TECHNOLOGYDRAWING LIST
T100
DWG# TITLE
COVER PAGE
T101 EXISTING DEVICES
T102 NEW COUNCIL CHAMBER LAYOUT
T103 SECTIONS
T104 WORKSPACE DETAILS
T105 EQUIPMENT DETAILS
T200 AV SYSTEMS SCHEMATIC
1. ELECTRICAL NON-METALLIC TUBING (ENT, COMMONLY REFERRED TO AS "CORELINE") ISNOT ACCEPTABLE.
2. CONTRACTOR TO PROVIDE COVERS ON ALL JUNCTION BOXES, A PULL STRING IN ALLINSTALLED CONDUITS, AND NYLON GROMMETS ON ALL CONDUIT STUBS.
3. PROVIDE NYLON BUSHINGS FOR CONDUITS, COVERS FOR ALL JUNCTION BOXES ANDPULLSTRINGS IN ALL EMPTY CONDUITS.
4. NO MORE THAN (3) 90° BENDS BETWEEN JUNCTION BOXES FOR ALL A/V CONDUITS. REFERTO TIA STANDARDS FOR MINIMUM BEND RADIUS ON ALL CONDUITS.
5. PROVIDE SEISMIC RESTRAINT AS REQUIRED BY LOCAL BUILDING CODE. PROVIDE SEISMICREVIEW BY SEISMIC PROFESSIONAL ENGINEER. SUBMIT SIGNED AND SEALED REVIEWREPORT WITH OPERATIONS AND MAINTENANCE MANUALS.
6. PROVIDE FIRE STOPPING AS REQUIRED BY LOCAL BUILDING CODE. FIRE STOPPINGASSEMBLY MUST BE RATED AS SUCH TO MAINTAIN THE FIRE RATING WHERE THEPENETRATION OCCURS. CONSULT WITH FIRE STOPPING EXPERT TO REVIEW FIRESTOPPINGINSTALLATION. SUBMIT REVIEW REPORT WITH THE OPERATIONS AND MAINTENANCEMANUAL.
7. ALL SURFACE MOUNT AV EQUIPMENT REQUIRES SUFFICIENT BACKING.INSTALLATION MUST CONFORM TO BC BUILDING CODE.
TYPICAL VOICE/DATA WALL OUTLET.
TECHNOLOGY SYMBOL SCHEDULE
1. FREE AIR RUNNING OF CABLES WITHIN ACCESSIBLE DROP CEILING SPACES ISACCEPTABLE. PROVIDE J-HOOKS TO SUPPORT THE CABLES. ALL CABLES MUST BEFT6 RATED.
2. ALL CABLING FOR AV AND AV CONTROL SYSTEM DEVICES TO BE SUPPLIED ANDINSTALLED BY AV CONTRACTOR.
AV WIRING NOTES
FB
CAM EXISTING PTZ CAMERA
EXISTING FLOORBOX
EXISTING CEILING MOUNT PROJECTOR
EXISTING CEILING MOUNT PROJECTORSCREEN
IPCAM
EXISTING IP CAMERA
WIDE ANGLE PTZ CAMERA
CEILING MOUNT PROJECTOR
CEILING MOUNT PROJECTOR SCREEN
LONG THROW PTZ CAMERA
EXISTING IP CAMERA TO REMAIN
GENERAL NOTES
MICROPHONE STATION
BACKUP MICROPHONE
TOUCH PANEL
AV INPUT PLATE
T
FLOORBOX
1
3
IP
80" LCD MONITOR
1. ALL FASTENING LOCATIONS MUST HAVE SCANS TO LOCATE. RE-BAR PRIOR TOINSTALL.
2. FOR SCANNING OF ALL FASTENING BOLT LOCATIONS, CUTTING AND CORING, AVCONTRACTOR MUST BE CO-ORDINATE WITH SCANNING CONTRACTOR.
3. ALL MOUNTING LOCATIONS MUST BE APPROVED BY STRUCTURAL ENGINEER.
AV MOUNTING NOTES
1. LOCATIONS OF AV DEVICES IN MILLWORK MUST BE CONFIRMED ON SITE WITHOWNER'S REPRESENTATIVE.
2. MILLWORK CUTOUTS ARE TO BE COMPLETED BY MILLWORK CONTRACTOR.
MILLWORK NOTES
NAME OF PROJECT: NEW WESTMINSTER CITY HALL COUNCIL CHAMBER
CIVIC ADDRESS: 511 ROYAL AVENUE NEW WESTMINSTER, BC V3L 1H9.
PROJECT INFORMATION
T201 AV CONTROL SYSTEMS
CEILING SPEAKER
COUNCIL CHAMBERS
NEW WESTMINSTER CITY HALLAV SYSTEMS
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
COVERCOUNCIL CHAMBERS T100
FOR REFERENCE ONLY
FB
FBFB FB
FB
CAM
+76" AFF
CAM+95" AFF
CAM+84" AFF
CAM
IPCAM
EXISTING WALLMOUNT AV RACK
EXISTING MOVABLEPRODUCTION RACK
EXISTING LIGHTINGCONTROL INTERFACE
EXISTING CORING
CAMCAM
7'-1
1"
7'-0
"
CAM
6'-4
"
SYMBOL SCHEDULE
FB
CAM EXISTING PTZ CAMERA
EXISTING FLOORBOX
EXISTING CEILING MOUNTPROJECTOR
EXISTING CEILING MOUNTPROJECTOR SCREEN
NOTE:
EXISTING DEVICES SHOWN ON THE DRAWING IS FORINFORMATION ONLY. EXACT LOCATION TO BE CONFIRMED BYCONTRACTOR ON SITE.
IPCAM EXISTING IP CAMERA
CAM IPCAM
9'-6
1/4
"
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
EXISTING DEVICESCOUNCIL CHAMBERS T101
2COUNCIL NORTH WALL SECTION1/4" = 1'
3COUNCIL SOUTH WALL SECTION1/4" = 1'
4COUNCIL EXISTING DEVICES PLAN1/4" = 1'
1COUNCIL EAST WALL SECTION1/4" = 1'
3
1
1
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
8'-6
"
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
NEW CORING LOCATION.LOCATION TO BECONFIRMED ON SITE.
EXISTING IP CAMERA TOREMAIN
NEW WALL MOUNT RACK
NEW PRODUCTION RACK
EXISTING CRESTRON LIGHTINGCONTROL INTERFACE
AV
AV
AV
AV
AV
AV
AV
AV
AV
T
T
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
WALL MOUNT TOUCH PANEL+ 60" AFF . CONFIRM EXACT
LOCATION ON SITE.
AV80" LCD MONITOR
AV
IP
T
3
T103
5
6
SYMBOL SCHEDULE
WIDE ANGLE PTZ CAMERA
CEILING MOUNT PROJECTOR
CEILING MOUNTPROJECTION SCREEN
LONG THROW PTZ CAMERA
EXISTING IP CAMERA TOREMAIN
MICROPHONE STATION
BACKUP MICROPHONE
T
AV
TOUCH PANEL
AV INPUT PLATE
FLOORBOX
1
3
IP
80" LCD MONITOR
CEILING SPEAKER
TEL.
SERVER ROOM
LEGISLATIVESTORAGE
NEW AV RACKLOCATION TO BECO-ORDINATED ON SITE
1REFER TO ELECTRICAL DRAWINGFOR ROUTING OF CONDUIT
3
1
1
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
8'-6
"NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
NEW CORING LOCATION.LOCATION TO BECONFIRMED ON SITE.
EXISTING IP CAMERA TOREMAIN
NEW WALL MOUNT RACK
NEW PRODUCTION RACK
EXISTING CRESTRON LIGHTINGCONTROL INTERFACE
AV
AV
AV
AV
AV
AV
AV
AV
AV
T
T
NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.
WALL MOUNT TOUCH PANEL+ 60" AFF . CONFIRM EXACT
LOCATION ON SITE.
AV80" LCD MONITOR
AV
IP
T
3
T103
5
6
19'-8"
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
NEW COUNCIL CHAMBER LAYOUT T102
COUNCIL CHAMBER PLAN - COUNCIL MEETING1/4" = 1'-0"
SERVER ROOM PLAN1/4" = 1'-0"
COUNCIL CHAMBER PLAN - COMMITTEE OF WHOLE1/4" = 1'-0"
COUNCIL CHAMBER REFLECTED CEILING PLAN1/4" = 1'-0"
T102
1T102
2
T102
3T102
4
19'-8"
1'-0
"
1'-0"
11°
16°
7'-0
"
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
1
19'-8"
1'-0
"
1'-0"
6'-4
"
NEW PTZ CAMERA ATEXISTING CAMERA LOCATION
5'-0"
6'-8
"
12
7'-0
"
8'-6"3'-0"
7'-0
"
NEW DIGITAL CLOCK
10'-11 3/16"
6'-6
9/1
6"
7'-5
1/2
"
3
NEW PTZ CAMERA AT EXISTINGCAMERA LOCATION
EXISTING IP CAMERA TO REMAIN
NEW DIGITAL CLOCK
9'-0
"
3'-0"
IP3
5'-0
"
WALL MOUNTRACKFRONT VIEW
PRODUCTION RACKCONSOLE
ROLLINGPRODUCTION RACKSIDE VIEW
MONITOR MOUNTATTACHED TOPLATE
22" MONITOR
5'-0
"
WALL MOUNT RACKSIDE VIEW
PRODUCTION RACKCONSOLEWITH 22" MONITOR
ROLLINGPRODUCTION RACKFRONT VIEW
AV
T103
5
6
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
NORTH WALL SECTION1/4" = 1'-0"
SOUTH WALL SECTION1/4" = 1'-0"
WEST WALL SECTION1/4" = 1'-0"
EAST WALL SECTION1/4" = 1'-0"
AV CLOSET SOUTH ELEVATION1/2" = 1'-0"
AV CLOSET WEST ELEVATION1/2" = 1'-0"
SECTIONSCOUNCIL CHAMBERS T103
AV CLOSET WEST ELEVATION1/2" = 1'-0"
T103
1T103
2T103
3
T103
7T103
6T103
5T103
4
CITY CLERK
AV INPUT
POWER/DATA/USBCHARGING
AV INPUT
CABLE TRAY
CONF.STATION TABLE TOPTOUCHSCREENFOR CITY CLERK
MAYORCHAMBER CLERK
CABLING FORTOUCHSCREEN
TOGGLE SWITCH
TABLE TOPTOUCHSCREENFOR MAYOR
CABLE TRAY
DISPLAY MONITORCONF. STATIONTOGGLE SWITCH
POWER/DATA/USBCHARGING
AV INPUT PLATE
HATCH
CABLE TRAY(TYPICAL OF 2)
(2) 1.5" CONDUITSTO AV CABLING SPACE
BACKUP MIC
PRESENTATION DESK SECTIONPRESENTATION DESK ELEVATION
HATCH
CABLE TRAY(TYPICAL OF 2)
(2) 1.5" CONDUITSTO AV CABLING SPACE
CABLE TRAY
AUDIO INPUT
AV INPUT PLATE
PRESENTATION DESK PLAN PRESENTATION DESK SIDE ELEVATION
FOR CONNECTION OF PTTMICROPHONE SYSTEM. PLATE &CONNECTOR ON BOTH SIDE OFTABLE
5U
10U
15U
20U
25U
30U
35U
40U
44U CRESTRON CP 3SWITCH
OWNER SUPPLIED
CRESTRON AV MATRIX
WEPRESENT SENNHEISER
ADN CU 1
BIAMP AUDIAOWNER SUPPLIED
BIAMP TESIRAFORTE
TOA DA 250
SENNHEISER ADN CU 1
SERVER ROOM EQUIPMENT RACK BTU CALC
DESCRIPTION MANUFACTURER MODELRACKUNITS
POWERCONSUMPTION
QTY TOTALPOWER
EFFICIENCY BTU/Hr
CONTROL PROCESSOR CRESTRON CP3 1 24 1 24 5.00% 50OWNER SUPPLIED SWITCH N/A N/A 2 100 1 100 5.00% 325AV MATRIX CRESTRON DM-MD32X32 14 1100 1 1100 6.00% 3000WIRELESS PRESENTATION WEPRESENT WIPG1000 1 50 1 50 0.00% 171DISCUSSION CENTRAL UNIT SENNHEISER ADN CU1 2 245 2 490 0.00% 1673OWNER SUPPLIED DSP BIAMP AUDIA 2 100 1 100 0.00% 342DSP BIAMP TESIRA FORTE 2 100 1 100 0.00% 342POWER AMPLIFIER TOA DA 250 1 1200 1 1200 0.00% 4096
25 3164W 0W 9,999BTU/Hr
5U
10U
12U
RDL RU-MX4
EXTRON SMP351LISTEN LT-800
O/S (2) SHURE SLX4O/S SHURE UA844O/S POWER BAR
NETWORK SWITCH
AV PANEL
2 RU RACKMOUNT DRAWER
AV CLOSET WALL MOUNT RACK BTU CALC
DESCRIPTION MANUFACTURER MODELRACKUNITS
POWERCONSUMPTION
QTY TOTALPOWER
EFFICIENCY BTU/Hr
ANTENNA DISTRIBUTION SHURE UA844 1 25 1 25 50.00% 43DIVERSITY RECEIVER SHURE SLX44 1 10 1 10 50.00% 18STREAMING MEDIA PROCESSOR EXTRON SMP351 1 30 1 30 - 96AUDIO MIXER RDL RU-MX4 2 10 1 10 0.00% 35
5 75W 0W 192BTU/Hr"O/S" DENOTED "OWNER SUPPLIED"
5U
10U
14U
QCCUQCCUQCCUQCCUUPS
POWER BAR
2 RU RACKMOUNT DRAWER
AV CLOSET PRODUCTION RACK BTU CALC
DESCRIPTION MANUFACTURER MODELRACKUNITS
POWERCONSUMPTION
QTY TOTALPOWER
EFFICIENCY BTU/Hr
UPS N/A N/A 1 15 1 15 5.00% 49CAMERA CONTROL UNIT VADDIO ROBOSHOT 4 100 4 400 5.00% 1297
5 415W 0W 1,346BTU/Hr
CONNECT TOPRESENTATIONTABLE
MOVABLE TABLE PLAN
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
WORKSPACE DETAILSCOUNCIL CHAMBERS T104
CHAMBER CLERK / CITY CLERK / MAYOR ELEVATION3/4" = 1'-0"
TYPICAL COUNCILOR WORKSPACE ELEVATION3/4" = 1'-0"
TYPICAL WORKSPACE SECTION3/4" = 1'-0"
PRESENTATION PODIUM DETAILS3/4" - 1'-0"
SERVER ROOM RACK LAYOUTNTS
AV CLOSET WALL MOUNT RACK LAYOUTNTS
AV CLOSET PRODUCTION RACK LAYOUTNTS
T104
1
T104
3
T104
2
T104
5
T104
6
T104
7
T104
8
COMMITTEE OF WHOLE MOVABLE TABLES3/4" = 1'-0"T104
4
SIDE VIEW 2
REAR VIEWFRONT VIEW
BOTTOM VIEW
TOP VIEW
SIDE VIEW 1
7.0" [178.76]
6.7" [170.75] 1/4" x 20INSERT
7.0" [178.21]
2.2" [56.45]
4.8" [121.92]
3.5" [87.87] 3.459 [87.87]
5.4" [137.01]
7.0" [178.76]
5.5" [139.89]
4 1/
8"
3 1/2"
2 5/
8"
1 5/16"
4 1/2"
1 3/
4"
3 1/2"
1 7/
16"
10 1/8"
8 9/16"
6 7/
16"
5 3/
8"
2 1/4"
1/2"
2"
3 3/8"
3 3/8"
2 3/8"
WALL MOUNT BACK VIEW
WALL MOUNT BOTTOM VIEW
WALL MOUNT FRONT VIEW
WALL MOUNT TOP VIEW
WALL MOUNT SIDE VIEW
FINISHED WALL
4"
3"
5 5/16"
4 13
/16"
TABLE TOP SIDE VIEW
10 1/8"
TABLE TOP FRONT VIEW
4 13
/16"
GROUND
60"
3'-7
1/1
6"
1'-8
7/8
"
5'-10"
3'-3
1/2
"
2'-3"
6'-1 9/16"
6'-8
"
5'
9 1/2"
4 5/
8" 2
COUNCIL CHAMBER FINISHED FLOOR
VARIABLE AUDIO OUTPUT FIXED AUDIO OUTPUT
HD/SDI SDICOMPOSITECOMPOSITECOMPOSITEARCHIVERECORD
1'-1 13/16"
1'-5
5/1
6"
1'-3
5/1
6"
4 1/
8"
5 1/4"
4 1/
2"
7 7/
8"
ALL CABLING TO BE SECURED/CONCEALED TO PROVIDEA CLEAN INSTALL.
10 9
/16"
NOTE:ROUGH-INS BY DIV. 26CABLING AND TERMINATIONS BY DIV. 27
4"[103mm] SQUARE DEEP BOX
3-1/2"
35mm CONDUIT STUBBED-OUTTO ACCESSIBLE CEILING SPACE.PROVIDE NYLON BUSHINGAND PULL STRING.(BY DIV.26)
DIV.26 TO PROVIDE J-HOOKSAND/OR CONDUIT(S).
USE FLAT RECTANGULAROPENING (TILE) MUDRINGS
NOTES:
1. PATHWAYS FOR TECHNOLOGY CABLES SHALL BE PARALLEL TO BUILDING LINES. HORIZONTAL CABLING SHALL BE SUPPORTED BY J-HOOKS(BY DIV.27), CABLE TRAYS AND/OR PLACED IN CONDUIT.
2. THE NUMBER OF CABLES SUPPORTED BY J-HOOKS AND THE SPACING BETWEEN THE J-HOOKS SHALL FOLLOW MANUFACTURERS RECOMMENDATIONS.
3. CABLES OF DIFFERENT SYSTEMSSHALL BE BUNDLED SEPARATELY.
MAXIMUM 3 FEET
FASTENER
J-HOOK
VELCRO WRAPS FOREVERY 2 METER
A/VCABLE
WHITE (COMMON)BLACK (HOT)
GREEN120VAC 60Hz
GROUND MUST BECONNECTED TOBUILDING GROUND
GREEN
GROUNDTO CASE
MOTOR
UP
+5V
CO
MD
N
SPLITTERDRY CONTACTS
SUPPLIED ANDINSTALLED BYELECTRICALCONTRACTOR
SUPPLIED ANDINSTALLED BY
AVCONTRACTOR
TO 3-POSITIONLOW-VOLTAGEWALL SWITCH
4-CONDUCTORCABLING
ELECTRIC PROJECTION SCREEN WIRING DETAIL
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
EQUIPMENT DETAILSCOUNCIL CHAMBERS T105
PROJECTOR SCREEN DETAILS1/2" = 1'-0"
PTZ CAMERA DETAILS3" = 1'-0"
TYPICAL AV TRANSMITTER DETAILS6" = 1'-0"
TOGGLE SWITCH DETAILS3" = 1'-0"
TOUCHSCREEN CONTROL PANELNTS
80" LCD TV ELEVATION1/2" = 1'-0"
AV PRODUCTION AUDIO / VIDEO OUTPUT PLATE6" = 1'-0"
PRESS FEED FLOOR BOX DETAILS3" = 1'-0"
COUNCILLOR STATION AV INPUT DETAIL6" = 1'-0"
PROJECTOR MOUNTING DETAILS1" = 1'-0"
T105
1
T105
5
T105
2T105
4
T105
9
T105
11
T105
13
T105
3
T105
8T105
7
TYPICAL WALLMOUNTED AV BOX1-1/2" = 1'-0"T105
10
TYPICAL WALLMOUNTED AV DEVICE1-1/2" = 1'-0"T105
12
ELECTRICAL PROJECTION SCREEN WIRING DETAILNTST105
6
PRESENTATION TABLE AUDIO INPUT DETAIL6" = 1'-0"T105
14 PTT CONNECTION PLATE DETAIL6" = 1'-0"T105
15
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
AV SCHEMATICCOUNCIL CHAMBERS T200
REV DESCRIPTION BY DATE
Drawing scale may be affected by printing, scanning or copying.
- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER
- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19
650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545
ACUMENENGINEERING.CA
THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE
OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN
WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.
AV CONTROL SYSTEMCOUNCIL CHAMBERS T201