Nexxtender DUAL & SINGLE Manual
1
Nexxtender Single & Dual Pole Installation, Connection and Start-‐up Instructions
Introduction: This document describes the standard installation procedure for the Nexxtender SINGLE & DUAL pole charging station. As a general rule, the installation must be performed by a capable and qualified individual, in compliance with local laws and regulations, following the proper rules and safety measures. As concerns the Start-‐up: besides possessing the necessary technical competences required for the installation and connection of the charging station, the installer must also possess sufficient knowledge and skills concerning electric vehicles (ISO standard 61851-‐1).
Nexxtender DUAL & SINGLE Manual
2
Installation instructions for a single or dual pole charging station:
Unpacking and opening the station In order to install the charging station, open the rear panel to access the different connection points. To do this, place the station vertically on its base and remove the 8 screws on the rear door. Disconnect the ground wire between the pole and the door.
Figure 1: rear view of the station pedestal with door closed
Nexxtender DUAL & SINGLE Manual
3
Figure 2: station pedestal with door opened
Nexxtender DUAL & SINGLE Manual
4
Figure 3: anchorage zone
Nexxtender DUAL & SINGLE Manual
5
Assembling the pedestal In order to maintain the station in a vertical position, a floor anchoring is required. Before starting the installation, a concrete base with central incoming cables is needed. In order to maintain the screen readability and to avoid discoloration of the Nexxtender front side (due to UV) it is recommended not to orient the station towards the south. According to the nature of the floor, plan for an adequate foundation to ensure sufficient stability and solidity for the device. Minimum dimensions of the pedestal and drill template:
Figure 4: see plan in Annexes for further details
Nexxtender DUAL & SINGLE Manual
6
Example of ground preparation:
Figure 5: example of pedestal preparation with incoming power and data cables
The pedestal will have a visible surface of min. 540 mm x 245mm. Prepare, per charge line, a power cable of 6mm² or 10 mm², according to the distance from the start panel. For a single pole: ONE single-‐phase cable (240VAC) or 3-‐phase cable + N (380VAC +N) For a dual pole: TWO single-‐phase cables (240VAC) or 3-‐phase cables + N (380VAC +N). Allow for 120 cm of cable length above the concrete level, so as to easily make the connection. If a network cable is used, allow for 220 cm of cable above ground.
Nexxtender DUAL & SINGLE Manual
7
Installing the terminal After drilling 4 anchoring holes in the concrete base and placing the fixing rods, position the station’s terminal while making sure that the cables are inserted through the central hole, as shown in the figure below:
Figure 6: clamping the anchorage
Nexxtender DUAL & SINGLE Manual
8
Recommended fixings: Anchor FIX3 (code 057450) The anchor that nears concrete’s resistance!
Features: Drill diameter (mm) 8 Max. thickness (mm) 5 Anchor length (mm) 55 Drilling depth (mm) 50
Making the connections in the junction box Every power entry (1 per charging point) has a junction box, itself equipped with a differential switch and a circuit breaker with the following features: Circuit breaker:
Ref. 006567 DX Circuit Breaker -‐6 kA – tetrapolar – Curve C – nominal current 40 A – four 17.5 mm modules – Lexic 400 V
Cheville FIX3 (code 057450)
La cheville qui atteint la résistance du béton !
Construction métallique Construction bois Fixation en facade
Diamètre perçage (mm) 8
Epaisseur maxi pièce à fixer (mm) 5
Longueur Cheville (mm) 55
Profondeur perçage (mm) 50
30% de performances en plus : sa limite sera celle de votre béton !
FICHE SUR LE PRODUIT www.ecataleg.be V2014.01
Legrand Group BelgiumKouterveldstraat 9, 1831 Diegem
Tel.: (+32) 02 719 17 11 - Fax : (+32) 02 719 17 00
Réf. 006567Disjoncteur DX - 6 kA - tétrapolaire - courbe C -intensité nominale 40 A - 4 modules de 17,5 mm -Lexic 400 V
Caractéristiques • ICGME: 210060 • Description de facturation : Disj. DX - 6 kA - 4p c40 4 mod Lexic 400V• Fabricant : Legrand
Documentation Catalogue Legrand 2013-2014 - p.41
Fiche Technique F00407FR-00.pdf
Fiche Technique F00407EN-00.pdf
Images 006356_pw_92153.jpg
http://www.ecataleg.be/fr/ref/006567
Créée le: 17/11/2014 Legrand Group Belgium nv-s.a. 1 / 1
Nexxtender DUAL & SINGLE Manual
9
Differential switch:
Reference 008865 Differential switch – tetrapolar – 30 mA – 40 A – Type A – Lexic 400 V – four 17.5 mm modules
Connect every entry point completely and make sure that the ground wire is also connected. Insert the cables and thread into the cable glands provided for that purpose. It should be noted that the cable coming from the ground will be mechanically locked with the fixing lug (see picture below) with cable ties (colson).
FICHE SUR LE PRODUIT www.ecataleg.be V2014.01
Legrand Group BelgiumKouterveldstraat 9, 1831 Diegem
Tel.: (+32) 02 719 17 11 - Fax : (+32) 02 719 17 00
Réf. 008865Interrupteur différentiel - tétrapolaire - 30 mA - 40 A -Type A - Lexic 400 V - 4 modules de 17,5 mm
Caractéristiques • ICGME: 210060 • Description de facturation : Inter dif 4p 30mA 40A Type A Lexic 400V - 4 mod• Fabricant : Legrand
Documentation Catalogue Legrand 2013-2014 - p.58
Notice Produit 096871005-05.pdf
Fiche Technique F00406EN-00.pdf
Images bpc008865.jpg
http://www.ecataleg.be/fr/ref/008865
Créée le: 17/11/2014 Legrand Group Belgium nv-s.a. 1 / 1
Nexxtender DUAL & SINGLE Manual
10
After completely connecting the power cables, check the connection clamping and check the ground wiring on the metal frame. Then put the ground wire back on the holding socket provided for that purpose on the service door.
Figure 7: example of preparing the cables with open panelboard
Nexxtender DUAL & SINGLE Manual
11
Start-‐up Instructions In case the Nexxtender is connected with GPRS/3G or with LAN, the following text will appear on the screen after turning it on and complete boot-‐up:
-‐ LED in bleu -‐ NET = OK -‐ Automatically synchronized time via the network.
Then, test the proper functioning of the station with a station simulator. This will simulate all the states planned by the ISO standard 62851-‐1. If possible, start a power test with an electric vehicle. Complete start up requires a specific training provided by Powerdale.
Main features of the single or dual Nexxtender station:
-‐ Single-‐phase 230 VAC or 3-‐phase 380VAC with Neutral -‐ Up to 32A per phase adaptable on demand -‐ Mode 3 type 2 -‐ Mechanical locking of the Type 2 plug -‐ GPRS Communication available -‐ RFID reader available -‐ LAN Communication available
Also see the product datasheet.
Nexxtender DUAL & SINGLE Manual
12
Annexes:
Pedestal template
Overall dimensions