What’s New in NFPA 13 – 2010 (That I can cover in 30 minutes) Kenneth E. Isman, P.E., F.S.F.P.E. Vice President of Engineering

Upload: luis-enrique-rodriguez-rios

Post on 21-Apr-2015

237 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: NFPA 13 2010 Changes in a Nutshell

What’s New in NFPA 13 – 2010(That I can cover in 30 minutes)

Kenneth E. Isman, P.E., F.S.F.P.E.Vice President of Engineering

Page 2: NFPA 13 2010 Changes in a Nutshell

Outline• Seismic Load Tables• Shortened Density-Area Curves• High Clearance for Storage• New Discharge Rules for Specific Situations

• Back-to-Back Shelf Storage• Record Storage in Racks• Compact Storage• High-Bay Record Storage

• Darcy-Weisbach Friction Loss for Antifreeze

Page 3: NFPA 13 2010 Changes in a Nutshell

Seismic Load Tables

• 2007 – Load tables added for Schedule 10 and Schedule 40 steel

• 2010 – Load tables added for other types▫ Schedule 5 steel pipe▫ CPVC pipe▫ Type M copper tube

Page 4: NFPA 13 2010 Changes in a Nutshell

Seismic Load Tables

• Other types of pipe with different wall thicknesses▫ Use the tables in NFPA 13 for the same

pipe material with a thinner wall; or▫ Use Manufacturer’s Tables

Page 5: NFPA 13 2010 Changes in a Nutshell

Seismic Load Tables

Page 6: NFPA 13 2010 Changes in a Nutshell

Seismic Load Tables

Page 7: NFPA 13 2010 Changes in a Nutshell

Shortened Density-Area Curves

• No change to Chapter 11 (light, ordinary and extra hazard curves)

• For high-piled storage ▫ 2000 ft2 (186 m2) through 3000 ft2 (279 m2)

• For miscellaneous storage▫ 1500 ft2 (139 m2) through 3000 ft2 (279 m2)

Page 8: NFPA 13 2010 Changes in a Nutshell

General Storage Density/Area Curves

Former

New

Page 9: NFPA 13 2010 Changes in a Nutshell

Rack Storage Density/Area Curves

Former

Page 10: NFPA 13 2010 Changes in a Nutshell

Rack Storage Density/Area Curves

New

A BC D E FG H J

I

Page 11: NFPA 13 2010 Changes in a Nutshell

High Clearance above Storage

• Solid Piled Storage▫ 12.1.3.4.2▫ Where the clearance exceeds 20 ft (6.1 m)▫ Base protection on the storage height that would

result in a 20 ft (6.1 m) clearance

▫ Example: 15 ft storage in 40 ft high building▫ Design sprinkler system for 20 ft storage

Page 12: NFPA 13 2010 Changes in a Nutshell

High Clearance above Storage

• Rack Storage ≤ 25 ft (7.62 m) in height Class I-IV▫ 12.1.3.4.3▫ Where the clearance exceeds 20 ft (6.1 m)▫ Base protection on the storage height that would

result in a 20 ft (6.1 m) clearanceOR▫ Provide one level of supplemental, quick-response

in-racks sprinklers located directly below the top tier of storage at every flue space intersection.

Page 13: NFPA 13 2010 Changes in a Nutshell

High Clearance above Storage• Rack Storage > 25 ft (7.62 m) Class I-IV & all

Plastics▫ 12.1.3.4.4▫ Where the clearance exceeds 10 ft (3.05 m)▫ Base protection on the storage height that would

result in a 10 ft (3.05 m) clearanceOR▫ Provide one level of supplemental, quick-response

in-racks sprinklers located directly below the top tier of storage and every flue space intersection

Page 14: NFPA 13 2010 Changes in a Nutshell

High Clearance above Storage

• In-Rack Sprinklers

▫ 12.1.3.4.5.1 When applying the supplemental in-rack sprinkler option, the ceiling density shall be based upon the given storage height with an assumed acceptable clearance to ceiling

Page 15: NFPA 13 2010 Changes in a Nutshell

Back-to-Back Shelf Storage

Page 16: NFPA 13 2010 Changes in a Nutshell

Back-to-Back Shelf Storage• Design criteria was added to Chapters

14 and 15

Aisle

Max 60”Min 60”For Group A

Max15’

Page 17: NFPA 13 2010 Changes in a Nutshell

Back-to-Back Shelf Storage

• Back-to-Back Shelf Storage▫ Two solid or perforated shelves up to 30 inches

(762 mm) in depth each▫ Not exceeding a total depth of 60 inches (1.5 m)▫ Separated by a longitudinal vertical barrier such

as plywood, particle board, sheet metal, or equivalent

▫ Maximum ¼-inch diameter penetrations▫ No longitudinal flue space▫ Maximum storage height of 15 feet (4.5 m).

Page 18: NFPA 13 2010 Changes in a Nutshell

Cartoned Record Storage With Catwalk Access (20.5)

Transverse flue sprinklers

Catwalk sprinklers

Page 19: NFPA 13 2010 Changes in a Nutshell

Record Storage in Cartons on Racks

• Protection scenario is only permitted for Class III▫ Sprinklers at the ceiling▫ Sprinklers under catwalks▫ Sprinklers in transverse flue spaces

Page 20: NFPA 13 2010 Changes in a Nutshell

Carton Records Storage

• Carton Records Storage▫ A Class III commodity consisting of predominantly

paper records in cardboard cartons on shelving in a rack storage system.

• Annex ▫ Class III commodity can have up to 5% plastics

▫ Materials stored include Class I and II, paper business records, books, magazines, stationery, newspapers, and cardboard dividers

Page 21: NFPA 13 2010 Changes in a Nutshell

Carton Records Storage• Structural Criteria▫ Single-row or double-row rack structure with

uprights 10 ft 6 in (3.2 m) apart maximum ▫ Shelving – 50% open▫ Transverse flue spaces; Longitudinal flues not

required▫ Catwalk aisles between racks are open metal

grating that is at least 50% open Catwalk aisles at the ends of racks – solid

▫ Maximum 12 ft (3.7 m) vertical separation for catwalks

Page 22: NFPA 13 2010 Changes in a Nutshell

Criteria for Carton Records Storage

• Ceiling sprinkler spacing, maximum 100 ft2 (9.3 m2)• Ceiling sprinkler discharge criteria

Up to 25 ft High Over 25 ft High

Ord. Temp

High Temp

Ord. Temp

High Temp

Density 0.33 0.29 0.3 0.4

Area 2000 2000 2000 2000

Hose 500 500 500 500

Duration 2 2 2 2

Page 23: NFPA 13 2010 Changes in a Nutshell

Sprinkler Criteria

• Catwalk Sprinklers▫ QR, ordinary temp, K-5.6, K-8.0 or K-11.2.▫ In the center +/- 4 inches (102 mm) of each aisle

below each Catwalk level. ▫ Min. 6 inches (152 mm) above the top of storage▫ Supplied from the in-rack sprinkler system.

• Sprinkler spacing within the aisles aligns with the transverse flues and the center of the storage unit when staggered and does not exceed 10 ft 6 in (3.2 m) on center

Page 24: NFPA 13 2010 Changes in a Nutshell

Compact Storage (Mobile Shelves)(20.6)

Pictures courtesy of Spacesaver

Page 25: NFPA 13 2010 Changes in a Nutshell

Compact Storage

• Compact Storage▫ Solid shelves▫ 36 inches (914 mm) or less in total depth▫ Arranged as part of a compact storage module▫ 30 inches (762 mm) maximum between shelves

vertically▫ No internal vertical flue spaces other than those

between individual shelving sections.• Compact Storage Module▫ Units move so storage can be pushed together▫ No flues, minimal spaces between units▫ Aisles created by moving the shelving unit

Page 26: NFPA 13 2010 Changes in a Nutshell

Compact Storage

• Protected w/light hazard sprinkler sys.▫ Limited to 8 ft (2.4 m) in height▫ Only paper files, magazines, books and

similar documents▫ Miscellaneous 5% plastics allowed▫ Must have 18 inches (457 mm) of clearance

above unit to sprinkler deflectors Ordinary temperature, quick-response

sprinklers

Page 27: NFPA 13 2010 Changes in a Nutshell

High-Bay Record Storage (mobile) (20.7)

Page 28: NFPA 13 2010 Changes in a Nutshell

High Bay Record Storage

• Ceiling only sprinkler protection ▫ Class III Commodity paper products (files, magazines, books etc)

▫ Corrugated containers either closed or open top, to include corrugated totes, with no more than 5% plastics stored

▫ Mobile (or fixed) shelving units greater than 12 ft (3.7 m) and up to 34 ft (10.4 m) high and up to 30 shelving units (storage tiers) high.

• ESFR Sprinklers▫ K-factor 25.2 at 40 psi (2.8 bar)

Page 29: NFPA 13 2010 Changes in a Nutshell

High Bay Records Storage

Page 30: NFPA 13 2010 Changes in a Nutshell

Antifreeze Calculations

• Solutions▫ Weight or volume

• Darcy-Weisbach friction loss for systems over 40 gal in size▫ Finding the friction factor (f)▫ Using the right value of ε for aged pipe

• K-Factor adjustment for sprinklers

Page 31: NFPA 13 2010 Changes in a Nutshell

Finding “ f ”

• If Reynolds Number (Re) is less than 2000

f = 64/Re

• If Reynolds number is greater than 3000, use Moody Diagram to find “ f ”

• If Reynolds number is between 2000 and 3000, extension of Moody Diagram curves is most conservative solution

Page 32: NFPA 13 2010 Changes in a Nutshell

Roughness of Pipe

• Measured by the variable “ε” in units of length (inches or feet)

• Divided by diameter of pipe to become dimensionless

• No standardization of how to treat pipes like we have for “C” factor in H-W

Page 33: NFPA 13 2010 Changes in a Nutshell

Roughness of Pipes

• According to Isman▫ C of 100 = ε of 0.015 inches▫ C of 120 = ε of 0.004 inches▫ C of 150 = ε of 0.000084 inches▫ New steel pipe averages 0.0018 inches▫ These values are in A.22.4.4.5.1 in NFPA 13

• According to Viking▫ C of 120 = ε of 0.00015 ft▫ C of 120 = ε of 0.0018 inches

Page 34: NFPA 13 2010 Changes in a Nutshell

Roughness of Pipe

0

0.001

0.002

0.003

0.004

0.005

0.006

0.007

0.008

0.009

0.01

0.011

0.012

0.013

0.014

0.015

0.016

80 100 120 140 160

Hazen-Williams C Factor

Dar

cy W

eisb

ach

E Fa

ctor

Isman

Viking

Page 35: NFPA 13 2010 Changes in a Nutshell

Adjusting K-Factors for Cold Antifreeze

• Sprinkler has a K-factor of 11.2 with water• Being used in a large antifreeze system with

50% Propylene Glycol by weight• Density is 66.8 lbs/cubic ft (see Figure 7.6.2.5(b)

of NFPA 13 and know that 1g/ml = 62.43 lbs/cu. ft.)

( ) 9.108.66

12.1194.7194.7 ===A

WA KKγ

Page 36: NFPA 13 2010 Changes in a Nutshell

Antifreeze Example

12345 678910 111213

40 ft of 1¼ inch schedule 40

50 ft of 4 inch schedule 40

2 ft of 2 inch schedule 40

TR1BR1

BR2

BR310’

12’

Page 37: NFPA 13 2010 Changes in a Nutshell

Antifreeze Example

• Complete calculation using same technique• Final Demand using Darcy-Weisbach▫ Flow = 405 gpm▫ Pressure = 41 psi

• Final Demand using Hazen-Williams▫ Flow = 350 gpm▫ Pressure = 19 psi▫ H-W incorrectly predicted pressure by more than

100% and flow by about 20%