November 2016 Welcome to our “e-REW Express. Electrical safety of hawker stalls has drawn public attention in recent years. In view of the increasing installation work for hawker stalls, we will address the supply requirements and common departures of weather- proof enclosure for hawker stalls in this issue of e-REW Express. We hope you will find the information useful and handy. If you have any suggestion, please send an email to us at [email protected] or contact our Customer Installation Section at 2887 3455 so that we can further improve our service. Supply Requirements and Common Departures of Customer Installations for Hawker Stalls Requirements of Mild Steel Weather-proof Enclosure for Single Phase Supply to Hawker Stall The customer should build the enclosure by the following instructions: 1. The enclosure should be supplied and mounted at the hawker stall by the customer. It is also owned and maintained by the customer. 2. The earthing installation of the enclosure is installed by the customer. 3. The cables between HK Electric service cutout and main switch must not exceed 3 metres. 4. The customer must gain the approval from HK Electric before making new design / arrangement of the enclosure for the hawker stall. 5. Double-lock arrangement should be provided if the enclosure is locked-up by customer. The diameter of locking hole shall not be less than 14mm.

Upload: others

Post on 28-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

November 2016

Welcome

to our “e-REW Express”. Electrical safety of hawker stalls has drawn

public attention in recent years. In view of the increasing installation

work for hawker stalls, we will address the supply requirements and common departures of weather-

proof enclosure for hawker stalls in this issue of “e-REW Express”.

We hope you will find the information useful and handy. If you have any suggestion, please send an

email to us at [email protected] or contact our Customer Installation Section at 2887 3455 so that we

can further improve our service.

Supply Requirements and Common Departures of

Customer Installations for Hawker Stalls

Requirements of Mild Steel Weather-proof Enclosure for

Single Phase Supply to Hawker Stall

The customer should build the enclosure by the following instructions:

1. The enclosure should be supplied and mounted at the hawker stall by the customer. It is also owned

and maintained by the customer.

2. The earthing installation of the enclosure is installed by the customer.

3. The cables between HK Electric service cutout and main switch must not exceed 3 metres.

4. The customer must gain the approval from HK Electric before making new design / arrangement of

the enclosure for the hawker stall.

5. Double-lock arrangement should be provided if the enclosure is locked-up by customer. The

diameter of locking hole shall not be less than 14mm.

Page 2: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

2

6. The enclosure should be installed at the hawker stall by the customer according to the attached

diagrams (option 1 or 2).

Page 3: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

3

Page 4: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

4

7. The size of the enclosure is shown below.

Page 5: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

5

Page 6: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

6

8. Customer may slightly enlarge the enclosure size to suit the different type of customer’s main

switch.

9. Two insert plates as shown below should be provided to facilitate cable installation by HK Electric.

Page 7: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

7

Common Departures

1. The space for HK Electric’s cutout and main installation is occupied by customer’s main switch.

2. No cable duct or cable ducts not up to HK Electric’s requirement.

Insufficient space for HK Electric’s equipment Sufficient space for HK Electric’s equipment

No cable duct Cable duct not straight

Page 8: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

8

Cable duct not up to bottom of enclosure

No yellow / black stripes

Cable duct not down

to pavement

Page 9: November 2016 Welcome - HK Electric · November 2016 . Welcome . to our “e-REW Express”. Electrical safety of hawker stalls has drawn public attention in recent years. In view

e-REW Express November 2016

9

3. No Insertion Plates

4. No double lock arrangement is provided.

No insertion plates, only two holes Two insertion plates