navien manual

28
Installation Manual and Owners Guide Model KD-HBO100 & KD-HBC100 * KD-HB100 (Open-Loop System) * KD-HBC100 (Close-Loop System) Automatic Hot Water Management System A Combination System for Domestic Water and Space Heating KyungDong America, Inc. 800 519-8794 www.HeatingBox.com THE HEATING BOX™

Upload: marathon8ca

Post on 04-Mar-2015

1.092 views

Category:

Documents


21 download

TRANSCRIPT

Page 1: Navien Manual

Installation Manual and Owner’s Guide

Model KD-HBO100 & KD-HBC100

* KD-HB100 (Open-Loop System) * KD-HBC100 (Close-Loop System)

Automatic Hot Water Management System A Combination System for Domestic Water and Space Heating

KyungDong America, Inc.

800 519-8794 www.HeatingBox.com

THE HEATING BOX™

Page 2: Navien Manual

2

Table Contents

SAFETY INSTRUCTIONS ........................................................................... 3 INTRODUCTION ...................................................................................... 4

INSPECT SHIPMENT......................................................................... 4 SPECIFICATIONS ...................................................................................... 5 INSTALLATION ......................................................................................... 6

INSTALLATION LOCATION .............................................................. 6 INSTALLING THE HEATING BOX....................................................... 7 PIPING CONNECTIONS .................................................................... 7 WATER FILLING AND PURGING SYSTEM ......................................... 10 CLEARANCE REQUIREMENTS ......................................................... 10 THE HEATING BOX AS A PRIMARY LOOP........................................ 11

APPLICATIONS ....................................................................................... 11 DOMESTIC HOT WATER SUPPLY .................................................... 11 IN-FLOOR RADIANT FLOOR HEATING SYSTEM............................... 12 FAN-ASSISTED HYDRO HEATING SYSTEM...................................... 13 SNOW MELTING SYSTEM ............................................................... 14 SPA WATER HEATING SYSTEM ....................................................... 15

WIRING .................................................................................................. 15 IN-FLOOR RADIANT FLOOR/BASEBOARD HEATING SYSTEM ......... 16 FAN-ASSISTED HYDRO HEAITNG SYSTEM...................................... 16

OPERATION............................................................................................ 17 IMPORTANT SET-UP INSTRUCTIONS ............................................. 17 DOMESTIC HOT WATER SUPPLY ................................................... 18 SPACE HEATING ........................................................................... 19 FREEZING PROTECTION ................................................................ 20 PUMP EXERCISE............................................................................. 20

LADDER DIAGRAM.................................................................................. 20 DESIGN REFERENCE FOR HEAT LOSS CALCULATION ...................... 21

TROUBLESHOOTING GUIDE..................................................................... 23 PARTS LISTS ........................................................................................... 24

MODEL KD-HBO100 OPEN LOOP SYSTEM PARTS DIAGRAMS ......... 24 MODEL KD-HBO100 OPEN LOOP SYSTEM PARTS LIST ................... 25 MODEL KD-HBC100 CLOSE LOOP SYSTEM PARTS DIAGRAMS ........ 26 MODEL KD-HBC100 CLOSE LOOP SYSTEM PARTS LIST .................. 27

LIMITED WARRANTY............................................................................... 28

KyungDong America, Inc. reserves the right to change specifications and/or designs without prior notice in anytime and without incurring obligations.

Page 3: Navien Manual

3

This is the safety alert symbol. Recognize this symbol as an indication of Important Safety Information! This symbol alerts you to potential hazards that can kill or hurt you and others.

• Please check specifications of the Heating Box™ to make sure it is right for your application.

• Please keep this manual in safe place for future reference. • The Heating Box™ must be installed and serviced by a licensed contractors or/and a

professional service technician following national building code, national electric code and all applicable local codes. Improper installation and/or operation and/or installed by unqualified person, the warranty will be voided by the manufacturer. Please refer to the warranty section on page 26.

• Please follow each manufacturer’s installation instructions for different appliances for your other applications used conjunction with our product such as space heating systems and water heating systems.

• Be sure your appliance is properly installed in accordance with local codes and the provided installation instructions.

• Do not touch the system with wet hands. • Do not pour water directly to the system for any purpose. Electric shock may occur

and serious body and/or property damages can result. • Water temperatures above 125 °F (50 °C) can cause severe burns or death from

scalding. • Do not store or use gasoline or other flammable vapors or liquids or other

combustible materials in the vicinity of this or any other appliances. To do so may result in an explosion or fire.

Safety Instructions – Important Information Please read prior to installation

Page 4: Navien Manual

4

Introduction

Thank you for purchasing the Heating Box™ Model KD-HBO100/KD-HBC100. This Heating Box™ provides a combination system ( heat potable water and space ) with just one heat source in convenience of simple installation. The unit consist with a high head bronze constructed pump to circulate water and built-in priority device for more effective distribution in domestic hot water.

The Heating Box™ can be used with conventional tank type water heaters, on-demand tankless water heaters or any hot water heating systems as a heat source. The Heating Box™ can be associated with applications like in-floor space heating system (radiant heating system) and fan assisted hydronic space heating system without interrupting domestic hot water supply and that means no more temperature fluctuations.

Please read the installation manual completely before attempting installation. Understand how the system operates and installation recommendations before beginning installation. Most of the questions that you will have will be answered in the manual. If you have any questions, please review the installation manual or contact manufacturer directly at 800-519-8794.

Please make sure to fill out your product warranty card and return the original form to KyungDong America, Inc. within 30 days of purchase.

Important to Owner: These instructions should be carefully read and kept near product, for future reference. While these instructions are addressed primarily to the installer, useful maintenance information is included. As expressed in product warranty, KyungDong America, Inc. will not be billed for any structural damage due to failure to follow these installation requirements.

Inspect Shipment

Description Picture Quantity

Manual

1

Bracket 1

Introduction

Page 5: Navien Manual

5

Air Separator

Thermostatic Mixing valve for Heating

Heating Box Controller 3-Way Valve

Expansion Tank Circulating Pump

Priority switch with check valve

Manual ball valve for expansion tank Thermostatic Mixing valve for Domestic Hot Water

Model KD-HBO100

Space heating side Air Separator Pressure Gage

Heat source side Air Separator Heating Box Controller Thermostatic Mixing valve for space heating Expansion Tank Flat Heat Exchanger(two)

Check valve Space heating side Circulating Pump

Heat source side Circulating Pump

Thermostatic Mixing valve for Domestic Hot Water

Domestic Hot Water Priority switch

Model KD-HBC100

Specifications

Page 6: Navien Manual

6

Model KD-HBO100

Open system

Model KD-HBC100

Close system

Minimum Flow Rate

(activate priority device) 0.5 GPM 0.5 GPM

Minimum Water Pressure 7 PSI 7 PSI

Hot and Cold Water Connections 3/4" NPT 3/4" NPT

Heat Source Supply & Return 3/4" NPT 3/4" NPT

Space Heating Supply & Return 3/4" NPT 1” NPT

Flat Heat Exchanger

(BTU/Hour) each Not Applicable

80,000 Btu/Hour Each,

Total 160,000 BTU/Hour

Expansion Tank 1.8 Gallons 1.8 Gallons

Electricity 120VAC, 60 Hz, Max. 5A,

Normal 2A

120 VAC,60 Hz, Max 10A,

Normal 4A

Physical Size (W x H x D) 15” x 25” x 10” 20” x 28” x 10”

The Heating Box™ Model KD-HBO100 is an open-loop system. If your application requires a close-loop system, you can add an extra heat exchanger in between systems to separate potable and space heating water; otherwise you can use the close-loop system, the Heating Box™ Model KD-HBC100.

WARNING The hot water coil or all radiant water lines must be purged of air before the hot water pump can be energized. Failure to purge the water system of air can result in damage to the pump.

• Locate the unit near the heat source and the space heating appliance such as in-floor radiant heating manifolds or a hydro space heating air handler.

• Extra care should be taken to avoid placing the product near noise sensitive location such as living areas.

• For ease of installation, top of the system should be installed at eye level and/or bottom of the system should be no less than 3 feet off from the floor.

• Allow 6” off set above the heat source for air to escape from the system.

Installation

Installation Location

Page 7: Navien Manual

7

1. To mount on the fire rated wall, locate wood or metal studs to properly hold the weight of the unit.

2. Drill a single screw hole for at least 2”; it should be for 16” OC. Insert and tighten the screw and hang the unit by the upper wall mounting bracket.

3. Determine the positions for remaining four screws (two for the top bracket and two for the bottom), and remove the unit to drill holes.

4. Hang the unit again by the first screw, and then insert and tighten the remaining four screws.

5. Make sure the unit is installed securely so that it will not fall or move due to vibration or earthquakes.

• Verify that matched pairs of supply and return pipes are connected to the appropriate outlets and inlet to the Heating Box™.

• From the Heating Box™, the piping labeled “To Water Heater Inlet” needs to be connected to the Cold Water Connection of the heat source and the piping labeled “To Water Heater Outlet” needs to be connected to the Hot Water Connection of the heat source.

• Connect the City Water Supply Line to the piping labeled “To City Water” and Domestic Hot Water Supply Line to “Hot Water Supply”.

• From the space heating appliance, connect its Inlet to the Heating Box’s piping labeled “To Space heat supply (IN)” and connect its Return Line to the piping labeled “To Space heat Return (OUT)”.

• Refer below figure for the Radiant Heating Manifold. • Provides filling ports/valves for water or/and Glycol mix working fluid and easy

accessible location for closed loop model KD-HBC100. • We suggest that you use pipe unions for all connections to the Heating Box™ for easy

maintenance (use pipe isolators such as Webstone or equivalent product). You can flush the entire system from the Heating Box™ to the water heater and your radiant or hydronic heat application.

Installing the Heating Box™

Piping Connections

Page 8: Navien Manual

8

Model KD-HBO100

To Space heat supply (IN)

To water heater Inlet

Hot water supply

120 VAC

To Space heat Return (OUT)

To City water

To water heater Outlet

Page 9: Navien Manual

9

Model KD-HBC100

To Space heat supply (IN)

Hot water supplyTo water heater Inlet

To water heater Outlet

To Space heat Return (OUT) To City water

120 VAC

Page 10: Navien Manual

10

• Make sure all electrical power is turned off before filling water to the system. • Close all domestic hot water faucets. • Open main cold water supply valve and purge valve slowly. If water leaks from the

purging valve, close the valve immediately. • Before connecting the electrical wires, strongly recommend to do water leaking test

with/without a pressurizing pipe system. When the system tests with pressurized air, the test pressure should not exceed 50 PSI. Before testing, check the pressure relief valve and see if it is in the test pressure range. The shut off valve to the expansion tank must be closed to prevent damages to it. After the test, open the shut off valve to the expansion tank.

• Turn on the power to both the unit and the thermostat for heating. • The Heating Box™ will start circulate water. Please check the purging valve to see

whether there is any air left in the system. • Above steps should be repeated until there is no air left inside the piping system.

WARNING The expansion tank comes pre-pressurized at 50 PSI (4 Kgf/Cm2). If necessary, adjust the pressure in the expansion tank to the anticipated system operating pressure.

* Maintain clearances in accordance with local installation codes and other appliances.

Piping Side 12”

Front (Maintenance Space) 24”

Back 1” (Bracket included)

Non Piping Side 1”

Water Filling and Purging System

Clearance Requirements

Page 11: Navien Manual

11

If separate secondary circulator has to be used in the system, the secondary circulator can be connected to the External Pump Port from the control box of the Heating Box™ to properly relay its power as an independent circuit (activating Port, dip switch No. 5 must be ON position). When room thermostat is ON, secondary circulator is also ON continuously. The control relay activates the primary circulator until it turns off the heating mode. When primary loop temperature gets close to the default set temperature, primary loop circulator will stop and the secondary circulator will continue to operate. When primary loop temperature falls below 5°F from the default set temperature, the primary circulator will start operating again to maintain the default set temperature range.

There are many applications you can apply with the Heating Box™ including radiant in-floor, radiant baseboard, hydronic air handlers, snow melting system and more.

Domestic Hot Water Supply

The Heating Box™ always prioritizes domestic hot water supply in operations. The Heating Box™ has a built-in priority switch to prioritize domestic hot water supply. For an example when it detects a demand from the domestic side while the unit is operating for the space heating side, it quickly switches over from the space heating mode to the domestic heating side by stopping a pump and/or a fan for the air handler until domestic hot water demand stops.

Radiant Heating Manifold

The Heating Box™ as a Primary Loop

Applications

Page 12: Navien Manual

12

In-Floor Radiant Space Heating System

Recommended application specifications:

1. ½” PEX or other comparable products with max 9” space and 150~350 feet tube length per loop 2. 0.75 ~ 1.25 GPM in each loop in depend on loop length and 6~8 Maximum loop per each

Heating Box. 3. 20 °F temperature drop in each loop recommended 4. Recommended size of space is about 2000 sq ft maximum with most tankless water heaters 5. Recommended heat source (water heater) temperature is 158°F and radiant heating supply

temperature sets between 100 ~130 °F depend on applications. 6. In cold weather, it is possible that areas of the slab may be below freezing even temporary

heat is being provided. The system should not be filled and purged until it is ready to have the system start circulating with the heat source in operation applying heat to the slab

Water heater set temperatures: 140, 160, 180 °F Radiant heating supply temperatures: 120 °F

Radiant Heating Manifold

Page 13: Navien Manual

13

Fan-Assisted Hydro Heating System

Recommended application specifications:

1. 2.5 ~ 5 GPM flow rate 2. 30 ~ 35 °F temperature drop at 140 °F hot water supply to the air handler 3. Maximum 5 ton air handler for 2000 sq ft space with most tankless water heaters

Water heater set temperature: 140, 160, 180 °F Hydro heating supply temperature: 140 °F

Fan Coil

Page 14: Navien Manual

14

Snow Melting System Snow Melting System’s format and specifications are very similar to other heating applications. As a working media, Glycol (propylene or ethylene glycol) can be used and recommended to mix with water in this system. Recommended application specifications:

1. ½” PEX or other comparable products with maximum 9” space 2. 150 ~ 250 feet tube length per loop 3. 0.75 ~ 1.25 GPM in each loop depend on the loop length 4. 6 ~ 8 Maximum loop 5. 20 °F temperature drop in each loop recommended 6. Recommended size of space is about 2000 sq ft maximum for most tankless water

heaters 7. Recommended heat source (water heater) temperature is 180 °F and radiant

heating supply temperature sets between 100 ~130 °F depend on the application. 8. On cold weather start up, that areas of the slab may be below freezing even

temporary heat being provided. The system should use propylene glycol mix not be filled and purged until it is ready to have the system circulating with the heat source in operation applying heat to the slab.

Page 15: Navien Manual

15

Spa Water Heating System

In Spa Heating Application, the Heating Box™ connect to the proper supply inlet and return outlet to maintain safe and steady spa water temperature of maximum 105 °F. You can lower the temperature by adjusting the thermostatic mixing valve on the heating side. Bromidanted water can be used in the spa, but not encourage the use of Chlorinated water in the spa.

The unit must be in OFF position before connecting the electrical wires. Make sure the circuit breaker on the distribution panel is OFF or GFI (ON/OFF switch) in Heating Box is OFF.

From the bottom of Heating Box™, connect the 120 VAC, 60Hz hot wire (Black), neutral (White) and ground (Green) wires to the marked terminals with minimum 14 AWG.

When Room Thermostat needs external 24 VAC power, Heating Box controller provide 24 VAC power to your convenience.

Please follow wiring diagram for 24 VAC for either radiant or snow melt application.

Wiring

Page 16: Navien Manual

16

In-Floor Radiant Heating System and Baseboard Heating System

ROOM THERMOSTAT (with Battery) ROOM THERMOSTAT (without Battery)

SWITCH MOVE TO OFF POSITION OFF ON

Fan-Assisted Hydro Heating System

SWITCH MOVE TO ON POSITION OFF ON

Page 17: Navien Manual

17

This Heating Box™ is designed to make a combination system (heat potable water and space) with just one heat source in convenience of simple installation. The unit consist with a high head bronze constructed pump to circulate water and built-in priority device for more effective distribution in domestic hot water. The Heating Box™ will make sure there will be no interruption to your domestic hot water even when the heating box is distributing its hot water to the space heating side. It supports domestic side fully as soon as it detects a demand from the domestic side and once the domestic hot water demand is done, it switches back to the space heating side until the room temperature reaches at its setting temperature. Also, its computer board monitors water movement and temperatures for both heat source and space heating to make steady and optimum performances.

The Heating Box™ can operate with any water heating systems offer in the market. The unit recommends the incoming water temperature from the heat source to be above 167 °F. After setting the temperature from the heat source, it needs to be entered into the computer board of the Heating Box™ for a proper control of each application. You need to set the temperature of the heat source into the computer board of the Heating Box so it control and distribute hot water to each application more effectively. In order to set the temperature, use dip switches and they are located on the front of controller in the Heating Box™. For heat source temperature between 158 °F – 167 °F, leave the dip switch settings at the factory default setting which is 158 °F.

* Above picture shows Space Heating’s return temperature and Dip Switches.

Operation

Important set up instructions before operating the Heating Box

Page 18: Navien Manual

18

ON CLOSE TYPE 1 2 3 Heat Source Temperature 4

OFF OPEN TYPE

ON EXTRA PUMP ON OFF OFF OFF 158℉(70℃) 5

OFF EXTRA PUMP OFF

ON CELSIUS(℃) ON OFF OFF 122℉(50℃) 6

OFF FAHRENHEIT(℉)

ON EXTRA POWER ON OFF ON OFF 140℉(60℃) 7

OFF EXTRA POWER OFF

OFF OFF ON 181℉(83℃) 8

Domestic Hot Water Supply Whether the Heating Box™ is in stand by mode or space heating mode, domestic hot water supply mode is the priority. The whole system of Heating Box™ does act like a water heater. When you open a hot water tap, city water passes through the Heating Box™ to a water heater and produced hot water passes through the Heating Box™ to supply domestic hot water as you demand. The Heating Box™ monitors incoming hot water temperature from the water heater to make sure hot water temperature is in its setting range. The Heating Box™ has a built-in thermostatic mixing valve to set the domestic hot water supply temperature. The factory set is at 110 °F for domestic hot water supply and the Heating Box™ tries maintain the set temperature if incoming hot water from the water heater is above the thermostatic mixing valve setting. Domestic hot water temperature can be easily adjusted at the mixing valve.

Page 19: Navien Manual

19

Domestic Hot water temperature adjustment mixing valve

WARNING Over 122°F (50 °C) water temperature is dangerous to human body and it cause scalds and burns resulting in serious personal injury and/or death. Typical factory set temperature for domestic hot water is 120°F.

Space Heating

Whether using radiant heating or hydronic fan coil heating, simply turn on the room thermostat. The Heating Box™ controller will turn on the circulating pump and the heat source will supply hot water to the space heating appliance. The Heating Box™ has a built in thermostatic mixing valve to adjust space heating water temperature. Space heating water temperature is typically recommended at 120 °F for a radiant space heating and above 140 °F for a fan coil space heating. The Heating Box™ continuously monitors the temperature of space heating and returning water temperatures. The temperature range of the mixing valve on space heating side is from 86 °F (30 °C) to 140 °F+ (60 °C+). At the maximum temperature setting of the mixing valve, the valve fully opens and will allow the heat source temperature directly in to the space heating side.

Space Heating Supply Temperature adjustment

In the process of initial set up for a radiant heating or a fan coil space heating, LED from the control board will show each temperature read so you can easily identify and adjust flow rates and temperature drops.

Page 20: Navien Manual

20

Freezing Protection

The Heating Box offers two different freezing protection systems. One continuously check incoming city water temperature and when its temperature reaches below 6°C (42°F), the Heating Box’s pump will turn on automatically until the temperature of inside water pipe reaches to 20°C (68°F). It runs for about two minute.

Pump Exercise

Pump will run pump exercises for about 30 seconds at the point of non-usage in the period of 24 hours.

Ladder Diagram

Page 21: Navien Manual

21

Design Reference for Heat Loss Calculation

This section gives a general idea to design a space heating system; it can vary system to system and case by case. Initial step in any heating system design is to determine the heating requirements (same as “heat loss”) of each individual room or area. More accurate heat loss calculation is to assure the potential of maximum energy savings and to achieve maximum level of comfortness. By using the conventional heat loss calculations for radiant heating design can result to over size the system. As an example, when desired room temperature is 65 °F ~ 70 °F and ambient temperature is -10 °F at seasonal low temperature, following resistance to heat flow values can be used for basic heat loss calculations in each construction site.

Constructed Components and Sections R Factor at -10 °F Seasonal

Temperature

Ceiling R-19 Insulation 5

R-30 Insulation 3

R-38 Insulation 2.5

Interior above Heated Ceiling 0

Walls R-11 Insulation 8

R-19 Insulation 5

Interior wall between rooms 0

Floor Un-insulated wood frame over a crawl space 18

R-11 insulation 8

R-19 Insulation 5

R-30 Insulation 3

Un-insulated slab on grade 13

R-10 insulated slab on grade 4

Interior between heated spaces 0

Window Single Glazed 80

Double Glazed 40

Door 1-1/2” Wood 35

* More detail heat loss data can be collected from the heating design software and heating design engineers.

Page 22: Navien Manual

22

From above table, factor in areas as square feet to figure out heat loss calculation (or required heat calculation and unit for the heat requirement is BTU/hr in each section. Pipe spacing in a radiant floor heating installation can directly affect the heat output. The commonly recommended pipe spacing is 8” ~ 9” with ½” PEX pipe. Also the typical pipe lengths are from 150’ to 450’ in each loop where pipe lengths can be calculated (in each loop, heating area times by 1.3). For an example, if heating area is 200 square feet, pipe lengths are approximately 260’. Finally calculating the each loop requires flow rate divides by the total required heat output (BTU/Hour) by 500 times the design ∆T of the system. A design ∆T of 28 °F is considered optimum for on-demand tankless water heaters. Required heat output (BTU/Hr) each loop

Flow Rate = ━━━━━━━━━━━━━━━━━━━━ 500 X ∆T This is very rough formula to design a radiant heating system, please consult you’re your heating design engineer for more accuracy of your heating system design.

Page 23: Navien Manual

23

Problem Check Water not hot enough Little or no heat from the fan coil or radiant heating The Heating Box doesn’t response when a room thermostat is ON Pump keeps turn ON & OFF Water temp fluctuates The Heating Box’s pump is circulating during the cooling cycle Pump noise T & P or pressure relief valve on water heater weeps

The set temp of the heat source and the heating box’s mixing valve The heat source – on Connections – could’ve been reversed The heat source is undersized for the space heating system Wire and the power supply of the room thermostat Wrong connection between the room thermostat & the air handler Check room thermostat Domestic hot water line is leaking The set temp of the heat source is too low Heating and cooling wire on the room thermostat could’ve been reversed or/and two different wires are shorted Domestic hot water line is leaking System may have not purged air completely In the Heating Box, the expansion tank’s manual ball valve might have closed Valve may be malfunction

Troubleshooting Guide

Page 24: Navien Manual

24

Model KD-HBO100 Open Loop System Parts Diagrams

Parts Lists

Page 25: Navien Manual

25

Model KD-HBO100 Open Loop System Parts List

Part No. Description Part No. Description

1 Expansion Tank 27 To Domestic hot supply connect

2 Base Bracket 28 Pipe clamp

3 3-Way Valve 29 Electric junction box

4 To water heater IN connection 30 Pipe isolator clamp

5 Controller 31 Case

6 Controller Bracket 32 Front cover

7 Thermostatic Mixing valve 33 Air separator clip

8 Manual Drain Port 34 Bottom bracket

9 Air Separator 35 GFI

10 Air Separator body 36 Case clamp

11 To Space heating return line 37 Front cover clamp hook

12 Base frame 38 Drain hose

13 To Space heating supply line 39 Pump holder bolt

14 Pump Bracket 40 Pump holder nut

15 Pump Flange 41 Packing gasket

16 Circulation pump 42 Packing gasket

17 To Space heating Return (OUT) 43 O-ring

18 Expansion Tank pipe (Right) 44 O-ring

19 To Space heating Supply (IN) 45 O-ring

20 Pump gasket 46 Wire holder packing

21 To City water pipe line 47 Gasket

22 To water heater OUT connection 48 Gasket

23 Domestic priority switch 49 Gasket

24 Expansion tank pipe (left) 50 Pipe connector holder screws

25 Expansion tank manual valve 51 Screws

26 To City water connection 52 Screws

Page 26: Navien Manual

26

Model KD-HBC100 Close Loop System Parts Diagrams

Page 27: Navien Manual

27

Model KD-HBC100 Close Loop System Parts List

Part No. Description Part No. Description

1 Case 33 To Water heater OUT pipe line

2 Front cover 34 To water heater OUT connection

3 Expansion Tank 35 Domestic hot supply pipe line

4 Controller 36 Domestic hot supply pipe line

5 Controller Bracket 37 To Domestic hot supply connect

6 Circulation pump 38 Expansion Tank pipe

7 Pump gasket 39 Sealing Rubber

8 Pump Flange 40 Sealing Rubber

9 Pump Bracket 41 Base frame

10 Pump holder bolt 42 Base frame

11 Pump holder nut 43 Bottom bracket

12 Thermostatic Mixing valve 44 Drain hose

13 Flat Heat Exchanger 45 Wire holder packing

14 GFI 46 Electric junction box

15 Pressure Gage 47 Pipe clamp

16 Base Bracket 48 Pipe isolator clamp

17 Domestic priority switch 49 Pipe clamp

18 Check Valve 50 Pipe isolator clamp

19 Air Separator 51 Case clamp hook

20 Manual Drain Port 52 Front cover clamp hook

21 Air Separator body (space heat) 53 O-ring Gasket

22 Air Separator body (heat source) 54 O-ring Gasket

23 Air separator clip 55 O-ring Pipe connector holder

24 Air separator clip 56 O-ring Pipe connector holder

25 To Space heating supply line 57 Rivet

26 To Space heating supply line 58 Packing gasket

27 To Space heating Supply (IN) 59 Packing gasket

28 To Space heating Return (OUT) 60 Screws

29 To City water pipe line 61 Screws

30 To City water connection 62 Screws

31 To Water Heater IN Pipe line

32 To water heater IN connection

Page 28: Navien Manual

28

Heating Box™ Limited Warranty Coverage KyungDong America, Inc. (“KyungDong”) warrants to the original purchaser of a Heating Box Model KD-HBO100 and Model KD-HBC100 unit installed in its original installation location in North America in accordance with all state, local and federal codes that the heating box will be free from defects in workmanship and materials, under normal use, for five (5) years from the original purchase date. The warranty registration card must be completed and mailed to KyungDong to establish your installation date. What is Not Covered under this Limited Warranty? This warranty excludes: external causes (i.e. accidents and Acts of God), abuse, misuse, alterations, or problems with electrical power or water supply pressure, problems caused by water freezing in unit or piping; failure to follow product instructions or failure to perform preventive maintenance; usage not in accordance with product instructions or use in conjunction with unapproved device(s); improper installation or installation in an area with corrosive atmosphere; damage resulting from use with well water and water with high pH and/or hardness levels; and improper sizing. Exclusive Remedies Should a covered defect occur during the warranty period and customer notifies Kyung Dong, customer’s sole and exclusive remedy shall be, at KyungDong’s sole option and expense, to repair or replace the heating box. Replacement products or parts may be new or reconditioned or comparable versions of the defective item and are subject to the same limitations and exclusions for the remainder of the original warranty period. Customer will be response for all other costs incurred including but not limited to labor cost, service fees, shipping, delivery, and handling of the replacement part or unit, cost for permits or materials necessary for the repair, or incidental costs resulting from damage external to the unit resulting from the defect. Warranties Exclusive To the full extent allowable by law, the foregoing warranties and remedies are exclusive and in lieu of all other warranties, terms or conditions, express or implied, including warranties of merchantability, fitness for a particular purpose, correspondence with description, and non-infringement, all of which are expressly disclaimed by KyungDong and its suppliers. Limitation of Liability Neither KyungDong nor its suppliers shall be liable for incidental, consequential, indirect, special, or punitive damages of any kind, or other financial loss arising out of or in connection with the sale or use of the heating box, whether based in contract, tort (including negligence) or any other theory, even if KyungDong had been advised of the possibility of such damages. The entire liability of KyungDong shall be limited to replacement or repair, at KyungDong’s sole option. Disclaimer Some states or provinces do not allow the exclusion or limitation of implied warranties or the limitation of incidental or consequential damages for certain products supplied to consumers or the limitation of liability for personal injury, so the above limitations and exclusions may not apply to you. When implied warranties may not be excluded in their entirety, they will be limited to the duration of the applicable written warranty. This warranty gives you specific legal rights and you may have other rights that may vary depending on local law. Governing Law This Limited Warranty shall be governed by the laws of the State of California, U.S.A., and by the laws of the United States, excluding their conflicts of laws principles. The United Nations Convention on Contracts for the International Sale of Goods is hereby excluded in its entirety from application to this Limited Warranty. How to Obtain Warranty Service To obtain warranty service for the heating box, you may contact KyungDong by calling 1-800-519-8794. Please be prepared to provide: (1) proof of original purchase, i.e. receipt or invoice (2) your name, address, telephone numbers; (3) model and serial number of the product; and (4) explanation of the problem.

Limited Warranty