TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERSSPLIT-TYPE, AIR CONDITIONERS
CONTENTS1. TECHNICAL CHANGES·································32. SAFETY PRECAUTION··································43. COMBINATION OF INDOOR AND OUTDOOR UNITS ···64. PART NAMES AND FUNCTIONS ··················75. SPECIFICATIONS···········································86. DATA ·····························································157. OUTLINES AND DIMENSIONS····················188. WIRING DIAGRAM·······································229. WIRING SPECIFICATIONS ··························26
10. REFRIGERANT SYSTEM DIAGRAM ··············2711. TROUBLESHOOTING···································3112. DISASSEMBLY PROCEDURE ·····················3613. PARTS LIST ··················································4014. OPTIONAL PARTS························Back Cover
Outdoor unit[model names]
PUH-P1VGAA
PUH-P1.6VGAA PU-P1.6VGAA
PUH-P1.6YGAA PU-P1.6YGAA
PUH-P2VGAA PU-P2VGAA
PUH-P2YGAA PU-P2YGAA
PUH-P2.5VGAA PU-P2.5VGAA
PUH-P2.5YGAA PU-P2.5YGAA
PUH-P3VGAA PU-P3VGAA
PUH-P3YGAA PU-P3YGAA
PUH-P4VGAA PU-P4VGAA
PUH-P4YGAA PU-P4YGAA
PUH-P5YGAA PU-P5YGAA
PUH-P6YGAA PU-P6YGAA
No.OC261REVISED EDITION-B
R407C
Service Ref. is on page 2.
Revision:• [PUH-5, 6YGAA1.UK PU-5, 6YGAA1.UK]
TECHNICAL CHANGES, SPECIFICATIONS,DATA and PARTS LIST have been partiallymodified.COMPRESSOR CONVERSION KIT(TFD-230)has been added to the PARTS LIST(page 69).
• Please void OC261 REVISED EDITION-A.
Model name indication
OC261-B--1.qxp 03.2.19 3:07 PM Page 1
2
[Service Ref.]
PUH-P1VGAA.UKPUH-P1.6VGAA.UK PU-P1.6VGAA.UKPUH-P1.6YGAA.UK PU-P1.6YGAA.UKPUH-P2VGAA.UK PU-P2VGAA.UKPUH-P2YGAA.UK PU-P2YGAA.UKPUH-P2.5VGAA.UK PU-P2.5VGAA.UKPUH-P2.5YGAA.UK PU-P2.5YGAA.UKPUH-P3VGAA.UK PU-P3VGAA.UKPUH-P3YGAA.UK PU-P3YGAA.UKPUH-P4VGAA.UK PU-P4VGAA.UKPUH-P4YGAA.UK PU-P4YGAA.UKPUH-P5YGAA.UK PU-P5YGAA.UKPUH-P6YGAA.UK PU-P6YGAA.UK
PUH-P1VGAA1.UKPUH-P1.6VGAA1.UK PU-P1.6VGAA 1.UKPUH-P1.6YGAA1.UK PU-P1.6YGAA 1.UKPUH-P2VGAA1.UK PU-P2VGAA 1.UKPUH-P2YGAA1.UK PU-P2YGAA 1.UKPUH-P2.5VGAA1.UK PU-P2.5VGAA 1.UKPUH-P2.5YGAA1.UK PU-P2.5YGAA 1.UKPUH-P3VGAA1.UK PU-P3VGAA 1.UKPUH-P3YGAA1.UK PU-P3YGAA 1.UKPUH-P4VGAA1.UK PU-P4VGAA 1.UKPUH-P4YGAA1.UK PU-P4YGAA 1.UKPUH-P5YGAA1.UK PU-P5YGAA 1.UKPUH-P6YGAA1.UK PU-P6YGAA 1.UK
OC261-B--1.qxp 03.2.19 3:07 PM Page 2
3
1 TECHNICAL CHANGES
(REVISED EDITION-A)PUH-P1, 1.6, 2, 2.5, 3, 4VGAA.UK ➔ PUH-P1, 1.6, 2, 2.5, 3, 4VGAA 1.UKPUH-P1.6, 2, 2.5, 3, 4YGAA.UK ➔ PUH-P1.6, 2, 2.5, 3, 4YGAA 1.UKPU-P1.6, 2, 2.5, 3, 4VGAA.UK ➔ PU-P1.6, 2, 2.5, 3, 4VGAA 1.UKPU-P1.6, 2, 2.5, 3, 4YGAA.UK ➔ PU-P1.6, 2, 2.5, 3, 4YGAA 1.UK● Strainer (#50) for stop valve of liquid pipe side and Filter Drier are not used.
(REVISED EDITION-A)PUH-P1, 1.6, 2, 2.5, 3, 4VGAA.UK ➔ PUH-P1, 1.6, 2, 2.5, 3, 4VGAA 1.UKPUH-P1.6, 2, 2.5, 3, 4, 5, 6YGAA.UK ➔ PUH-P1.6, 2, 2.5, 3, 4, 5, 6YGAA 1.UKPU-P1.6, 2, 2.5, 3, 4VGAA.UK ➔ PU-P1.6, 2, 2.5, 3, 4VGAA 1.UKPU-P1.6, 2, 2.5, 3, 4, 5, 6YGAA.UK ➔ PU-P1.6, 2, 2.5, 3, 4, 5, 6YGAA 1.UK● Microcomputer of Outdoor Controller Board has changed since Filter Drier is not used.
(The limit of discharging temperature has been added.)
(REVISED EDITION-A)PUH-P5YGAA.UK ➔ PUH-P5YGAA 1.UK● The method of connecting the Compressor’s terminals has changed from Faston type to
Screw type.
(REVISED EDITION-B)PUH-P5YGAA 1.UK PUH-P6YGAA 1.UKPU-P5YGAA 1.UK PU-P6YGAA 1.UK● Compressor has changed due to the change in refrigerant oil.
Refrigerant oil : 3MA-POE ➔ 3MAW-POECompressor model : ZR61KCE-TFD-522 ➔ ZR61KCW-TFD-522
ZR72KCE-TFD-522 ➔ ZR72KCW-TFD-522
OC261-B--1.qxp 03.2.19 3:07 PM Page 3
4
2 SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refriger-ant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil willresult.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just beforebrazing. (Store elbows and other joints in a plastic bag.) -If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performancemay drop.
· Do not use a refrigerant other than R407C.-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant.(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.-If water is mixed in the R407C, the refrigerant oil may deteriorate.-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.-The drier for R407C refrigerant is pre-attached to outdoor unit refrigerant circuit.-Some drier in the field are not in conformity with R407C refrigerant.
OC261-B--1.qxp 03.2.19 3:07 PM Page 4
5
[3] Refrigerant recharging(1) Refrigerant recharging process
1Direct charging from the cylinder.·R407C cylinder are available on the market has a syphon pipe.·Leave the syphon pipe cylinder standing and recharge it.(By liquid refrigerant)
(2) Recharge in refrigerant leakage case·After recovering the all refrigerant in the unit, proceed to working.·Do not release the refrigerant in the air.·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
Gravimeter
Unit
[1] Service toolsUse the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale
4 Gas leak detector ·Use the detector for R407C.
5 Adapter for reverse flow check. ·Attach on vacuum pump.
6 Refrigerant charge base.
7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
[2] Notice on repair·After recovering the all refrigerant in the unit, perform repair work.·Do not release refrigerant in the air.·After completing the repair work, recharge the specified amount of liquid refrigerant.
OC261-B--1.qxp 03.2.19 3:07 PM Page 5
6
3 COMBINATION OF INDOOR AND OUTDOOR UNITS
Heat pump typeOutdoor unit
PUH-P • GAA.UKPUH-P • GAA1.UK
Cooling only type
PU-P • GAA.UKPU-P • GAA1.UK
PEHD-P·EAHPCH-P·GAH1
PKH-P·GALH1
PKH-P·FALH2
PSH-P·GAH1
PLH-P·KAH1.UKPLH-P·AAH1.UKPEAD-P·EAPCA-P·GA1
PKA-P·GAL1
PKA-P·FAL2
PSA-P·GA1
PLA-P·KA1.UKPLA-P·AA1.UKPMH-P·BA1
PMH-P·BA2
PCA-P·HA
MEE 01K048OC182OC176OC175OC212OC235OC236MEE 01K048OC182OC176OC175OC212OC240OC241OC238OC279OC289
Y
—
—
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
V
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
Indoor unit
1.6ServiceManual No.
Service Ref.2 2.5 3 4 5 6 1.6 2 2.5 3 4 5 6
Heat
pu
mp
wit
hele
ctr
ic h
eate
rH
eat
pu
mp
wit
ho
ut
ele
ctr
ic h
eate
r o
rC
oo
lin
g o
nly
REVISED EDITION-BREVISED EDITION-BREVISED EDITION-B
REVISED EDITION-B
REVISED EDITION-AREVISED EDITION-AREVISED EDITION-A
REVISED EDITION-BREVISED EDITION-B
REVISED EDITION-B
REVISED EDITION-AREVISED EDITION-AREVISED EDITION-A
1V
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
—
—
—
—
V
—
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Y
—
—
—
—
—
—
—
—
—
—
—
—
—
OC261-B--1.qxp 03.2.19 3:07 PM Page 6
7
4 PART NAMES AND FUNCTIONS
CHARGELESS SYSTEMPRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.(Max.20m(PU(H)-P1~P2.5) / 30m(PU(H)-P3~P6))
The refrigerant circuit with LEV(Linear Expansion Valve) and a large accumulator always control the optimal refrigerantlevel regardless of the length (20/30m max. and 5m min.) of piping. The additional refrigerant charging work duringinstallation often causes problems. Heretofore it is completely eliminated. This unique system improves the qualityand reliability of the work done.It also helps to speed up the installation time.
Air intake
Air outlet(Expels warm air during cooling)
Air intake
Air outlet
Air intake
Air outlet
Air intake
Air outlet
PUH-P1VGAA.UKPU(H)-P1.6VGAA.UKPU(H)-P1.6YGAA.UK
PUH-P1VGAA1.UKPU(H)-P1.6VGAA1.UKPU(H)-P1.6YGAA1.UK
PU(H)-P2VGAA.UK PU(H)-P2YGAA.UKPU(H)-P2.5VGAA.UK PU(H)-P2.5YGAA.UKPU(H)-P3VGAA.UK PU(H)-P3YGAA.UK
PU(H)-P2VGAA1.UK PU(H)-P2YGAA 1.UKPU(H)-P2.5VGAA1.UK PU(H)-P2.5YGAA 1.UKPU(H)-P3VGAA1.UK PU(H)-P3YGAA 1.UK
PU(H)-P4VGAA.UKPU(H)-P4YGAA.UK
PU(H)-P4VGAA1.UKPU(H)-P4YGAA1.UK
PU(H)-P5YGAA.UKPU(H)-P6YGAA.UK
PU(H)-P5YGAA1.UKPU(H)-P6YGAA1.UK
OC261-B--1.qxp 03.2.19 3:07 PM Page 7
8
5 SPECIFICATIONS
kWAA
kW
W
kWK/min(CFM)
dBdB
mm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
ModelMotor outputStarter typeProtection devices
Crankcase heaterHeat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise level
Dimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingHeating
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limitUpper limitLower limit
IndoorD.B. 35˚C, W.B. 22.5˚CD.B. 19˚C, W.B. 15˚C
D.B. 28˚CD.B. 17˚C
OutdoorD.B. 46˚CD.B. -5˚C
D.B. 24˚C, W.B. 18˚CD.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref. PUH-P1VGAA.UKPUH-P1VGAA1.UK
PUH-P1.6VGAA / YGAA.UKPUH-P1.6VGAA1 / YGAA1.UK
Cooling
1.114.92
Single,50Hz,220-230-240V
30
RE189VHSMT0.9
45(1,590)
4648
50(110)
1.7(3.8)
6.35(1/4)12.7(1/2)
Max. 30mMax. 30m
Munsell 5Y 7/1Linear Expansion Valve
Hermetic
Line start
30Plate fin coil
Propeller (direct) o 10.07
Reverse cycle
900(35-7/16)330+20(13+3/4)
650(25-5/8)
R407C
0.57(Ester)MEL56
FlaredFlared
Heating
1.024.52
Cooling
1.597.36 / 2.49
Single,50Hz,220-230-240V / 3-ph,50Hz,380-400-415V
36/20
RE277VHSMT/RE277YFKM1.3
45(1,590)
4749
55(121)
2.5(5.5)
9.52(3/8)15.88(5/8)
Max. 40mMax. 40m
Heating
1.647.59 / 2.56
Internal thermostatHP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
Internal thermostatHP switchDischarge thermo
1. Heat pump
OC261-B--1.qxp 03.2.19 3:07 PM Page 8
9
kWAA
kW
W
kWK/min(CFM)
dBdB
mm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
ModelMotor outputStarter typeProtection devices
Crankcase heaterHeat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise level
Dimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingHeating
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limitUpper limitLower limit
IndoorD.B. 35˚C, W.B. 22.5˚CD.B. 19˚C, W.B. 15˚C
D.B. 28˚CD.B. 17˚C
OutdoorD.B. 46˚CD.B. -5˚C
D.B. 24˚C, W.B. 18˚CD.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref. PUH-P2VGAA / YGAA.UKPUH-P2VGAA1 / YGAA1.UK
PUH-P2.5VGAA / YGAA.UKPUH-P2.5VGAA1 / YGAA1.UK
Cooling
2.2910.26 / 3.70
62 / 31
NE36VMJMT / NE36YEKMT1.6
55(1,940)
49
71(157)
2.6(5.7)
Max. 40mMax. 40m
Single, 50Hz, 220-230-240V/3-ph, 50Hz, 380-400-415V(4wires)
Munsell 5Y 7/1Linear Expansion Valve
Hermetic
Line start
38Plate fin coil
Propeller (direct) o 10.07
Reverse cycle48
900(35-7/16)330+20(13+3/4)
855(33-5/8)
R407C
1.2 (Ester)MEL569.52(3/8)15.88(5/8)
FlaredFlared
Heating
2.3610.57 / 3.82
Cooling
2.7711.90 / 4.48
77 / 35
NE41VMJMT / NE41YEKMT 1.9
50(1,770)
50
82(181)
3.1(6.8)
Max. 50mMax. 50m
Heating
2.6811.51 / 4.34
Internal thermostatHP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
OC261-B--1.qxp 03.2.19 3:07 PM Page 9
10
kWAA
kW
W
kWK/min(CFM)
dBdB
mm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
ModelMotor outputStarter typeProtection devices
Crankcase heaterHeat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise level
Dimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingHeating
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limitUpper limitLower limit
IndoorD.B. 35˚C, W.B. 22.5˚CD.B. 19˚C, W.B. 15˚C
D.B. 28˚CD.B. 17˚C
OutdoorD.B. 46˚CD.B. -5˚C
D.B. 24˚C, W.B. 18˚CD.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref. PUH-P4VGAA / YGAA.UKPUH-P4VGAA1 / YGAA1.UK
PUH-P3VGAA / YGAA.UKPUH-P3VGAA1 / YGAA1.UKCooling
3.2714.81 / 5.29
93 / 47
NE52VNJMT / NE52YDKMT2.5
Propeller (direct) o 10.07
50(1,770)
4951
855(33-5/8)82(181)
3.3(7.3)
15.88(5/8)
Single, 50Hz, 220-230-240V/3-ph, 50Hz, 380-400-415V(4wires)
Munsell 5Y 7/1Linear Expansion Valve
Hermetic
Line start
38Plate fin coil
Reverse cycle
900(35-7/16)330+20(13+3/4)
R407C
1.3 (Ester)MEL569.52(3/8)
FlaredFlared
Max. 50mMax. 50m
Heating
3.4815.76 / 5.63
Cooling
3.4315.71 / 5.55
99 / 49
NE56VNJMT / NE56YDKMT2.7
Propeller (direct) o 20.07+0.0785(3,000)
5153
1,260(49-5/8)96(212)
4.0(8.8)
19.05(3/4)
Heating
3.6216.58 / 5.86
Internal thermostatHP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
OC261-B--1.qxp 03.2.19 3:07 PM Page 10
11
kWAA
kW
W
kWK/min(CFM)
dB(A)dB(A)
mm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
Model
Motor outputStarter typeProtection devicesCrankcase heater
Heat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise level
Dimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingHeating
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 3 phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limitUpper limitLower limit
IndoorD.B. 35˚C, W.B. 22.5˚CD.B. 19˚C, W.B. 15˚C
D.B. 28˚CD.B. 17˚C
OutdoorD.B. 46˚CD.B. -5˚C
D.B. 24˚C, W.B. 18˚CD.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref. PUH-P5YGAA.UKPUH-P5YGAA1.UK
Cooling
5.589.03
74
ZR72KCW-TFD-522
4.2
100(3,530)
5758
4.9(10.8)1.774 (Ester) 3MAW-POE
3-ph, 50Hz, 380-400-415V(4wires)
Munsell 5Y 7/1Linear Expansion Valve
Hermetic
Line startInternal thermostat, thermal relay, HP switch, Discharge thermo
38Plate fin coil
Propeller (direct) o 20.07 +0.07
Reverse cycle
1,050(41-5/16)330+20(13+3/4)
1,260(49-5/8)122(269)R407C
9.52(3/8)19.05(3/4)
FlaredFlared
Max. 50mMax. 50m
Heating
5.919.56
Cooling
4.707.60
65.5
ZR61KCE-TFD-230 (YGAA.UK) ZR61KCW-TFD-522 (YGAA1.UK)
3.5
95(3,360)
5556
4.6(10.1)1.690 (Ester) 3MAW-POE
Heating
5.048.15
PUH-P6YGAA.UKPUH-P6YGAA1.UK
OC261-B--1.qxp 03.2.19 3:07 PM Page 11
12
kWAA
kW
W
kWK/min(CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
ModelMotor outputStarter typeProtection devicesCrankcase heater
Heat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise level
Dimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingWDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 1 phase 240V 50Hz / 3phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limit
IndoorD.B. 35˚C, W.B. 22.5˚CD.B. 19˚C, W.B. 15˚C
OutdoorD.B. 46˚CD.B. -5˚C
Cooling
Service Ref. PU-P1.6VGAA / YGAA.UKPU-P1.6VGAA1 / YGAA1.UK
PU-P2VGAA / YGAA.UKPU-P2VGAA1 / YGAA1.UK
PU-P2.5VGAA / YGAA.UKPU-P2.5VGAA1 / YGAA1.UK
Cooling
1.597.36 / 2.49
36 / 20
RE277VHSMT/RE277YFKM1.3
30
45(1,590)
47
650(25-5/8)55(121)
2.5(5.5)0.57 (Ester)MEL56
Single, 50Hz, 220-230-240V / 3-ph, 50Hz, 380-400-415V(4wires)2.29
10.26 / 3.7062 / 31
Munsell 5Y 7/1Linear Expansion Valve
HermeticNE36VMJMT/NE36YEKMT
1.6Line start
Internal thermostat, HP switch, Discharge thermo / Thermal relay,Discharge thermo,HP switch
Plate fin coilPropeller (direct) o 1
0.0755(1,940)
—
900(35-7/16)330+20(13+3/4)
71(157)R407C2.6(5.7)
9.52(3/8)15.88(5/8)
FlaredFlared
Cooling
38
48
855(33-5/8)
1.2 (Ester)MEL56
2.7711.90 / 4.48
77 / 35
NE41VMJMT/NE41YEKMT1.9
50(1,770)
82(181)
3.1(6.8)
Max. 50mMax. 50m
Cooling
Max. 40mMax. 40m
2. Cooling only type
OC261-B--1.qxp 03.2.19 3:07 PM Page 12
13
kWAA
kW
W
kWK/min(CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
ModelMotor outputStarter typeProtection devices
Crankcase heaterHeat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise levelDimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingWDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 1 phase 240V 50Hz/3 phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limit
IndoorD.B. 35˚C , W.B. 22.5˚CD.B. 19˚C, W.B. 15˚C
Outdoor D.B. 46˚CD.B. -5˚C
Cooling
Service Ref. PU-P3VGAA / YGAA.UKPU-P3VGAA1 / YGAA1.UK
PU-P4VGAA / YGAA.UKPU-P4VGAA1 / YGAA1.UK
Cooling
3.2714.81 / 5.29
93 / 47
NE52VNJMT / NE52YDKMT2.5
Propeller (direct) o 10.07
50(1,770)
49
855(33-5/8)82(181)
3.3(7.3)
15.88(5/8)
Single, 50Hz, 220-230-240V/3-ph, 50Hz, 380-400-415V(4wires)
Munsell 5Y 7/1Linear Expansion Valve
Hermetic
Line start
38Plate fin coil
—
900(35-7/16)330+20(13+3/4)
R407C
1.3 (Ester)MEL569.52(3/8)
FlaredFlared
Max. 50mMax. 50m
Cooling
3.4315.71 / 5.55
99 / 49
NE56VNJMT / NE56YDKMT2.7
Propeller (direct) o 20.07+0.0785(3,000)
51
1,260(49-5/8)96(212)
4.0(8.8)
19.05(3/4)
Internal thermostatHP switch
Discharge thermo
Thermal relay HP switch Discharge thermo
OC261-B--1.qxp 03.2.19 3:07 PM Page 13
14
kWAA
kW
W
kWK/min(CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
FunctionPower supply (phase, cycle, voltage)
InputRunning currentStarting current
External finishRefrigerant controlCompressor
Model
Motor outputStarter typeProtection devicesCrankcase heater
Heat exchangerFan Fan(drive) o No.
Fan motor outputAirflow
Defrost methodNoise levelDimensions
WeightRefrigerant
ChargeOil (Model)
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
OU
TD
OO
R U
NIT
REF
RIG
ERAN
T PI
PIN
G
CoolingWDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Notes1. Rating Conditions (ISO T1)Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)Refrigerant piping length (one way) : 5m (16ft)
3. Above data based on indicated voltageIndoor Unit 1 phase 240V 50HzOutdoor Unit 3 phase 415V 50Hz
2. Guaranteed operating range
Upper limitLower limit
IndoorD.B. 35˚C , W.B.22.5˚CD.B. 19˚C, W.B. 15˚C
OutdoorD.B. 46˚CD.B. -5˚C
Cooling
Service Ref. PU-P5YGAA.UKPU-P5YGAA1.UK
PU-P6YGAA.UKPU-P6YGAA1.UK
Cooling
5.589.0374
ZR72KCW-TFD-522
4.2
100(3,530)
57
4.9(10.8)1.774 3MAW-POE
3-ph, 50Hz, 380-400-415V(4wires)
Munsell 5Y 7/1Linear Expansion Valve
Hermetic
Line startInternal thermostat, thermal relay, HP switch, Discharge thermo
38Plate fin coil
Propeller (direct) o 20.07+0.07
—
1,050(41-5/16)330+20(13+3/4)
1,260(49-5/8)122(269)R407C
9.52(3/8)19.05(3/4)
FlaredFlared
Max. 50mMax. 50m
Cooling
4.707.6065.5
ZR61KCE-TFD-230 (YGAA.UK) ZR61KCW-TFD-522 (YGAA1.UK)
3.5
95(3,360)
55
4.6(10.1)1.690 3MAW-POE
OC261-B--1.qxp 03.2.19 3:07 PM Page 14
15
6 DATA
1. REFILLING REFRIGERANT CHARGE (R407C : kg)
2. COMPRESSOR TECHNICAL DATA
Piping length (one way)10m 20m 30m 40m 50m
Factorycharged
1.6
2.4
2.4
2.5
2.5
2.9
2.9
2.9
2.9
3.4
3.4
4.0
4.3
1.7
2.5
2.5
2.6
2.6
3.1
3.1
3.1
3.1
3.7
3.7
4.3
4.6
1.8
2.6
2.6
3.1
3.1
3.3
3.3
3.3
3.3
4.0
4.0
4.6
4.9
—
3.0
3.0
3.7
3.7
3.9
3.9
3.9
3.9
4.7
4.7
5.3
5.6
—
—
—
—
—
4.5
4.5
4.5
4.5
5.4
5.4
6.0
6.3
1.7
2.5
2.5
2.6
2.6
3.1
3.1
3.3
3.3
4.0
4.0
4.6
4.9
Service Ref.
PUH-P1VGAA(1).UK
PUH-P1.6VGAA(1).UKPU-P1.6VGAA(1).UKPUH-P1.6YGAA(1).UKPU-P1.6YGAA(1).UKPUH-P2VGAA(1).UKPU-P2VGAA(1).UKPUH-P2YGAA(1).UKPU-P2YGAA(1).UKPUH-P2.5VGAA(1).UKPU-P2.5VGAA(1).UKPUH-P2.5YGAA(1).UKPU-P2.5YGAA(1).UKPUH-P3VGAA(1).UKPU-P3VGAA(1).UKPUH-P3YGAA(1).UKPU-P3YGAA(1).UKPUH-P4VGAA(1).UKPU-P4VGAA(1).UKPUH-P4YGAA(1).UKPU-P4YGAA(1).UKPUH-P5YGAA(1).UKPU-P5YGAA(1).UKPUH-P6YGAA(1).UKPU-P6YGAA(1).UK
Compressor model
WindingResistance
( " )
U-V(R-C)U-W(S-C)
W-V
U-V(R-C)U-W(S-C)
W-V
RE277VHSMT RE277YFKM
Unit PUH-P1.6VGAA(1).UKPU-P1.6VGA(1).UK
PUH-P2VGAA(1).UKPU-P2VGAA(1).UK
NE36VMJMT
1.80
3.00
—
10.8
10.8
10.8
5.01
5.01
5.01
NE36YEKMT
0.89
2.03
—
Unit
Compressor model
WindingResistance
( " )
PUH-P5YGAA(1).UKPU-P5YGAA(1).UK
PUH-P6YGAA(1).UKPU-P6YGAA(1).UK
ZR61KCE-TFDZR61KCW-TFD
(at 25°C) (at 25°C)
(at 20°C)[Except P5, P6]
ZR72KCW-TFD
0.628 ~ 0.722
0.628 ~ 0.722
0.628 ~ 0.722
0.517
0.517
0.517
PUH-P4YGAA(1).UKPU-P4YGAA(1).UK
NE56YDKMT
3.32
3.32
3.32
PUH-P3VGAA(1).UKPU-P3VGAA(1).UK
NE52VNJMT
0.64
1.67
—
3.59
3.59
3.59
PUH-P3YGAA(1).UKPU-P3YGAA(1).UK
PUH-P1VGAA(1).UK PUH-P1.6YGAA(1).UKPU-P1.6YGA(1).UK
PUH-P2YGAA(1).UKPU-P2YGAA(1).UK
U-V(R-C)U-W(S-C)
W-V
Unit
Compressor model
WindingResistance
( " )
PUH-P2.5VGAA(1).UKPU-P2.5VGAA(1).UK
NE41VMJMT
PUH-P2.5YGAA(1).UKPU-P2.5YGAA(1).UK
NE41NEKMT
5.00
5.00
5.00
PUH-P4VGAA(1).UKPU-P4VGAA(1).UK
NE56VNJMT
0.62
1.59
—
RE189VHSMT
2.79
3.36
—
0.87
2.22
—
NE52YDKMT
This is a dividing line between the ones thatneed no refrigerant charge and the ones thatneed additional refrigerant charge.
OC261-B--1.qxp 03.2.19 3:07 PM Page 15
16
1m
1mMICROPHONE UNIT
GROUND
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
PUH-P1.6VGAA(1).UKPUH-P1.6YGAA(1).UKPU-P1.6VGAA(1).UKPU-P1.6YGAA(1).UK
COOLINGMODE
HEATING47
SPL(dB)
49
LINE
3. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLINGMODE
HEATING
SPL(dB) LINEPUH-P2VGAA(1).UKPUH-P2YGAA(1).UKPU-P2VGAA(1).UKPU-P2YGAA(1).UK
4849
90
80
70
60
50
40
30
20
10OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
COOLINGMODE
HEATING
SPL(dB) LINEPUH-P2.5VGAA(1).UKPUH-P2.5YGAA(1).UKPU-P2.5VGAA(1).UKPU-P2.5YGAA(1).UK
4850
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
PUH-P1VGAA(1).UKCOOLING
MODE
HEATING46
SPL(dB)
48
LINE
OC261-B--1.qxp 03.2.19 3:07 PM Page 16
17
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLINGMODE
HEATING
SPL(dB) LINE5556
PUH-P5YGAA(1).UKPU-P5YGAA(1).UK
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLINGMODE
HEATING
SPL(dB) LINE5758
PUH-P6YGAA(1).UKPU-P6YGAA(1).UK
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLINGMODE
HEATING
SPL(dB) LINE5153
PUH-P4VGAA(1).UKPUH-P4YGAA(1).UKPU-P4VGAA(1).UKPU-P4YGAA(1).UK
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLINGMODE
HEATING
SPL(dB) LINE4951
PUH-P3VGAA(1).UKPUH-P3YGAA(1).UKPU-P3VGAA(1).UKPU-P3YGAA(1).UK
OC261-B--1.qxp 03.2.19 3:07 PM Page 17
18
7 OUTLINES AND DIMENSIONS
PUH-P1VGAA(1).UKPUH-P1.6VGAA(1).UKPUH-P1.6YGAA(1).UKPU-P1.6VGAA(1).UKPU-P1.6YGAA(1).UK
32
1T
SR
w1 248w1 196
500
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Rig
ht P
ipin
g H
ole
(Kno
ck-O
ut)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Term
inal
Con
nect
ions
Left.
..Pow
er s
uppl
y W
iring
Rig
ht..I
ndoo
r/O
utdo
or W
iring
70
70
155
155
155
109
30215 85
Bot
tom
Pip
ing
Hol
e(K
nock
-Out
)
Dra
in H
ole
(5-[
33ho
les)
18
18
424
900
318
Han
dle
for
mov
ing
Ear
th P
oint
Ser
vice
Pan
el
Fro
nt P
ipin
g C
over
Rea
r P
ipin
g C
over
1 2
Sid
e A
irIn
take
200
200
53
370(14)
412
29
330
55
4351
Rea
r Air
Inta
ke
Air
Dis
char
ge
2-U
Sha
ped
notc
hed
hole
s(F
ound
atio
n B
olt M
10)
2-12
x40
oval
hol
es(F
ound
atio
n B
olt M
10)
20
28
58
Inst
alla
tion
Fee
t
Rea
rA
irIn
take
Sid
eA
irIn
take
Han
dle
for
mov
ing
3
230
220
220
230
637650
3030
Rea
r Tr
unki
ng H
ole
(Kno
ck-O
ut)
< R
ear
Sid
e >
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
40
33
2255
6863
65
92R
ear
Pip
ing
Hol
e(K
nock
-Out
)
[92
Pip
ing
Kno
ck-O
ut H
ole
Det
ails
. .
Ref
riger
ant G
AS
pip
e co
nnec
tion
(FLA
RE
)P1.
6V(Y
)GA
A: [
15.8
8 (5
/8F)
. .
Ref
riger
ant L
IQU
ID p
ipe
conn
ectio
n (F
LAR
E)P
1.6V
(Y)G
AA
: [9.
52 (3
/8F)
. .
Hei
ght o
f ST
OP
VA
LVE
con
nect
ion
loca
tion.
1 2
Fro
nt T
runk
ing
Hol
e(K
nock
-Out
)
< R
ight
Sid
e >
< F
ront
Sid
e >
Exp
lana
tion
of N
otes 40
6863
2255
65
92
3327100
50
50
100
33
[92
Fro
nt P
ipin
g H
ole
(Kno
ck-O
ut)
5540
3 .
. 3-[
3.6
hole
s (f
or s
ecur
ing
the
top
of th
e un
it)
T
hese
hol
es a
re p
rovi
ded
for
case
s w
here
the
unit
mus
t
be
sec
ured
by
the
base
AN
D b
y th
e to
p su
rfac
e.
U
se S
elf T
appi
ng s
crew
s 5
x L1
5 or
less
.(O
btai
ned
loca
lly)
w1
. .
Ref
riger
ant G
AS
pip
e co
nnec
tion
(FLA
RE
)P1V
GA
A
: [
12.7
(1/2
F)
. .
Ref
riger
ant L
IQU
ID p
ipe
conn
ectio
n (F
LAR
E)P
1VG
AA
: [
6.35
(1/4
F)
1 2
Ove
r 10m
m
F R E E
Ove
r 500
mm
Less than30mm
FR
EE
SPA
CE
(A
roun
d th
e U
nit)
Pip
ing
and
wiri
ng c
onne
ctio
nsca
n be
mad
e fr
om 4
dire
ctio
ns:
Fro
nt, R
ight
, Rea
r an
d B
elow
.
FOUN
DATI
ON
BOLT
S1 T
he d
iagr
am b
elow
sho
ws
aba
sic
exam
ple.
Exp
lana
tion
of p
artic
ular
det
ails
are
give
n in
the
inst
alla
tion
man
uals
etc
.
SERV
ICE
SPAC
E
Dim
ensi
ons
of s
pace
nee
ded
for s
ervi
ce a
cces
s ar
esh
own
in th
e be
low
dia
gram
.
2
Ove
r500
Over500
PIPI
NG
-WIR
ING
DIR
ECTI
ON
S4
3
FOUN
DATI
ON
<F
ound
atio
n bo
lt he
ight
>
Ple
ase
secu
re th
e un
it fir
mly
with
4 fo
unda
tion
(M10
) bo
lts.
(Bol
ts a
nd w
ashe
rs m
ust b
epu
rcha
sed
loca
lly).
Ser
vice
Spa
ce
Ove
r 100
mm
Ove
r 10m
m
Ove
r10
Over100
Unit : mm
OC261-B--1.qxp 03.2.19 3:07 PM Page 18
19
PUH-P2VGAA(1).UKPUH-P2YGAA(1).UKPUH-P2.5VGAA(1).UKPUH-P2.5YGAA(1).UKPUH-P3VGAA(1).UKPUH-P3YGAA(1).UKPU-P2VGAA(1).UKPU-P2YGAA(1).UKPU-P2.5VGAA(1).UKPU-P2.5YGAA(1).UKPU-P3VGAA(1).UKPU-P3YGAA(1).UK 3
21
TS
R
w1 376w1 428
Han
dle
Rea
rA
irIn
take
Sid
eA
irIn
take
Inst
alla
tion
Fee
t
2-U
Sha
ped
notc
hed
hole
s(F
ound
atio
n B
olt M
10)
Sid
e A
irIn
take
Rea
r Air
Inta
ke
Air
Dis
char
ge
2-12
x40
oval
hol
es(F
ound
atio
n B
olt M
10)
Term
inal
Con
nect
ions
Left.
..Pow
er s
uppl
y W
iring
Rig
ht..I
ndoo
r/O
utdo
or W
iring
Ear
th P
oint
Ser
vice
Pan
el
Rea
r P
ipin
g C
over
Fro
nt P
ipin
g C
over
Bot
tom
Pip
ing
Hol
e(K
nock
-Out
)
Dra
in H
ole
(5-[
33ho
les)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Rea
r P
ipin
g H
ole
(Kno
ck-O
ut)
< R
ear
Sid
e >
Rea
r Tr
unki
ng H
ole
(Kno
ck-O
ut)
40
33
2255
6863
65
92[92
Pip
ing
Kno
ck-O
ut H
ole
Det
ails
Fro
nt P
ipin
g H
ole
(Kno
ck-O
ut)
Fro
nt T
runk
ing
Hol
e(K
nock
-Out
)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
< F
ront
Sid
e >
Rig
ht P
ipin
g H
ole
(Kno
ck-O
ut)
< R
ight
Sid
e >
40
6863
2255
65
92
3327100
50
50
100
33
[92
5540
70
70
155
155
155
109
30215 85
18
18
627
442
900
318
Han
dle
1 2
200
500
200
53370(14)
412
29
330
55
4351
20
28
58
Han
dle
3
230
220
220
230
840
855
3030
. . .
Ref
riger
ant G
AS
pip
e co
nnec
tion
(FLA
RE
) [
15.8
8 (5
/8F
). .
. R
efrig
eran
t LIQ
UID
pip
e co
nnec
tion
(FLA
RE
) [
9.52
(3/
8F)
. . .
Hei
ght o
f ST
OP
VA
LVE
con
nect
ion
loca
tion.
. . .
3-[
3.6
hole
s (f
or s
ecur
ing
the
top
of th
e un
it)
T
hese
hol
es a
re p
rovi
ded
for
case
s w
here
the
unit
mus
t
b
e se
cure
d by
the
base
AN
D b
y th
e to
p su
rfac
e to
geth
er.
Use
Sel
f Tap
ping
scr
ews
5 x
L15
or le
ss.
(Obt
aine
d Lo
cally
)
Exp
lana
tion
of N
otes
1 w12 3
Ove
r10
Over100
Ove
r500
Over500
Ser
vice
Spa
ce
Less than
<F
ound
atio
n bo
lt he
ight
>
30mm
The
dia
gram
bel
ow s
how
s a
basi
c ex
ampl
e.E
xpla
natio
n of
par
ticul
ar d
etai
ls a
regi
ven
in th
e in
stal
latio
n m
anua
ls e
tc.
Ple
ase
secu
re th
e un
it fir
mly
with
4 fo
unda
tion
(M10
) bo
lts.
(Bol
ts a
nd w
ashe
rs m
ust b
epu
rcha
sed
loca
lly).
SERV
ICE
SPAC
E2
Pip
ing
and
wiri
ng c
onne
ctio
nsca
n be
mad
e fr
om 4
dire
ctio
ns:
Fro
nt, R
ight
, Rea
r an
d B
elow
.
Dim
ensi
ons
of s
pace
nee
ded
for s
ervi
ce a
cces
s ar
esh
own
in th
e be
low
dia
gram
.
FOUN
DATI
ON
FOUN
DATI
ON
BOLT
S3
PIPI
NG
-WIR
ING
DIR
ECTI
ON
S4
FR
EE
SPA
CE
(A
roun
d th
e U
nit)
1
F R E EO
ver 1
0mm O
ver 5
00m
m
Ove
r 10m
m
Ove
r 100
mm
Unit : mm
OC261-B--1.qxp 03.2.19 3:07 PM Page 19
20
W1 376
W1 428
3
Rea
r Pip
ing
Cov
er
Fron
t Pip
ing
Cov
er
2-U
Sha
ped
notc
hed
hole
s(F
ound
atio
n B
olt M
10)
Inst
alla
tion
Fee
t
Rea
r Air
Inta
ke
Sid
e A
irIn
take
2-12
x40
oval
hol
es(F
ound
atio
n B
olt M
10)
Term
inal
Con
nect
ions
Left.
..Pow
er s
uppl
y W
iring
Rig
ht..I
ndoo
r/O
utdo
or W
iring
[92
92
65
63 68
55 22
33
40R
ear
Trun
king
Hol
e(K
nock
-Out
)
< R
ear
Sid
e >
Rea
r P
ipin
g H
ole
(Kno
ck-O
ut)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
40 55
[92
33
100 50
50
100 27 33
92
65
55 22
63 68
40
< R
ight
Sid
e >
Rig
ht P
ipin
g H
ole
(Kno
ck-O
ut)
< F
ront
Sid
e >
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Fro
nt T
runk
ing
Hol
e(K
nock
-Out
)
Fro
nt P
ipin
g H
ole
(Kno
ck-O
ut)
Pip
ing
Kno
ck-O
ut H
ole
Det
ails
Dra
in H
ole
(5-[
33H
oles
)
Bot
tom
Pip
ing
Hol
e(K
nock
-Out
)
85215 3010
915
515
515
5
70
7018
181 2Ear
th P
oint
598
Han
dle
Ser
vice
Pan
el
318
900
1033
352
33
4351
50
200
500
200
53
370(14)
412
29
330
Air
Dis
char
ge
20
58
28
Han
dle
Rea
rA
irIn
take
Sid
eA
irIn
take
Han
dle
230
220
220
230
1246
1260
3030
PUH-P4VGAA(1).UKPUH-P4YGAA(1).UKPU-P4VGAA(1).UKPU-P4YGAA(1).UK
4PI
PIN
G-W
IRIN
G D
IREC
TIO
NS
3FO
UNDA
TIO
N BO
LTS
FOUN
DATI
ON
Pip
ing
and
wiri
ng c
onne
ctio
nsca
n be
mad
e fr
om 4
dire
ctio
ns:
Fro
nt, R
ight
, Rea
r an
d B
elow
.
SERV
ICE
SPAC
E
Ple
ase
secu
re th
e un
it fir
mly
with
4 fo
unda
tion
(M10
) bo
lts.
(Bol
ts a
nd w
ashe
rs m
ust b
epu
rcha
sed
loca
lly).
30mm
<F
ound
atio
n bo
lt he
ight
>
Less than
Over500Over100
Ser
vice
Spa
ce
Ove
r500
1F
RE
E S
PAC
E (
Aro
und
the
Uni
t)
Dim
ensi
ons
of s
pace
nee
ded
for s
ervi
ce a
cces
s ar
esh
own
in th
e be
low
dia
gram
.
2T
he d
iagr
am b
elow
sho
ws
aba
sic
exam
ple.
Exp
lana
tion
of p
artic
ular
det
ails
are
give
n in
the
inst
alla
tion
man
uals
etc
.
Ove
r10
Ove
r 10m
m
F R E E
Ove
r 500
mm
Ove
r 100
mm
Ove
r 10m
m
Exp
lana
tion
of N
otes
. .
. Ref
riger
ant G
AS
pip
e co
nnec
tion(
FLA
RE
) [
19.0
5 (3
/4F
).
. . R
efrig
eran
t LIQ
UID
pip
e co
nnec
tion(
FLA
RE
) [
9.52
(3/
8F)
. .
. Hei
ght o
f ST
OP
VA
LVE
con
nect
ion
loca
tion.
. .
. 3-[
3.6
hole
s (f
or s
ecur
ing
the
top
of th
e un
it)
T
hese
hol
es a
re p
rovi
ded
for
case
s w
here
the
unit
mus
t
be s
ecur
ed b
y th
e ba
se A
ND
by
the
top
surf
ace
toge
ther
.
U
se S
elf T
appi
ng s
crew
s 5
x L1
5 or
less
.
(
Obt
aine
d Lo
cally
)
32 w11
Unit : mm
OC261-B--1.qxp 03.2.19 3:07 PM Page 20
21
PUH-P5YGAA(1).UKPU-P5YGAA(1).UKPUH-P6YGAA(1).UKPU-P6YGAA(1).UK
398
w1 478
w1 422
1033
Ear
th P
oint
Term
inal
Con
nect
ions
Left.
..Pow
er s
uppl
y W
iring
Rig
ht..I
ndoo
r/O
utdo
or W
iring
Han
dle
Sid
eA
irIn
take
Rea
rA
irIn
take
Han
dle
Sid
e A
irIn
take
2-12
x40
oval
hol
es(F
ound
atio
n B
olt M
10)
2-U
Sha
ped
notc
hed
hole
s(F
ound
atio
n B
olt M
10)
Rea
r Air
Inta
ke
Air
Dis
char
ge
Han
dle
Ser
vice
Pan
el
Dra
in H
ole
(5-[
33H
oles
)
Bot
tom
Pip
ing
Hol
e(K
nock
-Out
)
Rea
r P
ipin
g C
over
Fro
nt P
ipin
g C
over
[92 92
65
63 68
55 22
33
40R
ear
Trun
king
Hol
e(K
nock
-Out
)
< R
ear
Sid
e >
Rea
r P
ipin
g H
ole
(Kno
ck-O
ut)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
40 55
[92
33
100
50
50
100 27 33
92
65
55 22
63 68
40
< R
ight
Sid
e >
Rig
ht P
ipin
g H
ole
(Kno
ck-O
ut)
< F
ront
Sid
e >
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Pow
er S
uppl
y W
iring
Hol
e(2
-[27
Kno
ck-O
ut)
Fro
nt T
runk
ing
Hol
e(K
nock
-Out
)
Fro
nt P
ipin
g H
ole
(Kno
ck-O
ut)
Pip
ing
Kno
ck-O
ut H
ole
Det
ails
7018
1890
148
148
148
172
3010
9
215 85598
1 2
1050
352
50
225
600
53
370(14)
29
330 20
Inst
alla
tion
Fee
t
4453
58
323
029
529
523
0
55
12461260
FOUN
DATI
ON
30mm
<F
ound
atio
n bo
lt he
ight
>
Less than
Over500Over100
Ser
vice
Spa
ce
Ove
r500
Ove
r10
The
dia
gram
bel
ow s
how
s a
basi
c ex
ampl
e.E
xpla
natio
n of
par
ticul
ar d
etai
ls a
regi
ven
in th
e in
stal
latio
n m
anua
ls e
tc.
SERV
ICE
SPAC
E1
FR
EE
SPA
CE
(A
roun
d th
e U
nit)
23
FOUN
DATI
ON
BOLT
S
Ple
ase
secu
re th
e un
it fir
mly
with
4 fo
unda
tion
(M10
) bo
lts.
(Bol
ts a
nd w
ashe
rs m
ust b
epu
rcha
sed
loca
lly).
Dim
ensi
ons
of s
pace
nee
ded
for s
ervi
ce a
cces
s ar
esh
own
in th
e be
low
dia
gram
.
4PI
PIN
G-W
IRIN
G D
IREC
TIO
NS
Pip
ing
and
wiri
ng c
onne
ctio
nsca
n be
mad
e fr
om 4
dire
ctio
ns:
Fro
nt, R
ight
, Rea
r an
d B
elow
.
Ove
r 10m
m
F R E E
Ove
r 500
mm
Ove
r 100
mm
Ove
r 10m
m
Exp
lana
tion
of N
otes
. . .
Ref
riger
ant G
AS
pip
e co
nnec
tion(
FLA
RE
) [
19.0
5 (3
/4F
). .
. R
efrig
eran
t LIQ
UID
pip
e co
nnec
tion(
FLA
RE
) [
9.52
(3/
8F)
. . .
Hei
ght o
f ST
OP
VA
LVE
con
nect
ion
loca
tion.
. . .
3-[
3.6
hole
s (f
or s
ecur
ing
the
top
of th
e un
it)
T
hese
hol
es a
re p
rovi
ded
for
case
s w
here
the
unit
mus
t
b
e se
cure
d by
the
base
AN
D b
y th
e to
p su
rfac
e to
geth
er.
Use
Sel
f Tap
ping
scr
ews
5 x
L15
or le
ss.
(Obt
aine
d Lo
cally
)
321 w1
Unit : mm
OC261-B--1.qxp 03.2.19 3:07 PM Page 21
22
8 WIRING DIAGRAM
PUH-P1, 1.6, 2, 2.5, 3, 4VGAA.UKPUH-P1, 1.6, 2, 2.5, 3, 4VGAA 1.UK
OC261-B--1.qxp 03.2.19 3:08 PM Page 22
23
PUH-P1.6, 2, 2.5, 3, 4, 5, 6YGAA.UKPUH-P1.6, 2, 2.5, 3, 4, 5, 6YGAA 1.UK
OC261-B--1.qxp 03.2.19 3:08 PM Page 23
24
PU-P1.6, 2, 2.5, 3, 4VGAA.UKPU-P1.6, 2, 2.5, 3, 4VGAA 1.UK
OC261-B--1.qxp 03.2.19 3:08 PM Page 24
25
PU-P1.6, 2, 2.5, 3, 4, 5, 6YGAA.UKPU-P1.6, 2, 2.5, 3, 4, 5, 6YGAA 1.UK
OC261-B--1.qxp 03.2.19 3:08 PM Page 25
26
9 WIRING SPECIFICATIONS
Cross section of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
(50)✽2
(45)✽3
60✽4
Notapplicable
✽5
Flat
✽1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.✽2 : In case that cable with stripe of yellow and green is available.✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm2. ✽4 : In case of regular polarity connection (S1-S2-S3). ✽5 : In the flat cables are connected as this picture, they can be used up to 80m.
✽6 : Mentioned cable length is just a reference value. It may be different depending on the condition of installation, Humidity or materials, etc.
Flat
Round
Wire size(mm2)
Numberof wires
Clockwise : S1-S2-S3w Pay attention to stripe of yellow and green
Clockwise : S1-S2-S3-Openw Connect S1 and S3 to the opposite angle
Not applicable(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
PolarityL(m) ✽6
(3C Flat cable ✕ 2)
S1 S2 S3
WIRING SPECIFICATIONS FOR 220~240V 50Hz(INDOOR-OUTDOOR CONNECTING CABLE)
PU(H)-P1VGAA(1).UK~P6YGAA(1).UK(Except PUH-8YE,PUH-10YE)
OC261-B--1.qxp 03.2.19 3:08 PM Page 26
27
10 REFRIGERANT SYSTEM DIAGRAM
PUH-P5YGAA.UK PUH-P6YGAA.UKPUH-P5YGAA1.UK PUH-P6YGAA 1.UK
Indoor unit
Outdoor unit
Thermistor(TH2)
Strainer
Flexible tubeServiceport
AccumulatorCompressor
Refrigerant pipe19.05A({3/4")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
4-way valve Serviceport
High pressureprotect switch
Thermistor(TH3)
Capillary tube(O.D.4.0✕I.D.3.0-L200)✕2pcs
Distributorwithstrainer
Flaredconnection
Drier
Liner expansion valve
Bypassvalve
Thermistor(TH5)
Thermistor(TH1)
Muffler
Thermistor(TH4)
Thermistor(TH6)
Distributorwithstrainer
Capillarytube w1
Refrigerant flow in coolingRefrigerant flow in heating
w1 : O.D.4.0✕I.D.2.0-L400(PUH-P5YGAA(1).UK)O.D.4.0✕I.D.3.0-L450(PUH-P6YGAA(1).UK)
Ball valve
(#50)Strainer
Strainer(#100)
Strainer(#100)
Strainer(#50)
PUH-P4VGAA.UKPUH-P4YGAA.UK
Indoor unit
Outdoor unit
Thermistor(TH5)
Strainer
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe19.05A({3/4")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
4-way valve
Serviceport
High pressureprotect switch
Thermistor(TH3)
Capillary tube(O.D.4.0✕I.D.3.0-L350)✕2pcs
Distributorwithstrainer
Flaredconnection
Refrigerant flow in coolingRefrigerant flow in heating
Liner expansion valve
Drier
Thermistor(TH1)
Indoor coilthermistor(TH2)
Thermistor(TH4)
Muffler
Thermistor(TH6)
Distributorwithstrainer
Ball valve
(#50)Strainer
(#100)Strainer
(#100)Strainer
(#50)Strainer
PUH-P1, 1.6, 2, 2.5, 3VGAA.UKPUH-P1.6, 2, 2.5, 3YGAA.UK
Indoor unitOutdoor unit
Thermistor(TH1)
Strainer Flaredconnection
Flexible tubeServiceport
Accumulator
Ball valve
(#50)Strainer
Compressor
Refrigerant pipeP1···12.7A({1/2")P1.6~P3···15.88A({5/8")(with heat insulator)
Refrigerant pipeP1···6.35A({1/4")P1.6~P3···9.52A({3/8")(with heat insulator)
Stop valve(with service port)
4-way valve
Serviceport
High pressureprotect switch
Outdoor heat exchanger
Thermistor(TH3)
Distributorwithstrainer
Thermistor(TH6)
Distributorwithstrainer
(#100)Strainer
(#100)Strainer
Drier
Indoor coilthermistor(TH2)
Thermistor(TH5)
Muffler
Thermistor(TH4)
Linear expansion valve
(#50)Strainer
Refrigerant flow in coolingRefrigerant flow in heating
<4-way valve solenoid coil>Heating : ONCooling : OFF
OC261-B--1.qxp 03.2.19 3:08 PM Page 27
28
PU-P5YGAA.UK PU-P6YGAA.UKPU-P5YGAA1.UK PU-P6YGAA 1.UK
Indoor unit
Outdoor unit
Thermistor(TH2)
Strainer
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe19.05A({3/4")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Serviceport
High pressureprotect switch
Thermistor(TH3)
Capillary tube(O.D.4.0✕I.D.3.0-L200)✕2pcs
Distributorwithstrainer
Flaredconnection
Drier
Thermistor(TH5)
Thermistor(TH1)
Thermistor(TH4)
Thermistor(TH6)
Distributorwithstrainer
Refrigerant flow in cooling
Stop valve(with service port) Liner expansion valve
Ball valve
(#50)Strainer
Strainer(#100)
Strainer(#100)
(#50)Strainer
PU-P4VGAA.UKPU-P4YGAA.UK
Indoor unit
Outdoor unit
Thermistor(TH5)
Strainer
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe19.05A({3/4")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
Serviceport
High pressureprotect switch
Thermistor(TH3)
Capillary tube(O.D.4.0✕I.D.3.0-L350)✕2pcs
Distributorwithstrainer
Flaredconnection
Refrigerant flow in cooling
Liner expansion valve
Drier
Thermistor(TH1)
Indoor coilthermistor(TH2)
Thermistor(TH4)
Thermistor(TH6)
Distributorwithstrainer
Ball valve(#50)
Strainer
(#100)Strainer
(#100)Strainer
(#50)Strainer
PU-P1.6, 2, 2.5, 3VGAA.UKPU-P1.6, 2, 2.5, 3YGAA.UK
Indoor unitOutdoor unit
Thermistor(TH1)
Strainer Flaredconnection
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe15.88A({5/8")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
Serviceport
High pressureprotect switch
Outdoor heat exchanger
Thermistor(TH3)
Distributorwithstrainer
Thermistor(TH6)
Distributorwithstrainer
Drier
Indoor coilthermistor(TH2)
Thermistor(TH5)
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in cooling
Ball valve(#50)
Strainer
(#100)Strainer
(#100)Strainer
(#50)Strainer
OC261-B--1.qxp 03.2.19 3:08 PM Page 28
29
PUH-P4VGAA1.UKPUH-P4YGAA1.UK
Indoor unit
Outdoor unit
Thermistor(TH5)
Strainer
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe19.05A({3/4")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
4-way valve
Serviceport
High pressureprotect switch
Thermistor(TH3)
Capillary tube(O.D.4.0✕I.D.3.0-L350)✕2pcs
Distributorwithstrainer
Flaredconnection
Refrigerant flow in coolingRefrigerant flow in heating
Liner expansion valve
Thermistor(TH1)
Indoor coilthermistor(TH2)
Thermistor(TH4)
Muffler
Thermistor(TH6)
Distributorwithstrainer
Ball valve(#50)
Strainer
(#100)Strainer
(#100)Strainer
PUH-P1, 1.6, 2, 2.5, 3VGAA 1.UKPUH-P1.6, 2, 2.5, 3YGAA 1.UK
Indoor unitOutdoor unit
Thermistor(TH1)
Strainer Flaredconnection
Flexible tubeServiceport
Accumulator
Ball valve
Compressor
Refrigerant pipeP1···12.7A({1/2")P1.6~P3···15.88A({5/8")(with heat insulator)
Refrigerant pipeP1···6.35A({1/4")P1.6~P3···9.52A({3/8")(with heat insulator)
Stop valve(with service port)
4-way valve
Serviceport
High pressureprotect switch
Outdoor heat exchanger
Thermistor(TH3)
Distributorwithstrainer
Thermistor(TH6)
Distributorwithstrainer
Indoor coilthermistor(TH2)
Thermistor(TH5)
Muffler
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in coolingRefrigerant flow in heating
(#50)Strainer
(#100)Strainer
(#100)Strainer
<4-way valve solenoid coil>Heating : ONCooling : OFF
OC261-B--1.qxp 03.2.19 3:08 PM Page 29
30
PU-P4VGAA1.UKPU-P4YGAA1.UK
Indoor unit
Outdoor unit
Thermistor(TH5)
Strainer
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe19.05A({3/4")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
Serviceport
High pressureprotect switch
Thermistor(TH3)
Capillary tube(O.D.4.0✕I.D.3.0-R350)✕2pcs
Distributorwithstrainer
Flaredconnection
Refrigerant flow in cooling
Liner expansion valve
Thermistor(TH1)
Indoor coilthermistor(TH2)
Thermistor(TH4)
Thermistor(TH6)
Distributorwithstrainer
Ball valve(#50)
Strainer
(#100)Strainer
(#100)Strainer
PU-P1.6, 2, 2.5, 3VGAA1.UKPU-P1.6, 2, 2.5, 3YGAA1.UK
Indoor unitOutdoor unit
Thermistor(TH1)
Strainer Flaredconnection
Flexible tubeServiceport
Accumulator
Compressor
Refrigerant pipe15.88A({5/8")(with heat insulator)
Refrigerant pipe9.52A({3/8")(with heat insulator)
Stop valve(with service port)
Serviceport
High pressureprotect switch
Outdoor heat exchanger
Thermistor(TH3)
Distributorwithstrainer
Thermistor(TH6)
Distributorwithstrainer
Indoor coilthermistor(TH2)
Thermistor(TH5)
Thermistor(TH4)
Linear expansion valve
Refrigerant flow in cooling
Ball valve(#50)
Strainer
(#100)Strainer
(#100)Strainer
OC261-B--1.qxp 03.2.19 3:08 PM Page 30
31
11 TROUBLESHOOTING
1 blink
2 blinks
LED1 (Green)
LED2 (Red)
1 blink
2 blinks
1 blink
2 blinks
3 blinks
4 blinks
•Negative Phase detection•The wires of power supply and connecting wires of indoor / outdoor units are crossed with one another.•51CM connector open
•Start-up time is up
•Indoor / outdoor unit connector mis-wiring•Excessive numbers of indoor units per an outdoor unit (five or more)•Mis-wiring of indoor / outdoor unit connection wires (crossed wiring or disconnection)
•Indoor / outdoor unit transmission error(Transmitting error: Outdoor controller side)
•Indoor / outdoor unit transmission error(Signal receiving error: Indoor controller side)•Indoor / outdoor unit transmission error(Transmitting error: Indoor controller side)•Indoor / outdoor unit transmission error(Signal receiving error :Outdoor controller side)
•Remote controller transmission error(Transmitting error: Indoor controller side)•Undefined error code
•Remote controller transmission error(Signal receiving error: Remote controller side)•Remote controller transmission error(Transmitting error: Remote controller side)•Remote controller transmission error(Signal receiving error: Indoor controller side)
1 Check if the wires of power supply are connected to their corresponding terminals on TB1. 2 Check if the wirings are correct on power supply (TB1) and outdoor power supply board (TB2).
1 Check if the wirings are correct on the connecting wires of indoor / outdoor units.2 Check if a single outdoor unit connects five or more indoor units.
1 Check if the connectors of 51CM (51C) on outdoor controller board are disconnected. 2 Check the continuity of connector 51CM (51C) by using a tester.
1 Check if the wirings are correct on indoor units or remote controllers.2 Check if there is noise on the transmission lines of remote controllers.3 Turn the power off and let the units operate again to confirm.
1 Check if there is noise on the transmission lines of remote controllers.2 Check if there is noise on the connecting wires of indoor/outdoor units.3 Turn the power off and let the units operate again to confirm.
To be continued on the next page.
1 Check if the wirings are correct on the connecting wires of indoor / outdoor units.2 Check if there is noise on the wires of power supply and connecting wires of indoor / outdoor units.3 Check if there is noise on both indoor and outdoor controller board.4 Turn the power off and let the units operate again to confirm.
Indication (O.B) Error Name Inspection method
LED1 (Green)
LED2 (Red)
1. SELF-DIAGNOSTIC FUNCTION• The blinking patterns of two LEDs—LED1(Green) and LED2(Red)—show the diagnoses of troubles in case of malfunction.• By 7SEG indicator board indicates the operation mode and inspection types. For the details, refer to “OCT03 REVISED
EDITION-C”.
OC261-B--2.qxp 03.2.19 3:12 PM Page 31
32
3 blinks
4 blinks
LED1 (Green)
LED2 (Red)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
1 blinks
2 blinks
3 blinks
•Abnormal high discharge temperature(TH4)
From the preceding page.
•Abnormal high pressure (High-pressure switch 63H has been tripped)
•Protection from overheat operation (TH3)
•Compressor's overcurrent (Overload)•Thermal relay (51C) has been tripped•Overcurrent has locked the operation of compressor in start-up.
•Open / short circuit of discharge thermistor (TH4)•Open / short circuit of liquid pipe thermistor (TH3)•Open / short circuit of EVA / COND pipe thermistor (TH5)•Abnormality of room temperature thermistor(Indoor unit side: TH1)•Abnormality of Liquid pipe thermistor (Indoor unit side:TH2)•Abnormality of EVA / COND pipe thermistor (Indoor unit side: TH5)•Abnormality of drain sensor (Indoor unit side : (DS))•Malfunction of drain-up machine
•Abnormality of pipe temperature
1 Check if ball valves are open. 2 Check the continuity of connector (TH4) on outdoor controller board by using a tester.
1 Check if outdoor unit has a short cycle on its air duct.2 Check if the connector of TH3 on outdoor controller board is disconnected.
1 Check if the connectors of TH4, TH3, and TH6 on outdoor controller board are disconnected.2 Measure the resistance values of each thermistor (TH4, TH3, and TH6).1 Check if the connectors of CN20, CN21, and CN29 on outdoor controller board are disconnected.2 Measure the resistance values of each thermistor (TH1, TH2, and TH5).
3 Check if the unit fills the refrigerant at the same amount as specified. 1 Check if indoor / outdoor units have a short cycle on their air ducts.2 Check if the connector of 52C (63H) on outdoor controller board is disconnected.3 Check if the units get their heat exchanger and filter dirty and clogged.4 Measure resistance values among terminals on linear expansion valve by using a tester.
1 Check if ball valves are open.2 Measure resistance values among terminals on compressor by using a tester. 3 Check if outdoor unit has a short cycle on its air duct.
1 Check if the connector of CN31 on outdoor controller board is disconnected.2 Measure the resistance value of drain sensor.3 Measure resistance values among terminals on drain-up machine by using a tester. 1 Check if the connectors of CN20, CN21, and CN29 on outdoor controller board are disconnected.2 Check if ball valves are open.3 Check if the wirings are correct on the connecting wires of indoor / outdoor units.
4 Check if the connector of 51CM (51C) on outdoor controller board is disconnected.5 Check if the units get their heat exchanger and filter dirty and clogged.
Indication (O.B) Error Name Inspection method
OC261-B--2.qxp 03.2.19 3:12 PM Page 32
33
M
4
6
2
3
51
Blue
Brown
Yellow
OrangeRedWhite
Linear expansion valve(LEV)
Parts name Check points
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 20:)
(Refer to the next pege for a detail.)
Liquid temperature thermistor (TH3)
Discharge temperature thermistor (TH4)
Condenser/evaporatortemperature thermistor (TH6)
Normal
160k"~410k"
4.3k"~9.6k"
4.3k"~9.6k"
TH3
TH4
TH6
Abnormal
Open or short
Measure the resistance between the terminals using a tester.(Surrounding temperature 20C°)
4-WAY VALVE SOLENOID COIL (21S4)
Normal
1430"
Normal
(1) - (5)White - Red
(2) - (6)Yellow - Brown
(3) - (5)Orange - Red
(4) - (6)Blue - Brown
Abnormal
Abnormal
150" ±10%
Open or short
Open or short
Measure the resistance between the terminals using a tester.(Surrounding temperature 20°)
BYPASS VALVE SOLENOID COIL (21R)
PUH-P5/6YGAA.UKonly
Normal
P5, P6
1970"
P1, P1.6
1920" ±7%
P2~P6
1516" ±7%
Abnormal
Open or short
Measure the resistance between the terminals using a tester.CRANKCASE HEATER (HC)
Normal Abnormal
Open or short
Measure the resistance between the terminals using a tester.(Surrounding temperature 20C°)
FAN MOTOR(MF)
Normal
57.4" ±10%
99.7" ±10%
Motor lead wire Abnormal
Open or shortWhite — Black
White — RedRed
Black
White
Orange
ProtectorOPEN :130i5:CLOSE :88i15:
2. HOW TO CHECK THE PARTSPUH-P1, 1.6, 2, 2.5, 3, 4VGAA (1).UK PUH-P1.6, 2, 2.5, 3, 4, 5, 6YGAA (1).UKPU-P1.6, 2, 2.5, 3, 4VGAA (1).UK PU-P1.6, 2, 2.5, 3, 4, 5, 6YGAA (1).UK
OC261-B--2.qxp 03.2.19 3:12 PM Page 33
34
4 [4
3
6
5
[3
2 [2
1 [1
[4
[3
[2
[1
Controller board
Drive circuit
Connector(CNLEV)
DC12V
Brown
Red
Blue
Orange
Yellow
White
M
4
6
2
3
51
Blue
Brown
Yellow
OrangeRedWhite
Linear expansion valve
Linear expansion valve① Operation summary of the linear expansion valve.• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the controller board.• Valve position can be changed in proportion to the number of pulse signal.<Connection between the controller board and the linear expansion valve>
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Res
ista
nce
(K"
)500
400
300
200
100
025 50 75 100 120
< Thermistor for higher temperature >
Temperature (:)
Res
ista
nce
(K"
)
<Thermistor characteristic graph>
Liquid temperature thermistor(TH3)Condenser/evaporator temperature thermistor(TH6)
Thermistor R0=15k' ± 3%Fixed number of B=3480k' ± 2%
Rt=15exp { 3480( ) }
0: 15k'10: 9.6k'20: 6.3k'25: 5.2k'30: 4.3k'40: 3.0k'
Discharge temperature thermistor(TH4)
Thermistor R120=7.465k' ±2%Fixed number of B=4057k' ±2%
Rt=7.465exp { 4057( ) }
20: 250k'30: 160k'40: 104k'50: 70k'60: 48k'70: 34k'80: 24k'90: 17.5k'100: 13.0k'110: 9.8k'
Thermistor for lower temperature
1273+t
1273
1273+t
1393
Thermistor for higher temperature
OC261-B--2.qxp 03.2.19 3:12 PM Page 34
35
➂ Trouble shooting
Problem Check point Corrective measureRemove the connector from the controller board and connect diagnostic LEDs.
Pulse signal will be sent out for 10 seconds as soon as the main switch is turn on. If there is LED with lights on or lights off, it means the operation circuit is abnormal.
Motor will idle and make ticking noise when motor is operated while the linear expansion valve is locked. This ticking sound is the sign of the abnormality.
Measure the resistance between the each coil (red-white, red-orange, brown-yellow, brown-blue) using a tester. It is normal if the resistance is in the range of 150'±10%.
1 Check improperly connected connector terminals and the wire colors. 2 Remove the connector on the controller board side and check electrical conductance
Operation circuit failure of the micro processor.
Exchange the linear expansion valve.
Exchange the indoor controller board at drive circuit failure.
Exchange the linear expansion vale.
Disconnect the connector at the controller board, then check the continuity.
Wrong connection of the connector or contact failure.
Short or breakage of the motor coil of the linear expansion valve.
Linear expansion valve mechanism is locked.
654321
1k" LED
Output(Phase)
Output
{1
1
ON
{2 ON
{3 OFF
{4 OFF
2
OFF
ON
ON
OFF
3
OFF
OFF
ON
ON
4
ON
OFF
OFF
ON
<Output pulse signal and the valve operation>
➁ Linear expansion valve operation
D
A
E
B
C
Open
Extra tightning (80~100pulse)
Pulse number
2000 pulseOpening a valveall the way
Close
Val
ve p
ositi
on (
capa
city
)
Closing a valve : 1 → 2 → 3 → 4 → 1Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.❈ 1. When linear expansion valve operation stops, all output phase
become OFF.2. At phase interruption or when phase does not shift in order,
motor does not rotate smoothly and motor will locks and vibrates.
❈ When the switch is turned on, 2200 pulse closing valve signalwill be send till it goes to A point in order to define the valve posi-tion.
When the valve move smoothly, there is no noise or vibrationoccurring from the linear expansion valve : however, when thepulse number moves from E to A or when the valve is locked,more noise can be heard than normal situation.
❈ Noise can be detected by placing the ear against the screw dri-ver handle while putting the screw driver to the linear expansionvalve.
OC261-B--2.qxp 03.2.19 3:12 PM Page 35
36
12 DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS
PUH-P5YGAA(1).UK, PUH-P6YGAA (1).UK
1. Removing the Service panel and Top panel(1) Remove the 3 service panel fixing screws (5 ✕ 15) and
slide the hook to remove the service panel.(2) Remove the screws (3 for front, 2 for rear/5 ✕ 15) of the
top panel and remove it.
<When the rear screws of the top panel are not possibleto remove>Remove the 3 front screws (5 ✕ 15) of the top panel andlift the front side of the top panel.
Photo 1 Top panel screws Top panel
Service panelscrews
Service panel
Fan guard screws
Fan guard
2. Removing the Fan and Fan motor(1) Remove the 6 fan guard screws (5 ✕ 15) to remove it.
(See Photo 1)(2) Remove the propeller nut (M8) and propeller fan.(3) Remove the 3 fan motor screws (5 ✕ 25) to remove the
fan motor.
Fan motor screws
Fan motor
Photo 33. Removing the Electrical box(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)(3) Remove the Bypass valve, Crankcase heater, Pressure
switch<for high pressure>, Liquid temperature thermistor,Discharge temperature thermistor, condenser/evaporatortemperature thermistor and 4-way valve from the connectorhousing on the controller board,then disconnect the fanmotor lead wire from the housing mentioned before and thecondenser lead wire for the fan from the electrical box.
<Diagram symbol in the connector housing>Bypass valve solenoid coil (SV) · Crankcase heater (CH)Pressure switch <for high pressure> (63H)Liquid temperature thermistor (TH3)Discharge temperature thermistor (TH4)Condenser/evaporator temperature thermistor (TH6)4-way valve solenoid coil (21S4) · Fan motor (MF3, MF4)
(4) Remove the terminal cover and disconnect the compressorlead wire and inner thermal device terminal.
(5) Remove the electrical box screw (4 ✕ 10) and lift thebox to remove it. The electric box cover is hooked at 2points on the left and 1 point on the right.
Fan guard Electric parts box
Outdoor unitcontroller board
Electrical boxfixing screw
Terminal cover
Cover panel
Cover panel fixing screwCompressor
Photo 2
OC261-B--2.qxp 03.2.19 3:12 PM Page 36
37
OPERATING PROCEDURE PHOTOS
Photo 44. Removing the liquid temperature thermistor, discharge temperature thermistor and condenser/evaporator temperature thermistor(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)
(When the top panel removing is not possible, removethe electric parts box. Refer to 3.)
w When removing liquid temperature thermistor and thedischarge temperature thermistor, it unnecessary toremove the top panel. (See Photo 5)
(3) Disconnect the lead wire of the liquid temperature thermistor,discharge temperature thermistor and condenser/evaporatortemperature thermistor from the housing (TH3, TH4, TH6)on the controller board.
(4) Loosen the 1 lead wire clamps on the electrical box.(5) Pull out the thermistor from the sensor holder.
5. Removing the bypass valve solenoid coil (SV)(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)
(When the top panel removing is not possible, removethe electrical box. Refer to 3. )
(3) Remove coil fixing screw (M4 ✕ 8) and disconnect thelead wire of the bypass valve solenoid coil (SV) from on the controller board.
8. Removing the 4-way valve(1) Remove the service panel. (See Photo 1)(2) Remove the 4-way valve solenoid coil. (See Photo 5)(3) Recover gas from the refrigerant circuit.(4) Remove the braze pipe of the 4-way valve.
Note :● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.● When installing the 4-way valve, cover it with a wet cloth to
prevent it from heating, then braze the pipes.
6. Removing the bypass valve(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)(3) Remove the bypass valve solenoid coil. (See Photo 4)(4) Recover gas from the refrigerant circuit.(5) Remove the braze at the intake and outlet of the bypass
valve.Note :● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.● When installing the bypass valve, cover it with a wet cloth to
prevent it from heating, then braze the pipes.
Photo 5
Clamp
Bypass valvesolenoid coilfixing screw
Rear panel
Condenser/evaporatortemperature thermistor
4-way valvesolenoid coil
4-way valvesolenoid coilfixing screw
4-way valve
Pressure switch <High>
Liquidtemperaturethermistor
Dischargetemperaturethermistor
7. Removing the 4-way valve solenoid coil (21S4)(1) Remove the service panel. (See Photo 1)(2) Remove 4-way valve solenoid coil fixing screw (M5 ✕ 6)
and disconnect the lead wire of the 4-way valve solenoid coil (21S4) from the controller board.
Linearexpansionvalve coil
Bypass valvesolenoid coil
Electrical box
OC261-B--2.qxp 03.2.19 3:12 PM Page 37
38
OPERATING PROCEDURE PHOTOS
9. Removing the High pressure switch(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)(3) Remove the electrical box. (See Photo 3)(4) Disconnect the lead wire of the pressure switch.
(See Photo 6)(5) Remove the braze part of the pressure switch.
Note : When installing the pressure switch, cover the pressureswitch with a wet cloth to prevent the pressure switchfrom heating, then braze it.
10. Removing the linear expansion valve(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)(3) Remove the electrical box. (See Photo 3)(4) Recover gas from the refrigerant circuit.(5) Remove the linear expansion valve coil. (See Photo 7) (6) Remove the braze pipes of the linear expansion valve.
Note 1: When installing the linear expansion valve, removeits coil and cover the valve with a wet cloth so as toprevent it from heating, then braze the pipes.
Note 2: By detaching the rear panel, the brazed parts willeasily become separated.
Note 3:● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
11. Removing the Bell mouth(1) Remove the 6 fan guard fixing screws (5 ✕ 15) to
remove it. (See Photo 1)(2) Remove the top panel.(3) Remove a bell mouth fixing screw (5 ✕ 15) to remove it.
Bell mouth fixing screw
Photo 6
Photo 8
Pressure switch <High>
Capillarytube
Valvebedfixingscrews
Lead wire
Photo 7
Linearexpansionvalve coil
Linearexpansionvalve
Bypass valve
Bypass valvesolenoid coil
Accumulator
OC261-B--2.qxp 03.2.19 3:12 PM Page 38
39
OPERATING PROCEDURE PHOTOS
12. Removing the compressor(1) Remove the service panel. (See Photo 1)(2) Remove the top panel. (See Photo 1)(3) Remove the electric parts box. (See Photo 3)(4) Remove the bell mouth. (See Photo 8)(5) Remove the 3 valve bed fixing screws (4 ✕ 10) and the
4 ball valve fixing screws(5 ✕ 16) to remove the valve bed.(6) Remove the 3 rear panel fixing screws (5 ✕ 15) to the panel.(7) Remove the cover panel fixing screw (5 ✕ 15) to remove
the front side of cover panel.(8) Recover gas from the refrigerant circuit.(9) Remove the 3 points of the compressor fixing nut with a
monkey wrench.(10) Remove the brazed pipe of compressor intake and outlet
to remove the compressor
<Reference>w When the power supply terminal block of the compressor
is fixed with the screws, the tightening torque is from 1.4 to 1.7 N.m.
NOTE● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
13. Removing the accumulator.(1) Recover gas from the refrigerant circuit.(2) Remove the compressor or remove the rear panel.(3) Remove the brazed pipe of accumulator intake and outlet
to remove the accumulator
NOTE :● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
Photo 9
Compressor fixing nuts
Compressor
Accumulator
OC261-B--2.qxp 03.2.19 3:13 PM Page 39
40
13 PARTS LIST
Part No. SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Price
Unit Amount
Part Name
Q,ty/setPUH-P1·.UK
PUH-P1.6· .UK
PU-P1.6· .UK
VGAAVGAA1
VGAAVGAA1
YGAAYGAA1
VGAAVGAA1
YGAAYGAA1
Remarks(Drawing No.)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(DG12F536H15)
(RG00R045G01)
(RG00R048G01)
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(5✕15)
S70 30L 641
—
S70 30L 613
S70 23T 614
S70 30L 119
S70 E01 675
—
S70 E01 686
S70 96W 130
—
S70 001 699
S70 31L 658
S70 30L 658
S70 E00 682
S70 30L 655
S70 E09 661
S70 E08 661
S70 E01 661
S70 E05 661
S70 30L 698
TOP PANEL
F.ST SCREW
REAR SUPPORT
FRONT SUPPORT
BELL MOUTH
WIRE GRILL - S
SEPARATOR ASSY
BASE
MOTOR SUPPORT
VALVE BED ASSY
LABEL (MITSUBISHI)
COVER PANEL 1
COVER PANEL 2
REAR PANEL
PANEL HANDLE
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
REAR GUARD
1
17
2
4
7 8 11
12
5
6
16
14
15
3
13
9 10
STRUCTURAL PARTSPUH-P1VGAA.UK PUH-P1VGAA 1.UK PUH-P1.6VGAA.UK PUH-P1.6VGAA 1.UK PUH-P1.6YGAA.UK PUH-P1.6YGAA 1.UK PU-P1.6VGAA.UK PU-P1.6VGAA 1.UK PU-P1.6YGAA.UK PU-P1.6YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 40
Part No. Part Name SpecificatioNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Q,ty/set
VGAAVGAA1
YGAAYGAA1
VGAAVGAA1
YGAAYGAA1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
TOP PANEL
F.ST SCREW
REAR SUPPORT
FRONT SUPPORT
BELL MOUTH
WIRE GRILL-M
MOTOR SUPPORT
SEPARATOR ASSY
VALVE BED ASSY
BASE
PANEL HANDLE
COVER PANEL-1
COVER PANEL-2
REAR PANEL
LABEL (MITSUBISHI)
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
REAR GUARD
(5✕15)
AmountUnit
PriceRemarks
(Drawing No.)
(DG12F536H15)
(RG00R045G02)
(RG00R048G02)
S70 30L 641
—
S70 97W 613
S70 E00 614
S70 36L 119
S70 E02 675
S70 97W 130
—
—
S70 E02 686
S70 30L 655
S70 31L 658
S70 30L 658
S70 E01 682
S70 001 699
S70 E10 661
S70 E11 661
S70 E02 661
S70 E06 661
S70 31L 698
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
PUH-P2 · .UK PU-P2 · .UK
41
1
17
2
7 8 11 12
5
6
16
14
15
13
4
3
9 10
STRUCTURAL PARTSPUH-P2VGAA.UK PUH-P2VGAA 1.UKPUH-P2YGAA.UK PUH-P2YGAA 1.UKPU-P2VGAA.UK PU-P2VGAA 1.UKPU-P2YGAA.UK PU-P2YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 41
42
Part No. Part Name SpecificatioNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Q,ty/set
VGAAVGAA1
YGAAYGAA1
VGAAVGAA1
YGAAYGAA1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
TOP PANEL
F.ST SCREW
REAR SUPPORT
FRONT SUPPORT
BELL MOUTH
WIRE GRILL-M
MOTOR SUPPORT
SEPARATOR ASSY
VALVE BED ASSY
BASE
PANEL HANDLE
COVER PANEL-1
COVER PANEL-2
REAR PANEL
LABEL (MITSUBISHI)
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
REAR GUARD
(5✕15)
AmountUnit
PriceRemarks
(Drawing No.)
(DG12F536H15)
(RG00R045G02)
(RG00R048G02)
S70 30L 641
—
S70 97W 613
S70 E00 614
S70 36L 119
S70 E02 675
S70 97W 130
—
—
S70 E02 686
S70 30L 655
S70 31L 658
S70 30L 658
S70 E01 682
S70 001 699
S70 E10 661
S70 E11 661
S70 E02 661
S70 E06 661
S70 30L 698
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
PUH-P2.5 · UK PU-P2.5 · UK
1
17
2
7 8 11 12
5
6
16
14
15
13
4
3
9 10
STRUCTURAL PARTSPUH-P2.5VGAA.UK PUH-P2.5VGAA 1.UKPUH-P2.5YGAA.UK PUH-P2.5YGAA 1.UKPU-P2.5VGAA.UK PU-P2.5VGAA 1.UKPU-P2.5YGAA.UK PU-P2.5YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 42
43
Part No. Part Name SpecificatioNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Q,ty/set
VGAAVGAA1
YGAAYGAA1
VGAAVGAA1
YGAAYGAA1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
TOP PANEL
F.ST SCREW
REAR SUPPORT
FRONT SUPPORT
BELL MOUTH
WIRE GRILL-M
MOTOR SUPPORT
SEPARATOR ASSY
VALVE BED ASSY
BASE
PANEL HANDLE
COVER PANEL-1
COVER PANEL-2
REAR PANEL
LABEL (MITSUBISHI)
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
REAR GUARD
(5✕15)
AmountUnit
PriceRemarks
(Drawing No.)
(DG12F536H15)
(RG00R045G03)
(RG00R048G02)
S70 30L 641
—
S70 97W 613
S70 E00 614
S70 36L 119
S70 E02 675
S70 97W 130
—
—
S70 E02 686
S70 30L 655
S70 31L 658
S70 30L 658
S70 E02 682
S70 001 699
S70 E10 661
S70 E11 661
S70 E02 661
S70 E06 661
S70 30L 698
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
16
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
PUH-P3 · .UK PU-P3 · .UK
1
17
2
7 8 11 12
5
6
16
14
15
13
4
3
9 10
STRUCTURAL PARTSPUH-P3VGAA.UK PUH-P3VGAA 1.UKPUH-P3YGAA.UK PUH-P3YGAA 1.UKPU-P3VGAA.UK PU-P3VGAA 1.UKPU-P3YGAA.UK PU-P3YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 43
44
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Price
Unit Amount
(5✕15)
PUH-P4 · .UK PU-P4 · .UK Remarks(Drawing No.)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
18
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
18
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
18
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
18
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
(DG12F536H15)
(RG00R045G04)
(RG00R048G02)
S70 30L 641
—
S70 98W 613
S70 E01 614
S70 41L 119
S70 E03 675
S70 30L 119
S70 42L 130
—
—
S70 E03 686
S70 30L 655
S70 31L 658
S70 30L 658
S70 E03 682
S70 001 699
S70 E12 661
S70 E13 661
S70 E03 661
S70 E07 661
S70 30L 698
TOP PANEL
F.ST SCREW
REAR SUPPORT
FRONT SUPPORT
BELL MOUTH
WIRE GRILL - L
BELL MOUTH
MOTOR SUPPORT
SEPARATOR ASSY
VALVE BED ASSY
BASE
PANEL HANDLE
COVER PANEL-1
COVER PANEL-2
REAR PANEL
LABEL (MITSUBISHI)
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
SERVICE PANEL
REAR GUARD
Q,ty/set
VGAAVGAA1
YGAAYGAA1
VGAAVGAA1
YGAAYGAA1
13 1824
7
6 16 15
14
175
8 9 10 11 12 13
STRUCTURAL PARTSPUH-P4VGAA.UK PUH-P4VGAA 1.UK PU-P4VGAA.UK PU-P4VGAA 1.UKPUH-P4YGAA.UK PUH-P4YGAA 1.UK PU-P4YGAA.UK PU-P4YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 44
45
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Price
Unit Amount
(5✕15)
Q,ty/set
Remarks(Drawing No.)
PUH-P5,6 PU-P5,6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
1
18
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
18
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
(DG12F536H15)
(RG00R046G01)
(RG00R048G03)
YGAA.UKYGAA1.UK
YGAA.UKYGAA1.UK
S70 17T 641
—
S70 98W 613
S70 17T 614
S70 41L 119
S70 E03 675
S70 30L 119
S70 42L 130
—
S70 A04 529
—
S70 E04 686
S70 30L 655
S70 31L 658
S70 30L 658
S70 E04 682
S70 001 699
S70 E14 661
S70 E04 661
S70 17T 698
TOP PANEL
F.ST SCREW
REAR SUPPORT
FRONT SUPPORT
BELL MOUTH
WIRE GRILL - L
BELL MOUTH
MOTOR SUPPORT
SEPARATOR ASSY
ACCUMULATOR DRAIN PAN
VALVE BED ASSY
BASE
PANEL HANDLE
COVER PANEL-1
COVER PANEL-2
REAR PANEL
LABEL(MITSUBISHI)
SERVICE PANEL
SERVICE PANEL
REAR GUARD
1
18
19
2
4
5
12 136
17 16
15
3
1198 107 14
STRUCTURAL PARTSPUH-P5YGAA.UK PUH-P5YGAA 1.UKPUH-P6YGAA.UK PUH-P6YGAA 1.UKPU-P5YGAA.UK PU-P5YGAA 1.UKPU-P6YGAA.UK PU-P6YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 45
46
FUNCTIONAL PARTSPUH-P1VGAA.UKPUH-P1VGAA1.UK
15
14
13
12
1
6
18
19
20
2126 2225 2324
7 8 9 10 11
2
4
5
17
16
3
FUSE
OC261-B--2.qxp 03.2.19 3:13 PM Page 46
47
Price
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
52C
TB1
TB2
MF
TH4
MC
CH
LEV
21S4
TH3, TH6
63H
O.B
FUSE
C3
C5
S70 249 708
S70 E03 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 E00 467
S70 E00 413
S70 400 418
S70 061 400
S70 E02 236
S70 E02 440
S70 E01 411
S70 66L 450
S70 E03 405
S70 E03 401
S70 350 242
S70 E01 403
S70 E15 202
S70 E99 408
S70 E00 208
S70 31L 315
S70 520 239
S70 30L 255
S70 E00 723
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE(LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
LINEAR EXPANSION VALVE
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
PUH-P1V
S-U12 240V
2P(L,N)
3P(S1,S2,S3)
N026P72MT
M8
1/4˝
RE189VHSMT
240V / 30W
1/2˝
#50-12
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ 440V
30+ 420V
(PART OF BOARD)
OC261-B--2.qxp 03.2.19 3:13 PM Page 47
48
15
14
13
12
1
6
18
19
20
2126 2225 2324
7 8 9 10 11
2
4
5
17
16
3
FUSE
FUNCTIONAL PARTSPUH-P1.6VGAA.UK PUH-P1.6VGAA 1.UKPU-P1.6VGAA.UK PU-P1.6VGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 48
49
Part number that is circled is not shown in the figure.
Price
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK
GAA1.UK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
GAA.UK
GAA1.UK
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
52C
TB1
TB2
MF
TH4
MC
CH
LEV
21S4
TH3, TH6
63H
O.B
FUSE
C3
C5
S70 249 708
S70 E03 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 E00 467
S70 E00 413
S70 200 418
S70 062 400
S70 E02 236
S70 E02 440
S70 E03 411
S70 66L 450
S70 E03 405
S70 E03 401
S70 350 242
S70 E01 403
S70 E15 202
S70 E00 408
S70 E00 208
S70 31L 315
S70 520 239
S70 30L 255
S70 E01 723
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE(LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
LINEAR EXPANSION VALVE
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
STRAINER
S-U12 240V
2P(L,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
RE277VHSMT
240V / 30W
5/8˝
#50-12
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ 440V
40+ 400V
#50-9.52
(PART OF BOARD)
PUH-P1.6V PU-P1.6V
OC261-B--2.qxp 03.2.19 3:13 PM Page 49
50
15
14
13
12
1
6
18
19
20
212225 2324
7 8 9 10 11
2
4
5
17
16
3
FUSE
FUNCTIONAL PARTSPUH-P1.6YGAA.UK PUH-P1.6YGAA 1.UKPU-P1.6YGAA.UK PU-P1.6YGAA 1.UK
OC261-B--2.qxp 03.2.19 3:13 PM Page 50
51
Part number that is circled is not shown in the figure.
Price
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK
GAA1.UK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
GAA.UK
GAA1.UK
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
51C,52C
TB1
TB2
MF
TH4
MC
CH
LEV
21S4
TH3, TH6
63H
O.B
FUSE
C3
S70 250 708
S70 E03 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 E00 467
S70 E00 413
S70 200 418
S70 063 400
S70 E02 236
S70 E02 440
S70 E03 411
S70 66L 450
S70 E03 405
S70 E03 401
S70 350 242
S70 E01 403
S70 E15 202
S70 E00 408
S70 E00 208
S70 32L 315
S70 520 239
S70 30L 255
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE(LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
LINEAR EXPANSION VALVE
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
STRAINER
PUH-P1.6Y PU-P1.6Y
MSO-N11
4P(L1,L2,L3,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
RE277YFKM
240V / 38W
5/8˝
#50-12
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ 440V
#50-9.52
(PART OF BOARD)
OC261-B--2.qxp 03.2.19 3:13 PM Page 51
52
18
17
15
14
13
12
1
5
7 8 9 10 11
6
19
21222326 2425
4
20
16
FUNCTIONAL PARTSPUH-P2VGAA.UK PUH-P2VGAA 1.UKPU-P2VGAA.UK PU-P2VGAA 1.UK
3
2
FUSE
OC261-B--2.qxp 03.2.19 3:13 PM Page 52
53
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK GAA.UK GAA1.UK
S-N18EX
2P(L,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
NE36VMJMT
240V / 38W
5/8˝
#50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ ✕ 440V
50+ ✕ 420V
#50-9.52
(PART OF BOARD)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
52C
TB1
TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
C5
S70 330 708
S70 E03 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 36L 467
S70 E00 413
S70 300 418
S70 064 400
S70 E04 236
S70 E04 440
S70 E04 411
S70 36L 450
S70 E03 405
S70 350 242
S70 A00 403
S70 E15 202
S70 E02 401
S70 E02 408
S70 E00 208
S70 31L 315
S70 520 239
S70 30L 255
S70 100 723
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE (LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
STRAINER
PUH-P2V PU-P2V
Price
Part number that is circled is not shown in the figure.
OC261-B--2.qxp 03.2.19 3:13 PM Page 53
54
18
17
15
14
13
12
1
5
7 8 9 10 11
6
19
21222326 2425
4
20
16
FUNCTIONAL PARTSPUH-P2.5VGAA.UK PUH-P2.5VGAA 1.UKPU-P2.5VGAA.UK PU-P2.5VGAA 1.UK
3
2
FUSE
OC261-B--2.qxp 03.2.19 3:13 PM Page 54
55
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK GAA.UK GAA1.UK
S-N18EX
2P(L,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
NE41VMJMT
240V / 38W
5/8˝
#50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ ✕ 440V
45+ ✕ 440V
#50-9.52
(PART OF BOARD)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
52C
TB1
TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
C5
S70 330 708
S70 E03 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 36L 467
S70 E00 413
S70 300 418
S70 066 400
S70 E04 236
S70 E03 440
S70 E04 411
S70 36L 450
S70 E03 405
S70 350 242
S70 A00 403
S70 E15 202
S70 E02 401
S70 E01 408
S70 E00 208
S70 31L 315
S70 520 239
S70 30L 255
S70 869 723
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE (LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
STRAINER
PUH-P2.5V PU-P2.5V
Price
Part number that is circled is not shown in the figure.
OC261-B--2.qxp 03.2.19 3:13 PM Page 55
56
18
17
15
14
13
12
1
5
7 8 9 10 11
6
19
21222326 2425
4
20
16
FUNCTIONAL PARTSPUH-P3VGAA.UK PUH-P3VGAA 1.UKPU-P3VGAA.UK PU-P3VGAA 1.UK
3
2
FUSE
OC261-B--2.qxp 03.2.19 3:14 PM Page 56
57
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK GAA.UK GAA1.UK
S-N18EX
2P(L,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
NE52VNJMT
240V / 38W
5/8˝
#50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ ✕ 440V
60+ ✕ 450V
#50-9.52
(PART OF BOARD)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
52C
TB1
TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
C5
S70 330 708
S70 E03 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 36L 467
S70 E00 413
S70 300 418
S70 068 400
S70 E04 236
S70 E03 440
S70 E04 411
S70 36L 450
S70 E03 405
S70 350 242
S70 A00 403
S70 E15 202
S70 E02 401
S70 E03 408
S70 E00 208
S70 31L 315
S70 520 239
S70 30L 255
S70 976 723
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE (LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
STRAINER
PUH-P3V PU-P3V
Price
Part number that is circled is not shown in the figure.
OC261-B--2.qxp 03.2.19 3:14 PM Page 57
58
18
17
15
14
13
12
1
2
3
5
7 8 9 10 11
6
19
2122232425
4
20
16
FUNCTIONAL PARTSPUH-P2YGAA.UK PUH-P2YGAA 1.UKPU-P2YGAA.UK PU-P2YGAA 1.UK
FUSE
OC261-B--2.qxp 03.2.19 3:14 PM Page 58
59
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK GAA.UK GAA1.UK
MSO-N11
4P(L1,L2,L3,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
NE36YEKMT
240V 38W
5/8˝
#50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ ✕ 440V
#50-9.52
(PART OF BOARD)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
51C,52C
TB1
TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
S70 332 708
S70 E10 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 36L 467
S70 E00 413
S70 300 418
S70 065 400
S70 E04 236
S70 E04 440
S70 E04 411
S70 36L 450
S70 E03 405
S70 350 242
S70 A00 403
S70 E15 202
S70 E02 401
S70 E02 408
S70 E00 208
S70 32L 315
S70 520 239
S70 30L 255
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE (LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
STRAINER
PUH-P2Y PU-P2Y
Price
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
Part number that is circled is not shown in the figure.
OC261-B--2.qxp 03.2.19 3:14 PM Page 59
60
18
17
15
14
13
12
1
2
3
5
7 8 9 10 11
6
19
2122232425
4
20
16
FUNCTIONAL PARTSPUH-P2.5YGAA.UK PUH-P2.5YGAA 1.UKPU-P2.5YGAA.UK PU-P2.5YGAA 1.UK
FUSE
OC261-B--2.qxp 03.2.19 3:14 PM Page 60
61
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK GAA.UK GAA1.UK
MSO-N11
4P(L1,L2,L3,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
NE41YEKMT
240V / 38W
5/8˝
#50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ ✕ 440V
#50-9.52
(PART OF BOARD)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
51C,52C
TB1
TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
S70 333 708
S70 E10 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 36L 467
S70 E00 413
S70 300 418
S70 067 400
S70 E04 236
S70 E03 440
S70 E04 411
S70 36L 450
S70 E03 405
S70 350 242
S70 A00 403
S70 E15 202
S70 E02 401
S70 E01 408
S70 E00 208
S70 32L 315
S70 520 239
S70 30L 255
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE (LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
STRAINER
PUH-P2.5Y PU-P2.5Y
Price
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
Part number that is circled is not shown in the figure.
OC261-B--3.qxp 03.2.19 3:18 PM Page 61
62
18
17
15
14
13
12
1
2
3
5
7 8 9 10 11
6
19
2122232425
4
20
16
FUNCTIONAL PARTSPUH-P3YGAA.UK PUH-P3YGAA 1.UKPU-P3YGAA.UK PU-P3YGAA 1.UK
FUSE
OC261-B--3.qxp 03.2.19 3:18 PM Page 62
63
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty Unit Amount
Remarks
Q,ty/set
GAA.UK GAA1.UK GAA.UK GAA1.UK
MSO-N11
4P(L1,L2,L3,N)
3P(S1,S2,S3)
N026P72MT
M8
3/8˝
NE52YDKMT
240V / 38W
5/8˝
#50-16
OFF:3.3MPa ON:2.6MPa
6.3A
2.2+ ✕ 440V
#50-9.52
(PART OF BOARD)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
51C,52C
TB1
TB2
MF
TH4
MC
CH
21S4
TH3, TH6
LEV
63H
O.B
FUSE
C3
S70 331 708
S70 E10 716
S70 E04 716
S70 E03 763
S70 30L 115
S70 30L 097
S70 E16 202
S70 36L 467
S70 E00 413
S70 300 418
S70 069 400
S70 E04 236
S70 E03 440
S70 E04 411
S70 36L 450
S70 E03 405
S70 350 242
S70 A00 403
S70 E15 202
S70 E02 401
S70 E03 408
S70 E00 208
S70 32L 315
S70 520 239
S70 30L 255
S70 30L 450
CONTACTOR
TERMINAL BLOCK
TERMINAL BLOCK
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
THERMISTOR (DISCHARGE)
MUFFLER
CHARGE PLUG
STOP VALVE (LIQUID)
COMPRESSOR
CRANKCASE HEATER
ACCUMULATOR
BALL VALVE
STRAINER
FILTER DRYER
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
HEAT EXCHANGER
HIGH PRESSURE SWITCH
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
STRAINER
PUH-P3Y PU-P3Y
Price
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
Part number that is circled is not shown in the figure.
OC261-B--3.qxp 03.2.19 3:18 PM Page 63
64
FUNCTIONAL PARTSPUH-P4VGAA.UK PUH-P4VGAA 1.UKPU-P4VGAA.UK PU-P4VGAA 1.UK
14
13
7 9 111086
4
15
18
19
22
221
12
29
1
27 2628 2425 23
3
20
5
16
17
19
FUSE
OC261-B--3.qxp 03.2.19 3:18 PM Page 64
65
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty
Price
Unit Amount
N026P72MT
M8
N02A672MT
OFF:3.3MPa ON:2.6MPa
NE56VNJMT
3/8˝
240V / 38W
3/4˝
#50-19.1
[4.0 ✕ [3.0 ✕ 350mm
[4.0 ✕ [3.0 ✕ 350mm
6.3A
2.2+ ✕ 440V
3P(S1,S2,S3)
2P(L,N)
S-N18EX
#50-9.52
60+ ✕ 450V
RemarksPUH-P4V PU-P4V
Q,ty/set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
1
2
2
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
2
2
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
MF
MF
63H
TH4
MC
CH
TH3, TH6
LEV
21S4
O.B
FUSE
C3, C4
TB2
TB1
52C
C5
S70 E03 763
S70 30L 115
S70 30L 097
S70 E05 408
S70 E04 763
S70 E00 208
S70 42L 467
S70 E18 202
S70 E00 413
S70 071 400
S70 300 418
S70 E05 236
S70 E05 411
S70 E05 440
S70 42L 450
S70 E03 405
S70 E01 425
S70 E02 425
S70 E14 202
S70 E05 401
S70 350 242
S70 260 403
S70 31L 315
S70 520 239
S70 30L 255
S70 E04 716
S70 E03 716
S70 330 708
S70 E04 408
S70 30L 450
S70 976 723
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
HEAT EXCHANGER
OUTDOOR FAN MOTOR
HIGH PRESSURE SWITCH
MUFFLER
THERMISTOR (DISCHARGE)
CHARGE PLUG
COMPRESSOR
STOP VALVE (LIQUID)
CRANKCASE HEATER
BALL VALVE
ACCUMULATOR
STRAINER
FILTER DRYER
CAPILLARY TUBE
CAPILLARY TUBE
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
TERMINAL BLOCK
TERMINAL BLOCK
CONTACTOR
HEAT EXCHANGER
STRAINER
COMPRESSOR CAPACITOR
GAA.UK GAA1.UK GAA1.UKGAA.UK
(PART OF BOARD)
Part number that is circled is not shown in the figure.
OC261-B--3.qxp 03.2.19 3:18 PM Page 65
66
FUNCTIONAL PARTSPUH-P4YGAA.UK PUH-P4YGAA 1.UKPU-P4YGAA.UK PU-P4YGAA 1.UK
14
13
7 9 111086
4
15
18
19
22
221
12
29
1
27 2628 2425 23
3
20
5
16
17
19
FUSE
OC261-B--3.qxp 03.2.19 3:18 PM Page 66
67
Part No. Part Name SpecificationNo.WiningDiagramSymbol
Recom-mended
Q,ty
Price
Unit Amount
N026P72MT
M8
N02A672MT
OFF:3.3MPa ON:2.6MPa
NE56YDKMT
3/8˝
240V / 38W
3/4˝
#50-19.1
[4.0 ✕ [3.0 ✕ 350mm
[4.0 ✕ [3.0 ✕ 350mm
6.3A
2.2+ ✕ 440V
3P(S1,S2,S3)
4P(L1,L2,L3,N)
MSO-N11
#50-9.52
RemarksPUH-P4Y PU-P4Y
Q,ty/set
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
1
2
2
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
2
2
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
MF
MF
63H
TH4
MC
CH
TH3, TH6
LEV
21S4
O.B
FUSE
C3, C4
TB2
TB1
51C, 52C
S70 E03 763
S70 30L 115
S70 30L 097
S70 E05 408
S70 E04 763
S70 E00 208
S70 42L 467
S70 E18 202
S70 E00 413
S70 070 400
S70 300 418
S70 E05 236
S70 E05 411
S70 E05 440
S70 42L 450
S70 E03 405
S70 E01 425
S70 E02 425
S70 E14 202
S70 E05 401
S70 350 242
S70 260 403
S70 32L 315
S70 520 239
S70 30L 255
S70 E04 716
S70 E10 716
S70 331 708
S70 E04 408
S70 30L 450
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
HEAT EXCHANGER
OUTDOOR FAN MOTOR
HIGH PRESSURE SWITCH
MUFFLER
THERMISTOR (DISCHARGE)
CHARGE PLUG
COMPRESSOR
STOP VALVE (LIQUID)
CRANKCASE HEATER
BALL VALVE
ACCUMULATOR
STRAINER
FILTER DRYER
CAPILLARY TUBE
CAPILLARY TUBE
THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
LINEAR EXPANSION VALVE
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
OUTDOOR CONTROLLER BOARD
FUSE
OUTDOOR FAN CAPACITOR
TERMINAL BLOCK
TERMINAL BLOCK
CONTACTOR
HEAT EXCHANGER
STRAINER
GAA.UK GAA1.UK GAA1.UKGAA.UK
(PART OF BOARD)
Part number that is circled is not shown in the figure.
OC261-B--3.qxp 03.2.19 3:18 PM Page 67
68
18
24
25
11
96 8
12
13
3
21
19
2
4
10
16
1
33 32 2931 30 28 27
FUNCTIONAL PARTSPUH-P5YGAA.UK PUH-P5YGAA 1.UKPU-P5YGAA.UK PU-P5YGAA 1.UK
15
17
26
22
14
75
12
23
20
FUSE
OC261-B--3.qxp 03.2.19 3:18 PM Page 68
69
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Price
Unit AmountRemarks
Q,ty/set
PUH-P5Y PU-P5Y
GAA.UK GAA1.UK GAA.UK GAA1.UK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
MF
MF
TH4
LEV
MC
CH
TH3, TH6
63H
21S4
SV
O.B
FUSE
C3, C4
TB2
TB1
51C, 52C
S70 E03 763
S70 30L 115
S70 30L 097
S70 E07 408
S70 E04 763
S70 E19 202
S70 E06 401
S70 080 400
S70 300 418
S70 E05 411
S70 E01 236
S70 E17 202
S70 42L 450
S70 42L 467
S70 E00 208
S70 E01 413
S70 251 242
S70 E02 403
S70 E03 405
S70 E05 425
S70 E06 425
S70 E03 425
S70 A14 428
S70 351 242
S70 E06 440
S70 E00 413
S70 32L 315
S70 520 239
S70 17T 255
S70 E04 716
S70 E10 716
S70 334 708
S70 E06 408
S70 30L 450
S70 516 495
S70 516 496
S70 516 497
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
HEAT EXCHANGER
OUTDOOR FAN MOTOR
THERMISTOR (DISCHARGE)
LINEAR EXPANSION VALVE
COMPRESSOR (WITH CONVERSION KIT)
STOP VALVE (LIQUID)
BALL VALVE
CRANKCASE HEATER
THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
STRAINER
MUFFLER
HIGH PRESSURE SWITCH
CHARGE PLUG
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
FILTER DRYER
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
BYPASS VALVE
BYPASS VALVE SOLENOID COIL
ACCUMULATOR
CHARGE PLUG
OUTDOOR CONTROLLER BOARD
FUSE
FAN MOTOR CAPACITOR
TERMINAL BLOCK
TERMINAL BLOCK
CONTACTOR
HEAT EXCHANGER
STRAINER
ACOCSTIC COMPRESSOR CAP
ACOCSTIC COMPRESSOR BASE
ACOCSTIC COMPRESSOR JACKET
N026P72MT
M8
N02A672MT
ZR61KCW-TFD-522
3/8"
3/4"
240V / 38W
#50-19.1
OFF:3.3MPa ON:2.6MPa
[4.0 ✕ [3.0 ✕ 200mm
[4.0 ✕ [3.0 ✕ 200mm
[4.0 ✕ [2.0 ✕ 400mm
6.3A
3.5+ ✕ 440V
3P(S1,S2,S3)
4P(L1,L2,L3,N)
MSO-N20
#50-9.52
(PART OF BOARD)
W
COMPRESSOR COVERSION KIT (TFD-230) is packaged with compressor ZR61KCE-TFD-522 which Parts No. is S70 080 400.COMPRESSOR CONVERSION KIT (TFD-230) is necessary only for replacing faston type COMPRESSOR ZR61KCE-TFD-230 with screw type COMPRESSOR ZR61KCW-TFD-522.
W
Part number that is circled is not shown in the figure.
OC261-B--3.qxp 03.2.19 3:19 PM Page 69
70
18
24
25
11
96 8
12
13
3
21
19
2
4
10
16
1
33 32 2931 30 28 27
FUNCTIONAL PARTSPUH-P6YGAA.UK PUH-P6YGAA 1.UKPU-P6YGAA.UK PU-P6YGAA 1.UK
15
17
26
22
14
75
12
23
20
FUSE
OC261-B--3.qxp 03.2.19 3:19 PM Page 70
71
Part No. Part Name SpecificationNo.Wining
DiagramSymbol
Recom-mended
Q,ty
Price
Unit AmountRemarks
Q,ty/set
PUH-P6Y PU-P6Y
GAA.UK GAA.UKGAA1.UK GAA1.UK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
1
1
1
1
1
1
MF
MF
TH4
LEV
MC
CH
TH3, TH6
63H
21S4
SV
O.B
FUSE
C3, C4
TB2
TB1
51C, 52C
S70 E03 763
S70 30L 115
S70 30L 097
S70 E07 408
S70 E04 763
S70 E19 202
S70 E06 401
S70 081 400
S70 300 418
S70 E05 411
S70 E01 236
S70 E17 202
S70 42L 450
S70 42L 467
S70 E00 208
S70 E01 413
S70 251 242
S70 E02 403
S70 E03 405
S70 E05 425
S70 E06 425
S70 E04 425
S70 A14 428
S70 351 242
S70 E06 440
S70 E00 413
S70 32L 315
S70 520 239
S70 17T 255
S70 E04 716
S70 E10 716
S70 334 708
S70 E06 408
S70 30L 450
S70 516 495
S70 516 496
S70 516 497
OUTDOOR FAN MOTOR
PROPELLER FAN 4
NUT
HEAT EXCHANGER
OUTDOOR FAN MOTOR
THERMISTOR (DISCHARGE)
LINEAR EXPANSION VALVE
COMPRESSOR
STOP VALVE (LIQUID)
BALL VALVE
CRANKCASE HEATER
THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
STRAINER
MUFFLER
HIGH PRESSURE SWITCH
CHARGE PLUG
4-WAY VALVE SOLENOID COIL
4-WAY VALVE (REVERSING)
FILTER DRYER
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
BYPASS VALVE
BYPASS VALVE SOLENOID COIL
ACCUMULATOR
CHARGE PLUG
OUTDOOR CONTROLLER BOARD
FUSE
FAN MOTOR CAPACITOR
TERMINAL BLOCK
TERMINAL BLOCK
CONTACTOR
HEAT EXCHANGER
STRAINER
ACOCSTIC COMPRESSOR CAP
ACOCSTIC COMPRESSOR BASE
ACOCSTIC COMPRESSOR JACKET
N026P72MT
M8
N02A672MT
ZR72KCW-TFD-522
3/8"
3/4"
240V / 38W
#50-19.1
OFF:3.3MPa ON:2.6MPa
[4.0 ✕ [3.0 ✕ 200mm
[4.0 ✕ [3.0 ✕ 200mm
[4.0 ✕ [3.0 ✕ 450mm
6.3A
3.5+ ✕ 440V
3P(S1,S2,S3)
4P(L1,L2,L3,N)
MSO-N20
#50-9.52
(PART OF BOARD)
Part number that is circled is not shown in the figure.
OC261-B--3.qxp 03.2.19 3:19 PM Page 71
14 OPTIONAL PARTS
1. Drain Socket
Part No.Applied models
PAC-SF37DS-EPU(H)-P • GAA
Part No.Applied models
PAC-SF08SG-EPU(H)-P • GAA
2. Air Outlet Guide
Part No.Applied models
PAC-SF16DP-EPU(H)-P1 ~ 4 • GAA
3. Drain Pan
Part No.Applied models
PAC-SF48MA-EPU(H)-P • GAA
4. A / M-NET Adapter
PAC-SF17DP-EPU(H)-P5/6YGAA
w PU(H)-P4/P5/P6 • GAA needs two piece.
cCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.Distributed in Feb. 2003 No.OC261 REVISED EDITION-B 36Distributed in Jul. 2002 No.OC261 REVISED EDITION-A 247Distributed in Sep. 2001 No.OC261 250Made in Japan.
New publication, effective Feb. 2003Specifications subject to change without notice.