Table of Contents NORTH DAVIS SEWER DISTRICT Detail No. Detail Title Pages ND-01 NOTICE TO CONTRACTORS 1 ND-02 MANHOLE CONSTRUCTION NOTES AND INDEX 2 ND-03 MANHOLE DIAMETER REQUIREMENTS 2 ND-04 MANHOLE COLLAR AND GRADE RING 1 ND-10 STANDARD MANHOLE CONNECTION 2 ND-11 STANDARD MANHOLE DETAIL 54" DIA OR LARGER DISTRICT PIPE 2 ND-12 STANDARD MANHOLE DETAIL FRP DISTRICT PIPE 2 ND-13 STANDARD MANHOLE DETAIL FRP 2 ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETE 3 ND-15 STANDARD GREASE INTERCEPTOR 2 ND-16 NOT USED ND-17 PARTIAL MANHOLE REPLACEMENT 2 ND-18 MANHOLE CONNECTION TO CIPP LINED PIPE 1 ND-20 STANDARD SERVICE CONNECTION - CONCRETE PIPE 1 ND-21 STANDARD SERVICE CONNECTION - CIPP LINED PIPE 2 ND-22 STANDARD SERVICE CONNECTION - FRP FIBERGLASS PIPE 3 ND-23 STANDARD SERVICE CONNECTION - ABANDONMENT 1 ND-30 CRACKED PIPE REPAIR 1 ND-31 STRUCTURAL SUPPORT AT CROSSING 2 NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS

Upload: others

Post on 18-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

Table of Contents

NORTH DAVIS SEWER DISTRICT

Detail No. Detail Title

Pages

ND-01 NOTICE TO CONTRACTORS 1

ND-02 MANHOLE CONSTRUCTION NOTES AND INDEX 2

ND-03 MANHOLE DIAMETER REQUIREMENTS 2

ND-04 MANHOLE COLLAR AND GRADE RING 1

ND-10 STANDARD MANHOLE CONNECTION 2

ND-11 STANDARD MANHOLE DETAIL 54" DIA OR LARGER DISTRICT PIPE 2

ND-12 STANDARD MANHOLE DETAIL FRP DISTRICT PIPE 2

ND-13 STANDARD MANHOLE DETAIL FRP 2

ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETE 3

ND-15 STANDARD GREASE INTERCEPTOR 2

ND-16 NOT USED

ND-17 PARTIAL MANHOLE REPLACEMENT 2

ND-18 MANHOLE CONNECTION TO CIPP LINED PIPE 1

ND-20 STANDARD SERVICE CONNECTION - CONCRETE PIPE 1

ND-21 STANDARD SERVICE CONNECTION - CIPP LINED PIPE 2

ND-22 STANDARD SERVICE CONNECTION - FRP FIBERGLASS PIPE 3

ND-23 STANDARD SERVICE CONNECTION - ABANDONMENT 1

ND-30 CRACKED PIPE REPAIR 1

ND-31 STRUCTURAL SUPPORT AT CROSSING 2

NORTH DAVIS SEWER DISTRICT

STANDARD COLLECTION DETAILS

Page 2: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

ND-01 Notice to Contractors

NORTH DAVIS SEWER DISTRICT

1.a)

b)c)

2.a)

b)

c)

d)e)

3.a)b)

c)

4.a)

Effective immediately, the following will be accomplished by all contractors before starting any work or excavationaround or on any sewer line owned by the North Davis Sewer District

Hours of OperationThe District's working hours are 7:00 a.m. to 3:30 p.m., Monday through Friday. No sewer inspection willbe done on weekends, holidays or after 3:00 p.m.All inspections lasting after 3:30 p.m. will result in overtime being billed to the contractor.Multiple inspection visits required for work that is incomplete, not to District standards, or not ready for inspection will result in additional time being billed to the Contractor.

Sewer Lateral Connections:No work shall begin until the proper fees of $240.00 for connection and inspection, plus impact fees as calculated by the City or District (whichever may apply) are certified to the District as having been paid. The District only accepts cash or check.No work shall begin until the proper building permits and licenses have been obtained from the City, County, or Sewer District.Minimum notice of 48 hours shall be given to the District prior to any work commencing on or digging being done on District-owned lines.No digging or work shall be done on District-owned lines without the presence of a District Inspector.All sewer taps must be Core Drilled, INSERTA TEE, GPK PRODUCTS, INC, or equivalent. The Contractormust accurately size and procure sewer taps based on the existing District's sewer (material anddiameter) and the sewer lateral (material and diameter) to be connected.

Setting of Manholes on District-Owned LineManholes are required to be set for connecting lines 6 inches or larger.No manholes shall be set on District-owned lines without prior approval by the District. Contractors shallsubmit design drawings and manhole details of proposed manholes on District line for approval 14 daysprior to work commencing. Design drawings shall be submitted in PDF electronic format unless otherwiserequested by the District.After approval of drawings, a minimum of 48 hours notice shall be given to the District inspectors beforeany manhole is set on a District-owned line. The manhole must be set in the presence of a District inspector.

Flow Control and Bypass Pumping OperationsThe Contractor is solely responsible for bypass control and maintaining sanitary sewer flows within the sewer system during the Work in accordance with Utah State Code R317-801. Service shall be maintainedat all times throughout the duration of the project. The Contractor shall provide proof of flow calculationsproving adequacy of the system and the selected equipment if the District chooses to review.

Concrete BatchingReady mix concrete shall be provided in accordance with ASTM C94, Standard Specification for Ready-Mixed Concrete.The design water content of the mix (w/c ratio) shall not be exceeded. Addition of water, air entrainment orsuperplasticizer shall only be performed by the Supplier.Non-air entrained concrete shall be discharged ninety (90) minutes after batching. Air entrained concreteor concrete that includes silica fume shall be discharged within sixty (60) minutes of batching.Requests for longer batching times shall be submitted and accepted by the District prior to procurement ofconcrete by the Contractor.The District shall not be responsible for the cost of rejected batches exceeding time limitations, loss of air-entrainment or slump.

Warranty:Contractor shall guarantee work for a period of one year from the date of installation.

Failure of Contractors to comply with these guidelines could result in the Contractor being barred from working onDistrict lines. If there are any questions on a line being a District line, please contact the District office at801-825-0712.

5.a)

6.a)

b)

c)

d)

e)

Revision 3, Adopted 4/23/2019

Page 3: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

STANDARD MANHOLE ON EXISTING SEWER LINE

1. Manhole shall be constructed so as to prevent load to the existing pipe. The base of the manhole shallprovide a minimum of 9 inches of concrete beneath the existing pipe unless otherwise shown, placed on 12inches of one inch gravel bedding compacted to 95% density.

2. Manhole floor elevation shall be a minimum of 2 inches above top of pipe, have a 12:1 slope to the pipe, anda smooth finish.

3. Connection to manhole shall be made using a flexible, double banded, watertight connection per ASTMC923 and ASTM C1173. The flexible seals shall not exceed 50% of the manufacturer's recommendationsfor axial deflection for the installed condition. Acceptable products include Kor-n-seal, Fernco, MissionRubber Company, or approved equal. All hardware shall be 316 series stainless steel, unless otherwiseapproved.

4. Manhole shall be constructed using a pre-cast eccentric type sections and cast iron traffic type frame andcover marked "NORTH DAVIS SEWER". Section joints shall be sealed with rubber gaskets and shall bewatertight.

5. Wrap exterior joints. Wrap shall conform to ASTM C877 Type II or Type III. Press-seal Ez-Wrap, CretexWrap, Conseal 2/2 or approved equal.

6. Invert of branch line at manhole connection shall be adjusted to be at or near crown of existing main line.

7. Branch line channel to be formed with same slope, size, depth, and shape as pipe with smooth finish; it shallbe curved in direction of flow with uniform radius and minimize dropping and splashing of flow.

8. Cutting into existing line shall be made by smooth saw cuts.

9. Installing Contractor shall be responsible for proper slope and installation of connecting line.

10. Installing Contractor shall be responsible for proper backfilling, compacting, and pavement restoration.

11. Contractor shall notify District 48 hours before installation begins and a District inspector must be presentbefore installation takes place.

12. The Contractor shall test each manhole with either a Low Pressure Air Test, a Vacuum Test, an ExfiltrationTest, or with an Infiltration Test according to the given soil and groundwater conditions of the site. The LowPressure Test and Vacuum Test shall be performed per ASTM F1417 and ASTM C1244 accordingly. TheInfiltration and Exfiltration Tests shall be performed per ASTM C969. If the groundwater is less than 2 feetabove the crown of the pipe, perform the exfiltration test. If the groundwater is greater than 2 feet above thecrown of the pipe, perform the infiltration test.

13. Contractor shall meet all restoration requirements of the Agency, City or UDOT where the manhole isinstalled and shall coordinate any additional installation or inspection requirements with the Agency.

CONNECTION TO AN EXISTING MANHOLE

14. Item numbers 3, 5, 8, 9, 10 and 11 above shall apply.

15. In addition, the manhole junction channel shall be constructed to the same size, shape, and slope of theincoming line. Channel shall curve in the direction of flow with uniform radius and minimize dropping andsplashing of flow.

16. No manhole connection shall be made until complete design drawings of the manhole and line installationsare submitted to the District for approval - 14 days prior to work commencing.

ND-02 Manhole Construction Notes and Index 1 of 2

NORTH DAVIS SEWER DISTRICT

Page 4: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

ND-02 Manhole Construction Notes and Index 2 of 2

NORTH DAVIS SEWER DISTRICT

Detail no. Detail Title Use

ND-10 STANDARD MANHOLE CONNECTIONConcrete, RCP, and PVC District Pipe <54" DIA. (See Note 1)

ND-11STANDARD MANHOLE DETAIL 54" DIA OR LARGERDISTRICT PIPE RCP District Pipe ≥ 54" DIA

ND-12 STANDARD MANHOLE DETAIL FRP DISTRICT PIPE FRP Pipe ≥ 18" DIA

ND-13 STANDARD MANHOLE DETAIL FRPLined Concrete and RCP, FRP or asdirected by District

ND-14 STANDARD MANHOLE DETAIL POLYMER CONCRETELined Concrete and RCP, FRP or asdirected by District

ND-15 STANDARD GREASE INTERCEPTOR As directed by District

ND-18 MANHOLE CONNECTION TO CIPP LINED PIPE CIPP Lined District Pipe

NOTE

1. District reserves the right to require precast FRP or polymer manholes on pipes that are planned to berehabilitated by cured-in-place (CIPP) or other methods within two years of drawing submittal.

Page 5: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

MANHOLE DIAMETER

Minimum manholes diameters where District pipes diameters are greater than 48-inch, where greater than three(3) inlets are present, where more than one outlet is provided, where trough patterns require angles less than 90degrees, or where inlet pipe and outlet pipe elevations are separated by one-foot or more shall be reviewed andaccepted on a case-by-case basis by the District. The District shall be contacted as soon as possible in thedesign process to determine any additional requirements for manholes.

Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed andapproved by the District on a case-by-case basis.

Minimum internal manhole diameter shall be selected based on the following criteria:

ND-03 Manhole Diameter Requirements 1 of 2

NORTH DAVIS SEWER DISTRICT

For alternative configurations, manhole sizing recommendations may be provided by the precast fabricator. Theminimum structural support between openings is 6 inches. Recommendations must be supported by designmethods (drawings, calculations) provided by the precast manufacturer in accordance with applicable industrystandards such as NPCA.

INLET

OUTLET(a.) SINGLE INLET & OUTLET

STRAIGHT THROUGH

OUTLET(a.) SINGLE INLET & OUTLETTROUGH ANGLE MIN. 135°

OUTLET(b.) MAXIMUM 2 INLETS

& 1 OUTLET

OUTLET(c.) MAXIMUM 3 INLETS

& 1 OUTLET

INLET

INLET INLETINLET

INLET INLET

180°135°

90°

135°135°

90° 90°

90°90°

Page 6: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

ND-03 Manhole Diameter Requirements 2 of 2

NORTH DAVIS SEWER DISTRICT

Page 7: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

FINISH GRADECONCRETE COLLAR, 12" WIDE, 8"DEEP (ALL LOCATIONS) W/ (1) #4

REINFORCEMENT BAR ALL AROUND

30" MANHOLE RING AND COVER VENTEDMARKED "NORTH DAVIS SEWER"

(D & L SUPPLY A-1180-18, OR EQUAL)

PLACE AND COMPACTBACKFILL EQUALLY AROUND

MANHOLE IN MAXIMUM8-INCH LIFTS IN PAVEDAREAS AND MAXIMUM

12-INCH LIFTS IN UNPAVEDAREAS. PROVIDE CLSM

BACKFILL IF MANHOLERISER OR CONE SECTIONS

ARE EXPOSED OR INUNPAVED AREAS

POLYMER OR EPP GRADERINGS AS APPROVED BY THE

DISTRICT. MIN. ONE, 6"GRADE RING, 18" MAX TOTAL

HEIGHT INCLUDING FRAME, RINGS & GROUT

GROUT FOR SETTING GRADE RINGS ANDFRAME SHALL PROVIDE A WATERTIGHTBARRIER TO PREVENT INFILTRATION ANDBE PLACED ACROSS THE FULL WIDTH,1/2-INCH MIN AND 1-INCH MAX THICK.

6" MIN

SLOPE AWAY FROM FRAME AND COVER

NOTES:

1. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION. GROUT SHALL BEFULL STRENGTH, NON-METTALIC, NON-SHRINK TYPE V GROUT (MASTERFLOW 713,FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINSTHYDROGEN SULFIDE ATTACK.

2. EPP GRADE RINGS SHALL BE PROVIDED WITH COMPATIBLE SEALANT ASRECOMMENDED BY THE EPP GRADE RING FABRICATOR, CRETEX PRO RING EPPGRADE RINGS + M-1 SEALANT, OR EQUAL.

NORTH DAVIS SEWER DISTRICT

ND-04 Manhole Collar and Grade Ring

Revision 2, Adopted 9/6/2018

30" MIN

Page 8: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE ANDCONSTRUCTION OF CONNECTING PIPELINE.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTINGSEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING,AND PAVEMENT RESTORATION.

3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

5. PRECAST MANHOLE BASES SHALL BE USED FOR CONSTRUCTION OFALL NEW DISTRICT SEWER SYSTEMS. PRECAST MANHOLE BASES ORCAST-IN-PLACE MANHOLE BASES MAY BE USED AT THECONTRACTOR'S OPTION FOR NEW MANHOLES INSTALLED ON EXISTINGDISTRICT SANITARY SEWERS. CONTRACTOR SHALL PROVIDE ASUITABLE FOUNDATION IN ALL AREAS.

6. CAST-IN-PLACE BASE SHALL BE COMPLETED IN A SINGLE POUR.CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 4000 PSI PERASTM C39. NO ADDITIVES SHALL BE PERMITTED WITHOUT PRIORAPPROVAL BY THE DISTRICT.

7. PRECAST MANHOLE BASES SHALL CONFORM TO ASTM C478.CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 4000 PSI PERASTM C39. CONNECTIONS TO PRECAST BASES SHALL BE FACTORYINSTALLED AND MEET THE REQUIREMENTS OF ASTM C923, Z-LOK,PRES-SEAL PSX OR APPROVED EQUAL.

8. MANHOLES ON FRP OR CIPP LINED DISTRICT SEWERS SHALL BEPRECAST FRP (HOBAS, LFM MANUFACTURING INC OR EQUAL) ORPOLYMER (ARMOROCK OR EQUAL) UNLESS OTHERWISE APPROVED BYTHE DISTRICT. SEE DETAIL ND-12, ND-13 AND ND-14.

9. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION.GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINK TYPEV GROUT (MASTERFLOW 713, FIVESTAR GROUT OR APPROVED EQUAL)WITH ADDITIVES FOR PROTECTION AGAINST HYDROGEN SULFIDEATTACK.

10. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CASTCONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIREBRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN,DURABLE SURFACE. SECURE WATERSTOP TO PIPE USINGMANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OFGREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEENWATERSTOP AND PIPE.

11. NO LADDER RUNGS SHALL BE INSTALLED ON DISTRICT MANHOLES.

2'-0"MAX.

6" (TYP)JUNCTION CHANNEL SHALL BE

FORMED WITH SAME SLOPE, SIZE,DEPTH, AND SHAPE AS CONNECTING

PIPE WITH SMOOTH FINISH -CHANNEL SHALL CURVE IN DIRECTION

OF FLOW WITH UNIFORM RADIUSAND MINIMIZE DROPPING AND

SPLASHING OF FLOW

EXISTING DISTRICTPIPE

FLOW

CUTTING OF EXISTING LINE TO FORMCHANNEL SHALL BE ACCOMPLISHED

WITH SMOOTH SAW CUTS

CONNECTING PIPE

PLAN

AA

ND-10 Standard Manhole Connection 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 4, Adopted 4/23/2019

IF A BOOTED CONNECTION IS NOTPOSSIBLE, PLACE HYDROPHILIC

WATERSTOP ALL AROUND EXISTINGDISTRICT PIPE AND CONNECTING

PIPE(S) (TYPICAL), GREENSTREAKHYDROTITE (OR APPROVED EQUAL),

SEE NOTE 10.

MINIMUM INTERNALMANHOLE DIAMETER

PER ND-03

Page 9: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

6"

30" DIA.

12"

9" MIN

SEAL ALL JOINTS WITH RAMNECK OR EQUAL(ALL JOINTS SHALL BE TESTED FORWATERTIGHTNESS) TAPE WRAP EXTERIORJOINTS. WRAP SHALL CONFORM TO ASTM C877TYPE II OR TYPE III. (PRESS-SEAL EZ-WRAP,CRETEX WRAP, CONSEAL 2/2 OR APPROVED EQUAL)

PRECAST CONCRETE MANHOLESECTIONS PER ASTM C-478.

PRECAST OR CAST-IN-PLACEMANHOLE BASE

UNDISTURBEDNATIVE SOIL

1" MINUSGRAVEL BASE

CONNECTING PIPE SHALL BE INSTALLEDIN CORE DRILLED OPENING WITH A FLEXIBLE

WATERTIGHT BOOT PER ASTM C923. (PSX,PRESS SEAL, KOR-N-SEAL OR EQUAL)

TOP OF FLOOR SHALLBE 2" MIN. ABOVE PIPE

MINIMUM INTERNAL DIAMETER PER ND-03 FORDISTRICT PIPE SIZES TO 48". SEE DETAIL ND-11

FOR DISTRICT PIPES 54" OR LARGER

PRECAST ECCENTRIC CONE (SHALL MEET ASTMC-478 STANDARDS) WHEN INSUFFICIENT DEPTH

PREVENTS THE USE OF A CONE, A CONCRETEPRECAST H-20 FLAT LID SHALL BE USED.

FOR MANHOLE FRAME,COVER, AND COLLAR

SEE ND-04

INVERT OF CONNECTING PIPESHALL BE AT OR NEAR

CROWN OF EXITINGDISTRICT SEWER PIPE

1:12 FLOOR SLOPEWITH SMOOTHTROWELED FINISH

DISTRICT SEWERPIPE

SECTION A

ND-10 Standard Manhole Connection 2 of 2

NORTH DAVIS SEWER DISTRICT

PRECAST RISER TO BE SET IN CONCRETE (TYP)(CAST-IN-PLACE BASE)

Revision 2, Adopted 3/12/2018

IF A BOOTED CONNECTION IS NOTPOSSIBLE, PLACE HYDROPHILIC

WATERSTOP ALL AROUND EXISTINGDISTRICT PIPE AND CONNECTING PIPE(S)

(TYPICAL), GREENSTREAK HYDROTITE(OR APPROVED EQUAL), SEE NOTE 10.

POLYMER OR EPP GRADE RINGS.SEE ND-04 FOR GROUT ANDGRADE RING REQUIREMENTS

Page 10: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

MIN

LE

NG

TH P

ER

TA

BLE

"A"

MIN WIDTH PER TABLE "A"

MIN DIA PERTABLE "A"

MIN WIDTH PER TABLE "A"

8" MIN3" MIN

1'-0

" MIN

45° TYP

VARIESSEE TABLE "A"

1'-0" MIN

3" MIN (TYP)

1'-0

"M

IN

#5 BAR 12" OC BOTH WAYSTOP & BOTTOM GRADE 60

CLE

AR

HE

IGH

T

6' M

IN T

O T

RA

NS

ITIO

N(M

IN 4

8" R

ISE

RTO

GR

AD

E)

PRECAST POLYMERMANHOLE PERSTANDARD DETAIL ND-14AND TABLE A

SAW CUT & REMOVEEXISTING PIPE CROWN

FLO

W

FRAME & COVER PERDETAIL ND-10

PRECAST POLYMERMANHOLE PER

STANDARD DETAIL ND-14AND TABLE A

CONNECTINGPIPE

PLAN

SECTION A

L VARIES

HYDROPHILIC WATERSTOPALL AROUND EXISTING

DISTRICT PIPE ANDCONNECTING PIPE(S)

(TYPICAL), GREENSTREAKHYDROTITE (OR APPROVED

EQUAL), SEE NOTE 4.

"L" M

IN

EXISTING DISTRICTSEWER PIPE

CONNECTING PIPE

AA

12" GRANULAR BEDDINGCOMPACTED TO 95% DRYDENSITY (OR CONTROLDENSITY FILL)

UNDISTURBED NATIVESOIL

ND-11 Standard Manhole Detail 54" DIA or Larger District Pipe 1 of 2

NORTH DAVIS SEWER DISTRICT

PROVIDE STAINLESS STEEL BAND

(NON-SHEAR) TYPE.(FERNCO OR

APPROVED EQUAL)

HYDROPHILICWATERSTOP ALL AROUND

EXISTING DISTRICT PIPEAND CONNECTING PIPE(S)(TYPICAL), GREENSTREAK

HYDROTITE (ORAPPROVED EQUAL), SEE

NOTE 4.

6"MAX

6" FROM WATERSTOPTO OUTSIDE EDGEOF MANHOLE

6" MIN FROM EDGE OFCONCRETE

PRE-POLYMER RISERSEE NOTE 9

Page 11: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NOTES:

1. THIS STANDARD DRAWING SHALL BE USED FOR ACCESS TOEXISTING DISTRICT SEWER PIPES WITH DIAMETERS 54" DIA ORLARGER. THIS DETAIL SHALL NOT APPLY TO NEW DISTRICTSANITARY SEWER AND MANHOLE CONSTRUCTION.

2. WHERE DEPTH OF COVER OVER THE TOP OF PIPE EXCEEDS 10FEET, REINFORCEMENT REQUIREMENTS SHALL BE REVIEWEDAND VERIFIED BY A UTAH LICENSED CIVIL OR STRUCTURALENGINEER.

3. CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM 4000 PSICOMPRESSIVE STRENGTH AT 28 DAYS UNLESS OTHERWISEDIRECTED BY THE DISTRICT.

4. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPE AND CASTCONCRETE, BOTH SIDES, ALL AROUND. CLEAN PIPE USING WIREBRUSH, POWER WASH OR SAND BLAST TO PROVIDE A CLEAN,DURABLE SURFACE. SECURE WATERSTOP TO PIPE USINGMANUFACTURER'S RECOMMENDED METHODS. APPLY LAYER OFGREENSTREAK LEAKMASTER OR APPROVED EQUAL BETWEENWATERSTOP AND PIPE.

5. MINIMUM MANHOLE DIAMETER SHALL BE AS SHOWN IN TABLE A.MANHOLE COMPONENTS SHALL BE PROVIDED IN ACCORDANCEWITH DETAIL ND-10.

6. WHERE EXISTING DISTRICT PIPES HAVE BEEN REHABILITATEDWITH CURED-IN-PLACE PIPE LINERS, CIPP LINERS SHALL BE CUTAND THE CIPP LINER ROUGHENED AND SEALED WITH ANAPPROVED EPOXY PER DETAIL ND-16.

7. INVERT OF CONNECTING PIPE SHALL MATCH THE CROWN OFEXISTING DISTRICT PIPE. SAW CUT AND REMOVE EXISTING PIPEFROM CROWN TO SPRINGLINE OR AS OTHERWISE DIRECTED BYTHE DISTRICT. CONSTRUCT SLOPING INLET CHANNEL AND SHAPECHANNEL TO FORM A SMOOTH FLOW SURFACE.

8. PIPE CONNECTIONS SET IN THE CONCRETE BASE SHALL BEWATERTIGHT. PROVIDE HYDROPHILIC WATER STOPS, GROUTRINGS OR CAST-IN-PLACE RUBBER BOOTS MEETING APPLICABLEREQUIREMENTS OF ASTM C923. (PRESS SEAL, LINK-SEAL, ORAPPROVED EQUAL) SUBMIT PRODUCT DETAILS AND PROPOSEDCONNECTION FOR APPROVAL BY THE DISTRICT.

9. PRE-POLYMER RISER TO BE SET AND TIED TO BASE. PROVIDE (8)#4 BARS EQUALLY SPACED DOWELS CAST INTO POLYMER RISERAT TIME OF FABRICATION. MIN 6" EMBEDMENT INTO CASTCONCRETE TIED TO ENCASEMENT REBAR.

TABLE "A"

DISTRICT PIPEDIA (IN)

MIN MANHOLEDIA (IN)

ENCASEMENTMIN WIDTH (IN)

ENCASEMENTMIN LENGTH (IN)

78" OR LESS 72" 118" 118"

84" OR LESS 84" 124" 124"

ND-11 Standard Manhole Detail 54" DIA or Larger District Pipe 2 of 2

NORTH DAVIS SEWER DISTRICT

Page 12: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

EQ EQ

MIN

WID

TH P

ER

TA

BLE

"A"

2'-0"

MIN LENGTH PER TABLE "A"

24" MIN

MIN DIA PERTABLE "A"

FRP TEE BASEOR FITTING

EXISTING DISTRICT PIPE(FRP, 18" DIAOR GREATER)

PRECAST POLYMERMANHOLE PER

DETAIL ND-14

CONNECTING PIPEPROVIDE WATERTIGHT SEAL(INSERTA TEE OR APPROVED EQUAL WHERE CONNECTING TO FRP)

FIELD CUT EXISTING PIPE,CLOSURE COUPLINGPER FRP MFR

PRECAST POLYMERMANHOLE PER

DETAIL ND-13 OR ND-14.FRP TEE BASEOR FITTING

MIN.

2'-0"MIN.

12" GRANULAR BEDDINGCOMPACTED TO 95%DRY DENSITY (ORCONTROLLED DENSITYFILL)

CONCRETEENCASEMENT

2'-0"MIN.

NOTES:

1. THIS STANDARD DRAWING SHALL APPLY WHEREMANHOLES ARE CONSTRUCTED ON FRP (FIBERGLASS)DISTRICT PIPES. AT THE CONTRACTORS OPTION, APRECAST MANHOLE BASE MAY BE INSTALLED.CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERMANHOLE CONNECTIONS AS ACCEPTED BY THEDISTRICT.

2. CUT EXISTING PIPE TO NEAT STRAIGHT LINES WITHCUTTING TOOLS SUITABLE FOR THE PIPE MATERIAL.DAMAGED PIPE SHALL BE REPAIRED OR REPLACED ATNO ADDITIONAL COST TO THE DISTRICT. EXISTINGDISTRICT PIPELINES SHALL BE FULLY SUPPORTED ATALL TIMES.

3. CONCRETE SHALL BE TYPE V CEMENT WITH A MINIMUM4000 PSI COMPRESSIVE STRENGTH AT 28 DAYS.

4. MINIMUM MANHOLE DIAMETER SHALL BE AS SHOWN INTABLE "A". PRECAST MANHOLES COMPONENTS SHALLBE PROVIDED IN ACCORDANCE WITH DETAIL ND-13 ORND-14.

5. ADDITIONAL DETAIL AND REINFORCING REQUIREMENTSSHOWN ON PAGE 2 OF 2.

6. PROVIDE HYDROPHILIC WATER STOP BETWEEN PIPEAND CAST CONCRETE, BOTH SIDES, ALL AROUND.CLEAN PIPE USING WIRE BRUSH, POWER WASH ORSAND BLAST TO PROVIDE A CLEAN, DURABLESURFACE. SECURE WATERSTOP TO PIPE USINGMANUFACTURER'S RECOMMENDED METHODS. APPLYLAYER OF GREENSTREAK LEAKMASTER OR APPROVEDEQUAL BETWEEN WATERSTOP AND PIPE.

TABLE "A"

DISTRICTPIPE DIA

(IN)

MINMANHOLE

DIA (IN)

MINENCASEMENT

WIDTH (IN)

MINENCASEMENTLENGTH (IN)

18" TO 45" 48" 74" 78"

60" ORLESS 60" 88" 102"

84" ORLESS 90" 112" 132"

UNDISTURBEDNATIVE SOILPLAN SECTION A

AA

ND-12 Standard Manhole Detail FRP District Pipe 1 of 2

NORTH DAVIS SEWER DISTRICT

PRE-POLYMER RISER TO BESET AND TIED TOSTRUCTURE WITH CAST INPLACE CONCRETE

HYDROPHILIC WATERSTOP ALLAROUND EXISTING DISTRICT PIPE

AND CONNECTING PIPE(S) (TYPICAL),GREENSTREAK HYDROTITE (OR

APPROVED EQUAL), SEE NOTE 6.

HYDROPHILIC WATERSTOP ALLAROUND EXISTING DISTRICT PIPE

AND CONNECTING PIPE(S) (TYPICAL),GREENSTREAK HYDROTITE (OR

APPROVED EQUAL), SEE NOTE 6.

Page 13: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NON SHRINK GROUT

(18 @ 20°) #4 X 1'-4"TYP. EACH END

#4 H2E @ 12" - TYP.4 SIDES

#4 H2E - TYP. 4 SIDES

#6

ADD (2) #6 EACHSIDE OF MANHOLE

FRP TEE BASEOR FITTING

EXISTING DISTRICTPIPE (FRP, 18" DIAOR GREATER)

PRECAST MANHOLE PER DETAIL ND-14

(4) #6 @ 12"

2'-0"MIN.

#5 @ 12" EW

(18 @ 20°) #4

#6 @ 12" -LAP 2'-4"

#5 H2E @ 12" EF

#5 @ 12" EF

#5 @ 12"#5 H2E @ 12"

VA

RIE

S

2'-0

"1'

-0"

SECTION BREINFORCING

SECTION AREINFORCING

B

B

ND-12 Standard Manhole Detail FRP District Pipe 2 of 2

NORTH DAVIS SEWER DISTRICT

PRE-POLYMER RISER TO BE SET AND TIEDTO STRUCTURE WITH CAST IN PLACECONCRETE

Page 14: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

30"

12"

MIN

FACTORY-BONDED JOINT

FACTORY INSTALLEDPVC STUBOUTS ORCONNECTIONS

DISTRICT SEWERPIPE

#4 REBAR 12" OCEW

PROVIDE MIN 12",1" MINUS GRAVEL

BASE

WATER TIGHT, FLEXIBLE PIPECONNECTION, APPROVED

BY THE DISTRICT

ALL MANHOLES SHALL BE PROVIDED WITHANTI-FLOTATION RINGS FULLY ENCASED IN A

CONCRETE PAD OF SUFFICIENT SIZE ANDTHICKNESS TO PREVENT FLOTATION.

FRP MANHOLE BASE FACTORY CAST FLOWCHANNEL WITH FRP CHANNEL SUPPORTS

FRP MANHOLE. WALL THICKNESS PERMANUFACTURER PRODUCT SUBMITTAL

MIN 1/2" WALL THICKNESS

FRP NECK TO EXTEND INSIDEGRADE RINGS. GRADE RINGS TO

EXTEND A MINIMUM OF 1" PASTFLAT SURFACE OF MANHOLE CONE

PLACE AND COMPACT MANHOLE BACKFILL IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS

NORTH DAVIS SEWER DISTRICT

ND-13 Standard Manhole Detail FRP 1 of 2

MINIMUM INTERNAL MANHOLE DIAMETER PERND-03 FOR DISTRICT PIPE SIZES TO 48". SEEDETAIL ND-11 FOR DISTRICT PIPES 54" ORLARGER

UNDISTURBED NATIVE SOIL

CONNECTING PIPE

Revision 4, Adopted 4/18/2018

POLYMER OR EPP GRADE RINGS.SEE ND-04 FOR GROUT ANDGRADE RING REQUIREMENTS

FOR MANHOLE FRAME, COVERAND COLLAR SEE ND-04

Page 15: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-13 Standard Manhole Detail FRP 2 of 2

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE ANDCONSTRUCTION OF CONNECTING PIPELINE.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWERAND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATIONBEGINS.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

5. MANHOLE BASE SHALL BE PRECAST FRP UNLESS OTHERWISE APPROVED BY THEDISTRICT.

6. THE CONTRACTOR SHALL BE A LICENSED OR CERTIFIED INSTALLER BY THEMANUFACTURER OF THE MANHOLE PROVIDED.

7. MANHOLES AND THEIR BASES SHALL BE CIRCULAR FIBERGLASS REINFORCEDPOLYESTER MANHOLES DESIGNED, FABRICATED AND TESTED TO MEET OR EXCEEDTHE REQUIREMENTS OF ASTM D3753. HOBAS, LFM MANUFACTURING OR APPROVEDEQUAL.

8. PRECAST CONCRETE AND CAST-IN-PLACE COMPONENTS SHALL NOT BE ALLOWEDUNLESS OTHERWISE APPROVED BY THE DISTRICT.

9. INVERT OF CONNECTING PIPE SHALL MATCH CROWN OF DISTRICT PIPE UNLESSOTHERWISE DIRECTED BY THE DISTRICT.

Revision 4, Adopted 4/18/2018

Page 16: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

30"

PRECAST POLYMER MANHOLEMIN WALL THICKNESS PERMANUFACTURER PRODUCTSUBMITTAL

DISTRICT SEWERPIPE

PROVIDE MIN 12",1" MINUS GRAVEL BASEOVER UNDISTURBEDNATIVE SOIL

WATER TIGHT, FLEXIBLEPIPE CONNECTIONS MEETING

THE REQUIREMENTS OFASTM C923 AND

APPROVED BY DISTRICT

NORTH DAVIS SEWER DISTRICT

ND-14 Standard Manhole Detail Polymer 1 of 3

MINIMUM INTERNAL DIAMETER PER ND-03 FORDISTRICT PIPE SIZES TO 48". SEE DETAIL ND-11FOR DISTRICT PIPES 54" OR LARGER

PRECAST POLYMER BASEWITH MONOLITHIC FACTORYCAST WALL, BENCH AND CHANNEL

Revision 5, Adopted 3/12/2018

RUBBER GASKET

THREADEDLIFTINGINSERT

BUTYL MASTIC

POLYMER OR EPP GRADE RINGS.SEE ND-04 FOR GROUT ANDGRADE RING REQUIREMENTS

MANHOLE WATERTIGHT JOINT. PROVIDE ADDITIONALRUBBER GASKET FOR BELL AND SPIGOT JOINTS AND

EXTERIOR WRAP FOR FLUSH JOINTS TO PREVENTGROUNDWATER INFILTRATION

FOR MANHOLE FRAME,COVER AND COLLAR SEEND-04

Page 17: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-14 Standard Manhole Detail Polymer 2 of 3

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERSLOPE AND CONSTRUCTION OF CONNECTING PIPELINE.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTIONOF EXISTING SEWER AND OTHER UTILITIES, PROPERBACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

3. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OFONE YEAR.

5. THE CONTRACTOR SHALL BE A LICENSED OR CERTIFIEDINSTALLER BY THE MANUFACTURER OF THE MANHOLEPROVIDED.

6. MANHOLES AND THEIR BASE SHALL BE CIRCULAR PRECASTPOLYMER DESIGNED, FABRICATED AND TESTED TO MEETOR EXCEED THE REQUIREMENTS OF D6783. POLYMERCOMPONENTS SHALL BE A MIXTURE OF UNSATURATEDISOPHTHALIC POLYESTER RESIN, SAND AND AGGREGATE.NO CEMENTIOUS OR CALCIUM CARBONATE MATERIALSSHALL BE ALLOWED. ARMOROCK OR APPROVED EQUAL.

7. JOINTS SHALL BE WATERTIGHT. PROVIDE BUTYL MASTICAND RUBBER GASKETS FOR BELL AND SPIGOT STYPEMANHOLE JOINTS (72-IN DIA. OR SMALLER) AND RUBBERGASKETS WITH EXTERIOR WRAP FOR FLUSH MANHOLEJOINTS (GREATER THAN 72-IN DIA.). BUTYL MATSIC SHALLBE CONSEAL CS-102 OR APPROVED EQUAL. RUBBERGASKETS SHALL BE HK TYLOX SOC PROFILE GASKETS, ORAPPROVED EQUAL. WRAP SHALL CONFORM TO ASTM C877TYPE II OR TYPE III.PRESS-SEAL EZ-WRAP, CRETEX WRAP,CONSEAL 2/2 OR APPROVED EQUAL.

8. WHERE REQUIRED, CSLM BACKFILL SHALL BE TYPE II/V 300PSI AT 28 DAYS. DEPTH OF CLSM BELOW GRADE SHALL BEEQUAL OR GREATER THAN THE HEIGHT ABOVE GRADE ANDINCLUDE AT A MINIMUM ONE JOINT.

Revision 3, Adopted 3/12/2018

Page 18: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-14 Standard Manhole Detail Polymer 3 of 3

MANHOLE I.D.

BA

SE

HE

IGH

TP

ER

MA

NU

FAC

TUR

ER

PRECAST POLYMER BASE

FACTORY CASTMONOLITHIC

FLOW CHANNEL

#5 FIBERGLASSREBAR MAT

Revision 3, Adopted 4/18/2018

MONOLITHIC, FACTORYCAST RESIN AGGREGATE

WALL & BENCH

ANTI FLOTATIONRING/EXTENDED

SLAB

SLOPE 1:12

NOTES:

1. MANHOLE BASE SHALL BE PRECAST POLYMER. PRECAST CONCRETE ANDCAST-IN-PLACE COMPONENTS SHALL NOT BE ALLOWED.

2. INVERT OF CONNECTING PIPE SHALL MATCH CROWN OF DISTRICT PIPEUNLESS OTHERWISE DIRECTED BY THE DISTRICT.

3. IN AREAS WHERE FLOATATION OR BUOYANT CONDITIONS EXIST, PROVIDEANTI-FLOATATION RINGS FULLY ENCASED IN A CONCRETE PAD OFSUFFICIENT SIZE AND THICKNESS TO PREVENT FLOATATION. SIZE SHALLBE BASED ON GROUNDWATER TO GRADE.

4. CONTRACTOR SHALL PROVIDE SUITABLE FOUNDATION AS DIRECTED BYTHE DISTRICT IN AREAS OF UNSTABLE TRENCH BOTTOM, WET CONDITIONS,OR OVER EXCAVATION.

Page 19: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

TEE - 6" MIN.PRECAST CONCRETETANK

RISER SECTION / GRADE RINGS (NOTTO EXCEED 12" TOTAL HEIGHT).GROUT FOR SETTING GRADE RINGSAND FRAME SHALL PROVIDE AWATERTIGHT BARRIER TO PREVENTINFILTRATION AND BE PLACED ACROSSTHE FULL WIDTH, 1/2-INCH MIN AND1-INCH MAX THICK.

FINISH GRADE(PAVEMENT ORLANDSCAPING)

DOUBLESWEEP

CLEANOUT

SANITARYTEES

LIQUIDLEVEL

GREASESTORAGE

MANHOLE RING AND NON-VENTEDCOVER MARKED "SEWER" - (TYPICAL)

(D & L A-1024, OR EQUAL)

6"

1" MINUSGRAVEL BASE

UNDISTURBEDNATIVE SOIL

20"MIN. DIA.

OUTLETINLET

INLET OUTLET

MANHOLE COVERSLOCATED TO ALLOWVIEWING OF ANDSAMPLING FROM INLETAND OUTLET TEES(TYPICAL)

PLAN

SECTION

SEWER

SST PIPE SUPPORTSREQUIRED (TYP)

12"

SEWER

1'-6" WIDE, 6" DEEP CONCRETECOLLARS IN PAVED AREAS.REINFORCEMENT REQUIRED.(1) #4 BAR ALL AROUND

ND-15 Standard Grease Interceptor 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

Page 20: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

ND-15 Standard Grease Interceptor 2 of 2

NORTH DAVIS SEWER DISTRICT

NOTE:

ALL HARDWARE316 STAINLESSSTEEL

NOTES:

1. GREASE INTERCEPTOR SHALL BE LOCATED TO BECONTINUOUSLY AND EASILY ACCESSIBLE FOR INSPECTION ANDCLEANING AND AS CLOSE AS PRACTICAL TO THE SOURCE OFWASTEWATER.

2. WHEN LOCATED IN PAVED AREA, THE TRAP, MANHOLE COVERS,ETC, SHALL BE TRAFFIC RATED.

3. INLET AND OUTLET TEES SHALL BE LOCATED DIRECTLY BELOWMANHOLE ACCESSES.

4. GREASE INTERCEPTORS SHALL HAVE A MINIMUM OF TWOCOMPARTMENTS.

5. MINIMUM HYDRAULIC VOLUME OF THE TRAP SHALL BE 1000GALLONS UNLESS OTHERWISE APPROVED BY THE DISTRICTMANAGER.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALLUTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENTRESTORATION.

7. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

8. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONEYEAR.

9. GRADE RINGS SHALL BE GROUTED TO PREVENT INFILTRATION.GROUT SHALL BE FULL STRENGTH, NON-METALLIC, NON-SHRINKTYPE V GROUT (MASTERFLOW 713, FIVESTAR GROUT ORAPPROVED EQUAL) WITH ADDITIVES FOR PROTECTION AGAINSTHYDROGEN SULFIDE ATTACK.

2 SS EXP ANCHORSEACH CLAMP

WALL

"Z" SHAPED SSSTRAP FITTING,TYP

SST PIPE SUPPORT

Revision 4, Adopted 9/6/2018

Page 21: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

REMOVE AND DISPOSE OF EXISTINGFRAME AND COVER UNLESSOTHERWISE SPECIFIED

SEE SECTION B FOR JOINT REQUIREMENTBETWEEN EXISTING AND REPLACEMENTMANHOLE SECTION

EXISTING DISTRICT MANHOLE

SHEETING AND SHORINGAS REQUIRED

SAW CUT EXISTING RISERSECTION FLUSH BELOW

MANHOLE JOINT. SEE NOTE 3

DEMOLISH EXISTING MANHOLECOMPONENTS AS SPECIFIED.

PROVIDE REPLACEMENTCOMPONENTS PER SECTION B

AND NOTE 1

SAW CUT TO NEAT LINE. PAVEMENT REMOVALSHALL INCLUDE REPLACEMENT FULL LANEWIDTH IN PAVED AREAS AND MIN 10' (TYP)

WIDTH CENTERED ON THE MANHOLE IN THEDIRECTION OF TRAVEL

ND-17 Partial Manhole Replacement 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 2, Adopted 11/7/2014

DIAMETERAS SHOWN

DE

PTH

VA

RIE

S

SECTION A

Page 22: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

Revision 3, Adopted 4/18/2018

REPLACEMENT WALLSECTION. BELL OR

SPIGOT REMOVED ANDSET IN GROUT

ND-17 Partial Manhole Replacement 2 of 2

NORTH DAVIS SEWER DISTRICT

EXISTING MANHOLEWALL

TAPE WRAP JOINT EXTERIORTO PROVIDE A WATER TIGHTSEAL. WRAP PER ASTM C-887SELF ADHERING. MINIMUM 12"WIDE

314 STL BAND ANDHARDWARESTABILIZER

NOTES:

1. CONTRACTOR TO INSPECT PRECAST MANHOLE PRIOR TOPROCURING REPLACEMENT COMPONENTS TO FIELD VERIFYDEPTH OF REPLACEMENT. PRECAST COMPONENTS PROVIDEDSHALL BE ARMOROCK POLYMER CONCRETE PROVIDED PERSTANDARD DETAIL ND-14 UNLESS OTHERWISE SPECIFIED.

2. PRECAST CONCRETE COMPONENTS PER STANDARD DETAILND-10 SHALL ONLY BE PROVIDED WHERE APPROVED BY THEDISTRICT. CONCRETE MANHOLES SHALL BE PROVIDED WITHCORROSION PROTECTION MATCHING EXISTING COATINGS ORLINERS. WHERE COATINGS OR LINERS ARE NOT PRESENT,REHABILITATION OF THE MANHOLE IN ITS ENTIRETY SHALL BEPROVIDED AS DIRECTED BY THE DISTRICT.

3. WHERE EXISTING CONES ARE DAMAGED, DEMOLITION SHALLINCLUDE THE CONE IN IT'S ENTIRETY. CONES SHALL BEREPLACED IN KIND. FLAT-TOPS SHALL ONLY BE PROVIDED WITHAPPROVAL BY THE DISTRICT.

4. MANHOLE SECTIONS SHALL BE SAWCUT TO CLEAN, NEAT LINES.CUTS AND PREPARED SURFACES SHALL BE INSPECTED PRIOR TOPLACEMENT OF GROUT. GROUT SHALL BE FULL STRENGTH,NON-METALLIC, NON-SHRINK, TYPE V GROUT (MASTERFLOW 713,FIVESTAR GROUT OR APPROVED EQUAL) WITH ADDITIVES FORPROTECTION AGAINST HYDROGEN SULFIDE ATTACK.

5. PROVIDE MINIMUM 1" GOOD QUALITY CONCRETE COVERAGEBOTH SIDES OF WATER STOP.

SECTION B

NON-SHRINK GROUTSEE NOTE 4

REPLACED MANHOLECOMPONENT

PROVIDE HYDROPHILICWATER STOP ALL AROUND.GLUE TO REPLACEMENTSECTION W/ CONTACTCEMENT, ADEKA KBA-1510FPAND ULTRA P-201 ORAPPROVED EQUAL - (SEENOTE 5)

Page 23: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-18 Manhole Connection to CIPP Lined Pipe

Revision 2, Adopted 4/18/2018

NOTES:

1. THIS STANDARD APPLIES WHEN CONNECTING A NEWMANHOLE TO A CIPP LINED PIPE.

2. WHERE FRP LINERS ARE CUT, REMOVE PRE LINER SHEETAND FOIL (IF INSTALLED). SMOOTH LINER EDGE PRIOR TOCOATING.

3. IF THE CIPP LINER IS DAMAGED, THE CIPP LINER SHALL BEREPAIRED AT NO ADDITIONAL COST TO THE OWNER. THESEWER AND CIPP LINER SHALL BE CLEANED AND INSPECTEDVIA CCTV PRIOR TO CUTTING THE PIPE.

4. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PERASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF4000 PSI PER ASTM C39. NO ADDITIVES SHALL BE PERMITTEDWITHOUT PRIOR APPROVAL BY THE DISTRICT.

AFTERBEFORE

BOOT CONNECTION

EXISTING DISTRICTPIPE W/ CIPP LINER

CHIP BACK EXISTINGPIPE 6 INCHES TOEXPOSE LINER

NEW POLYMERMANHOLE

NEW POLYMERMANHOLE

PVC STUB-OUT

EXISTING DISTRICTPIPE W/ CIPP LINER

FERNCO SHIELED(STRONG BACK)

RC COUPLINGOR APPROVED

EQUAL. PROVIDEFLUSH INVERT

PLACE CONCRETE TOSPRINGLINE OF SEWER

BOOT CONNECTION

PVC STUBOUT

Page 24: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

45° MANUFACTUREDBEND

PEA GRAVEL FILL SHALL BE PLACEDAND COMPACTED BENEATH CONNECTING

SERVICE TO UNDISTURBED SUBGRADEAND TO A MINIMUM DEPTH OF 6" ABOVE PIPE

CONNECTING SERVICE LATERAL(MATERIAL AND CONSTRUCTIONSHALL CONFORM TOREQUIREMENTS OF APPLICABLEJURISDICTIONAL AGENCY)

EXISTING DISTRICT PIPE.VERIFY PIPE MATERIALAND DIAMETER PRIOR TOCONSTRUCTION.

LATERAL SHALL BEFLUSH WITH INSIDEOF PIPE

CORE DRILLED OPENING(INSTALLATION OF ANCHOR BOLTSIN THE PIPE WALL OR HAMMER DRILLINGSHALL NOT BE ALLOWED AS PART OF THECORE DRILLING OPERATION)

FLEXIBLE AND WATERTIGHT CONNECTIONFITTING - FITTING SHALL HAVE POSITIVE STOPTO PREVENT PROTRUSION INTO SEWER LINE(INSERTA-TEE*, GPK 4, OR EQUAL)

45°

NOTES:

1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TO THE SERVICELATERAL AND FURNISH MEASUREMENT TO DISTRICT.

2. THE CONTRACTOR MUST ACCURATELY SIZE AND PROCURE SEWER TAPS BASED ON THE EXISTINGDISTRICT SEWER (MATERIAL AND DIAMETER) AND THE SEWER LATERAL (MATERIAL AND DIAMETER)TO BE CONNECTED.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE AND CONSTRUCTION OF CONNECTINGSERVICE LATERAL.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHERUTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION.

5. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS.

6. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

7. CONCRETE CORES SHALL BE RETAINED AND NOT ALLOWED TO FALL INTO THE SEWER LINE.

ND-20 Standard Service Connection - Concrete Pipe

NORTH DAVIS SEWER DISTRICT

Revision 4, Adopted 4/23/2019

PROVIDE ENCASED FULL STAINLESS STEELBAND (NON-SHEAR) TYPE. (FERNCO OR

APPROVED EQUAL) WHERE CONNECTING TOEXISTING SERVICE LATERAL

ENCASE IN CONCRETE,MINIMUM 12" BELOW &6" ABOVE

Page 25: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

45° MANUFACTUREDBEND

PEA GRAVEL FILL SHALL BE PLACEDAND COMPACTED BENEATH CONNECTINGSERVICE TO UNDISTURBED SUBGRADEAND TO A MINIMUM DEPTH OF 6" ABOVE PIPE

CONNECTING SERVICE LATERAL,(MATERIAL AND CONSTRUCTION SHALL CONFORM

TO REQUIREMENTS OF APPLICABLEJURISDICTIONAL AGENCY)

CORE DRILLED OPENING IN HOST PIPE

FLEXIBLE AND WATERTIGHT CONNECTIONFITTING - FITTING SHALL HAVE POSITIVE STOPTO PREVENT PROTRUSION INTO SEWER LINEAND ENGAGE AT CIPP LINER - (INSERTA-TEE*OR EQUAL - SEE NOTE 12)

NOTES:

1. CONTRACTOR SHALL MEASURE DISTANCE FROM THE NEAREST MANHOLE TOTHE SERVICE LATERAL AND FURNISH MEASUREMENT TO DISTRICT.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPE ANDCONSTRUCTION OF CONNECTING SERVICE LATERAL.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTINGSEWER AND OTHER UTILITIES, PROPER BACKFILLING, COMPACTING, ANDPAVEMENT RESTORATION.

4. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATIONBEGINS.

5. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

6. SERVICE CONNECTION BANDS, SCREWS, HOUSING AND HARDWARE SHALLBE 316 SST. RUBBER MATERIALS SHALL BE NITRILE OR NEOPRENE UNLESSOTHERWISE DIRECTED BY THE DISTRICT.

7. CONTRACTOR SHALL MANUALLY BACKFILL AND COMPACT AROUNDINSERTA- TEE* OR SADDLE UNTIL A MIN OF 12” OF COVER IS PLACED OVERTHE CONNECTION.

8. CORE DRILLING OF CONCRETE PIPE SHALL USE THE WET DIAMOND BITPROCESS. DO NOT ATTACH GUIDES TO THE EXISTING PIPE TO PERFORMCORE DRILLING. CORE DRILL DIAMETER SHALL BE PER THE CONNECTIONMANUFACTURER'S REQUIREMENTS FOR INSTALLATION OF THE PROVIDEDPRODUCT. CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACEDAMAGED PIPE AND LINER.

9. CORE DRILLING OF THE CIPP LINER SHALL BE ACCOMPLISHED EITHERROBOTICALLY FROM INSIDE THE PIPE OR EXTERNALLY. DIAMETER OF THEHOLE SHALL BE SIZED FOR THE FLEXIBLE AND WATERTIGHT CONNECTIONFITTING.

10. FILL VOIDS, OVER CUT OR REMOVED CONCRETE PIPE WITH NON SHRINK NONMETALLIC CEMENT GROUT.

11. CONCRETE AND CIPP LINER CORES SHALL BE RETAINED AND NOT ALLOWEDTO FALL INTO THE SEWER LINE.

12. INSERTA-TEE* PROVIDED SHALL BE PER TABLE 1 UNLESS OTHERWISERECOMMENDED BY THE MANUFACTURER BASED ON THE EXISTINGREHABILTATED DISTRICT PIPE DIAMETER, SERVICE CONNECTION DIAMETER,AND EXISTING CIPP LINER THICKNESS. CONTRACTOR SHALL VERIFY THELINER THICKNESS PRIOR TO INSTALLING THE CONNECTION INTO THE COREDLINER.

EXISTING CIPP LINERTHICKNESS AS PROVIDEDBY THE DISTRICT - SEENOTE 12.

EXISTING REHABILITATEDDISTRICT PIPE (NTS)

PROVIDE ENCASED FULLSTAINLESS STEEL BAND

(NON-SHEAR) TYPE. (FERNCOOR APPROVED EQUAL) WHERE

CONNECTING TO EXISTINGSERVICE LATERAL

45°

NON SHRINK, NON METALLIC GROUT

ENCASE IN CONCRETE, MINIMUM12" BELOW & 6" ABOVE

NORTH DAVIS SEWER DISTRICT

ND-21 Standard Service Connection - CIPP Lined Pipe 1 of 2

CORE DRILLED OPENING IN CIPP LINER

Revision 3, Adopted 4/23/2019

PVC LATERALSERVICE

Page 26: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-21 Standard Service Connection - CIPP Lined Pipe 2 of 2

Revision 3, Adopted 4/23/2019

TABLE 1Rehabilitated District

Concrete Pipe CIPP Liner ThicknessINSERTA-TEE* ORDERING INFORMATION

Lateral Nominal Diameter (inch)Nominal Pipe Diameter

(in)Minimum LinerThickness (mm)

Maximum LinerThickness (mm) 4 6 8

12 3.5 5 4P26FB12CIP 6P26FB12CIP 8P3512CIP15 4.5 6 4P26FB15CIP 6P26FB15CIP 8P3515CIP18 5 7 4P26FB18CIP 6P26FB18CIP 8P3518CIP21 5.5 8 4P26FB21CIP 6P26FB21CIP 8P3521CIP24 7 9 4P26FB24CIP 6P26FB24CIP 8P3524CIP27 8 10 4P26FB27CIP 6P26FB27CIP 8P3527CIP30 8 12 4P26FB30CIP 6P26FB30CIP 8P3530CIP36 8 12 4P26FB36CIP 6P26FB36CIP 8P3536CIP42 8 12 4P26FB42CIP 6P26FB42CIP 8P3542CIP

WHEN ORDERING INSERTA-TEE*, CONTRACTOR SHALL PROVIDE THE NOMINAL DISTRICT PIPE DIAMETER, LATERALDIAMETER AND MATERIAL TO BE INSTALLED, AND EXISTING CIPP LINER THICKNESS TO VERIFY PROPER SIZING OF THERUBBER SLEEVE. INSERTA-TEE* WITH RUBBER SLEEVE THICKNESS SIZED WITHOUT VERIFICATION SHALL NOT BE ACCEPTEDBY THE DISTRICT.

Page 27: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

45° MANUFACTUREDBEND

CONNECTING SERVICE LATERAL,(MATERIAL AND CONSTRUCTION SHALL CONFORM

TO REQUIREMENTS OF APPLICABLEJURISDICTIONAL AGENCY)

CORE DRILLED OPENING

FLEXIBLE AND WATERTIGHT CONNECTIONFITTING - FITTING SHALL HAVE POSITIVE STOPTO PREVENT PROTRUSION INTO SEWER LINE(INSERTA-TEE* OR EQUAL - SEE NOTE 12).

EXISTING FRP (FIBERGLASS) DISTRICTPIPE (16" DIA OR GREATER) NTS.VERIFY PIPE MATERIAL AND DIAMETERPRIOR TO CONSTRUCTION.

PEA GRAVEL FILL SHALL BE PLACEDAND COMPACTED BENEATH CONNECTINGSERVICE TO UNDISTURBED SUBGRADE ANDTO A MINIMUM DEPTH OF 6" ABOVE PIPE

PROVIDE ENCASED FULL STAINLESS STEELBAND (NON-SHEAR) TYPE. (FERNCO OR

APPROVED EQUAL) WHERE CONNECTING TOEXISTING SERVICE LATERAL 45°

NON SHRINK, NON METALLIC GROUT

ENCASE IN CONCRETE, MINIMUM12" BELOW & 6" ABOVE

NORTH DAVIS SEWER DISTRICT

ND-22 Standard Service Connection - FRP Pipe 1 of 3

Revision 3, Adopted 4/23/2018

Page 28: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-22 Standard Service Connection - FRP Pipe 2 of 3

Revision 1, Adopted 4/23/2019

NOTES:

1. CONTRACTOR SHALL MEASURE DISTANCE FROM THENEAREST MANHOLE TO THE SERVICE LATERAL ANDFURNISH MEASUREMENT TO DISTRICT.

2. CONTRACTOR MUST ACCURATELY SIZE AND PROCURESEWER TAPS BASED ON THE EXISTING DISTRICT SEWER(MATERIAL AND DIAMETER) AND THE SEWER LATERAL(MATERIAL AND DIAMETER) TO BE CONNECTED.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SLOPEAND CONSTRUCTION OF CONNECTING SERVICE LATERAL.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTIONOF EXISTING SEWER AND OTHER UTILITIES, PROPERBACKFILLING, COMPACTING, AND PAVEMENT RESTORATION.

5. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFOREINSTALLATION BEGINS.

6. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OFONE YEAR.

7. SERVICE CONNECTION BANDS, SCREWS, HOUSING ANDHARDWARE SHALL BE 316 SST. RUBBER MATERIALS SHALLBE NITRILE OR NEOPRENE UNLESS OTHERWISE DIRECTEDBY THE DISTRICT.

8. CONTRACTOR SHALL MANUALLY BACKFILL AND COMPACTAROUND INSERTA-TEE* UNTIL A MIN OF 12” OF COVER ISPLACED OVER THE CONNECTION.

9. CORE DRILLING OF PIPE SHALL BE PERFORMED USINGCUTTING EQUIPMENT RECOMMENDED BY MANUFACTURERSOF FIBERGLASS PIPE. DO NOT ATTACH GUIDES TO THEEXISTING PIPE TO PERFORM CORE DRILLING. CONTRACTORSHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGEDPIPE.

10. FLEXIBLE AND WATERTIGHT FITTING SHALL BE SIZED FORTHE FRP PIPE.

11. FIBERGLASS CORES SHALL BE RETAINED AND NOTALLOWED TO FALL INTO THE SEWER LINE.

12. INSERTA-TEE* PROVIDED SHALL BE PER TABLE 1 UNLESSOTHERWISE RECOMMENDED BY THE MANUFACTURERBASED ON THE EXISTING DISTRICT PIPE DIAMETER ANDSERVICE CONNECTION DIAMETER. CONTRACTOR SHALLVERIFY THE DIAMETERS AND THICKNESS PRIOR TOINSTALLING THE CONNECTION INTO THE CORED PIPE.

Page 29: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NORTH DAVIS SEWER DISTRICT

ND-22 Standard Service Connection - CIPP Lined Pipe 3 of 3

Revision 1, Adopted 4/23/2019

TABLE 1District FRP (HOBAS) Pipe(Minimum Stiffness, SN,

of 72 PSI)INSERTA-TEE* ORDERING INFORMATION

Lateral Nominal Diameter (inch)HOBAS Nominal Pipe

Diameter (in) 4 6 818 4P26FB18HB72 6P26FB18HB72 8P3518HB7220 4P26FB20HB72 6P26FB20HB72 8P3520HB7236 4P26FB36HB72 6P26FB36HB72 8P3536HB7242 4P26FB42HB72 6P26FB42HB72 8P3542HB7245 4P26FB45HB72 6P26FB45HB72 8P3545HB7254 4P26FB54HB72 6P26FB54HB72 8P3554HB7284 4P26FB84HB72 6P26FB84HB72 8P3584HB72

WHEN ORDERING INSERTA-TEE* FOR FRP PIPE, CONTRACTOR SHALL PROVIDE THENOMINAL DISTRICT PIPE DIAMETER, WALL THICKNESS, AND STIFFNESS, AND LATERALDIAMETER AND MATERIAL, TO BE INSTALLED TO VERIFY PROPER SIZING OF THE RUBBERSLEEVE. INSERTA-TEE* WITH RUBBER SLEEVE THICKNESS SIZED WITHOUT VERIFICATIONSHALL NOT BE ACCEPTED BY THE DISTRICT.

Page 30: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

EXISTING SERVICE LATERAL, VARIES

EXISTING DISTRICTPIPE

EXISTING SERVICE LATERAL, ABANDON IN PLACE

INSTALL WATER TIGHT EXPANSIONPLUG AT EXISTING SERVICELATERAL CONNECTION TO MAIN

RO

W

NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF EXISTING SEWER AND OTHERUTILITIES, PROPER BACKFILLING, COMPACTING, AND PAVEMENT RESTORATION.

2. CONTRACTOR SHALL NOTIFY DISTRICT 48 HOURS BEFORE INSTALLATION BEGINS.

3. CONCRETE THRUST BLOCKS SHALL BE A MINIMUM ONE CUBIC FOOT IN SIZE PLACED AT CAP TOPREVENT DISPLACEMENT OF CAP DURING SEWER CLEANING AND OTHER MAINTENANCEACTIVITIES. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PER ASTM C150 WITH A MINIMUMCOMPRESSIVE STRENGTH OF 4000 PSI PER ASTM C39.

4. CONTRACTOR SHALL GUARANTEE WORK FOR A PERIOD OF ONE YEAR.

REMOVE INTERFERINGPORTIONS OF EXISTINGSERVICE LATERAL, CUT ANDCAP PIPE (TYP)

ND-23 Standard Service Connection Abandonment

NORTH DAVIS SEWER DISTRICT

ENCASE CAP INCONCRETETHRUST BLOCK

Revision 1, Adopted 8/14/2014

Page 31: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NOTES:

1. REPAIR COUPLINGS SHALL PROVIDE A WATER TIGHT SEALAND BE MANUFACTURED FOR USE WITH THE GRAVITYSEWER PIPE MATERIAL TO BE REPAIRED. CONTRACTORSHALL SUBMIT PRODUCT DATA FOR REVIEW ANDACCEPTANCE BY THE DISTRICT.

2. ALL HARDWARE (SHELLS, NUTS, BOLTS, WASHERS, TAKE UPCLAMPS OR RINGS) SHALL BE TYPE 304 STAINLESS STEELPER ASTM A240 UNLESS OTHERWISE APPROVED BY THEDISTRICT.

3. GASKETS SHALL BE FULL LENGTH CIRCUMFERENTIAL SBROR NITRILE (BUNA-N) UNLESS OTHERWISE APPROVED BYTHE DISTRICT.

4. REPAIRS SHALL BE INSPECTED AND APPROVED BY THEDISTRICT PRIOR TO ENCASEMENT AND BACKFILLING.

5. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PERASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF4000 PSI PER ASTM C39. NO ADDITIVES SHALL BEPERMITTED WITHOUT PRIOR APPROVAL BY THE DISTRICT.

6. MINIMUM ENCASEMENT SHALL BE AS FOLLOWS:

REINFORCED CONCRETEENCASEMENT

STAINLESS STEELREPAIR COUPLINGOVER CRACKS

REINFORCEMENTSTEEL, 4 - CONT #4#4 @ 24" OC MIN (2)

EACH SIDE OF REPAIRCOUPLING, MIN 3" CLR

GRAVEL BEDDING

CRACKED PIPE SECTION

DISTRICT PIPE

NOMINAL DIAMETER (IN) A (IN) ENCASEMENT

24" OR LESS 6 OD + 12

33" OR LESS 8 OD + 16

39" OR LESS 10 OD + 20

42" OR LARGER 12 OD + 24

2 x EXISTING PIPE ODBUT NOT LESS THAN 12"

A

ND-30 Cracked Pipe Repair

NORTH DAVIS SEWER DISTRICT

Revision 1, Adopted 8/14/2014

Page 32: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

ND-31 Structural Support at Crossings 1 of 2

NORTH DAVIS SEWER DISTRICT

Revision 3, Adopted 4/18/2018

6" M

IN24

" MA

X(S

EE

NO

TE3

AN

D 4

)

1/2

OD

6" MIN6" MINOD

12"MIN

12"MIN

1/2" FELT EXPANSIONJOINT FILLER

EXIST PIPE

CONCRETE PER NOTE 1 & 2

1/2"EXPANSION JOINTFILLER MATERIAL ALLAROUND, SEE NOTE 2

PROVIDE BEDDING PER DISTRICTREQUIREMENTS

NEW SEWERPIPE

6" SCH 80 PVCDRAIN HOLEFILL W/ PEAGRAVEL (TYP)

TRENCH WIDTH

EXISTING PIPE OVER NEW SEWER MAIN

NOTES:

1. CONCRETE SHALL BE TYPE II/V PORTLAND CEMENT PERASTM C150 WITH A MINIMUM COMPRESSIVE STRENGTH OF300 PSI PER ASTM C39. NO ADDITIVES SHALL BEPERMITTED WITHOUT PRIOR APPROVAL BY THE DISTRICT.

2. CONCRETE OR FLOWABLE FILL SHALL NOT BE INSTALLEDTO SUPPORT OR BACK FILL ASBESTOS CEMENT PIPE (ACP).WHERE ACP REQUIRES SUPPORT OR BACKFILL, PROVIDE3/4-INCH MINUS OR IMPORTED SAND MATERIALS.

Page 33: NORTH DAVIS SEWER DISTRICT STANDARD COLLECTION DETAILS std details.pdf · Minimum internal diameter for FRP tee base manholes to be installed on FRP mainlines shall be reviewed and

NOTES:

1. INSTALL #15 FELT OR NEOPRENE WATERSTOPAROUND NEW WATER PIPE PRIOR TO THEPOUR OF CONCRETE ENCASEMENT TOPREVENT BONDING.

2. BACKFILL TO BE BROUGHT UP UNIFORMLY ONBOTH SIDES OF CONC. SUPPORT.

3. THIS DETAIL SHALL APPLY WHERE VERTICALCLEARANCE OUTSIDE TO OUTSIDE OF SEWERPIPE OR LATERAL IS LESS THAN 24 INCHES.

4. WASTEWATER LINES SHALL BE INSTALLEDBELOW POTABLE WATER LINES. A MINIMUMSEPARATION OF 18 INCHES BETWEEN THEBOTTOM OF THE POTABLE WATER LINE ANDTHE TOP OF THE WASTEWATER LINE SHALL BEMAINTAINED. WHERE A POTABLE WATERLINECROSSES UNDER A WASTEWATER OR STORMLINE, A FULL LENGTH OF PIPE SHALL BECENTERED ABOVE THE WATER LINE SO THATBOTH JOINTS WILL BE AS FAR FROM THEPOTABLE WATER LINE AS POSSIBLE.ADDITIONAL MITIGATION MEASURES MAY BEREQUIRED PER UTAH DEQ AND UTAH STATECODE R309-105-6(2)(b).

5. CONCRETE SHALL BE TYPE II/V PORTLANDCEMENT PER ASTM C150 WITH A MINIMUMCOMPRESSIVE STRENGTH OF 300 PSI PERASTM C39. NO ADDITIVES SHALL BEPERMITTED WITHOUT PRIOR APPROVAL BYTHE DISTRICT.

6. CONCRETE OR FLOWABLE FILL SHALL NOT BEINSTALLED TO SUPPORT OR BACK FILLASBESTOS CEMENT PIPE (ACP). WHERE ACPREQUIRES SUPPORT OR BACKFILL, PROVIDE3/4-INCH MINUS OR IMPORTED SANDMATERIALS.

ND-31 Structural Support at Crossings 2 of 2

NORTH DAVIS SEWER DISTRICT

Revision 3, Adopted 4/18/2018

6"M

IN

SP

RIN

GLI

NE6"MIN6"MIN

D

-

12"MIN

12"MIN TRENCH WIDTH

CONCRETE PER NOTE 5 & 6

1/2"EXPANSION JOINTFILLER MATERIAL ALLAROUND, SEE NOTE 2

EXIST PIPE

1/2" FELT EXPANSIONJOINT FILLER IFCONCRETE EXTENDUP TO BOTTOM OFNEW PIPE

DO NOT DISTURBEXISTING PIPEBEDDING BELOWSPRINGLINE OF PIPE

UNDISTURBED SOIL (TYP)

NEW SEWER PIPE

SECTION D

EXISTING PIPE UNDER NEW SEWER MAIN

24" M

AX

(SE

E N

OTE

3 A

ND

4)

OD