
CORRIDOR D1011 EST 12/31/2011
C AREA I1191372
CORRIDOR C1025 EST 12/31/2011
D AREA CC1041375
TREATMENT D1013 EST 12/31/2011
D AREA CC1081376
CORRIDOR D1011 EST 12/31/2011
D AREA CC1091377
LAB D1014 EST 12/31/2011
D AREA CC1101378
DENTAL SUITE D1015 EST 12/31/2011
D AREA CC1151379
CORRIDOR D1011 EST 12/31/2011
D AREA CC1191381
ISOLATION VESTIBULE EST 12/31/2011
D AREA CC2051385
CLASSROOM D1031 EST 12/31/2011
D AREA CC2061386
CLASSROOM D1031 EST 12/31/2011
D AREA CC1221388
GED D1028 EST 12/31/2011
D AREA CC961389
CORRIDOR D1030 EST 12/31/2011
D AREA CC951392
CORRIDOR D1030 EST 12/31/2011
D AREA CC941395
CORRIDOR D1030 EST 12/31/2011
D AREA CC1971396
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2021397
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2011398
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2161399
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2081400
STORAGE D1036 EST 12/31/2011
D AREA CC1061402
WAITING D1001 EST 12/31/2011
D AREA CC1051403
EXAM D1012 EST 12/31/2011
C AREA I631404
DAYROOM C1030 EST 12/31/2011
C AREA I671405
DAYROOM C1030 EST 12/31/2011
C AREA I681406
DAYROOM C1030 EST 12/31/2011
C AREA I621407
DAYROOM C1030 EST 12/31/2011
C AREA I571412
STAFF DINING C1005 EST 12/31/2011
C AREA I561413
STAFF DINING C1005 EST 12/31/2011
C AREA I501414
DIVERSION DINING C1002 EST 12/31/2011
C AREA I491415
DIVERSION DINING C1002 EST 12/31/2011
Page 69 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I521416
DIVERSION DINING C1002 EST 12/31/2011
C AREA I511417
DIVERSION DINING C1002 EST 12/31/2011
C AREA I461419
JANITOR C1017 EST 12/31/2011
A AREA B2571441
STORAGE A1029 EST 12/31/2011
A AREA B2141442
ELECTRICAL A1030 EST 12/31/2011
A AREA B2151443
STORAGE A1090 EST 12/31/2011
A AREA 1STDAYROOM A10611446
STORAGE A1058 EST 12/31/2011
A AREA B2841447
ELECTRICAL ROOM A1056 EST 12/31/2011
B AREA RET1C1091461
WAITING B1051 RTU8 EST 12/31/2011
B AREASUP1C1081464
WAITING B1051 RTU8 EST 12/31/2011
C AREA I991498
VEST. ROOM D1114 EST 12/31/2011
C AREA I921500
STORAGE C1042 EST 12/31/2011
A AREA B2511507
ELECT. ROOM D1115 EST 12/31/2011
C AREA I1201508
STORAGE C1017 EST 12/31/2011
D AREA CC1071509
CORRIDOR C1016 EST 12/31/2011
Alarm Notification Appliance
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Audible And Visible
1st Floor Notification EST 2/29/2016
Page 70 of 70
Entec Systems Inc.
Inspection and Testing CertificatePresented To
Gwinnett County-Police SemiFor
Correctional Institute750 Hi Hope Road
Lawrenceville GA 30043USA
This site has been inspected and tested in compliance with applicable standards.
CompletedWednesday, September 14, 2016
Test Session: 9/14/16 Semi Annual Correctional Complex
ACCEPTED BY TESTED BYJeff Anderson Jared CoileGwinnett County-Police Semi Entec Systems Inc.75 Langely DriveLawrenceville GA 30043USA
450 Satellite Blvd. NE, Suite PSuwanee GA 30024USA
Entec Systems Inc.
Inspection Summary
Building InformationPROPERTY Correctional InstituteADDRESS 750 Hi Hope RoadCITY/STATE/ZIP Lawrenceville, GA 30043COUNTRY USA
CONTACT Jeff AndersonPHONEMOBILEEMAIL
Inspector InformationCOMPANY Entec Systems Inc.ADDRESS 450 Satellite Blvd. NE, Suite PCITY/STATE/ZIP Suwanee, GA 30024COUNTRY USA
CONTACT Jared CoilePHONEMOBILE (678) 858-4950EMAIL [email protected]
NAME INITIALS QUALIFICATION AND PROFICIENCIESJared Coile JC
Testing SummaryEQUIPMENT TYPE TOTAL TESTED PASSED FAILED
Fire Control Panel 1 1(100 %) 1(100 %) 0(0 %)Initiating Device 42 42(100 %) 42(100 %) 0(0 %)Alarm Notification Appliance 1 1(100 %) 1(100 %) 0(0 %)
CertificationThe equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspectioncompleted on Wednesday, September 14, 2016
ACCEPTED BY9/14/2016Jeff AndersonBuilding RepresentativeGwinnett County-Police Semi
TESTED BY9/14/2016Jared CoileTechnicianEntec Systems Inc.
Page 2 of 11
Entec Systems Inc.
System Details
Control Units
MANUFACTURER EdwardsMODEL EST3SERIAL NUMBERINSTALL DATE 9/30/2015
DESCRIPTION Main FACPS/W VERSIONLAST UPDATES/W LOCATION
Monitoring Information
Page 3 of 11
Entec Systems Inc.
Open Corrective Action & Solution SummaryThe following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor NotificationCreated By: Jared CoileCreation Date: 9/14/2016Corrective Action: L Dorm the horn strobe over the pull station did not work.Proposed Solution: Troubleshoot/Replace horn strobe.
Page 4 of 11
Entec Systems Inc.
Resolved Corrective Action & Solution SummaryThe following 1 corrective action(s) were resolved during the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor NotificationCreated By: Jared CoileCreation Date: 10/1/2015
Corrective Action: A Dorm had no audio or visual notification during sound test. I dorm, J dorm, and Kdorm had no strobes during sound test, audio only.
Resolution Issues were resolved.Resolved By: Jared CoileResolved On: 9/14/2016
Page 5 of 11
Entec Systems Inc.
Testing Details
Fire Control Panel
PassedEQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel Main FACP Manual 9/14/2016 2:24 PM
Comment: Replace pull station cover in L Dorm.I I Manufacturer EdwardsI I Model EST3I I Serial Number II I Visual Inspection TrueI I Functional Inspection TrueI I Ground Fault TrueI I Disconnect Switches TrueI I
Initiating Device
PassedEQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box A AREA B2105 Dayroom Officer A1061 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B2124 Waiting A1037 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B2129 Vestibule A1001 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B224 Concs Lab Exit Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B227 Dayroom Officer A1086 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B237 Dayroom Officer A1044 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B240 Concs Lab AES1 Manual 9/14/2016 2:19 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B276 Dayroom Officer A1026 Manual 9/14/2016 2:19 PM
Page 6 of 11
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C10 Dayroom B1001 Manual 9/14/2016 2:20 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C100 Dayroom Officer B1015 Manual 9/14/2016 2:20 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C101 Waiting B1051 Manual 9/14/2016 2:20 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C106 Search B1027 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C20 Dayroom Officer B1028 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C70 Dayroom Officer B1057 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA CC15 Corridor B1060 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA CC27 Staff Break B1095 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA CC8 Corridor B1060 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B2123 AA1043 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA 1stCORRIDOR Outside Dining Hall Manual 9/14/2016 2:21 PM
I I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I21 Kitchen C1008 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Page 7 of 11
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box C AREA I33 Mechanical Room C1024 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I35 Electrical Room C1023 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I70 Officer Station C1030 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I74 Corridor C1049 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I93 Corridor C1064 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC107 D1004 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC126 D1047 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC209 A1017 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC209 A1043 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC107 Nurse Station D1004 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC168 Corridor D1077 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC187 Release Lobby Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC70 Public Lobby Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Page 8 of 11
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box D AREA CC77 Visitor Waiting D1098 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC84 Corridor D1038 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box I108 C1079 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W11 Vocational Classroom Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W12 Storage E1003 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W17 Equipment Room E1004 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W27 Warehouse E1010 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W35 Warehouse E1010 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection TrueI I Alarm Verification Participation False
Manual Fire Box Warehouse W36 Vestibule E1001 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Alarm Notification Appliance
PassedEQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Audible And Visible 1st Floor Notification Manual 9/14/2016 2:23 PMI I Visual Inspection TrueI I Functional Inspection True
Page 9 of 11
Entec Systems Inc.
Device/Equipment Details
Fire Control PanelADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Fire Alarm PanelMain FACP Edwards EST3 9/30/2015
Initiating DeviceADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Manual Fire BoxA AREA B2105 Dayroom Officer A1061 Edwards 9/30/2015A AREA B2124 Waiting A1037 Edwards 9/30/2015A AREA B2129 Vestibule A1001 Edwards 9/30/2015A AREA B224 Concs Lab Exit Edwards 9/30/2015A AREA B227 Dayroom Officer A1086 Edwards 9/30/2015A AREA B237 Dayroom Officer A1044 Edwards 9/30/2015A AREA B240 Concs Lab AES1 Edwards 9/30/2015A AREA B276 Dayroom Officer A1026 Edwards 9/30/2015B AREA 1C10 Dayroom B1001 Edwards 9/30/2015B AREA 1C100 Dayroom Officer B1015 Edwards 9/30/2015B AREA 1C101 Waiting B1051 Edwards 9/30/2015B AREA 1C106 Search B1027 Edwards 9/30/2015B AREA 1C20 Dayroom Officer B1028 Edwards 9/30/2015B AREA 1C70 Dayroom Officer B1057 Edwards 9/30/2015B AREA CC15 Corridor B1060 Edwards 9/30/2015B AREA CC27 Staff Break B1095 Edwards 9/30/2015B AREA CC8 Corridor B1060 Edwards 9/30/2015B2123 AA1043 Edwards 9/30/2015C AREA 1stCORRIDOR Outside Dining Hall Edwards 9/30/2015
C AREA I21 Kitchen C1008 Edwards 9/30/2015C AREA I33 Mechanical Room C1024 Edwards 9/30/2015C AREA I35 Electrical Room C1023 Edwards 9/30/2015C AREA I70 Officer Station C1030 Edwards 9/30/2015C AREA I74 Corridor C1049 Edwards 9/30/2015C AREA I93 Corridor C1064 Edwards 9/30/2015CC107 D1004 Edwards 9/30/2015CC126 D1047 Edwards 9/30/2015CC209 A1017 Edwards 9/30/2015CC209 A1043 Edwards 9/30/2015D AREA CC107 Nurse Station D1004 Edwards 9/30/2015D AREA CC168 Corridor D1077 Edwards 9/30/2015D AREA CC187 Release Lobby Edwards 9/30/2015D AREA CC70 Public Lobby Edwards 9/30/2015D AREA CC77 Visitor Waiting D1098 Edwards 9/30/2015D AREA CC84 Corridor D1038 Edwards 9/30/2015I108 C1079 Edwards 9/30/2015Warehouse W11 Vocational Classroom Edwards 9/30/2015Warehouse W12 Storage E1003 Edwards 9/30/2015Warehouse W17 Equipment Room E1004 Edwards 9/30/2015
Page 10 of 11
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Warehouse W27 Warehouse E1010 Edwards 9/30/2015Warehouse W35 Warehouse E1010 Edwards 9/30/2015Warehouse W36 Vestibule E1001 Edwards 9/30/2015
Alarm Notification ApplianceADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Audible And Visible1st Floor Notification 9/30/2015
Page 11 of 11
Entec Systems Inc.
Inspection and Testing CertificatePresented To
Gwinnett County-Police Semi
For
Correctional Institute750 Hi Hope Road
Lawrenceville GA 30043USA
CompletedThursday, October 01, 2015
ACCEPTED BY TESTED BY
Richard Turner Jared Coile
Gwinnett County-Police Semi Entec Systems Inc.
75 Langely DriveLawrenceville GA 30043USA
450 Satellite Blvd. NE, Suite PSuwanee GA 30024USA
This site has been inspected and tested in compliance with applicable standards.
Entec Systems Inc.
Inspection Summary
Building Information
PROPERTY Correctional Institute
ADDRESS 750 Hi Hope Road
CITY/STATE/ZIP Lawrenceville, GA 30043
COUNTRY USA
CONTACT Richard Turner
PHONE 0
MOBILE 0
Inspector Information
COMPANY Entec Systems Inc.
ADDRESS 450 Satellite Blvd. NE, Suite P
CITY/STATE/ZIP Suwanee, GA 30024
COUNTRY USA
CONTACT Jared Coile
PHONE (678) 858-4950
MOBILE
EMAIL [email protected]
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
Fire Control Panel 1 1(100 %) 1(100 %) 0(0 %)
Initiating Device 42 42(100 %) 42(100 %) 0(0 %)
Alarm Notification Appliance 1 1(100 %) 1(100 %) 0(0 %)
Certification
The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, withthe inspection completed on Thursday, October 01, 2015
ACCEPTED BY
10/1/2015
Richard Turner
Gwinnett County-Police Semi
TESTED BY
10/1/2015
Jared Coile
Technician
Entec Systems Inc.
Page 2 of 10
Entec Systems Inc.
System Details
Control Units
MANUFACTURER Edwards
MODEL EST3
SERIAL NUMBER
INSTALL DATE 10/1/2015
DESCRIPTION Main FACP
S/W VERSION
LAST UPDATE
S/W LOCATION
Page 3 of 10
Entec Systems Inc.
Corrective Action SummaryThe following 1 corrective action(s) were identified during the system inspection, testing or maintenance activities.
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor Notification
Corrective Action: A Dorm had no audio or visual notification during sound test. I dorm, J dorm, and Kdorm had no strobes during sound test, audio only.
Page 4 of 10
Entec Systems Inc.
Testing Details
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel Main FACP Manual 10/1/2015 10:49 AM
I I Manufacturer Edwards
I I Model EST3
I I Serial Number I
I I Visual Inspection True
I I Functional Inspection True
I I Ground Fault True
I I Disconnect Switches True
I I Alarm Verification Timer (s) I
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box A AREA B2105 Dayroom Officer A1061 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B2124 Waiting A1037 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B2129 Vestibule A1001 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B224 Concs Lab Exit Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B227 Dayroom Officer A1086 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B237 Dayroom Officer A1044 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B240 Concs Lab AES1 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box A AREA B276 Dayroom Officer A1026 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
Page 5 of 10
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C10 Dayroom B1001 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C100 Dayroom Officer B1015 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C101 Waiting B1051 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C106 Search B1027 Manual 10/1/2015 10:50 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C20 Dayroom Officer B1028 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA 1C70 Dayroom Officer B1057 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA CC15 Corridor B1060 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA CC27 Staff Break B1095 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B AREA CC8 Corridor B1060 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box B2123 AA1043 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA 1stCORRIDOR
Outside Dining Hall Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I21 Kitchen C1008 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I33 Mechanical Room C1024 Manual 10/1/2015 10:51 AM
Page 6 of 10
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I35 Electrical Room C1023 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I70 Officer Station C1030 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I74 Corridor C1049 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box C AREA I93 Corridor C1064 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC107 D1004 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC126 D1047 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC209 A1017 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box CC209 A1043 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC107 Nurse Station D1004 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC168 Corridor D1077 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC187 Release Lobby Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC70 Public Lobby Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC77 Visitor Waiting D1098 Manual 10/1/2015 10:51 AM
Page 7 of 10
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box D AREA CC84 Corridor D1038 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box I108 C1079 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W11 Vocational Classroom Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W12 Storage E1003 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W17 Equipment Room E1004 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W27 Warehouse E1010 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box Warehouse W35 Warehouse E1010 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
I I Alarm Verification Participation False
Manual Fire Box Warehouse W36 Vestibule E1001 Manual 10/1/2015 10:51 AM
I I Manufacturer Edwards
I I Visual Inspection True
I I Functional Inspection True
Alarm Notification Appliance
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Audible And Visible 1st Floor Notification Manual 10/1/2015 10:55 AM
I I Visual Inspection True
I I Functional Inspection True
Page 8 of 10
Entec Systems Inc.
Device/Equipment Details
Fire Control Panel
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Fire Alarm Panel
Main FACP Edwards EST3 10/1/2015
Initiating Device
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Manual Fire Box
A AREA B2105 Dayroom Officer A1061 Edwards 10/1/2015
A AREA B2124 Waiting A1037 Edwards 10/1/2015
A AREA B2129 Vestibule A1001 Edwards 10/1/2015
A AREA B224 Concs Lab Exit Edwards 10/1/2015
A AREA B227 Dayroom Officer A1086 Edwards 10/1/2015
A AREA B237 Dayroom Officer A1044 Edwards 10/1/2015
A AREA B240 Concs Lab AES1 Edwards 10/1/2015
A AREA B276 Dayroom Officer A1026 Edwards 10/1/2015
B AREA 1C10 Dayroom B1001 Edwards 10/1/2015
B AREA 1C100 Dayroom Officer B1015 Edwards 10/1/2015
B AREA 1C101 Waiting B1051 Edwards 10/1/2015
B AREA 1C106 Search B1027 Edwards 10/1/2015
B AREA 1C20 Dayroom Officer B1028 Edwards 10/1/2015
B AREA 1C70 Dayroom Officer B1057 Edwards 10/1/2015
B AREA CC15 Corridor B1060 Edwards 10/1/2015
B AREA CC27 Staff Break B1095 Edwards 10/1/2015
B AREA CC8 Corridor B1060 Edwards 10/1/2015
B2123 AA1043 Edwards 10/1/2015
C AREA 1stCORRIDOR
Outside Dining Hall Edwards 10/1/2015
C AREA I21 Kitchen C1008 Edwards 10/1/2015
C AREA I33 Mechanical Room C1024 Edwards 10/1/2015
C AREA I35 Electrical Room C1023 Edwards 10/1/2015
C AREA I70 Officer Station C1030 Edwards 10/1/2015
C AREA I74 Corridor C1049 Edwards 10/1/2015
C AREA I93 Corridor C1064 Edwards 10/1/2015
CC107 D1004 Edwards 10/1/2015
CC126 D1047 Edwards 10/1/2015
CC209 A1017 Edwards 10/1/2015
CC209 A1043 Edwards 10/1/2015
D AREA CC107 Nurse Station D1004 Edwards 10/1/2015
D AREA CC168 Corridor D1077 Edwards 10/1/2015
D AREA CC187 Release Lobby Edwards 10/1/2015
D AREA CC70 Public Lobby Edwards 10/1/2015
D AREA CC77 Visitor Waiting D1098 Edwards 10/1/2015
D AREA CC84 Corridor D1038 Edwards 10/1/2015
I108 C1079 Edwards 10/1/2015
Warehouse W11 Vocational Classroom Edwards 10/1/2015
Warehouse W12 Storage E1003 Edwards 10/1/2015
Warehouse W17 Equipment Room E1004 Edwards 10/1/2015
Page 9 of 10
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Warehouse W27 Warehouse E1010 Edwards 10/1/2015
Warehouse W35 Warehouse E1010 Edwards 10/1/2015
Warehouse W36 Vestibule E1001 Edwards 10/1/2015
Alarm Notification Appliance
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Audible And Visible
1st Floor Notification 10/1/2015
Page 10 of 10
Entec Systems Inc.
Inspection and Testing CertificatePresented To
Gwinnett County-Police
For
Correctional Institute750 Hi Hope Road
Lawrenceville GA 30044USA
This site has been inspected and tested in compliance with applicable standards.
CompletedThursday, February 25, 2016
Test Session: 2/25/16 Annual Fire Alarm Inspection Correctional Complex
ACCEPTED BY TESTED BY
Richard Turner Jared Coile
Gwinnett County-Police Entec Systems Inc.
75 Langely DriveLawrenceville GA 30043USA
450 Satellite Blvd. NE, Suite PSuwanee GA 30024USA
Entec Systems Inc.
Inspection Summary
Building Information
PROPERTY Correctional Institute
ADDRESS 750 Hi Hope Road
CITY/STATE/ZIP Lawrenceville, GA 30044
COUNTRY USA
CONTACT Richard Turner
PHONE
MOBILE
Inspector Information
COMPANY Entec Systems Inc.
ADDRESS 450 Satellite Blvd. NE, Suite P
CITY/STATE/ZIP Suwanee, GA 30024
COUNTRY USA
CONTACT Jared Coile
PHONE (678) 858-4950
MOBILE
EMAIL [email protected]
NAME INITIALS QUALIFICATION AND PROFICIENCIES
Jared Coile JC
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
Fire Control Panel 1 1(100 %) 1(100 %) 0(0 %)
Initiating Device 516 516(100 %) 516(100 %) 0(0 %)
Alarm Notification Appliance 1 1(100 %) 1(100 %) 0(0 %)
CertificationThe equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspectioncompleted on Thursday, February 25, 2016
ACCEPTED BY
3/1/2016
Richard Turner
Gwinnett County-Police
TESTED BY
3/1/2016
Jared Coile
Technician
Entec Systems Inc.
Page 2 of 70
Entec Systems Inc.
System Details
Control Units
MANUFACTURER EST
MODEL
SERIAL NUMBER
INSTALL DATE 2/29/2016
DESCRIPTION Main FACP
S/W VERSION
LAST UPDATE
S/W LOCATION
Monitoring Information
Page 3 of 70
Entec Systems Inc.
Open Corrective Action & Solution SummaryThe following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor Notification
Created By: Jared Coile
Creation Date: 3/1/2016
Corrective Action: K Dorm the strobe circuit is down.
Proposed Solution: Trouble shoot NAC circuit and/or relay.
Page 4 of 70
Entec Systems Inc.
Testing Details
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel Main FACP Manual 3/1/2016 11:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
I I
I I
I I
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralB AREA 1C681014
STORAGE B2035 Manual 2/25/2016 9:17 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C671013
DAYROOM B1057 Manual 2/25/2016 9:17 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C691003
DAYROOM B1057 Manual 2/25/2016 9:17 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C661012
DAYROOM B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C651011
DAYROOM B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C561009
DAYROOM MEZZ B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C631010
DAYROOM B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
Page 5 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C571008
DAYROOM MEZZ B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C581007
DAYROOM MEZZ B1057 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1121001
CORRIDOR B1026 Manual 2/25/2016 9:18 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C641006
DAYROOM B1057 Manual 2/25/2016 9:19 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C621005
DAYROOM B1057 Manual 2/25/2016 9:20 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C611004
DAYROOM B1057 Manual 2/25/2016 9:20 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C491016
CORRIDOR B1044 Manual 2/25/2016 9:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C521017
STORAGE B1041 Manual 2/25/2016 9:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C431018
CORRIDOR B1044 Manual 2/25/2016 9:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C481019
STORAGE B1042 Manual 2/25/2016 9:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I991498
VEST. ROOM D1114 Manual 2/25/2016 9:28 AM
I I Manufacturer EST
I I Visual Inspection True
Page 6 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C471020
STORAGE B1043 Manual 2/25/2016 9:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC771312
VISITOR WAITING D1098 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC831313
PUBLIC LOBBY D1117 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC671314
WAITING B1070 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2511507
ELECT. ROOM D1115 Manual 2/25/2016 9:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C201033
DAYROOM OFFICER B1028 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC661315
WAITING B1070 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC651316
WAITING B1070 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC431317
CORRIDOR B1079 Manual 2/25/2016 9:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC421320
MEETING ROOM B1077 Manual 2/25/2016 9:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC2801318
ADMIN ASSISTANTS B1080 Manual 2/25/2016 9:31 AM
I I Manufacturer EST
I I Visual Inspection True
Page 7 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C351029
DAYROOM B1028 Manual 2/25/2016 9:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C331030
DAYROOM B1028 Manual 2/25/2016 9:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C321031
DAYROOM B1028 Manual 2/25/2016 9:32 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C311032
DAYROOM B1028 Manual 2/25/2016 9:33 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C231026
CONC SLAB BES2 Manual 2/25/2016 9:35 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C341023
DAYROOM B1028 Manual 2/25/2016 9:36 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C361022
DAYROOM B1028 Manual 2/25/2016 9:37 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C371021
DAYROOM B1028 Manual 2/25/2016 9:38 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC401321
WORK ROOM B1086 Manual 2/25/2016 9:42 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC391322
SUPPLY ROOM B1085 Manual 2/25/2016 9:43 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC341324
BREAK ROOM B1089 Manual 2/25/2016 9:43 AM
I I Manufacturer EST
I I Visual Inspection True
Page 8 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Manual Fire BoxB AREA 1C701015
DAYROOM OFFICER B1057 Manual 2/25/2016 9:44 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1001069
DAYROOM OFFICER B1015 Manual 2/25/2016 9:46 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C891064
DAYROOM MEZZ B1015 Manual 2/25/2016 9:46 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C881063
DAYROOM MEZZ B1015 Manual 2/25/2016 9:47 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C871062
DAYROOM MEZZ B1015 Manual 2/25/2016 9:47 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C861061
DAYROOM MEZZ B1015 Manual 2/25/2016 9:48 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C931068
DAYROOM B1015 Manual 2/25/2016 9:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C951067
DAYROOM B1015 Manual 2/25/2016 9:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C961066
DAYROOM B1015 Manual 2/25/2016 9:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C981065
DAYROOM B1015 Manual 2/25/2016 9:51 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C971070
STORAGE B2034 Manual 2/25/2016 9:52 AM
I I Manufacturer EST
I I Visual Inspection True
Page 9 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C991058
DAYROOM B1015 Manual 2/25/2016 9:52 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C941059
DAYROOM B1015 Manual 2/25/2016 9:53 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C921060
DAYROOM B1015 Manual 2/25/2016 9:54 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C911057
DAYROOM B1015 Manual 2/25/2016 9:55 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C791055
CORRIDOR B1109 Manual 2/25/2016 9:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C811056
STORAGE B1055 Manual 2/25/2016 9:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C731052
CORRIDOR B1109 Manual 2/25/2016 9:59 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C781054
ELECTRICAL B1054 Manual 2/25/2016 9:59 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C771053
STORAGE B1053 Manual 2/25/2016 10:01 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C101051
DAYROOM B1001 Manual 2/25/2016 10:03 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C91043
DAYROOM MEZZ B1001 Manual 2/25/2016 10:04 AM
I I Manufacturer EST
I I Visual Inspection True
Page 10 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C71044
DAYROOM MEZZ B1001 Manual 2/25/2016 10:05 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C121040
DAYROOM B1001 Manual 2/25/2016 10:20 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C141041
DAYROOM B1001 Manual 2/25/2016 10:21 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C191042
DAYROOM B1001 Manual 2/25/2016 10:22 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C111039
DAYROOM B1001 Manual 2/25/2016 10:23 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1051036
SEARCH AREA B1027 Manual 2/25/2016 10:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1301035
SEARCH AREA B1027 Manual 2/25/2016 10:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C1061034
SEARCH B1027 Manual 2/25/2016 10:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1041037
CORRIDOR B1110 Manual 2/25/2016 10:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1031038
CORRIDOR B1051 Manual 2/25/2016 10:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA 1C1011462
WAITING B1051 Manual 2/25/2016 10:32 AM
I I Manufacturer EST
I I Visual Inspection True
Page 11 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralD AREA 1STHALL1354
OUSIDE ROOM D1120 Manual 2/25/2016 10:43 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1021074
WAITING B1051 Manual 2/25/2016 10:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA RET1C1091461
WAITING B1051 RTU8 Manual 2/25/2016 10:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREASUP1C1081464
WAITING B1051 RTU8 Manual 2/25/2016 10:49 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1101072
CORRIDOR B1026 Manual 2/25/2016 10:52 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1111071
CORRIDOR B1026 Manual 2/25/2016 10:52 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC91365
CORRIDOR B1060 Manual 2/25/2016 10:53 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC71366
CORRIDOR B1060 Manual 2/25/2016 10:53 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC61367
CORRIDOR B1060 Manual 2/25/2016 10:54 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC51368
CORRIDOR B1060 Manual 2/25/2016 10:55 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21091077
EQUIPMENT ROOM A1042 Manual 2/25/2016 10:56 AM
Page 12 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B21051474
DAYROOM OFFICER A1061 Manual 2/25/2016 10:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2931236
DAYROOM MEZZ A1061 Manual 2/25/2016 11:01 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2921237
DAYROOM MEZZ A1061 Manual 2/25/2016 11:02 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2981239
DAYROOM A1061 Manual 2/25/2016 11:05 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21001241
DAYROOM A1061 Manual 2/25/2016 11:11 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21021242
DAYROOM A1061 Manual 2/25/2016 11:11 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA 1STDAYROOM A10611446
STORAGE A1058 Manual 2/25/2016 11:22 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C601002
STORAGE B 1066 Manual 2/25/2016 11:22 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2841447
ELECTRICAL ROOM A1056 Manual 2/25/2016 11:24 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2371107
DAYROOM OFFICER A1044 Manual 2/25/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General A AREA B241 DAYROOM A1044 Manual 2/25/2016 11:30 AM
Page 13 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1096
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2501101
DAYROOM A1044 Manual 2/25/2016 11:34 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2491094
DAYROOM A1044 Manual 2/25/2016 11:41 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2461093
DAYROOM A1044 Manual 2/25/2016 11:42 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2531091
DAYROOM A1044 Manual 2/25/2016 11:43 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2271105
DAYROOM OFFICER A1086 Manual 2/25/2016 11:45 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2241104
CONC SLAB EXIT Manual 2/25/2016 11:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2401106
CONC SLAB AES1 Manual 2/25/2016 11:50 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2281108
DAYROOM A1086 Manual 2/25/2016 11:56 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2351109
DAYROOM A1086 Manual 2/25/2016 11:56 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2311111
DAYROOM A1086 Manual 2/25/2016 11:57 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General A AREA B229 DAYROOM A1086 Manual 2/25/2016 11:58 AM
Page 14 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1110
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2151443
STORAGE A1090 Manual 2/25/2016 12:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2181468
STORAGE A1090 Manual 2/25/2016 12:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2171119
STORAGE A1090 Manual 2/25/2016 12:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2141442
ELECTRICAL A1030 Manual 2/25/2016 12:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2561118
STORAGE A1029 Manual 2/25/2016 12:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2571441
STORAGE A1029 Manual 2/25/2016 12:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2611467
STORAGE A1029 Manual 2/25/2016 12:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC961389
CORRIDOR D1030 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC951392
CORRIDOR D1030 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC941395
CORRIDOR D1030 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General D AREA CC205 CLASSROOM D1031 Manual 2/25/2016 2:29 PM
Page 15 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1385
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2061386
CLASSROOM D1031 Manual 2/25/2016 2:29 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1221388
GED D1028 Manual 2/25/2016 2:30 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1191372
CORRIDOR C1025 Manual 2/25/2016 2:30 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I701408
OFFICER STATION C1030 Manual 2/25/2016 2:30 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I631404
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I671405
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I681406
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I621407
DAYROOM C1030 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1061402
WAITING D1001 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1051403
EXAM D1012 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General D AREA CC104 TREATMENT D1013 Manual 2/25/2016 2:31 PM
Page 16 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1375
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1081376
CORRIDOR D1011 Manual 2/25/2016 2:31 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1091377
LAB D1014 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1101378
DENTAL SUITE D1015 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1151379
CORRIDOR D1011 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2171371
CORRIDOR D1011 Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1191381
ISOLATION VESTIBULE Manual 2/25/2016 2:32 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1201369
ISOLATION D1018 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1181370
ISOLATION D1020 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I801298
DAYROOM C1041 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I861299
DAYROOM C1041 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General C AREA I72 CORRIDOR C1049 Manual 2/25/2016 2:33 PM
Page 17 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1300
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I731301
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I741302
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I751303
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I761304
CORRIDOR C1049 Manual 2/25/2016 2:33 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I921500
STORAGE C1042 Manual 2/25/2016 2:34 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC841244
CORRIDOR D1038 Manual 2/25/2016 2:34 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA 1STCORRIDOR1276
OUTSIDE DINING HALL Manual 2/25/2016 2:35 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA CCADD1247
CORRIDOR C1092 Manual 2/25/2016 2:35 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I961293
DAYROOM C1056 Manual 2/25/2016 2:35 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I871294
DAYROOM C1056 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 18 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - DuctC AREA I891454
DAYROOM C1056 RETURN Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I911295
CORRIDOR C1064 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I931296
CORRIDOR C1064 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I941297
CORRIDOR C1064 Manual 2/25/2016 2:36 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1331281
CORRIDOR D1047 Manual 2/25/2016 2:39 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC901251
CORRIDOR D1038 Manual 2/25/2016 2:39 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1281282
CORRIDOR D1047 Manual 2/25/2016 2:40 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC1261283
CORRIDOR D1047 Manual 2/25/2016 2:40 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1311285
CORRIDOR D1047 Manual 2/25/2016 2:40 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC921253
CORRIDOR D1038 Manual 2/25/2016 2:41 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1571279
EQUIPMENT D1040 Manual 2/25/2016 2:42 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 19 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralD AREA CC1581272
DAYROOM D1054 Manual 2/25/2016 2:42 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1641273
DAYROOM D1054 Manual 2/25/2016 2:43 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1521274
CORRIDOR D1062 Manual 2/25/2016 2:44 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1501275
CORRIDOR D1062 Manual 2/25/2016 2:44 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box
1ST C AREACORRIDOROUTSIDE .11245
DINING HALL Manual 2/25/2016 2:45 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire Box
1ST C AREACORRIDOROUTSIDE .21246
DINING HALL Manual 2/25/2016 2:45 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1491277
CORRIDOR D1062 Manual 2/25/2016 2:45 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1531278
CORRIDOR D1062 Manual 2/25/2016 2:46 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC931254
CORRIDOR D1038 Manual 2/25/2016 2:47 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC941255
CORRIDOR D1038 Manual 2/25/2016 2:47 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC951256
CORRIDOR D1038 Manual 2/25/2016 2:48 PM
Page 20 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1801265
DAYROOM D1069 SUP Manual 2/25/2016 2:48 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1841266
DAYROOM D1069 Manual 2/25/2016 2:48 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1731271
CORRIDOR D1077 Manual 2/25/2016 2:49 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1711270
CORRIDOR D1077 Manual 2/25/2016 2:49 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC1681269
CORRIDOR D1077 Manual 2/25/2016 2:50 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1701268
CORRIDOR D1077 Manual 2/25/2016 2:50 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1741267
CORRIDOR D1077 Manual 2/25/2016 2:51 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC961257
CORRIDOR D1038 Manual 2/25/2016 2:52 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC971258
CORRIDOR D1038 Manual 2/25/2016 2:53 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC981259
CORRIDOR D1038 Manual 2/25/2016 2:54 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1881263
CORRIDOR D1084 Manual 2/25/2016 2:55 PM
Page 21 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1851260
INTERVIEW ROOM D1085 Manual 2/25/2016 2:55 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1891264
CORRIDOR D1084 Manual 2/25/2016 2:55 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1861261
RELEASE LOBBY D1085 Manual 2/25/2016 2:56 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC1871262
RELEASE LOBBY Manual 2/25/2016 2:56 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC471343
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC481340
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC461342
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC491341
VISITING ROOM D1105 Manual 2/25/2016 2:59 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C801122
SUPSTORAGE B1055 RTU7 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C511124
STORAGE B1041 RTU10 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C461125
CORRIDOR B1044 Manual 2/25/2016 3:00 PM
Page 22 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C751123
CORRIDOR B1109 RTU6 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2811121
STORAGE A1055 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B2851120
STORAGE A1056 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC541339
SEARCH AREA D1106 Manual 2/25/2016 3:00 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA CC181126
M SHOWER B1093 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA CC221127
JANITOR ROOM B1098 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C541129
TOILET B1040 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA CC301128
W LOCKER B1092 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C551130
SHOWER B1039 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C711132
JANITOR ROOM B1103 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C841133
TOILET B1014 Manual 2/25/2016 3:01 PM
Page 23 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C411135
JANITOR ROOM B1047 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C851134
SHOWER B1013 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C391131
JANITOR B1048 Manual 2/25/2016 3:01 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C271137
TOILET B1038 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC791344
STORAGE D1101 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC801345
VSP ROOM D1100 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C281136
JANITOR ROOM B1045 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C261138
SHOWER B1037 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C11139
JANITOR ROOM B1108 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C31140
SHOWER B1011 Manual 2/25/2016 3:02 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2771142
JANITOR ROOM A1041 Manual 2/25/2016 3:02 PM
Page 24 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotB AREA 1C21141
TOILET B1012 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2891143
TOILET A1059 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2901144
SHOWER A1060 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2581145
TOILET A1028 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2591146
SHOWER A1027 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2541147
JANITOR ROOM A1032 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B21151148
JANITOR ROOM A1033 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2201149
TOILET A1088 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2211150
SHOWER A1088 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2361151
JANITOR ROOM A1035 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2441153
TOILET A1064 Manual 2/25/2016 3:03 PM
Page 25 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2431152
SHOWER A1063 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotA AREA B2451154
JANITOR ROOM A1039 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I411155
LAUNDRY C1021 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I421156
LAUNDRY C1021 Manual 2/25/2016 3:03 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I401157
LAUNDRY C1021 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I371158
DRY AREA C1022 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I31159
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I41160
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I21161
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I11163
DISH WASH C1087 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I111164
KITCHEN C1008 Manual 2/25/2016 3:04 PM
Page 26 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I171165
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I201166
KITCHEN C1008 Manual 2/25/2016 3:04 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I181168
KITCHEN C1008 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I191167
KITCHEN C1008 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I231169
DRY STORAGE C1011 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I221170
DRY STORAGE C1011 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I71171
JANITOR ROOM C1012 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I531172
SERVERY C1003 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I541173
JANITOR ROOM C1006 Manual 2/25/2016 3:05 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I551174
SERVERY C1005 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1121175
JANITOR ROOM Manual 2/25/2016 3:06 PM
Page 27 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I591176
JANITOR ROOM C1027 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I811177
LAUNDRY C1044 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I821178
JANITOR ROOM C1043 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I981179
JANITOR ROOM C1058 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I971180
LAUNDRY C1059 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I1041181
JANITOR ROOM C1073 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I1051182
LAUNDRY C1074 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1391183
JANITOR ROOM D1040 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1381184
LAUNDRY D1042 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1561185
JANITOR ROOM D1041 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1551186
LAUNDRY D1042 Manual 2/25/2016 3:06 PM
Page 28 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1771187
TOILET D1070 Manual 2/25/2016 3:06 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC1761188
LAUNDRY D1072 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC811189
JANITOR ROOM D1104 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotD AREA CC721190
JANITOR ROOM D1112 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW261194
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW241195
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW251196
SECURED STORAGE Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW231199
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW221200
WAREHOUSE E1010 Manual 2/25/2016 3:07 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW321201
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
Page 29 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW331202
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW211203
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW201204
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW191205
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW341206
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW181207
WAREHOUSE E1010 Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW151208
MAINTENANCE SHOP Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW141209
MAINTENANCE SHOP Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW101217
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W91218
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
Page 30 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W71219
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W81220
VOCATIONAL CLASSROOM Manual 2/25/2016 3:08 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W61221
VOCATIONAL CLASSROOM Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSE W51222
VOCATIONAL CLASSROOM Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW131223
STORAGE E1003 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotWAREHOUSEW281226
EQUIPMENT STORAGE E1004 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I341228
MECHANICAL ROOM C1024 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Heat Detector - Restorable SpotC AREA I241229
MECHANICAL ROOM C1024 Manual 2/25/2016 3:09 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2011398
MULTIPURPOSE D1037 Manual 2/25/2016 3:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2021397
MULTIPURPOSE D1037 Manual 2/25/2016 3:10 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 31 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralD AREA CC2161399
MULTIPURPOSE D1037 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1971396
MULTIPURPOSE D1037 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2081400
STORAGE D1036 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I571412
STAFF DINING C1005 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I561413
STAFF DINING C1005 Manual 2/25/2016 3:11 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1071509
CORRIDOR C1016 Manual 2/25/2016 3:12 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I211418
KITCHEN C1008 Manual 2/25/2016 3:12 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I141162
KITCHEN C1008 Manual 2/25/2016 3:12 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I491415
DIVERSION DINING C1002 Manual 2/25/2016 3:13 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I501414
DIVERSION DINING C1002 Manual 2/25/2016 3:13 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I511417
DIVERSION DINING C1002 Manual 2/25/2016 3:14 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 32 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - GeneralC AREA I521416
DIVERSION DINING C1002 Manual 2/25/2016 3:17 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1201508
STORAGE C1017 Manual 2/25/2016 3:18 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I461419
JANITOR C1017 Manual 2/25/2016 3:18 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC1261494
A1017 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctI1081493
A1043 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC2091492
A1043 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC209.11491
D1004 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB21231490
DAYROOM C1041 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctCC1071489
DAYROOM D1039 SUPPLY Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctI781488
DAYROOM D1069 SUPPLY Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1351487
DAYROOM D1054 SUPPLY Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 33 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - DuctD AREA CC1821486
NEAR D 1075 SHOWER Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1601485
DAYROOM B1057 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC51RET1483
SHIFT SUPERVISOR D1121 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA R CC2001482
MULTIPURPOSE D1037 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA S CC1991481
MULTIPURPOSE D1037 Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1001480
COMPUTER LAB D1027 SUP Manual 2/25/2016 3:19 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1021479
COMPUTER LAB D1027 RET Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I391475
LAUNDRY C1021 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctA AREA B21131470
WAITING A1037 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C821459
RET STORAGE B1055 RTU7 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C451457
CORRIDOR B1042 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
Page 34 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - DuctB AREA 1C531456
STORAGE B1044 RTU10 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I791455
DAYROOM C1041 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I881453
DAYROOM A1056 SUPPLY Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctC AREA I111.11452
DAYROOM C1071 Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1361451
DAYROOM D1039 RETURN Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1831450
DAYROOM D1069 RETURN Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - DuctD AREA CC1611449
DAYROOM D1054 RETURN Manual 2/25/2016 3:20 PM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C211024
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C221025
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C251027
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C241028
DAYROOM MEZZ B1028 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
Page 35 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C51045
DAYROOM MEZZ B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C41046
DAYROOM MEZZ B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C131047
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C151048
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C161049
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C181050
DAYROOM B1001 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C1151073
EQUIPMENT ROOM B1104 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C721075
MULTIPURPOSE B1056 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA CC81076
CORRIDOR B1060 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2661078
EQUIPMENT ROOM A1016 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21101079
CORRIDOR A1015 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
Page 36 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21111080
CORRIDOR A1015 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21061081
EQUIPMENT ROOM A1042 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21181082
WAITING A1037 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21121083
COUNSELOR A1031 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21161084
SUPPLY ROOM A1034 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21251085
MULTIPURPOSE A1040 Manual 3/1/2016 11:25 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21201086
CORRIDOR A1015 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21211087
CORRIDOR A1015 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21221088
SEARCH A1043 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21521089
SEARCH A1043 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21231090
SEARCH A1043 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
Page 37 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2521092
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2421095
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2391097
DAYROOM MEZZ A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2381098
DAYROOM MEZZ A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2471099
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2481100
DAYROOM A1044 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2331102
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2341103
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2261112
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2251113
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2231114
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
Page 38 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2221115
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2301116
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2321117
DAYROOM A1086 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I361191
ELECTRICAL C1023 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I351192
ELECTRICAL C1023 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW271193
WAREHOUSE E1010 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSEW28.11197
ELECTRICAL ROOM E1011 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSEW291198
OFFICE E1013 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW351210
WAREHOUSE E1010 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSE W21211
CORRIDOR E1006 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - General WAREHOUSE W3 CORRIDOR E1006 Manual 3/1/2016 11:26 AM
Page 39 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
1212
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSE W11213
OFFICE E1007 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralWAREHOUSE W41214
VESTIBULE E1001 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW361215
VESTIBULE E1001 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW111216
VOCATIONAL CLASSROOM Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW121224
STORAGE E1003 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxWAREHOUSEW171225
EQUIPMENT STORAGE E1004 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxC AREA I331227
MECHANICAL ROOM C1024 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC45.11230
EQUIT D1119 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21041231
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21011232
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
Page 40 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2971233
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2961234
DAYROOM A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2941235
DAYROOM MEZZ A1061 Manual 3/1/2016 11:26 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2911238
DAYROOM MEZZ A1061 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2991240
DAYROOM A1061 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21031243
DAYROOM A1061 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC871248
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC881249
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC891250
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC911252
CORRIDOR D1038 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1431280
DAYROOM D1039 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
Page 41 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1291284
CORRIDOR D1047 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1021286
DAYROOM C1071 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1141287
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1101288
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1091289
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1081290
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1071291
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1061292
CORRIDOR C1079 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B251305
VESTIBULE A1001 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B21291306
VESTIBULE A1001 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B231307
HOLDING CELL A1004 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
Page 42 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B221308
HOLDING CELL A1005 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B211309
HOLDING CELL A1006 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2121310
CORRIDOR A1012 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA CC151311
CORRIDOR B1060 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC441319
INMATE RECORDS D1083 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC311323
CORRIDOR OF ADMIN B1080 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC361325
STORAGE B1090 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC251326
CORRIDOR B1094 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC281327
STAFF BREAK B1095 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxB AREA CC271328
STAFF BREAK B1095 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC241329
TRAINING B1096 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
Page 43 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC261330
TRAINING B1096 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC231331
CORRIDOR B1094 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC201332
FITNESS B1099 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC171333
M LOCKER B1106 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC191334
CORRIDOR B1094 Manual 3/1/2016 11:27 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC161335
CORRIDOR B1094 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC371336
UNIFORM STORAGE B1091 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC631337
MAIN VESTIBULE B1069 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC621338
MAIN VESTIBULE B1069 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC751346
VISITOR WAITING D1098 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC781347
VISITOR WAITING D1098 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 44 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC731348
STORAGE D1111 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC761349
VESTIBULE D1096 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxD AREA CC701350
PUBLIC LOBBY D1117 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC741351
CORRIDOR D1110 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC821352
OFFICE D1118 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC451353
EQUIPMENT D1119 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC591355
MASTER CONTROL D1129 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC531356
SHIFT SUPERVISOR D1121 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC551357
STORAGE D1122 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC561358
CORRIDOR D1125 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC611359
MAIL ROOM D1126 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 45 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC141360
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC131361
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC121362
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC111363
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC101364
CORRIDOR B1060 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1131373
ELECTRICAL ROOM D1008 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I581374
VESTIBULE C1026 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1111380
STORAGE D1005 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC41382
CORRIDOR A1068 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC31383
CORRIDOR A1068 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC21384
CORRIDOR A1068 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 46 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2071387
STORAGE D1035 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC991390
COMPUTER LAB D1027 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1031391
BARBER D1026 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2031393
LIBRARY D1034 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC2041394
LIBRARY D1034 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1211401
CORRIDOR C1025 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I611409
DAYROOM MEZZ C1030 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I691410
DAYROOM MEZZ C1030 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I601411
DAYROOM MEZZ C1030 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC2091420
VESITBULE A1017 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA CC11421
VESTIBULE A1017 Manual 3/1/2016 11:28 AM
I I Manufacturer EST
Page 47 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2101422
PROPERTY STORAGE A1014 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B271423
ISSUE A1073 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2131424
SEARCH AREA A1008 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B261425
INMATE WAITING A1002 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B241426
INTERVIEW A1003 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2751427
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2671428
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2681429
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2721430
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2621431
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2631432
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
Page 48 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2641433
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2651434
DAYROOM MEZZ A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2731435
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2741436
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2711437
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2701438
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2691439
DAYROOM A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2161440
CORRIDOR A1074 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2781444
CORRIDOR A1057 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2791445
CORRIDOR A1057 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2831448
STORAGE A1055 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
Page 49 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA RET1C761458
CORRIDOR B1109 RTU6 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C381460
COUNSELOR B1049 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C421463
SUPPLY ROOM B1046 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C291465
COUNSELOR B1050 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C901466
EQUPIMENT B1024 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21191469
COUNSELOR A1036 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B21241471
WAITING A1037 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Manual Fire BoxA AREA B2761472
DAYROOM OFFICER A1026 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA 1STDAYROOM A10611473
CORRIDOR A1057 B288 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I61476
IT TOILET C1013 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I51477
ST TOILET C1015 Manual 3/1/2016 11:29 AM
Page 50 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B2951478
STORAGE A1070 Manual 3/1/2016 11:29 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C591484
MAIN PANEL Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC691495
C1079 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC711496
D1047 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I831497
Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I951499
STORAGE D1113 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1371501
EQUIP. ROOM C1057 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC411502
CORRIDOR C1064 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA CC431503
CORRIDOR C1064 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC681504
DAYROOM D1039 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I471505
ADMIN. ASSISTS. B1080 Manual 3/1/2016 11:30 AM
Page 51 of 70
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I481506
CORRIDOR B1079 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1141510
DAYROOM A1044 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1171511
CORRIDOR C1025 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC1161512
NURSE STATION D1004 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralB AREA 1C301513
EMER. STORAGE D1007 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralC AREA I1111514
SOILED LINEN D1010 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralD AREA CC501515
CLEAN LINEN D1009 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Smoke Detector - GeneralA AREA B21171516
DAYROOM B1028 Manual 3/1/2016 11:30 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Alarm Notification Appliance
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Audible And Visible 1st Floor Notification Manual 3/1/2016 11:31 AM
I I Manufacturer EST
I I Visual Inspection True
I I Functional Inspection True
Page 52 of 70
Entec Systems Inc.
Device/Equipment Details
Fire Control Panel
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Fire Alarm Panel
Main FACP EST 2/29/2016
Initiating Device
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Heat Detector - Restorable Spot
B AREA CC181126
M SHOWER B1093 EST 12/31/2011
B AREA CC221127
JANITOR ROOM B1098 EST 12/31/2011
B AREA CC301128
W LOCKER B1092 EST 12/31/2011
B AREA 1C541129
TOILET B1040 EST 12/31/2011
B AREA 1C551130
SHOWER B1039 EST 12/31/2011
B AREA 1C391131
JANITOR B1048 EST 12/31/2011
B AREA 1C711132
JANITOR ROOM B1103 EST 12/31/2011
B AREA 1C841133
TOILET B1014 EST 12/31/2011
B AREA 1C851134
SHOWER B1013 EST 12/31/2011
B AREA 1C411135
JANITOR ROOM B1047 EST 12/31/2011
B AREA 1C281136
JANITOR ROOM B1045 EST 12/31/2011
B AREA 1C271137
TOILET B1038 EST 12/31/2011
B AREA 1C261138
SHOWER B1037 EST 12/31/2011
B AREA 1C11139
JANITOR ROOM B1108 EST 12/31/2011
B AREA 1C31140
SHOWER B1011 EST 12/31/2011
B AREA 1C21141
TOILET B1012 EST 12/31/2011
A AREA B2771142
JANITOR ROOM A1041 EST 12/31/2011
A AREA B2891143
TOILET A1059 EST 12/31/2011
A AREA B2901144
SHOWER A1060 EST 12/31/2011
A AREA B2581145
TOILET A1028 EST 12/31/2011
A AREA B2591146
SHOWER A1027 EST 12/31/2011
A AREA B2541147
JANITOR ROOM A1032 EST 12/31/2011
A AREA B21151148
JANITOR ROOM A1033 EST 12/31/2011
A AREA B220 TOILET A1088 EST 12/31/2011
Page 53 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1149
A AREA B2211150
SHOWER A1088 EST 12/31/2011
A AREA B2361151
JANITOR ROOM A1035 EST 12/31/2011
A AREA B2431152
SHOWER A1063 EST 12/31/2011
A AREA B2441153
TOILET A1064 EST 12/31/2011
A AREA B2451154
JANITOR ROOM A1039 EST 12/31/2011
C AREA I411155
LAUNDRY C1021 EST 12/31/2011
C AREA I421156
LAUNDRY C1021 EST 12/31/2011
C AREA I401157
LAUNDRY C1021 EST 12/31/2011
C AREA I371158
DRY AREA C1022 EST 12/31/2011
C AREA I31159
KITCHEN C1008 EST 12/31/2011
C AREA I41160
KITCHEN C1008 EST 12/31/2011
C AREA I21161
KITCHEN C1008 EST 12/31/2011
C AREA I11163
DISH WASH C1087 EST 12/31/2011
C AREA I111164
KITCHEN C1008 EST 12/31/2011
C AREA I171165
KITCHEN C1008 EST 12/31/2011
C AREA I201166
KITCHEN C1008 EST 12/31/2011
C AREA I191167
KITCHEN C1008 EST 12/31/2011
C AREA I181168
KITCHEN C1008 EST 12/31/2011
C AREA I231169
DRY STORAGE C1011 EST 12/31/2011
C AREA I221170
DRY STORAGE C1011 EST 12/31/2011
C AREA I71171
JANITOR ROOM C1012 EST 12/31/2011
C AREA I531172
SERVERY C1003 EST 12/31/2011
C AREA I541173
JANITOR ROOM C1006 EST 12/31/2011
C AREA I551174
SERVERY C1005 EST 12/31/2011
D AREA CC1121175
JANITOR ROOM EST 12/31/2011
C AREA I591176
JANITOR ROOM C1027 EST 12/31/2011
C AREA I811177
LAUNDRY C1044 EST 12/31/2011
C AREA I821178
JANITOR ROOM C1043 EST 12/31/2011
C AREA I981179
JANITOR ROOM C1058 EST 12/31/2011
C AREA I971180
LAUNDRY C1059 EST 12/31/2011
Page 54 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I1041181
JANITOR ROOM C1073 EST 12/31/2011
C AREA I1051182
LAUNDRY C1074 EST 12/31/2011
D AREA CC1391183
JANITOR ROOM D1040 EST 12/31/2011
D AREA CC1381184
LAUNDRY D1042 EST 12/31/2011
D AREA CC1561185
JANITOR ROOM D1041 EST 12/31/2011
D AREA CC1551186
LAUNDRY D1042 EST 12/31/2011
D AREA CC1771187
TOILET D1070 EST 12/31/2011
D AREA CC1761188
LAUNDRY D1072 EST 12/31/2011
D AREA CC811189
JANITOR ROOM D1104 EST 12/31/2011
D AREA CC721190
JANITOR ROOM D1112 EST 12/31/2011
WAREHOUSEW261194
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW241195
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW251196
SECURED STORAGE EST 12/31/2011
WAREHOUSEW231199
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW221200
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW321201
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW331202
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW211203
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW201204
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW191205
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW341206
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW181207
WAREHOUSE E1010 EST 12/31/2011
WAREHOUSEW151208
MAINTENANCE SHOP EST 12/31/2011
WAREHOUSEW141209
MAINTENANCE SHOP EST 12/31/2011
WAREHOUSEW10
VOCATIONAL CLASSROOM EST 12/31/2011
Page 55 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1217
WAREHOUSE W91218
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W71219
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W81220
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W61221
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSE W51222
VOCATIONAL CLASSROOM EST 12/31/2011
WAREHOUSEW131223
STORAGE E1003 EST 12/31/2011
WAREHOUSEW281226
EQUIPMENT STORAGE E1004 EST 12/31/2011
C AREA I341228
MECHANICAL ROOM C1024 EST 12/31/2011
C AREA I241229
MECHANICAL ROOM C1024 EST 12/31/2011
Manual Fire Box
B AREA CC81076
CORRIDOR B1060 EST 12/30/2011
C AREA I351192
ELECTRICAL C1023 EST 12/30/2011
WAREHOUSEW271193
WAREHOUSE E1010 EST 12/30/2011
WAREHOUSEW351210
WAREHOUSE E1010 EST 12/30/2011
WAREHOUSEW361215
VESTIBULE E1001 EST 12/30/2011
WAREHOUSEW111216
VOCATIONAL CLASSROOM EST 12/30/2011
WAREHOUSEW121224
STORAGE E1003 EST 12/30/2011
WAREHOUSEW171225
EQUIPMENT STORAGE E1004 EST 12/30/2011
C AREA I331227
MECHANICAL ROOM C1024 EST 12/30/2011
A AREA B21291306
VESTIBULE A1001 EST 12/30/2011
B AREA CC151311
CORRIDOR B1060 EST 12/30/2011
B AREA CC271328
STAFF BREAK B1095 EST 12/30/2011
D AREA CC701350
PUBLIC LOBBY D1117 EST 12/30/2011
A AREA B21241471
WAITING A1037 EST 12/30/2011
A AREA B2761472
DAYROOM OFFICER A1026 EST 12/30/2011
B AREA 1C701015
DAYROOM OFFICER B1057 EST 12/31/2011
B AREA 1C231026
CONC SLAB BES2 EST 12/31/2011
B AREA 1C20 DAYROOM OFFICER B1028 EST 12/31/2011
Page 56 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1033
B AREA 1C1061034
SEARCH B1027 EST 12/31/2011
A AREA B2241104
CONC SLAB EXIT EST 12/31/2011
A AREA B2271105
DAYROOM OFFICER A1086 EST 12/31/2011
A AREA B2401106
CONC SLAB AES1 EST 12/31/2011
A AREA B2371107
DAYROOM OFFICER A1044 EST 12/31/2011
D AREA CC841244
CORRIDOR D1038 EST 12/31/2011
1ST C AREACORRIDOROUTSIDE .11245
DINING HALL EST 12/31/2011
1ST C AREACORRIDOROUTSIDE .21246
DINING HALL EST 12/31/2011
D AREA CC1871262
RELEASE LOBBY EST 12/31/2011
D AREA CC1681269
CORRIDOR D1077 EST 12/31/2011
C AREA 1STCORRIDOR1276
OUTSIDE DINING HALL EST 12/31/2011
D AREA CC1261283
CORRIDOR D1047 EST 12/31/2011
C AREA I931296
CORRIDOR C1064 EST 12/31/2011
C AREA I741302
CORRIDOR C1049 EST 12/31/2011
D AREA CC771312
VISITOR WAITING D1098 EST 12/31/2011
C AREA I701408
OFFICER STATION C1030 EST 12/31/2011
C AREA I211418
KITCHEN C1008 EST 12/31/2011
B AREA 1C1011462
WAITING B1051 EST 12/31/2011
A AREA B21051474
DAYROOM OFFICER A1061 EST 12/31/2011
Smoke Detector - Duct
A AREA B2561118
STORAGE A1029 EST 12/31/2011
A AREA B2171119
STORAGE A1090 EST 12/31/2011
A AREA B2851120
STORAGE A1056 EST 12/31/2011
A AREA B2811121
STORAGE A1055 EST 12/31/2011
B AREA 1C801122
SUPSTORAGE B1055 RTU7 EST 12/31/2011
B AREA 1C751123
CORRIDOR B1109 RTU6 EST 12/31/2011
B AREA 1C511124
STORAGE B1041 RTU10 EST 12/31/2011
B AREA 1C461125
CORRIDOR B1044 EST 12/31/2011
D AREA CC161 DAYROOM D1054 RETURN EST 12/31/2011
Page 57 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1449
D AREA CC1831450
DAYROOM D1069 RETURN EST 12/31/2011
D AREA CC1361451
DAYROOM D1039 RETURN EST 12/31/2011
C AREA I111.11452
DAYROOM C1071 EST 12/31/2011
C AREA I881453
DAYROOM A1056 SUPPLY EST 12/31/2011
C AREA I891454
DAYROOM C1056 RETURN EST 12/31/2011
C AREA I791455
DAYROOM C1041 EST 12/31/2011
B AREA 1C531456
STORAGE B1044 RTU10 EST 12/31/2011
B AREA 1C451457
CORRIDOR B1042 EST 12/31/2011
B AREA 1C821459
RET STORAGE B1055 RTU7 EST 12/31/2011
A AREA B2611467
STORAGE A1029 EST 12/31/2011
A AREA B2181468
STORAGE A1090 EST 12/31/2011
A AREA B21131470
WAITING A1037 EST 12/31/2011
C AREA I391475
LAUNDRY C1021 EST 12/31/2011
D AREA CC1021479
COMPUTER LAB D1027 RET EST 12/31/2011
D AREA CC1001480
COMPUTER LAB D1027 SUP EST 12/31/2011
D AREA S CC1991481
MULTIPURPOSE D1037 EST 12/31/2011
D AREA R CC2001482
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC51RET1483
SHIFT SUPERVISOR D1121 EST 12/31/2011
D AREA CC1601485
DAYROOM B1057 EST 12/31/2011
D AREA CC1821486
NEAR D 1075 SHOWER EST 12/31/2011
D AREA CC1351487
DAYROOM D1054 SUPPLY EST 12/31/2011
I781488
DAYROOM D1069 SUPPLY EST 12/31/2011
CC1071489
DAYROOM D1039 SUPPLY EST 12/31/2011
B21231490
DAYROOM C1041 EST 12/31/2011
CC209.11491
D1004 EST 12/31/2011
CC2091492
A1043 EST 12/31/2011
I1081493
A1043 EST 12/31/2011
CC1261494
A1017 EST 12/31/2011
Smoke Detector - General
B AREA 1C211024
DAYROOM MEZZ B1028 EST 12/30/2011
Page 58 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C221025
DAYROOM MEZZ B1028 EST 12/30/2011
B AREA 1C251027
DAYROOM MEZZ B1028 EST 12/30/2011
B AREA 1C241028
DAYROOM MEZZ B1028 EST 12/30/2011
B AREA 1C51045
DAYROOM MEZZ B1001 EST 12/30/2011
B AREA 1C41046
DAYROOM MEZZ B1001 EST 12/30/2011
B AREA 1C131047
DAYROOM B1001 EST 12/30/2011
B AREA 1C151048
DAYROOM B1001 EST 12/30/2011
B AREA 1C161049
DAYROOM B1001 EST 12/30/2011
B AREA 1C181050
DAYROOM B1001 EST 12/30/2011
B AREA 1C1151073
EQUIPMENT ROOM B1104 EST 12/30/2011
B AREA 1C721075
MULTIPURPOSE B1056 EST 12/30/2011
A AREA B2661078
EQUIPMENT ROOM A1016 EST 12/30/2011
A AREA B21101079
CORRIDOR A1015 EST 12/30/2011
A AREA B21111080
CORRIDOR A1015 EST 12/30/2011
A AREA B21061081
EQUIPMENT ROOM A1042 EST 12/30/2011
A AREA B21181082
WAITING A1037 EST 12/30/2011
A AREA B21121083
COUNSELOR A1031 EST 12/30/2011
A AREA B21161084
SUPPLY ROOM A1034 EST 12/30/2011
A AREA B21251085
MULTIPURPOSE A1040 EST 12/30/2011
A AREA B21201086
CORRIDOR A1015 EST 12/30/2011
A AREA B21211087
CORRIDOR A1015 EST 12/30/2011
A AREA B21221088
SEARCH A1043 EST 12/30/2011
A AREA B21521089
SEARCH A1043 EST 12/30/2011
A AREA B21231090
SEARCH A1043 EST 12/30/2011
A AREA B2521092
DAYROOM A1044 EST 12/30/2011
A AREA B2421095
DAYROOM A1044 EST 12/30/2011
A AREA B2391097
DAYROOM MEZZ A1044 EST 12/30/2011
A AREA B2381098
DAYROOM MEZZ A1044 EST 12/30/2011
A AREA B2471099
DAYROOM A1044 EST 12/30/2011
A AREA B2481100
DAYROOM A1044 EST 12/30/2011
A AREA B2331102
DAYROOM A1086 EST 12/30/2011
Page 59 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
A AREA B2341103
DAYROOM A1086 EST 12/30/2011
A AREA B2261112
DAYROOM A1086 EST 12/30/2011
A AREA B2251113
DAYROOM A1086 EST 12/30/2011
A AREA B2231114
DAYROOM A1086 EST 12/30/2011
A AREA B2221115
DAYROOM A1086 EST 12/30/2011
A AREA B2301116
DAYROOM A1086 EST 12/30/2011
A AREA B2321117
DAYROOM A1086 EST 12/30/2011
C AREA I361191
ELECTRICAL C1023 EST 12/30/2011
WAREHOUSEW28.11197
ELECTRICAL ROOM E1011 EST 12/30/2011
WAREHOUSEW291198
OFFICE E1013 EST 12/30/2011
WAREHOUSE W21211
CORRIDOR E1006 EST 12/30/2011
WAREHOUSE W31212
CORRIDOR E1006 EST 12/30/2011
WAREHOUSE W11213
OFFICE E1007 EST 12/30/2011
WAREHOUSE W41214
VESTIBULE E1001 EST 12/30/2011
D AREA CC45.11230
EQUIT D1119 EST 12/30/2011
A AREA B21041231
DAYROOM A1061 EST 12/30/2011
A AREA B21011232
DAYROOM A1061 EST 12/30/2011
A AREA B2971233
DAYROOM A1061 EST 12/30/2011
A AREA B2961234
DAYROOM A1061 EST 12/30/2011
A AREA B2941235
DAYROOM MEZZ A1061 EST 12/30/2011
A AREA B2911238
DAYROOM MEZZ A1061 EST 12/30/2011
A AREA B2991240
DAYROOM A1061 EST 12/30/2011
A AREA B21031243
DAYROOM A1061 EST 12/30/2011
D AREA CC871248
CORRIDOR D1038 EST 12/30/2011
D AREA CC881249
CORRIDOR D1038 EST 12/30/2011
D AREA CC891250
CORRIDOR D1038 EST 12/30/2011
D AREA CC911252
CORRIDOR D1038 EST 12/30/2011
D AREA CC1431280
DAYROOM D1039 EST 12/30/2011
D AREA CC1291284
CORRIDOR D1047 EST 12/30/2011
C AREA I1021286
DAYROOM C1071 EST 12/30/2011
Page 60 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I1141287
CORRIDOR C1079 EST 12/30/2011
C AREA I1101288
CORRIDOR C1079 EST 12/30/2011
C AREA I1091289
CORRIDOR C1079 EST 12/30/2011
C AREA I1081290
CORRIDOR C1079 EST 12/30/2011
C AREA I1071291
CORRIDOR C1079 EST 12/30/2011
C AREA I1061292
CORRIDOR C1079 EST 12/30/2011
A AREA B251305
VESTIBULE A1001 EST 12/30/2011
A AREA B231307
HOLDING CELL A1004 EST 12/30/2011
A AREA B221308
HOLDING CELL A1005 EST 12/30/2011
A AREA B211309
HOLDING CELL A1006 EST 12/30/2011
A AREA B2121310
CORRIDOR A1012 EST 12/30/2011
B AREA CC441319
INMATE RECORDS D1083 EST 12/30/2011
B AREA CC311323
CORRIDOR OF ADMIN B1080 EST 12/30/2011
B AREA CC361325
STORAGE B1090 EST 12/30/2011
B AREA CC251326
CORRIDOR B1094 EST 12/30/2011
B AREA CC281327
STAFF BREAK B1095 EST 12/30/2011
B AREA CC241329
TRAINING B1096 EST 12/30/2011
B AREA CC261330
TRAINING B1096 EST 12/30/2011
B AREA CC231331
CORRIDOR B1094 EST 12/30/2011
B AREA CC201332
FITNESS B1099 EST 12/30/2011
B AREA CC171333
M LOCKER B1106 EST 12/30/2011
B AREA CC191334
CORRIDOR B1094 EST 12/30/2011
B AREA CC161335
CORRIDOR B1094 EST 12/30/2011
B AREA CC371336
UNIFORM STORAGE B1091 EST 12/30/2011
D AREA CC631337
MAIN VESTIBULE B1069 EST 12/30/2011
D AREA CC621338
MAIN VESTIBULE B1069 EST 12/30/2011
D AREA CC751346
VISITOR WAITING D1098 EST 12/30/2011
D AREA CC781347
VISITOR WAITING D1098 EST 12/30/2011
D AREA CC731348
STORAGE D1111 EST 12/30/2011
D AREA CC761349
VESTIBULE D1096 EST 12/30/2011
D AREA CC741351
CORRIDOR D1110 EST 12/30/2011
Page 61 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
D AREA CC821352
OFFICE D1118 EST 12/30/2011
D AREA CC451353
EQUIPMENT D1119 EST 12/30/2011
D AREA CC591355
MASTER CONTROL D1129 EST 12/30/2011
D AREA CC531356
SHIFT SUPERVISOR D1121 EST 12/30/2011
D AREA CC551357
STORAGE D1122 EST 12/30/2011
D AREA CC561358
CORRIDOR D1125 EST 12/30/2011
D AREA CC611359
MAIL ROOM D1126 EST 12/30/2011
B AREA CC141360
CORRIDOR B1060 EST 12/30/2011
B AREA CC131361
CORRIDOR B1060 EST 12/30/2011
B AREA CC121362
CORRIDOR B1060 EST 12/30/2011
B AREA CC111363
CORRIDOR B1060 EST 12/30/2011
B AREA CC101364
CORRIDOR B1060 EST 12/30/2011
D AREA CC1131373
ELECTRICAL ROOM D1008 EST 12/30/2011
C AREA I581374
VESTIBULE C1026 EST 12/30/2011
D AREA CC1111380
STORAGE D1005 EST 12/30/2011
A AREA CC41382
CORRIDOR A1068 EST 12/30/2011
A AREA CC31383
CORRIDOR A1068 EST 12/30/2011
A AREA CC21384
CORRIDOR A1068 EST 12/30/2011
D AREA CC2071387
STORAGE D1035 EST 12/30/2011
D AREA CC991390
COMPUTER LAB D1027 EST 12/30/2011
D AREA CC1031391
BARBER D1026 EST 12/30/2011
D AREA CC2031393
LIBRARY D1034 EST 12/30/2011
D AREA CC2041394
LIBRARY D1034 EST 12/30/2011
C AREA I1211401
CORRIDOR C1025 EST 12/30/2011
C AREA I611409
DAYROOM MEZZ C1030 EST 12/30/2011
C AREA I691410
DAYROOM MEZZ C1030 EST 12/30/2011
C AREA I601411
DAYROOM MEZZ C1030 EST 12/30/2011
A AREA CC2091420
VESITBULE A1017 EST 12/30/2011
A AREA CC11421
VESTIBULE A1017 EST 12/30/2011
A AREA B2101422
PROPERTY STORAGE A1014 EST 12/30/2011
A AREA B271423
ISSUE A1073 EST 12/30/2011
Page 62 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
A AREA B2131424
SEARCH AREA A1008 EST 12/30/2011
A AREA B261425
INMATE WAITING A1002 EST 12/30/2011
A AREA B241426
INTERVIEW A1003 EST 12/30/2011
A AREA B2751427
DAYROOM A1026 EST 12/30/2011
A AREA B2671428
DAYROOM A1026 EST 12/30/2011
A AREA B2681429
DAYROOM A1026 EST 12/30/2011
A AREA B2721430
DAYROOM A1026 EST 12/30/2011
A AREA B2621431
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2631432
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2641433
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2651434
DAYROOM MEZZ A1026 EST 12/30/2011
A AREA B2731435
DAYROOM A1026 EST 12/30/2011
A AREA B2741436
DAYROOM A1026 EST 12/30/2011
A AREA B2711437
DAYROOM A1026 EST 12/30/2011
A AREA B2701438
DAYROOM A1026 EST 12/30/2011
A AREA B2691439
DAYROOM A1026 EST 12/30/2011
A AREA B2161440
CORRIDOR A1074 EST 12/30/2011
A AREA B2781444
CORRIDOR A1057 EST 12/30/2011
A AREA B2791445
CORRIDOR A1057 EST 12/30/2011
A AREA B2831448
STORAGE A1055 EST 12/30/2011
B AREA RET1C761458
CORRIDOR B1109 RTU6 EST 12/30/2011
B AREA 1C381460
COUNSELOR B1049 EST 12/30/2011
B AREA 1C421463
SUPPLY ROOM B1046 EST 12/30/2011
B AREA 1C291465
COUNSELOR B1050 EST 12/30/2011
B AREA 1C901466
EQUPIMENT B1024 EST 12/30/2011
A AREA B21191469
COUNSELOR A1036 EST 12/30/2011
A AREA 1STDAYROOM A10611473
CORRIDOR A1057 B288 EST 12/30/2011
C AREA I61476
IT TOILET C1013 EST 12/30/2011
C AREA I51477
ST TOILET C1015 EST 12/30/2011
A AREA B2951478
STORAGE A1070 EST 12/30/2011
Page 63 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C591484
MAIN PANEL EST 12/30/2011
D AREA CC691495
C1079 EST 12/30/2011
D AREA CC711496
D1047 EST 12/30/2011
C AREA I831497
EST 12/30/2011
C AREA I951499
STORAGE D1113 EST 12/30/2011
D AREA CC1371501
EQUIP. ROOM C1057 EST 12/30/2011
B AREA CC411502
CORRIDOR C1064 EST 12/30/2011
B AREA CC431503
CORRIDOR C1064 EST 12/30/2011
D AREA CC681504
DAYROOM D1039 EST 12/30/2011
C AREA I471505
ADMIN. ASSISTS. B1080 EST 12/30/2011
C AREA I481506
CORRIDOR B1079 EST 12/30/2011
D AREA CC1141510
DAYROOM A1044 EST 12/30/2011
D AREA CC1171511
CORRIDOR C1025 EST 12/30/2011
D AREA CC1161512
NURSE STATION D1004 EST 12/30/2011
B AREA 1C301513
EMER. STORAGE D1007 EST 12/30/2011
C AREA I1111514
SOILED LINEN D1010 EST 12/30/2011
D AREA CC501515
CLEAN LINEN D1009 EST 12/30/2011
A AREA B21171516
DAYROOM B1028 EST 12/30/2011
B AREA 1C1121001
CORRIDOR B1026 EST 12/31/2011
B AREA 1C601002
STORAGE B 1066 EST 12/31/2011
B AREA 1C691003
DAYROOM B1057 EST 12/31/2011
B AREA 1C611004
DAYROOM B1057 EST 12/31/2011
B AREA 1C621005
DAYROOM B1057 EST 12/31/2011
B AREA 1C641006
DAYROOM B1057 EST 12/31/2011
B AREA 1C581007
DAYROOM MEZZ B1057 EST 12/31/2011
B AREA 1C571008
DAYROOM MEZZ B1057 EST 12/31/2011
B AREA 1C561009
DAYROOM MEZZ B1057 EST 12/31/2011
B AREA 1C631010
DAYROOM B1057 EST 12/31/2011
B AREA 1C651011
DAYROOM B1057 EST 12/31/2011
B AREA 1C661012
DAYROOM B1057 EST 12/31/2011
B AREA 1C671013
DAYROOM B1057 EST 12/31/2011
Page 64 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C681014
STORAGE B2035 EST 12/31/2011
B AREA 1C491016
CORRIDOR B1044 EST 12/31/2011
B AREA 1C521017
STORAGE B1041 EST 12/31/2011
B AREA 1C431018
CORRIDOR B1044 EST 12/31/2011
B AREA 1C481019
STORAGE B1042 EST 12/31/2011
B AREA 1C471020
STORAGE B1043 EST 12/31/2011
B AREA 1C371021
DAYROOM B1028 EST 12/31/2011
B AREA 1C361022
DAYROOM B1028 EST 12/31/2011
B AREA 1C341023
DAYROOM B1028 EST 12/31/2011
B AREA 1C351029
DAYROOM B1028 EST 12/31/2011
B AREA 1C331030
DAYROOM B1028 EST 12/31/2011
B AREA 1C321031
DAYROOM B1028 EST 12/31/2011
B AREA 1C311032
DAYROOM B1028 EST 12/31/2011
B AREA 1C1301035
SEARCH AREA B1027 EST 12/31/2011
B AREA 1C1051036
SEARCH AREA B1027 EST 12/31/2011
B AREA 1C1041037
CORRIDOR B1110 EST 12/31/2011
B AREA 1C1031038
CORRIDOR B1051 EST 12/31/2011
B AREA 1C111039
DAYROOM B1001 EST 12/31/2011
B AREA 1C121040
DAYROOM B1001 EST 12/31/2011
B AREA 1C141041
DAYROOM B1001 EST 12/31/2011
B AREA 1C191042
DAYROOM B1001 EST 12/31/2011
B AREA 1C91043
DAYROOM MEZZ B1001 EST 12/31/2011
B AREA 1C71044
DAYROOM MEZZ B1001 EST 12/31/2011
B AREA 1C101051
DAYROOM B1001 EST 12/31/2011
B AREA 1C731052
CORRIDOR B1109 EST 12/31/2011
B AREA 1C771053
STORAGE B1053 EST 12/31/2011
B AREA 1C781054
ELECTRICAL B1054 EST 12/31/2011
B AREA 1C791055
CORRIDOR B1109 EST 12/31/2011
B AREA 1C811056
STORAGE B1055 EST 12/31/2011
B AREA 1C911057
DAYROOM B1015 EST 12/31/2011
B AREA 1C991058
DAYROOM B1015 EST 12/31/2011
Page 65 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
B AREA 1C941059
DAYROOM B1015 EST 12/31/2011
B AREA 1C921060
DAYROOM B1015 EST 12/31/2011
B AREA 1C861061
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C871062
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C881063
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C891064
DAYROOM MEZZ B1015 EST 12/31/2011
B AREA 1C981065
DAYROOM B1015 EST 12/31/2011
B AREA 1C961066
DAYROOM B1015 EST 12/31/2011
B AREA 1C951067
DAYROOM B1015 EST 12/31/2011
B AREA 1C931068
DAYROOM B1015 EST 12/31/2011
B AREA 1C1001069
DAYROOM OFFICER B1015 EST 12/31/2011
B AREA 1C971070
STORAGE B2034 EST 12/31/2011
B AREA 1C1111071
CORRIDOR B1026 EST 12/31/2011
B AREA 1C1101072
CORRIDOR B1026 EST 12/31/2011
B AREA 1C1021074
WAITING B1051 EST 12/31/2011
A AREA B21091077
EQUIPMENT ROOM A1042 EST 12/31/2011
A AREA B2531091
DAYROOM A1044 EST 12/31/2011
A AREA B2461093
DAYROOM A1044 EST 12/31/2011
A AREA B2491094
DAYROOM A1044 EST 12/31/2011
A AREA B2411096
DAYROOM A1044 EST 12/31/2011
A AREA B2501101
DAYROOM A1044 EST 12/31/2011
A AREA B2281108
DAYROOM A1086 EST 12/31/2011
A AREA B2351109
DAYROOM A1086 EST 12/31/2011
A AREA B2291110
DAYROOM A1086 EST 12/31/2011
A AREA B2311111
DAYROOM A1086 EST 12/31/2011
C AREA I141162
KITCHEN C1008 EST 12/31/2011
A AREA B2931236
DAYROOM MEZZ A1061 EST 12/31/2011
A AREA B2921237
DAYROOM MEZZ A1061 EST 12/31/2011
A AREA B2981239
DAYROOM A1061 EST 12/31/2011
A AREA B21001241
DAYROOM A1061 EST 12/31/2011
A AREA B21021242
DAYROOM A1061 EST 12/31/2011
Page 66 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA CCADD1247
CORRIDOR C1092 EST 12/31/2011
D AREA CC901251
CORRIDOR D1038 EST 12/31/2011
D AREA CC921253
CORRIDOR D1038 EST 12/31/2011
D AREA CC931254
CORRIDOR D1038 EST 12/31/2011
D AREA CC941255
CORRIDOR D1038 EST 12/31/2011
D AREA CC951256
CORRIDOR D1038 EST 12/31/2011
D AREA CC961257
CORRIDOR D1038 EST 12/31/2011
D AREA CC971258
CORRIDOR D1038 EST 12/31/2011
D AREA CC981259
CORRIDOR D1038 EST 12/31/2011
D AREA CC1851260
INTERVIEW ROOM D1085 EST 12/31/2011
D AREA CC1861261
RELEASE LOBBY D1085 EST 12/31/2011
D AREA CC1881263
CORRIDOR D1084 EST 12/31/2011
D AREA CC1891264
CORRIDOR D1084 EST 12/31/2011
D AREA CC1801265
DAYROOM D1069 SUP EST 12/31/2011
D AREA CC1841266
DAYROOM D1069 EST 12/31/2011
D AREA CC1741267
CORRIDOR D1077 EST 12/31/2011
D AREA CC1701268
CORRIDOR D1077 EST 12/31/2011
D AREA CC1711270
CORRIDOR D1077 EST 12/31/2011
D AREA CC1731271
CORRIDOR D1077 EST 12/31/2011
D AREA CC1581272
DAYROOM D1054 EST 12/31/2011
D AREA CC1641273
DAYROOM D1054 EST 12/31/2011
D AREA CC1521274
CORRIDOR D1062 EST 12/31/2011
D AREA CC1501275
CORRIDOR D1062 EST 12/31/2011
D AREA CC1491277
CORRIDOR D1062 EST 12/31/2011
D AREA CC1531278
CORRIDOR D1062 EST 12/31/2011
D AREA CC1571279
EQUIPMENT D1040 EST 12/31/2011
D AREA CC1331281
CORRIDOR D1047 EST 12/31/2011
D AREA CC1281282
CORRIDOR D1047 EST 12/31/2011
D AREA CC1311285
CORRIDOR D1047 EST 12/31/2011
C AREA I961293
DAYROOM C1056 EST 12/31/2011
C AREA I871294
DAYROOM C1056 EST 12/31/2011
Page 67 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I911295
CORRIDOR C1064 EST 12/31/2011
C AREA I941297
CORRIDOR C1064 EST 12/31/2011
C AREA I801298
DAYROOM C1041 EST 12/31/2011
C AREA I861299
DAYROOM C1041 EST 12/31/2011
C AREA I721300
CORRIDOR C1049 EST 12/31/2011
C AREA I731301
CORRIDOR C1049 EST 12/31/2011
C AREA I751303
CORRIDOR C1049 EST 12/31/2011
C AREA I761304
CORRIDOR C1049 EST 12/31/2011
D AREA CC831313
PUBLIC LOBBY D1117 EST 12/31/2011
D AREA CC671314
WAITING B1070 EST 12/31/2011
D AREA CC661315
WAITING B1070 EST 12/31/2011
D AREA CC651316
WAITING B1070 EST 12/31/2011
D AREA CC431317
CORRIDOR B1079 EST 12/31/2011
B AREA CC2801318
ADMIN ASSISTANTS B1080 EST 12/31/2011
B AREA CC421320
MEETING ROOM B1077 EST 12/31/2011
B AREA CC401321
WORK ROOM B1086 EST 12/31/2011
B AREA CC391322
SUPPLY ROOM B1085 EST 12/31/2011
B AREA CC341324
BREAK ROOM B1089 EST 12/31/2011
D AREA CC541339
SEARCH AREA D1106 EST 12/31/2011
D AREA CC481340
VISITING ROOM D1105 EST 12/31/2011
D AREA CC491341
VISITING ROOM D1105 EST 12/31/2011
D AREA CC461342
VISITING ROOM D1105 EST 12/31/2011
D AREA CC471343
VISITING ROOM D1105 EST 12/31/2011
D AREA CC791344
STORAGE D1101 EST 12/31/2011
D AREA CC801345
VSP ROOM D1100 EST 12/31/2011
D AREA 1STHALL1354
OUSIDE ROOM D1120 EST 12/31/2011
B AREA CC91365
CORRIDOR B1060 EST 12/31/2011
B AREA CC71366
CORRIDOR B1060 EST 12/31/2011
B AREA CC61367
CORRIDOR B1060 EST 12/31/2011
B AREA CC51368
CORRIDOR B1060 EST 12/31/2011
D AREA CC120 ISOLATION D1018 EST 12/31/2011
Page 68 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
1369
D AREA CC1181370
ISOLATION D1020 EST 12/31/2011
D AREA CC2171371
CORRIDOR D1011 EST 12/31/2011
C AREA I1191372
CORRIDOR C1025 EST 12/31/2011
D AREA CC1041375
TREATMENT D1013 EST 12/31/2011
D AREA CC1081376
CORRIDOR D1011 EST 12/31/2011
D AREA CC1091377
LAB D1014 EST 12/31/2011
D AREA CC1101378
DENTAL SUITE D1015 EST 12/31/2011
D AREA CC1151379
CORRIDOR D1011 EST 12/31/2011
D AREA CC1191381
ISOLATION VESTIBULE EST 12/31/2011
D AREA CC2051385
CLASSROOM D1031 EST 12/31/2011
D AREA CC2061386
CLASSROOM D1031 EST 12/31/2011
D AREA CC1221388
GED D1028 EST 12/31/2011
D AREA CC961389
CORRIDOR D1030 EST 12/31/2011
D AREA CC951392
CORRIDOR D1030 EST 12/31/2011
D AREA CC941395
CORRIDOR D1030 EST 12/31/2011
D AREA CC1971396
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2021397
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2011398
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2161399
MULTIPURPOSE D1037 EST 12/31/2011
D AREA CC2081400
STORAGE D1036 EST 12/31/2011
D AREA CC1061402
WAITING D1001 EST 12/31/2011
D AREA CC1051403
EXAM D1012 EST 12/31/2011
C AREA I631404
DAYROOM C1030 EST 12/31/2011
C AREA I671405
DAYROOM C1030 EST 12/31/2011
C AREA I681406
DAYROOM C1030 EST 12/31/2011
C AREA I621407
DAYROOM C1030 EST 12/31/2011
C AREA I571412
STAFF DINING C1005 EST 12/31/2011
C AREA I561413
STAFF DINING C1005 EST 12/31/2011
C AREA I501414
DIVERSION DINING C1002 EST 12/31/2011
C AREA I491415
DIVERSION DINING C1002 EST 12/31/2011
Page 69 of 70
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
C AREA I521416
DIVERSION DINING C1002 EST 12/31/2011
C AREA I511417
DIVERSION DINING C1002 EST 12/31/2011
C AREA I461419
JANITOR C1017 EST 12/31/2011
A AREA B2571441
STORAGE A1029 EST 12/31/2011
A AREA B2141442
ELECTRICAL A1030 EST 12/31/2011
A AREA B2151443
STORAGE A1090 EST 12/31/2011
A AREA 1STDAYROOM A10611446
STORAGE A1058 EST 12/31/2011
A AREA B2841447
ELECTRICAL ROOM A1056 EST 12/31/2011
B AREA RET1C1091461
WAITING B1051 RTU8 EST 12/31/2011
B AREASUP1C1081464
WAITING B1051 RTU8 EST 12/31/2011
C AREA I991498
VEST. ROOM D1114 EST 12/31/2011
C AREA I921500
STORAGE C1042 EST 12/31/2011
A AREA B2511507
ELECT. ROOM D1115 EST 12/31/2011
C AREA I1201508
STORAGE C1017 EST 12/31/2011
D AREA CC1071509
CORRIDOR C1016 EST 12/31/2011
Alarm Notification Appliance
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Audible And Visible
1st Floor Notification EST 2/29/2016
Page 70 of 70
Entec Systems Inc.
Inspection and Testing CertificatePresented To
Gwinnett County-Police SemiFor
Correctional Institute750 Hi Hope Road
Lawrenceville GA 30043USA
This site has been inspected and tested in compliance with applicable standards.
CompletedWednesday, September 14, 2016
Test Session: 9/14/16 Semi Annual Correctional Complex
ACCEPTED BY TESTED BYJeff Anderson Jared CoileGwinnett County-Police Semi Entec Systems Inc.75 Langely DriveLawrenceville GA 30043USA
450 Satellite Blvd. NE, Suite PSuwanee GA 30024USA
Entec Systems Inc.
Inspection Summary
Building InformationPROPERTY Correctional InstituteADDRESS 750 Hi Hope RoadCITY/STATE/ZIP Lawrenceville, GA 30043COUNTRY USA
CONTACT Jeff AndersonPHONEMOBILEEMAIL
Inspector InformationCOMPANY Entec Systems Inc.ADDRESS 450 Satellite Blvd. NE, Suite PCITY/STATE/ZIP Suwanee, GA 30024COUNTRY USA
CONTACT Jared CoilePHONEMOBILE (678) 858-4950EMAIL [email protected]
NAME INITIALS QUALIFICATION AND PROFICIENCIESJared Coile JC
Testing SummaryEQUIPMENT TYPE TOTAL TESTED PASSED FAILED
Fire Control Panel 1 1(100 %) 1(100 %) 0(0 %)Initiating Device 42 42(100 %) 42(100 %) 0(0 %)Alarm Notification Appliance 1 1(100 %) 1(100 %) 0(0 %)
CertificationThe equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspectioncompleted on Wednesday, September 14, 2016
ACCEPTED BY9/14/2016Jeff AndersonBuilding RepresentativeGwinnett County-Police Semi
TESTED BY9/14/2016Jared CoileTechnicianEntec Systems Inc.
Page 2 of 11
Entec Systems Inc.
System Details
Control Units
MANUFACTURER EdwardsMODEL EST3SERIAL NUMBERINSTALL DATE 9/30/2015
DESCRIPTION Main FACPS/W VERSIONLAST UPDATES/W LOCATION
Monitoring Information
Page 3 of 11
Entec Systems Inc.
Open Corrective Action & Solution SummaryThe following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor NotificationCreated By: Jared CoileCreation Date: 9/14/2016Corrective Action: L Dorm the horn strobe over the pull station did not work.Proposed Solution: Troubleshoot/Replace horn strobe.
Page 4 of 11
Entec Systems Inc.
Resolved Corrective Action & Solution SummaryThe following 1 corrective action(s) were resolved during the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Audible And Visible 1st Floor NotificationCreated By: Jared CoileCreation Date: 10/1/2015
Corrective Action: A Dorm had no audio or visual notification during sound test. I dorm, J dorm, and Kdorm had no strobes during sound test, audio only.
Resolution Issues were resolved.Resolved By: Jared CoileResolved On: 9/14/2016
Page 5 of 11
Entec Systems Inc.
Testing Details
Fire Control Panel
PassedEQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel Main FACP Manual 9/14/2016 2:24 PM
Comment: Replace pull station cover in L Dorm.I I Manufacturer EdwardsI I Model EST3I I Serial Number II I Visual Inspection TrueI I Functional Inspection TrueI I Ground Fault TrueI I Disconnect Switches TrueI I
Initiating Device
PassedEQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box A AREA B2105 Dayroom Officer A1061 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B2124 Waiting A1037 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B2129 Vestibule A1001 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B224 Concs Lab Exit Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B227 Dayroom Officer A1086 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B237 Dayroom Officer A1044 Manual 9/14/2016 2:18 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B240 Concs Lab AES1 Manual 9/14/2016 2:19 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box A AREA B276 Dayroom Officer A1026 Manual 9/14/2016 2:19 PM
Page 6 of 11
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
I I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C10 Dayroom B1001 Manual 9/14/2016 2:20 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C100 Dayroom Officer B1015 Manual 9/14/2016 2:20 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C101 Waiting B1051 Manual 9/14/2016 2:20 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C106 Search B1027 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C20 Dayroom Officer B1028 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA 1C70 Dayroom Officer B1057 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA CC15 Corridor B1060 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA CC27 Staff Break B1095 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B AREA CC8 Corridor B1060 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box B2123 AA1043 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA 1stCORRIDOR Outside Dining Hall Manual 9/14/2016 2:21 PM
I I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I21 Kitchen C1008 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Page 7 of 11
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box C AREA I33 Mechanical Room C1024 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I35 Electrical Room C1023 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I70 Officer Station C1030 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I74 Corridor C1049 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box C AREA I93 Corridor C1064 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC107 D1004 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC126 D1047 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC209 A1017 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box CC209 A1043 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC107 Nurse Station D1004 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC168 Corridor D1077 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC187 Release Lobby Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC70 Public Lobby Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Page 8 of 11
Entec Systems Inc.
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Manual Fire Box D AREA CC77 Visitor Waiting D1098 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box D AREA CC84 Corridor D1038 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box I108 C1079 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W11 Vocational Classroom Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W12 Storage E1003 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W17 Equipment Room E1004 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W27 Warehouse E1010 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Manual Fire Box Warehouse W35 Warehouse E1010 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection TrueI I Alarm Verification Participation False
Manual Fire Box Warehouse W36 Vestibule E1001 Manual 9/14/2016 2:21 PMI I Manufacturer EdwardsI I Visual Inspection TrueI I Functional Inspection True
Alarm Notification Appliance
PassedEQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Audible And Visible 1st Floor Notification Manual 9/14/2016 2:23 PMI I Visual Inspection TrueI I Functional Inspection True
Page 9 of 11
Entec Systems Inc.
Device/Equipment Details
Fire Control PanelADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Fire Alarm PanelMain FACP Edwards EST3 9/30/2015
Initiating DeviceADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Manual Fire BoxA AREA B2105 Dayroom Officer A1061 Edwards 9/30/2015A AREA B2124 Waiting A1037 Edwards 9/30/2015A AREA B2129 Vestibule A1001 Edwards 9/30/2015A AREA B224 Concs Lab Exit Edwards 9/30/2015A AREA B227 Dayroom Officer A1086 Edwards 9/30/2015A AREA B237 Dayroom Officer A1044 Edwards 9/30/2015A AREA B240 Concs Lab AES1 Edwards 9/30/2015A AREA B276 Dayroom Officer A1026 Edwards 9/30/2015B AREA 1C10 Dayroom B1001 Edwards 9/30/2015B AREA 1C100 Dayroom Officer B1015 Edwards 9/30/2015B AREA 1C101 Waiting B1051 Edwards 9/30/2015B AREA 1C106 Search B1027 Edwards 9/30/2015B AREA 1C20 Dayroom Officer B1028 Edwards 9/30/2015B AREA 1C70 Dayroom Officer B1057 Edwards 9/30/2015B AREA CC15 Corridor B1060 Edwards 9/30/2015B AREA CC27 Staff Break B1095 Edwards 9/30/2015B AREA CC8 Corridor B1060 Edwards 9/30/2015B2123 AA1043 Edwards 9/30/2015C AREA 1stCORRIDOR Outside Dining Hall Edwards 9/30/2015
C AREA I21 Kitchen C1008 Edwards 9/30/2015C AREA I33 Mechanical Room C1024 Edwards 9/30/2015C AREA I35 Electrical Room C1023 Edwards 9/30/2015C AREA I70 Officer Station C1030 Edwards 9/30/2015C AREA I74 Corridor C1049 Edwards 9/30/2015C AREA I93 Corridor C1064 Edwards 9/30/2015CC107 D1004 Edwards 9/30/2015CC126 D1047 Edwards 9/30/2015CC209 A1017 Edwards 9/30/2015CC209 A1043 Edwards 9/30/2015D AREA CC107 Nurse Station D1004 Edwards 9/30/2015D AREA CC168 Corridor D1077 Edwards 9/30/2015D AREA CC187 Release Lobby Edwards 9/30/2015D AREA CC70 Public Lobby Edwards 9/30/2015D AREA CC77 Visitor Waiting D1098 Edwards 9/30/2015D AREA CC84 Corridor D1038 Edwards 9/30/2015I108 C1079 Edwards 9/30/2015Warehouse W11 Vocational Classroom Edwards 9/30/2015Warehouse W12 Storage E1003 Edwards 9/30/2015Warehouse W17 Equipment Room E1004 Edwards 9/30/2015
Page 10 of 11
Entec Systems Inc.
ADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Warehouse W27 Warehouse E1010 Edwards 9/30/2015Warehouse W35 Warehouse E1010 Edwards 9/30/2015Warehouse W36 Vestibule E1001 Edwards 9/30/2015
Alarm Notification ApplianceADDRESS DESCRIPTION Manufacturer Model SERIAL INSTALL DATE
Audible And Visible1st Floor Notification 9/30/2015
Page 11 of 11