THERMAL ANALYSIS OF

SHELL AND TUBE HEAT EXCHANGER

Prepared By: Guided By:Khalasi Bharat K. Dr. Prabhakaran Sir

Page 2: New shell & tube heat exchanger

Contents:

HEAT EXCHANGER Types Of Heat Exchangers Shell-and-Tube Heat Exchangers Thermal Analysis Example References

Page 3: New shell & tube heat exchanger

HEAT EXCHANGER:

A heat exchanger is a device that is used to transfer thermal energy between

two or more fluids, a solid surface and a fluid, solid particulates and a fluid

Typical applications involve heating or cooling of a fluid stream of concern and evaporation or condensation of single- or multicomponent fluid streams.

Page 4: New shell & tube heat exchanger

Types Of Heat Exchangers

Double-pipe heat exchanger Shell and tube heat exchanger Plate and frame heat exchanger Spiral heat exchanger Pipe coil exchanger Air-cooled heat exchangers

Page 5: New shell & tube heat exchanger

Heat Exchanger Types

• Concentric-Tube Heat Exchangers

Parallel Flow Counterflow

Page 6: New shell & tube heat exchanger

• Cross-flow Heat Exchangers

Finned-Both FluidsUnmixed

Unfinned-One Fluid Mixedthe Other Unmixed

Page 7: New shell & tube heat exchanger

Compact Heat Exchangers

• Achieve large heat rates per unit volume• Large heat transfer surface areas per unit volume, small

flow passages, and laminar flow.

Page 8: New shell & tube heat exchanger

Shell and Tube Heat Exchangers

• The shell and tube heat exchanger is the most common style found in industry.

• As the tube-side flow enters the exchanger, flow is directed into tubes that run parallel to each other. these tubes run through a shell that has a fluid passing through it.

• Heat energy is transferred through the tube wall into the cooler fluid.

• Heat transfer occurs primarily through conduction and convection.

Page 9: New shell & tube heat exchanger

Shell-and-Tube Heat Exchangers:

Baffles are used to establish a cross-flow and to induce turbulent mixing of the shell-side fluid.

One Shell Pass and One Tube Pass

One Shell Pass,Two Tube Passes

Two Shell Passes,Four Tube Passes

Page 10: New shell & tube heat exchanger

1.Connections2.Tube Sheets3.Gaskets4.Head5.Mounting6.Baffles7. Shell8.Tube bundle

Main Parts:

Page 11: New shell & tube heat exchanger

The Thermal Analysis:The fundamental equations for heat transfer across a surface are given by:

Q = U A ΔTlm

= w Cp(t) (t2 − t1)= W Cp(s) (T1 − T2) or W L

Where Q = heat transferred per unit time (kJ/h, Btu/h)U = the overall heat transfer coefficient (kJ/h-m2 oC, Btu/hft2-

ºF)A = heat-transfer area (m2, ft2)Δtlm = log mean temperature difference (oC, ºF)Cp(t) = liquid specific heat tube side, Cp(s) = liquid specific heat shell side (kJ/kg-ºK, Btu/lb-ºF)w = tube side flow

W = shell side flow (kg/h, lb/h)The log mean temperature difference ΔTlm (LMTD) for counter current flow is given by:

Page 12: New shell & tube heat exchanger

• A correction factor is applied to the LMTD to allow for the departure from true counter current flow to determine the true temperature difference.

ΔTm = Ft ΔTlm

• The correction factor is a function of the fluid temperatures and the number of tube and shell passes and

• Correlated as a function of two dimensionless temperature ratios

Page 13: New shell & tube heat exchanger

• The correction factor Ft for a 1-2 heat exchanger which has 1 shell pass and 2 or more even number of tube passes is given by:

• The overall heat transfer coefficient U is the sum of several individual resistances as follows:

• The combined fouling coefficient hf can be defined as follows:

Page 14: New shell & tube heat exchanger

Area of Flow:

• Shell side cross flow area aS is given by

• Maximum spacing is given by:

Spacing Required:

• Spacing does not normally exceed the shell diameter

Page 15: New shell & tube heat exchanger

Shell side Film Coefficient Methods for Single Component Condensation in Laminar Flow:

• Horizontal condenser sub coolers are less adaptable to rigorous calculation

• But give considerably higher overall clean coefficients than vertical condenser sub coolers which have the advantage of well defined zones.The Nusselt Method:

• The mean heat transfer coefficient for horizontal condensation outside a single tube is given by the relationship developed by Nusselt.

• This correlation takes no account of the influence of vapour flow which, in addition to the effect of vapour shear, acts to redistribute the condensate liquid within a tube bundle.

Page 16: New shell & tube heat exchanger

The Kern Method:

• Kern adapted the Nusselt equation to allow evaluation of fluid conditions at the film temperature

• For horizontal tube surfaces from 0° to 180° the above equation can be further developed to give

Page 17: New shell & tube heat exchanger

• McAdam extended the Kern equation to allow for condensate film and splashing affects.

• The loading per tube is taken to be inversely proportional to the number tubes to the power of 0.667.

• This equation requires the film to be in streamline flow

• Reynolds Numbers in range 1800 to 2100

Page 18: New shell & tube heat exchanger

Example:Problem : Design of a two-pass, shell-and-tube heat exchanger

to supply vapour for the turbine of an ocean thermal energy conversion system based on a standard (Rankine) power cycle. The power cycle is to generate 2 MW at an efficiency of 3%. Ocean water enters the tubes of the exchanger at 300K, and its desired outlet temperature is 292K. The working fluid of the power cycle is evaporated in the tubes of the exchanger at its phase change temperature of 290K, and the overall heat transfer coefficient is known.

FIND: (a) Evaporator area, (b) Water flow rate.

SCHEMATIC:

Page 19: New shell & tube heat exchanger

ASSUMPTIONS: (1) Negligible heat loss to surroundings, (2) Negligible kinetic and potential energy changes, (3) Constant properties.

PROPERTIES: Water ( mT = 296 K): cp = 4181 J/kgK.

ANALYSIS: (a) The efficiency is

W 2MW

0.03.q q

Hence the required heat transfer rate is

2MW

q 66.7 MW.0.03

Also

m,CF300 290 292 290 C

T 5 C300 290

n292 290

and, with P = 0 and S = , from Fig. it follows that F = 1. Hence

Page 20: New shell & tube heat exchanger

b) The water flow rate through the evaporator is

7

hp,h h,i h,o

q 6.67 10 Wm

4181 J / kg K 300 292c T T

hm 1994 kg / s.

COMMENTS: (1) The required heat exchanger size is enormous due to the small temperature differences involved,

(2) The concept was considered during the energy crisis of the mid 1970s but has not since been implemented.

7

2m,CF

q 6.67 10 WA

U F T 1200 W / m K 1 5 C

2A 11,100m .

Page 21: New shell & tube heat exchanger

REFERANCES:

1. Design And Rating Shell And Tube Heat Exchangers , By John E. Edwards

2. Engineering Data Book, By Professor John R. Thome

3. www.pidesign.co.uk4. en.wikipedia.org