Noise Control in HVACActive Passive or None

Dr Geoff LeventhallNoise and Vibration Consultant

[email protected]

Page 2: Noise Control in HVAC - CIBSE ASHRAE Group

2

Page 3: Noise Control in HVAC - CIBSE ASHRAE Group

3

Page 4: Noise Control in HVAC - CIBSE ASHRAE Group

4

Page 5: Noise Control in HVAC - CIBSE ASHRAE Group

5

Page 6: Noise Control in HVAC - CIBSE ASHRAE Group

6

Noise Sources in HVAC - B5

Page 7: Noise Control in HVAC - CIBSE ASHRAE Group

7Fan Noise Propagation

Page 8: Noise Control in HVAC - CIBSE ASHRAE Group

8

Page 9: Noise Control in HVAC - CIBSE ASHRAE Group

9

Page 10: Noise Control in HVAC - CIBSE ASHRAE Group

10

Control

of

Noise Transmission in Ducts

Attenuation of Travelling Noise

Page 11: Noise Control in HVAC - CIBSE ASHRAE Group

11

Page 12: Noise Control in HVAC - CIBSE ASHRAE Group

12

All duct systems have

Frequency dependent

attenuation

Frequency

dB

Page 13: Noise Control in HVAC - CIBSE ASHRAE Group

13

Lined Ducts used widely in the USA.Lined Ducts used widely in the USA.

Gives noise attenuation and thermal insulation, but raises concerns for health. Not now recommended for sensitive locations except with special precautions. Older systems taken out, for example in schools and health care.

UK uses more localised silencers than USA. UK ~100%. USA ~50%

Page 14: Noise Control in HVAC - CIBSE ASHRAE Group

14

Lined DuctRectangular duct attenuation depends on

Perimeter/area, (Pd/Ad), and Lining Thickness

Attenuation is not as well known for circular ducts

Page 15: Noise Control in HVAC - CIBSE ASHRAE Group

15

Johns Manville Superduct RC Air Duct Board

Page 16: Noise Control in HVAC - CIBSE ASHRAE Group

16

[From CIBSE B5]

Page 17: Noise Control in HVAC - CIBSE ASHRAE Group

17

Significance of Pd/Ad

Duct Dimensions

Pd/Ad

3m x 3m 1.3

1m x 1m 4

1.2m x 0.3m 8

0.3m x 0.3m 13

0.15m x 0.15m 27

Page 18: Noise Control in HVAC - CIBSE ASHRAE Group

18

Page 19: Noise Control in HVAC - CIBSE ASHRAE Group

19

Localised AttenuationParallel baffle (passive) silencer

Page 20: Noise Control in HVAC - CIBSE ASHRAE Group

20Parallel Baffle Silencer

Page 21: Noise Control in HVAC - CIBSE ASHRAE Group

21

Duct Silencers Duct Silencers -- parallel baffleparallel baffleConsiderations

• Length, width, height….. weight

• Baffle thickness, Air gap

• Air velocity

• Pressure loss - varies as (velocity)2

• Location wrt fan, bends etc

Page 22: Noise Control in HVAC - CIBSE ASHRAE Group

22

Silencer attenuation 200mm/200mm Variation with length

0

10

20

30

40

50

60

63 125 250 500 1000 2000 4000 8000 Octave band frequency Hz

Att

en

ua

tio

n d

B

2400mm

2100mm

1800mm

1500mm1200mm

900mm

Page 23: Noise Control in HVAC - CIBSE ASHRAE Group

23

Limitations of Passive SilencersLimitations of Passive Silencers

• Poor low frequency attenuation

• LF attenuation improved by narrow air gaps and longer length

• This leads to higher pressure loss

Page 24: Noise Control in HVAC - CIBSE ASHRAE Group

24

Energy loss in silencers

Power (W) used against pressure loss

Air flow (m3/s) x pressure loss(Pa)

fan-motor efficiency

10m3/s into 100Pa > 1KW

Page 25: Noise Control in HVAC - CIBSE ASHRAE Group

25

Energy use by fans in the UK(Lockwood - FETA Magazine December 2005)

Fans in the range 1.1kW to 400kW consume

33.5TWh per year of electricity33.5TWh per year of electricity

Potential saving of

22.5% (7.5TWh)22.5% (7.5TWh)

by improved fan and system efficiency.

Page 26: Noise Control in HVAC - CIBSE ASHRAE Group

26

Sector Electricity Use – UK 2003

Sector Use TWh

Industry 113.926Transport 8.528Domestic 115.761Public Admin 20.966Commercial 74.328Agriculture 4.025

Total 337.444 TWh

Page 27: Noise Control in HVAC - CIBSE ASHRAE Group

27

Signalmic

Loudspeaker

ControllerControlmic

Active silencer

Page 28: Noise Control in HVAC - CIBSE ASHRAE Group

28

Active silencersActive silencers• Good low frequency attenuation

• Normally combine active/passive for full range attenuation

• Lower pressure loss

• Smaller size and weight than passive for similar LF performance

• Higher initial cost?

Page 29: Noise Control in HVAC - CIBSE ASHRAE Group

29

Active Silencer attenuationActive Silencer attenuation

Page 30: Noise Control in HVAC - CIBSE ASHRAE Group

30

Silencer Requirements:1.5 m length; <50 Pa pressure loss; >25 dB attenuation at 125 HzNon-porous media

Not possible by passive silencer

Page 31: Noise Control in HVAC - CIBSE ASHRAE Group

31

Silencer Dimensions:1500 L x 1400 W x 1600 H

Page 32: Noise Control in HVAC - CIBSE ASHRAE Group

32

1400 mm

1600 mm

View from reverb room into end of silencer from discharge side

Page 33: Noise Control in HVAC - CIBSE ASHRAE Group

33

Page 34: Noise Control in HVAC - CIBSE ASHRAE Group
Page 35: Noise Control in HVAC - CIBSE ASHRAE Group

35

Gas Platform AHU Active-Passive Silencer

0

10

20

30

40

50

60

70

80

90

100

63 125 250 500 1000 2000 4000 8000Octave Band Frequency

Soun

d Pr

essu

re L

evel

PassiveActive

Vibro-Acoustics Wise Associates

Page 36: Noise Control in HVAC - CIBSE ASHRAE Group

36

Passive silencing √

Active silencing √

Is no silencing possible?

Page 37: Noise Control in HVAC - CIBSE ASHRAE Group

37

Is no silencing possible?

• Very quiet fan operating optimally

• Good duct design

• Modify our noise level requirements

- less demanding criteria

[One of the necessary lifestyle changes in the future?]

Page 38: Noise Control in HVAC - CIBSE ASHRAE Group

38[ASHRAE 2003]

Fan is quietest at maximum efficiencyFan is quietest at maximum efficiency

Page 39: Noise Control in HVAC - CIBSE ASHRAE Group

39

Fan outlet configuration - 1Slope 1 in 7

A > 1.5B

From SMACNA Guide - HVAC Sound and Vibration Manual 2005

Page 40: Noise Control in HVAC - CIBSE ASHRAE Group

40

Fan outlet configuration - 2Full radius turning vanes

Minimum

150mm radius

From SMACNA Guide

Page 41: Noise Control in HVAC - CIBSE ASHRAE Group

41

Reducing air flow generated noise

From SMACNA Guide

Page 42: Noise Control in HVAC - CIBSE ASHRAE Group

42From SMACNA Guide

Page 43: Noise Control in HVAC - CIBSE ASHRAE Group

43From SMACNA Guide

Page 44: Noise Control in HVAC - CIBSE ASHRAE Group

44From SMACNA Guide

Page 45: Noise Control in HVAC - CIBSE ASHRAE Group

45

Most duct elements have attenuation which increases with frequency, although attenuation may drop at higher frequencies.

Lined bends simple and effective

Hz

dB Lined

Unlined

Residual low frequency attenuation requirements obtained by active silencers

Page 46: Noise Control in HVAC - CIBSE ASHRAE Group

46

?Do we over-silence?

How much are criteria conditioned by culture and expectations?