DESCRIPTION
1TRANSCRIPT
FCU & AHU
Creates A Better Life
23/4/28
Fan coil unit
How to Read the Model Name?
T1 127V 60 Hz Duct Type
F1 Exposed Floor-stand Type (side air intake)
Nominal Air Volume(CFM)
Chilled Water Fan coil unit
C One Way Cassette T DuctA 4 Way Cassette B 4 Way Cassette (Compact)
T2 2nd Generation Duct Type
Type Code
F2 Exposed Flood-stand Type (below air intake)F3 Concealed Flood-stand Type
-- Normal Static Pressure H High Static Pressure
E with Electrical HeaterR Remote Control RA Remote Control with Electrical HeaterFunction Code
T3 New High-static Pressure Type
G Wall-mounted TypeH1 Exposed Ceiling and Floor Type (side air intake)
H2 Exposed Ceiling and Floor Type (back air intake)H3 Concealed Ceiling and Floor Typy
Fan Coil
Ceiling and
Floor
Duct Wall mounted
Floor Standing
Cassette
1-Way4-Way
Compact
4-Way 4 pipes
Cassette
MKCMKBMKA MKD
1.1. Cooling capacity: 5.7~10.4kW;Cooling capacity: 5.7~10.4kW;
2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);
3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);
4.4. Maximum water inlet temp. is 70 ;℃Maximum water inlet temp. is 70 ;℃
Four-way Cassette
Model List:Model List:
*EAH: Electric Auxiliary Heater
Without EAH With EAHMKA-600R MKA-600RA 2100wMKA-750R MKA-750RA 2100wMKA-850R MKA-850RA 2700wMKA-950R MKA-950RA 2700wMKA-1200R MKA-1200RA 2700w
Four-way cassette
Variable color for the panel:
5.5. LED display in the panel;LED display in the panel;6.6. Different color for the panel;Different color for the panel;7.7. Fresh air function;Fresh air function;8.8. Reserve spaces for air side-outletReserve spaces for air side-outlet
3 Pre-cut holeSend air to the nearby room
BlueWhite Grey Black
New design
1.1. Cooling capacity: 3.0~5.5kW;Cooling capacity: 3.0~5.5kW;
2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);
3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);
4.4. Maximum water inlet temp. is 70℃Maximum water inlet temp. is 70℃5.5. Dimension: 580×254×580Dimension: 580×254×580
Four-way Cassette(60*60)
Model List:Model List:Without EAH* With EAH
MKB-300R MKB-300RA 1000wMKB-400R MKB-400RA 1000wMKB-450R / /MKB-500R / /
*EAH: Electric Auxiliary Heater
Compact
1.1. Cooling capacity: 3040w, 3790w;Cooling capacity: 3040w, 3790w;
2.2. Electric auxiliary heater is optional (Assembled in factory);Electric auxiliary heater is optional (Assembled in factory);
3.3. Build in water pump & water level switch (Standard);Build in water pump & water level switch (Standard);
One-way Cassette
Model List:Model List:
Without EAH With EAHMKC-300R MKC-300RA 1000wMKC-400R MKC-400RA 1000w
*EAH: Electric Auxiliary Heater
4-way pipe
Heat water pipe
Chill water pipe
Models MKD-600F
MKD-750F
MKD-850F
MKD-950F
MKD-1200F
MKD-1500F
Cooling capacity(Btu/h) 17406 20239 21058 22867 31672 36109
Heating capacity(Btu/h)
22765 26860 27509 29590 39761 43072
1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.
2.2. Save a lot of energies in winter.Save a lot of energies in winter.
3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.
4-way pipe
Heat water pipe
Chill water pipe
Models MKD-300
MKD-400
MKD-500
Cooling capacity(Btu/h) 10236 12624 15354
Heating capacity(Btu/h)
13648 17401 20472
1.1. 2 recycle system,2 pipes per system.2 recycle system,2 pipes per system.
2.2. Save a lot of energies in winter.Save a lot of energies in winter.
3.3. Other function is same as 2 pipe Other function is same as 2 pipe cassette.cassette.
Accessories for cassette
EAH Filter Additional drain pan
3-way valve
Connection kit
Controller
MKA C S O O O SMKB C S O O O SMKC C S O O O SMKD C S O O O SC: the accessories is optional, but it should be assembled in the factory;
S: the accessories is standard;
O: the accessories is optional, it can installed by the installer.
Accessories table:
Block for air outlet hole:
Accessories for cassette
Note: the block is only for four-way cassette(80*80 type).
(Optional)
Accessories for cassette
Additional drain pan (optional):
For 4-way cassette compact For 4-way cassette
Accessories for cassette
3-way valve Connection Kit
Electronic coil
Valve
(Optional) (Optional)
Wireless controller
Wired controller
Central controller
Controllers for cassette
Standard Optional Optional
Note: NIM is necessary if use central controller to control the cassette.
2 Rows
3 Rows
4 Rows
Duct
HSP
MKT2 MKT3 MKT4 MKT5 MKT3H
4 Pipe
Duct (2-Rows without EAH)
1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are optional (Assembled in factory);Air return plenums (including filter) are optional (Assembled in factory);3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
12Pa 30(50)PaMKT2-200 MKT2H-200MKT2-300 MKT2H-300MKT2-400 MKT2H-400MKT2-500 MKT2H-500MKT2-600 MKT2H-600MKT2-800 MKT2H-800
MKT2-1000 MKT2H-1000MKT2-1200 MKT2H-1200MKT2-1400 MKT2H-1400
Model List:Model List:
MKT2, MKT2HMKT2, MKT2H
Duct (2-Rows with EAH)
MKT2-xxxE, MKT2H-xxxEMKT2-xxxE, MKT2H-xxxE
Model List:Model List:
12Pa 30(50)Pa EAHMKT2-200E MKT2H-200E 500wMKT2-300E MKT2H-300E 650wMKT2-400E MKT2H-400E 1000wMKT2-500E MKT2H-500E 1000wMKT2-600E MKT2H-600E 1500wMKT2-800E MKT2H-800E 2000w
MKT2-1000E MKT2H-1000E 2000wMKT2-1200E MKT2H-1200E 3000wMKT2-1400E MKT2H-1400E 3000w
1.1. Cooling capacity: 2~13Kw;Cooling capacity: 2~13Kw;2.2. Air return plenums (including filter) are standard;Air return plenums (including filter) are standard;3.3. For For MKT2H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
1.1. Cooling capacity:Cooling capacity: 2.2~12.1kW;2.2~12.1kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. For For MKT3H, 50Pa static pressure can be customized (in factory); 50Pa static pressure can be customized (in factory);4.4. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Duct (3-Rows without EAH)
12Pa 30(50)PaMKT3-200 MKT3H-200MKT3-300 MKT3H-300MKT3-400 MKT3H-400MKT3-500 MKT3H-500MKT3-600 MKT3H-600MKT3-800 MKT3H-800
MKT3-1000 MKT3H-1000 MKT3-1200 MKT3H-1200
Model List:Model List:
1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Duct (4-Rows without EAH)
30PaMKT4H-200MKT4H-300MKT4H-400MKT4H-500MKT4H-600MKT4H-800
MKT4H-1000MKT4H-1200MKT4H-1500MKT4H-2000
Model List:Model List:
1.1. Air volume: 2.2-17.9 kWAir volume: 2.2-17.9 kW2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Duct (4-Rows with EAH)
30PaMKT4H-200EMKT4H-300EMKT4H-400EMKT4H-500EMKT4H-600EMKT4H-800E
MKT4H-1000EMKT4H-1200EMKT4H-1500EMKT4H-2000E
Model List:Model List:
High Static Pressure Duct (without EAH)
1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
Static PressureMKT3H-800 70Pa
MKT3H-1000 70PaMKT3H-1200 70PaMKT3H-1400 70PaMKT3H-1600 100PaMKT3H-2000 100PaMKT3H-2200 100Pa
Model List:Model List:MKT3H SeriesMKT3H Series
With EAH EAH Static Pressure
MKT3H-800E 3Kw 70PaMKT3H-1000E 3Kw 70PaMKT3H-1200E 3Kw 70PaMKT3H-1400E 3Kw 70PaMKT3H-1600E 10Kw 100PaMKT3H-2000E 10Kw 100PaMKT3H-2200E 10Kw 100Pa
High Static Pressure Duct (with EAH)
Model List:Model List:MKT3H-xxxE SeriesMKT3H-xxxE Series
1.1. Cooling capacity: 8.8~19.9kW;Cooling capacity: 8.8~19.9kW;2.2. Air return plenums and air filter are standard;Air return plenums and air filter are standard;3.3. Pipe connection from left or right can be selected (in factory);Pipe connection from left or right can be selected (in factory);
4 Pipe ducted type
1 fan 2 fans 4 fans
Models MkT5-200
MkT5-300
MKT5-400
MKT5-500
MKT5-600
MkT5-800
MkT5-1000
MkT5-1200
Cooling capacity(Btu/h) 6826 9215 12287 14676 17065 23208 26621 34812
Heating capacity(Btu/h)
10239 13652 17747 19454 24573 32765 36860 46075
1.For ESP,12Pa and 30Pa are optional.1.For ESP,12Pa and 30Pa are optional.2.The functions are same as 2 pipe ducted type.2.The functions are same as 2 pipe ducted type.
Accessories for duct
EAH Air return plenum &Filter
Additional drain pan
3-way valve
Connection kit
Controller
MKT2No C S O O OYes S S O O O
MKT3 No C S O O O
MKT4No C S O O OYes S S O O O
MKT3HNo C S O O OYes S S O O O
MKT5 No C S O O OC: the accessories are optional, but it should be assembled in the factory;
S: the accessories are standard;
O: the accessories are optional, it can be installed by the installer.
Accessories table:
Air return plenums and electrical heaters:
Accessories for duct
The EAH must be installed in the factory;The air return plenums must be installed in the factory;The duct with EAH must select air return plenums, because the EAH is installed inside the air return plenums;
3-way valve
Electronic coil
Valve
Accessories for duct
(Optional)Connection Kit
(Optional)
Thermostat.
For the units without EAH
For the units with EAH
Controllers for Duct
OptionalOptional
MKF1 MKF2 MKF3 MKF5
Floor Standing
MKF4
ExposedFlat panel
Side intake
ExposedCurving panel
Bottom intake
ExposedFlat panel
Bottom intake
ConcealedExposedCurving panel
Side intake
Floor-standing
Exposed typeExposed type Exposed MKF1-150 MKF2-150MKF1-250 MKF2-250MKF1-300 MKF2-300MKF1-400 MKF2-400MKF1-450 MKF2-450MKF1-500 MKF2-500MKF1-600 MKF2-600MKF1-800 MKF2-800MKF1-900 MKF2-900
Model List:Model List:
MKF1: air return from front side
MKF2: air return from bottom ( standard with foot)
1. Vertical installation on the floor- much more comfortable in heating mode;
2. 3-way valve can be built in the cabinet;
3. Pipe connection can be left or right (installer change it).
Flat type air outlet grill
Exposed type New air outlet grill
Floor-standing
ExposedMKF4-150 MKF5-150MKF4-250 MKF5-250MKF4-300 MKF5-300MKF4-400 MKF5-400MKF4-450 MKF5-450MKF4-500 MKF5-500MKF4-600 MKF5-600MKF4-800 MKF5-800MKF4-900 MKF5-900MKF4: air return from front side
MKF5: air return from bottom ( standard with foot)
Model List:
The grill is modular design- easily removed and cleaned
Floor-standing
Concealed typeConcealed typeModel List:Model List:
ConcealedMKF3-150MKF3-250MKF3-300MKF3-400MKF3-450MKF3-500MKF3-600MKF3-800MKF3-900
1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;
Accessories for Floor standing
C: the accessories is optional, but it should be assembled in the factory;
S: the accessories is standard;
O: the accessories is optional, it can installed by the installer.
Accessories table:
Filter Additional drain pan
3-way valve
Connection kit
Controller
Exposed S S O O OConcealed / S O O O
Accessories for Floor standing
3-way valve, connection kit and additional drain pan
3-way valve-Optional
Connection kit-Optional
Thermostat (optional):
Controllers for Floor-standing
KJR-15B/E Simple controller
KJR-15B/E(P) With anti cold air function
The controller can be hided in the cabinet (only for MKF1,2,4,5)
Optional
Optional
MKH2 MKH3
Ceiling and Floor
ExposedCurving panel
Back intake
ConcealedExposedCurving panel
Side intake
MKH1
Ceiling-Floor
Exposed typeExposed type Model List:Model List:
air return from front side
1. Vertical installation on the floor- much more comfortable in heating mode;
2. 3-way valve can be built in the cabinet;
3. Pipe connection can be left or right (installer change it);
4. Ceiling and Vertical installation for optional will be more convenience.
ExposedMKH1-150MKH1-250MKH1-300MKH1-400MKH1-450MKH1-500MKH1-600MKH1-800MKH1-900
Ceiling-Floor
Exposed typeExposed type Model List:Model List:
air return from bottom
1. Vertical installation on the floor- much more comfortable in heating mode;
2. 3-way valve can be built in the cabinet;
3. Pipe connection can be left or right (installer change it);4. Ceiling and Vertical installation for optional will be more convenience.
ExposedMKH2-150MKH2-250MKH2-300MKH2-400MKH2-450MKH2-500MKH2-600MKH2-800MKH2-900
Concealed typeConcealed type Model List:Model List: ConcealedMKH3-150MKH3-250MKH3-300MKH3-400MKH3-450MKH3-500MKH3-600MKH3-800MKH3-900
1.1. Concealed installation- harmonic with the room Concealed installation- harmonic with the room ;;
Ceiling-Floor
Accessories for Ceiling and Floor
C: the accessories is optional, but it should be assembled in the factory;
S: the accessories is standard;
O: the accessories is optional, it can installed by the installer.
Accessories table:
Filter Additional drain pan
3-way valve
Connection kit
Controller
Exposed S S O O OConcealed / S O O O
3-way valve, connection kit and additional drain pan
3-way valve-Optional
Connection kit-Optional
Accessories for Ceiling and Floor
Wall Mounted
MKG-250MKG-300MKG-400MKG-500MKG-600
Model List:Model List:
1.1. Capacity: 2.24~4.5kW;Capacity: 2.24~4.5kW;
2.2. 3-way valve is inside the indoor unit;3-way valve is inside the indoor unit;
3.3. ON/OFF terminal for simple remote control ;ON/OFF terminal for simple remote control ;
4.4. Variable color for the panel;Variable color for the panel;
5.5. Multi direction of pipe connection.Multi direction of pipe connection.
MKG SeriesMKG Series
3-way valve Controller Filter
MKG S S See in next page
S: the accessories are standard;
Accessories for Wall mounted
Accessories table:
Bio filter Silver lon filterGTP filter Deodorization filterAnti- formaldehyde filter Silver lon filterHEAP filter Three-tier healthy filterHEPA air fresh filter Anti-acarus filtervitamin filter Active carbon filterNano photocatalyst filter Bio filterCompound air fresh filter
Accessories for Wall mounted
Filter list:
Wireless Wired controller Central controller
Controllers for wall mounted
Standard Optional Optional
Remark: It doesn’t need NIM when choose CCM.
Air Handle Unit
Dual Skinned Horizontal Type
Dual Skinned Vertical Type
Dual Skinned Ceiling Suspended Type
Standard AHU
Dual Skinned (56 Models)
Horizontal Vertical Ceiling Suspended
Models List
◆ Horizontal Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020W ~ MKW2-600W
◆ Vertical Type Air Volume: 2,000 ~ 60,000m3/h Model: MKW2-020L ~ MKW2-600L
◆ Ceiling Suspended Type Air Volume: 2,000 ~ 15,000m3/h Model: MKS020D1 ~ MKS150D1
Specification
Air Out Type
1 2
Ceiling suspended
V e r t ic a l
1 2
H o r iz o n t a l
3 4
http://www.mideacac.com
http://www.mideaaircon.com