new symmetrical components · 2020. 4. 8. · synthesis of unsymmetrical phases from their...
TRANSCRIPT
Symmetrical Components
Submitted By:Santosh Kumar GuptaAssistant ProfessorEE Departmet, SIT Sitamarhi
Symmetrical Components
⚫ Symmetrical Component Analysis
⚫ Synthesis of Unsymmetrical
Phases from Their Symmetrical
Components
⚫ The Symmetrical Components of
Unsymmetrical Phasors
⚫ Phase Shift of Symmetrical
Components in Y− or −Y Transformer Banks
⚫ Power in Terms of Symmetrical
Components
Symmetrical Components
⚫ Unsymmetrical Series
Impedance
⚫ Sequence Impedance and
Sequence Network
⚫ Sequence Networks of
Unloaded generators
⚫ Sequence Network
⚫ Zero-Sequence Network
Symmetrical Component Analysis
Goal :
Symmetrical component analysis is a very useful tool
for dealing with unbalanced three-phase faults.
Synthesis of Unsymmetrical Phases from TheirSymmetrical Components 1
“An unbalanced system of n related phasors can be resolved into
n systems of balanced phasors called the symmetrical components
of the original phasors. The n phasors of each set of components
are equal in lengths , and the angles between adjacent phasors of
the set are equal.”
by C.L Fortescue , 1918
Synthesis of Unsymmetrical Phases from TheirSymmetrical Components 2
(2) Negative-sequencecomponents
c2
n
b2
2. For negative-sequence
components
(1) Positive- sequence components
1a
1b
c1
1. For positive- sequence
components
a2n
Synthesis of Unsymmetrical Phases from TheirSymmetrical Components 3
(3) Zero-sequence components
Va0
Vb0
Vc0
0 For zero-sequence components
Synthesis of Unsymmetrical Phases from TheirSymmetrical Components 4
b 0
V a = V a 1 + V a 2 + V a 0
V + V= V b 1 + V b 2b
V c = V c 1 + V c 2 + V c 0
Va0
Va2
Va
a1V
Vb1
Vb0
Vb2
Vc0
Vc1
Vc
Vb
Vc2
Synthesis of Unsymmetrical Phases from TheirSymmetrical Components 5
Use a to designate the operator that causes a rotationof
counterclockwise direction ,
= 1 2 4 0 0 = − 0 . 5 − j 0 . 8 6 6
= 1 3 6 0 0 = 1
a 2
a 3
a = 1120 0 = − 0 . 5 + j 0 . 8 6 6
1200 in the
− a2
−1,−a3
a2− a
1,a3
a
1
a 2
V b 0
c 2
= V a 0 , V c 0 = V a 0
, V = a 2 VVb 2 = a V a 2
, Vc 1 = aV a 1V = a 2 V
b1 a1
a1b1
1c
a2
c2
b2
The Symmetrical Componentsof Unsymmetrical Phasors 2
= a V + a2V + Va1 a 2 a 0Vc = Vc1 + Vc 2 + Vc0
= a2V + aV + Va1 a 2 a 0Vb = Vb1 + Vb 2 + Vb0
Va = Va1 + Va 2 + Va 0
1 a 2
a 1
c
b
1 V a 0
a 2 V
a V
V
1 1V = 1 a 2
a
Va
3
1
a 2
a 1 1 1
a 2
a
A = 1 a
a 2
13
1 1 1
A− 1 =1 1 a
a 2
c
b a V V
a 2 V
a 2
a1
Va 0
1
1 Va 1 1
a
a 2 3 V =
1 1
* When three phase phasors are balanced , only the
positive-sequence component exists .
4
1.Sequence component representation of L-Lvoltage
c a
bc a V V
a 2 V
a b 2
ab1
Va b0
1
1 Va b 1 1
a
a 2 3 V =
1 1
2.Sequence component representation of current
c
b a I I
a 2 I
a 2
a 1
I a 0
1
1 I a 1 1
a
a 2 3 I =
1 1
5
3
3
cbaa 0
a b b c c aa b 0
a b ca 0
I
V
+ I + I )=1
( I3
=1
(V + V + V )
V =1
(V + V + V )
No zero-sequence components exist if the sum of the three
phasors is zero.
The Symmetrical Componentsof Unsymmetrical Phasors 6
3a b ca 0
V =1
(V + V + V )
Va0 = 0
Va0 0
When 3 is balanced
When (Va +Vb +Vc ) 0
* If is unbalanced.Va0 0 then 3
* Unbalanced 3 does not guarantee Va0 0 .
The Symmetrical Componentsof Unsymmetrical Phasors 7
3a b b c c aa b 0V =
1(V + V + V )
(Vab +Vb c +V c a ) is always zero (form closed loop)
Vab 0 is always zero whether the three phase system
is balanced or not.
b
a
c
8
Ia
bI
Ic
bI
Ic
I a
Ib
c
Ia
I nI
1Ia0 = (Ia + Ib + Ic ) = 0
3( ungrounded Y)
1Ia0 = 3
(Ia + Ib + Ic ) 0
(Ia + Ib + Ic ) = 3Ia0 = In
Y with a path to neutral
1Ia0 = 3
(Ia + Ib + Ic ) =0
connected
VECTOR
SOFTWARE
The Symmetrical Componentsof Unsymmetrical Phasors 9example : One conductor of a three-phase line is open. The current flowing to the
-connected load through line a is 10 A. With the current in line a as
reference and assuming that line c is open, find the symmetrical components
of the line currents
Z Z
Z
a
b
c
aI = 1 0 0 0 a m p
b
0180 ampI =10
I c = 0
aI = 1 0 0 0 A
bI = 101800 A
I c = 0 A
The line currents are :
10
3+ 1 0 1 8 0 0 + 0 ) = 0
a 0I =
1( 1 0 0 0
a 1I =
1( 1 0 0 0 + 1 0 1 8 0 0 + 1 2 0 0 + 0 )
3
= 5 − j 2 . 8 9 = 5 . 7 8 − 3 0 0 A
a 2I =
1( 1 0 0 0 + 1 0 1 8 0 0 + 2 4 0 0 + 0 )
3
= 5 + j 2 . 8 9 = 5 . 7 8 3 0 0 A
I b 1 = 5 . 7 8 − 1 5 0 A0
= 5 . 7 8 1 5 0 0 A
= 0
I b 2
I b 0
I c 1 = 5 . 7 8 9 0 A0
= 5 .78 − 90 0 A
= 0
I c 2
I c 0
a 0Since there no neutral current involved , I
should be zero .
Phase Shift of SymmetricalComponents
Y −in or −Y Transformers Banks 1
to neutral leads the voltage drop from X3 to
.
drop from H3
neutral by 300
The American standard for designatingterminal H1 and X1 on Y − or −Y
transformer requires that the positive-sequence voltage drop from H1 to
neutral leads the positive-sequence voltage drop from X1 to neutral by 300 ,
regardless of whether the Y or winding is on the high tension side .
Similarly, the positive-sequence voltage drop from H2 to neutral leads the
voltage drop from X2 to neutral by 300 and the positive-sequence voltage
Phase Shift of SymmetricalComponents
Transformers Banks 2in Y − or −Y
Example :
A
B
C a
b
c
H3
H1 X1
H2 X2
X3
A
B
C
a
b
c
H1
H3
H2
X1
X2
X3
VA1leads Vb1 by 300 leads Va1VA1 by 300
Phase Shift of SymmetricalComponentsin Y − or −Y Transformers Banks 3
,
The American standard for designating terminal H1and X1 on Y − or −Y
transformer requires that the negative-sequence voltage drop from H1 to
neutral lags the negative-sequence voltage drop from X1to neutral by 30
0
regardless of whether the Y or winding is on the high tension side .
Similarly, the negative-sequence voltage drop from H2 to neutral lags
the voltage drop from X2 to neutralby 300 and the negative-sequence
voltage drop from H3 to neutral lags the voltage drop from X3 to neutral
by 300 .
Phase Shift of SymmetricalComponents
Transformers Banks 4in Y− or −Y
A
B
C a
b
c
H3
H1
H2
X1
X2
X3
A
B
C
a
b
c
H1
H3
H2
X1
X2
X3
lags Va2A2(b) V by 300
b2V(a) lags byA2V 030
Example :
Phase Shift of Symmetrical Components in Y
− or −Y Transformers Banks 5
A
B
C a
b
c
H3
H1
H2
X1
X2
X3
2B
A2
C2
2b
c2
a 2
1B
1A
C1
b1
a1
c1
Va1 leads VA1 by 900
A2Va2 lags V by 900
leads Vb1VA1 by 300
b2A2V lags V by 300
Y
Example 11.7. The resistive Y-connected load bank of Example 11.2 is supplied from the low-voltage
Y-side of a Y- transformer. The voltages at the load are the same as in that example. Find the line
voltages and currents in per unit on the high-voltage side of the transformer.
I (1)a = 0.9857 43.60 per unit
I ( 2)a = 0.2346 250.30 per unit
V (1)an = 0.985743.60 per unit(line− to − neutral voltage base)
V (2)an = 0.2346 250.30 per unit(line − to − neutral voltage base)
V (1) A = 0.9857 43.60 + 300 = 0.9857 73.60 = 0.2785 + j0.9456
V (2)A = 0.2346250.30 − 300 = 0.2346220.30 = −0.1789 − j0.1517
VA = V A +V A = 0.0994 + j0.7939 = 0.882.8 per unit(1) (2) 0
V (1)B = a2V (1)
A = 0.9857 − 46.40 = 0.6798 − j0.7138
Phase Shift of Symmetrical Components in Y
− or −Y Transformers Banks 6
V (2)B = a2V ( 2)
A = 0.2346 −19.70 = 0.2209 − j0.0791
VB +V (2)B = 0.9007 − j0.7929 = 1.20 − 41.40 per unit= V (1)
B
V (1)C = a2V (1)
A = 0.9857 193 .60 = −0.9581 − j0.2318
V (2)C = a2V ( 2)
A = 0.2346 100.30 = −0.0419 − j0.2318
VC +V (2)C = −1.0 + j0 = 1.0180 0 per unit= V (1)
C
VAB = VA −V B= 0.0994 + j0.7939 − 0.9007 + j0.7929 = −0.8013 + j1.5868
= 1.78116 .80 per unit(line − neutral voltagae base)
3=
1.78116 .80 per unit(line − to − line voltagae base)
Phase Shift of Symmetrical Components in Y
− or −Y Transformers Banks 7
Phase Shift of SymmetricalComponents
3
VBC = VB −V C= 0.9007 − j0.7939 + 1.0 = 1.9007 − j0.7939
= 2.06 − 22.70 per unit(line − neutral voltagae base)
=2.06
− 22.70 = 1.19 − 22.70 per unit(line − to − line voltagae base)
3
VCA = VC −V A= −1.0 − 0.0994 − j0.7939 = 1.0994 − j0.97939
= 1.356 215 .80 per unit(line − neutral voltagae base)
=1.356
215 .80 = 0.783215 .80 per unit(line − to − line voltagae base)
IA = 0.8082.8 per unit0
IB = 1.20 − 41.4 per unit0
IC = 1.0180 per unit0
in Y− or Transformers Banks 8−Y
A
B
C a
b
c
H3
H1 X1
H2 X2
X3
A
B
C
a
b
cH3
H2
H1 X1
X2
X3
(b) by 300(a) V(1) A leads V(1)
a by 300 V(1) A leads V(1)
a
Figure 11.23
labeling of lines connected to a three-phase Y- transformer.
Phase Shift of Symmetrical Components in Y
− or −Y Transformers Banks 9
Power in terms of Symmetrical Components
S = P + j Q = V I *a + V I *
b + V I *c
a b c
*
0 1 20 1 2
IVa
T
a
= A V T A Ib
*
I
I c
b
Vc
S = V
0 1 20 1 2
*
0 1 20 1 2
T I *= 3 V= V T A T A * I
*
a 1
a 0
a 0 a 1 a 2
I a 2
I
= 3V V V I
a 1a 0 I *a 2 )I *
a 0I *
a 1 + Va 2
+ V= 3 ( V
, A T A *= 3 I
1
a
b
c
a '
b'
c'c
bZ
Z
Za
Ia
IbZcaZac
Zab
I c Z c Z c a
Z a c I a
Z b c I b
Z a b
= Z b a Z b
Z c b
Ic
Z a
Vb b '
V
c c '
V ' a a
2
Ia 2
I a 0
Z c Zca
Z b c A I a 1 V
c c ' 2
V ' Z a a a 0
A Vb b ' 1 = Z b a
−1 I a 0
Z c Ia 2
Z b c A I a 1
Z a c
V
c c ' 2
Vb b '1 = A
V ' aa 0
Z a b Z a c
Z b
Z c b
Z a Z a b
Z b a Z b
Zca Z c b
Z
3
Z 0 1 2
)
s1 M 1
(Z s 0 − 2ZM 0 )− 2ZM 2 )(Zs2
(Z s 2 + 2ZM 2= (Z − 2Z ) (Z − 2Z )
s 0 M 0
(Z s1 + 2ZM 1)
(Z s1 − 2ZM 1) (Z s 2 − 2ZM 2 )
= A − 1 ZA
(Z s 0 + 2ZM 0 )
Where
3
3
3
cbas2
cbas1
cbas0
+ aZ )+ a2 ZZ =1
(Z
+ aZ + a2 Z )Z =1
(Z
+ Z + Z )Z =1
(Z
3
abcabcM 2
abcabcM 1
abcabcM 0Z
Z =1
(Z + a 2Z + aZ ) 3
Z =1
(Z + aZ + a2 Z )
+ Z + Z )=1
(Z3
4
V ' = (Z + 2Z )I + (Z − 2Z )I + (Z − 2Z )Iaa 0 s 0 M 0 a0 s 2 M 2 a1 s1 M 1 a 2
V ' = (Z − 2Z )I + (Z − 2Z )I + (Z + 2Z )Iaa 1 s1 M 1 a0 s0 M 0 a1 s2 M 2 a2
V ' = (Z − 2Z )I + (Z + 2Z )I + (Z − 2Z )Iaa 2 s2 M 2 a0 s1 M 1 a1 s0 M 0 a2
5
= 0Case 1. If no coupling , Z i j ( i j )
V '
a a 0= Z s 0 I a 0 + Z s 2 I a 1 + Z s 1 I a 2
3 3 3a0 a b c a1 a b c
(Z +aZ + a2 Z )a2 a b c
=1
I (Z +Z + Z ) +1
I (Z +a2Z + aZ ) +1
I
V '
a a 2= Z s 2 I a 0 + Z s 1 I a 1 + Z s 0 I a 2
V '
a a 1= Z s 1 I a 0 + Z s 0 I a 1 + Z s 2 I a 2
3
1
3 3
2
a1 a b ca0 a b c(Z + a2 Z + Z )
a2 a b c(Z + Z + Z ) +
1I=
1I (Z + aZ + a Z ) + I
3
1
3
2
a1 a b ca 0 a b c a2 (Za + Zb + Zc )(Z + aZ + a Z ) + I=1
I (Z + a2 Z + aZ ) +1
I3
then = Z M 1 = Z M 2 = 0Z M 0
6
= 0Z i j ( i j )
Z a = Z b = Z c
V ' = I Zaa 1 a1 a
V ' = I Za a 2 a 2 a
V ' = I Za a 0 a 0 a
Symmetrical components of unbalanced currents flowing in a balanced- Y load
or in balanced series impedances produce voltage drops of the same sequence ,
provided no coupling exists between phases.
If the impedances are unequal, the voltage drop of any one sequence is dependent on the
current of all three sequences.
If coupling such as mutual inductance exists among the three impedances, then the
formula will become more complicated.
Case 2 . If 1.
2.
Complete transportation assumed
7
Assume:
1. No coupling
2.
Positive-sequence currents produce positive-sequence voltage drops.
Negative-sequence currents produce negative sequence voltage drops.
zero-sequence currents produce zero-sequence voltage drops.
Z a = Z b = Z c
Sequence Impedance and Sequence Network 1
The impedance of circuit when positive- sequence
current alone are flowing is called positive-sequence
impedance.
The impedance of circuit when negative-sequence
currents alone are flowing is called negative
sequence impedance.
When only zero-sequence currents are present, the
impedance is called zero sequence impedance.
Sequence Impedance and Sequence Network 2
The single-phase equivalent circuit composed of the impedance to
current of any one sequence only is called the sequence network.
Positive-sequence network contains positive sequence current and
positive sequence impedance only.
Negative-sequence network contains negative sequence current
and negative sequence impedance only.
Sequence Impedance and Sequence Network 3
Zero-sequence network contains zero sequence current and
zero sequence impedance only.
Sequence network carrying the individual currents Ia1 , Ia 2
and Ia 0 are interconnected to represent various
unbalanced fault condition.
Sequence Impedance and Sequence Network 4
Sequence Impedance of Various Devices
Positive Negative Zero
Line same same different
Transformer same same same
Machine different * different * different
* Usually they are assumed to be the same
Sequence Networks of Unloaded Generators 1
I a
I c
I n
Ea
b
Ib
c
a
+
-
- - Eb
+ Ec +
nZ
The generator voltage (Ea , Eb , Ec )
are of positive sequence only,
since the generator is designed
to supply balanced three-phase
voltage.
Sequence Networks of Unloaded Generators 2
Ia 2
c2I
b2I
a
cb
2Z
Z 2
Z 2Va 2
a 2Ia
Z 2
+
-
Negative-sequence
network
a1V
a1I
a
E a
Z 1
+
-
Positive-sequence
network
Reference
Reference
Ia1
b1
bE
E
b
Ic
a
+
++Ec
- a
--
1Z
Z1Z1
aI
V a 1 = E a − I a 1 Z 1
a 2 2a 2V = − I Z
Sequence Networks of Unloaded Generators 3
Ic1
Ia 0
Ia 0
Ia 0
a
Z g 0
Z g 0
Z g 0
b
V a 0
ag 0
Z+
-3Z n
Z 0
I a 0
Zero-sequence
network
Reference
Zn only appears in the zero-sequence
network
V a 0Zn
a 0
c
3I
= − I a 0 Z 0
= − I a 0 (Z g 0 + 3Zn )
na03I = I
Sequence Networks of Unloaded Generators 4
Determine the subtransient current in the generator and the line-t0-line voltages for subtransient
conditions due to the fault.
Example 11.6. A salient-pole generator without dampers is rated 20 MVA, 13.8kV and has a
direct=axis subtransient reactance of 0.25 per unit. The negative-and-zero-sequence reactance
are, respectively, 0.35 and 0.10 per unit. The neutral of the generator is solidly grounded. With the
generator operating unloaded at rated voltage with Ean = 1.00 per unit , a singleline-to-0
ground fault occurs at the machine terminals, which then have per-unit voltages to ground,
V a = 0 V = 1 . 0 1 3 − 1 0 2 . 2 5 0 V = 1 . 0 1 3 1 0 2 . 2 5 0
b c
I c = 0
I a
I a = I n
b
I b = 0
c
a
E a n
E b n
++ E c n
+
-
- -
Z n
n
Figure 11.15
Sequence Networks of Unloaded Generators 5
Figure 11.15 shows the line-to-ground fault of phase a of the machine.
Vb = −0.215 − j0.990 per unit
Vc = −0.215 + j0.990 per unit
V
V
c
a
=
b
− 0.143+ j0
a − 0.215 + j0.990 − 0.500 + j01
1
1 1 1 0
3 1
a 2
a a 2 − 0.215 − j0.990 = 0.643+ j0 per unit(0 )
V (0)
(0 )
Z g o j0.1 0
V ( 0 )a( 0 ) = − j1.43per un i t
( − 0 . 1 4 3 + j0)= −I a = −
Sequence Networks of Unloaded Generators 6
EI
j0.25
(1 ) = − j1.43per unit(1.0 + j0) − (0 .643+ j0)− V (1 )
aa = − a n =
Z 1
Ij0.35Z 2
V ( 2 )a( 2 ) = − j1.43per unit
(−0.500 + j0)= −a = −
+ I ( 2 )a = 3I (0 )
a = − j4.29+ I (1)a
Ia = I a(0 )
There, the fault current into the ground is
The base current is 20,000 ( 3 13.8) = 837 A and so the subtransient current in line a is
Ia = − j4.29 837 = − j3,590 A
Sequence Networks of Unloaded Generators 7
Line-to-line voltage during the fault are
ab a bV = V −V = 0.215 + j0.990 = 1.0177.70 per unit
bc b cV = V −V = 0 − j1.980 = 1.980270 0 per unit
ca c aV = V − V = −0.215 + j0.990 = 1.0177.70 per unit
ab3
V = 1.01 13.8
77.70 = 8.0577.70 kV
bc3
V = 1.980 13.8
270 0 = 15.78270 0 kV
ca3
V = 1.01 13.8
102.30 = 8.05102 .30 kV
Sequence Networks of Unloaded Generators 8
Before the fault the line voltages were balanced and equal to 13.8kV. For comparison with the line
voltages after the fault occurs, the prefault voltages, with Van = Ean as reference, are given as
abV =13.8300 kV
bcV = 13.8270 0 kV
caV = 13.81500 kV
Figure 11.6 shows phasor diagrams of prefault and postfault voltages.
Figure 11.6
(a) Prefault
Van
Vca
bcVVbc
VabVab
a an
Vca
bb
c c
(b) Postfault
Sequence Networks of Unloaded Generators 9
The positive-sequence diagram of a generator is
composed of an emf in series with the positive-sequence
impedance of the generator.
The negative and zero-sequence diagrams contain no
emfs but include the negative and zero-sequence
impedances of the generator respectively.
Sequence Networks 1
The matching reactance in positive-sequence network is the subtransient ,transient,
or synchronous reactance, depending of whether subtransient , transient, or
steady- state condition are being studied.
The reference bus for the positive and negative sequence networks is the neutral
of the generator. So for as positive and negative sequence components are
concerned , the neutral of the generator is at ground potential even if these is Zn
connection between neutral and ground.
The reference bus for the zero sequence network is the ground (not necessary
the neutral of the generator).
Sequence Networks 2
Convert a positive sequence network to a negative sequence
network by changing, if necessary, only the impedance
that represent rotating machine , and by omitting the emf.
The normal one-line impedance diagram plus the induced emf is the
positive sequence network.
Three-phase generators and motors have internal voltage of positive
sequence only.
Example of Positive and Negative-Sequence Network 1
Example: Draw the positive and negative-sequence networks
for the system described as below . Assume that the
negative-sequence reactance of each machine is
equal to its subtransient reactance .Omit resistance.
1T
M 1
T pm nk l
rM 2
Example of Positive and Negative-Sequence Network 2
+
--
j 0 .0 8 5 7 j 0 .0 8 1 5
j 0 .0 2
j 0 .2 7 4 5 j 0 . 5 4 9 0
+
E
- m 2
+
E m 1
gE
k l m
j 0 .0 9 1 5
n
p r
j 0 .0 8 5 7 j 0 .0 9 1 5j 0 .0 8 1 5
j 0 .0 2 j 0 .2 7 4 5
Reference bus
k l m
p
n
j 0 .5 4 9 0
q
(Positive)
(Negative)
Zero sequence Network 1
1 . Zero-sequence network currents will flow only if a return path exists.
2 . The reference bus of the zero-sequence network is the ground.
ZZ
Z
N
Z
Z
Z
N
Z N
R
N
Reference
Zero sequence Network 2
Z
Z
Z
NZ
R
Nn
In = 3Ia 0
3Zn
NIa 0
Z Z
Z
R
Z
Zero sequence Network 3
Zero-sequence equivalent circuit of three phase transform banks.
Symbols Connection DiagramsZero-Sequence
Equivalent Circuit
p Q
pQ p Q
Z0
Reference bus
p p Q pQ
Z0
Reference bus
Zero sequence Network 4
Symbols Connection DiagramsZero-Sequence
Equivalent Circuit
p
pQ
p Z0
Reference bus
Q
p
p Q
p Z0
Reference bus
Q
Zero sequence Network 5
Symbols Connection DiagramsZero-Sequence
Equivalent Circuit
p
p
pQ Q
Z0
Reference bus
Zero sequence Network 6
3 Z n
g 0Z
Q
R
S
T
M N
P
(Zero-Sequence)
Example:
Z n
Q S
P
R T
M N
Zero sequence Network 7
g 1Z
Q S
R T
MNP
E g 1
++
Z g 2
- E g 1-
Q
R TM
N
P
S
(Positive-Sequence)
(Negative-Sequence)
SEQUENCE
NETWORK
SOFTWARE
Zero sequence Network 8
Example 11.9. Draw the zero-sequence network for the system described in Example 6.1. Assume
zero-sequence network for the generator and motors of 0.05 per unit. A current-limiting reactor of
is in each of the each of the neutrals of the generator and the large motor. The zero-sequence0.4
reactance of the transmission line is 1.5 km
Generator:
Motor 1:
Motor 2:
X 0 = 0.05 per uni t
1 3.2
2 0 0 1 3.8
2
0 ) = 0 .0686 per uni tX = 0.05(3 0 0
) (
1 3.2
1 0 0 1 3.8
2
0 ) = 0 .1 3 7 2 p er uni tX = 0.05(3 0 0
) (
= 1.333300
(20) 2
Base Z =
= 0.635300
(13.8)2
Base Z =
Zero sequence Network 9
n1.333
3Z = 3(0.4
) = 0.900per unit
n0.635
0.4) = 1.890per unit3Z = 3(
176.30
Z =1.5 64
= 0.5445per unit
The zero-sequence network is shown in Fig. 11.28
j0.05
j0.900
j0.0857 j0.5445 j0.0915
l m
kn
p r
j0.0686
j1.890
j0.1372
reference
Thank You