to our “e-REW Express”. Electrical safety of hawker stalls has drawn
public attention in recent years. In view of the increasing installation
work for hawker stalls, we will address the supply requirements and common departures of weather-
proof enclosure for hawker stalls in this issue of “e-REW Express”.
We hope you will find the information useful and handy. If you have any suggestion, please send an
email to us at [email protected] or contact our Customer Installation Section at 2887 3455 so that we
can further improve our service.
Supply Requirements and Common Departures of
Customer Installations for Hawker Stalls
Requirements of Mild Steel Weather-proof Enclosure for
Single Phase Supply to Hawker Stall
The customer should build the enclosure by the following instructions:
1. The enclosure should be supplied and mounted at the hawker stall by the customer. It is also owned
and maintained by the customer.
2. The earthing installation of the enclosure is installed by the customer.
3. The cables between HK Electric service cutout and main switch must not exceed 3 metres.
4. The customer must gain the approval from HK Electric before making new design / arrangement of
the enclosure for the hawker stall.
5. Double-lock arrangement should be provided if the enclosure is locked-up by customer. The
diameter of locking hole shall not be less than 14mm.
e-REW Express November 2016
2
6. The enclosure should be installed at the hawker stall by the customer according to the attached
diagrams (option 1 or 2).
e-REW Express November 2016
3
e-REW Express November 2016
4
7. The size of the enclosure is shown below.
e-REW Express November 2016
5
e-REW Express November 2016
6
8. Customer may slightly enlarge the enclosure size to suit the different type of customer’s main
switch.
9. Two insert plates as shown below should be provided to facilitate cable installation by HK Electric.
e-REW Express November 2016
7
Common Departures
1. The space for HK Electric’s cutout and main installation is occupied by customer’s main switch.
2. No cable duct or cable ducts not up to HK Electric’s requirement.
Insufficient space for HK Electric’s equipment Sufficient space for HK Electric’s equipment
No cable duct Cable duct not straight
e-REW Express November 2016
8
Cable duct not up to bottom of enclosure
No yellow / black stripes
Cable duct not down
to pavement
e-REW Express November 2016
9
3. No Insertion Plates
4. No double lock arrangement is provided.
No insertion plates, only two holes Two insertion plates