Category 6A UTP vs. FTP

Nathan Benton, RCDD/NTS/WD

Technical Manager 

Page 2: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 2/29

UTP vs. FTP

• Two copper solutions for 10Gb/s –  UTP and FTP

• Effects of Alien Crosstalk (ANEXT)

•  ANEXT Mitigation Methods

• Standards Approach

Victim

Page 3: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 3/29

Comparison Chart

6A UTP 6A FTPParameter 

TIA-568-C.1

Data Rate

Max Distance

Cable Size

 ANEXT Testing

Shared Pathways

Training

Page 4: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 4/29

Standards Compliance

• TIA-568-C.1 Commercial BuildingTelecommunications Cabling Standard

• Ratified Feb 2008

•  Available Now on TIA Website

 – http://www.tiaonline.org/standards/catalog/search.cfm

Page 5: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 5/29

Page 6: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 6/29

UTP-vs-FTP Selection Matrix

YESYESMeet Class A Emission requirements

YES

NO

(YES if in metal

containment)

Meet immunity requirements per IEC/EN 61000-6-2(Heavy Industr ial environments)

YES

YESMeet immunity requirements per IEC CISPR 24,EN 55024 and IEC/EN 61000-6-1 (Off iceenvironments)

YESYESMeet or exceed TIA Category 6A channelspecifications (up to 4-connection channel)

YESYESMeet or exceed ISO/IEC Class E A channel

specifications (up to 4-connection channel)

YESYESSupport 10GBASE-T to 100 meters (upto 4-connection channel)

X10D FTPX10D UTPCustomer Requirements GenericCat 6A FTP

YES

YES

YES

YES

NO

YES

Must meet TIA-568-C.1

Page 7: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 7/29

Comparison Chart

6A UTP 6A FTPParameter 

TIA-568-C.1 Compliant Compliant

Data Rate

Max Distance

Cable Size

 ANEXT Testing

Shared Pathways

Training

Page 8: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 8/29

Data Rates

• Standard written around 10Gb/s• Category 6A Added to Standard

• Backwards Compatible with Cat6 and Cat5e

• Category 5e removed from standard

• IEEE 802.11an Standard

• 10Gb/s over installed base of Category 6 –  May Require Mitigation

Page 9: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 9/29

10GBASE-T Power ProjectionTechnology Improvements Reduce Power Needs

2006-7 2007-8 2008-9

TN

1010

130nm10W

TN

2020

5W

TN

3030

3W

Teranetics TeraPHY®

Source: Lin ley Group Conference May 2007

• Intel Penryn Processor (45 nm technology) available November 2007• 32 nm technology processors available in 2009

• Each improvement reduces power 30-40%

Page 10: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 10/29

Comparison Chart

6A UTP 6A FTPParameter 

TIA-568-C.1 Compliant Compliant

Data Rate 10 Gb/s 10Gb/s

Max Distance

Cable Size

 ANEXT Testing

Shared Pathways

Training

Page 11: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 11/29

Maximum Distance

• 100 Meters Channel

• Specifies a 4 Connector Model

• IEEE 802.11an Standard

• 10Gb/s over installed base of Category 6 –  37 Meters

 –  May Require Mitigation

Page 12: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 12/29

Performance of Channel vs.

Components

• Be careful of Cable test measurements that exceedthe TIA568.B.2 - 250 MHz frequency sweep

 –  600 MHz frequency is not achievable in a field channel

• When comparing performance specif ications it isimportant to view the entire channel

• Ensure manufacturer is warranting the entire channelnot just the components they manufacture

91A Series Cable

SYSTIMAX M3600

w/ MGS500

GS10E CordGS10E Cord

SYSTIMAX M3600

w/ MGS500 MGS500MGS500

GS10E CordGS10E Cord

3 6 1 2 3 6 1 2

Lucent PATCHMAXLucent PATCHMAX

Page 13: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 13/29

Verified Support of 10G

6@1 100m 4-conn Channel

Page 14: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 14/29

Comparison Chart

6A UTP 6A FTPParameter 

TIA-568-C.1 Compliant Compliant

Data Rate 10 Gb/s 10Gb/s

Max Distance 100 meters 100 meters

Cable Size

 ANEXT Testing

Shared Pathways

Training

Page 15: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 15/29

Cable Diameter 

• TIA-568-C.1 Specifes maximum cable diameter of 

.354 inches O.D.• Specified for both UTP and FTP

• Typical UTP O.D. .30 in to .33 in

 –  New UTP introduction of .285 in• Typical FTP O.D. .290 in

• 6 around 1 configuration

Page 16: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 16/29

Conduit Fill Ratio

Size Acond

FTP

OD

UTP

OD

 A-

FTP

 A-

UTP

40% Fill

UTP

40%Fill

FTP

0.5 0.20 0.29 0.31 0.07 0.08 1.04 1.19

0.75 0.44 0.29 0.31 0.07 0.08 2.34 2.68

1.00 0.79 0.29 0.31 0.07 0.08 4.16 4.76

1.25 1.23 0.29 0.31 0.07 0.08 6.50 7.43

1.50 1.77 0.29 0.31 0.07 0.08 9.37 10.70

* Plenum Cable used in this illustration

Page 17: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 17/29

1.24”

2.3”

Single gang boxes are not large enough

to maintain proper bend radius.

 – UTP – 4x Outside Diameter of the Cable

 – FTP – 8x Outside Diameter of the Cable

CAT6A FTPCAT6A UTP

Cable Diameter 

Page 18: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 18/29

Comparison Chart

6A UTP 6A FTPParameter 

TIA-568-C.1 Compliant Compliant

Data Rate 10 Gb/s 10Gb/s

Max Distance 100 meters 100 meters

Cable Size .285 in O.D. .290 in O.D.

 ANEXT Testing

Shared Pathways

Training

Page 19: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 19/29

Page 20: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 20/29

Example of 6 around 1 ConfigurationTest Equipment Setup

Measuring

 AlienCrosstalk 

Page 21: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 21/29

FIELD TESTING

• Field Testing is NOT specified in theStandards for UTP or FTP – it is an

option.

• Most UTP manufacturers do not require

 ANEXT testing to warranty system

• To ensure meeting quality metrics both

UTP and FTP should be tested.

• FTP Shield continuity testing

Page 22: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 22/29

Comparison Chart

6A UTP 6A FTPParameter 

TIA-568-C.1 Compliant Compliant

Data Rate 10 Gb/s 10Gb/s

Max Distance 100 meters 100 meters

Cable Size .285 in O.D. .290 in O.D.

 ANEXT Testing Not Required* Not Required*

Shared Pathway

Experience

Page 23: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 23/29

Shared Cable Pathways

• TIA-568-B.2-10 E.4 Test Configurations“ Alien Cross-talk requirements for category 6Achannels and permanent links are specif ied for bundled configurations containing only category

6A cabling requirements”• Manufacturers publish specific installation

guidelines for various situations

Page 24: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 24/29

• Separation of Cat6A UTP cabling from lower categories is an issueif the lower categories are supporting 10G. For all other applicationsthere is no issue.

• Typical Cabling Requirements

• Cable types are laid, routed, and/or bundled in separate groups

• Pull each cable type separately• Cables can be layered but not intermingled• If alternate pulling of each cable type is planned, then side by side

posit ions in the tray must be allocated for each cable type

Shared Cable Pathways

Page 25: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 25/29

Comparison Chart

6A UTP 6A FTP

Parameter TIA-568-C.1 Compliant Compliant

Data Rate 10 Gb/s 10Gb/s

Max Distance 100 meters 100 metersCable Size .285 in O.D. .290 in O.D.

 ANEXT Testing Not Required* Not Required*

Shared PathwayStd. Bundling/Layering Std. Bundling

Experience

Page 26: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 26/29

Structured Cabling Questionnaire

Question Answer  

1 What percentage of instal lat ions over the past 3 years have been FTP / STP (non-UTP) ?

2 What percentage of instal lat ions over the last 3 years have been UTP?

3 How many instal lat ion projects have you done in hospital environments in the last 3 years?

4 How many of these hospi tal projects ut il ized FTP / STP solut ions?

5Have your Technici ans received independent training for FTP /STP Solutions (BICSI, Global Know ledge,NJATC, etc) ?

6 If Yes, what percentage o f techn ic ians received t raining?

7 Have your Technicians received vendor specific t raining for FTP / STP solutions?

8 If Yes, what percentage o f techn ic ians received t raining?

9Have your Technici ans received independent training for UTP Solut ions (BICSI, Global Knowledge, NJATC,etc) ?

10 If Yes, what percentage of technicians received t raining?

11 Have your Technicians received vendor specific training for UTP solut ions?

12 If Yes, what percentage of technicians received t raining?

13 What percentage of current inventory consists of FTP / STP components?

14 What percentage of current inventory consists of UTP components?

Installation Experience

Page 27: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 27/29

Installation Experience

FTP v. UTP Installation s

1%

99%

1 2

Non-Vendor FTP Training

6%

94%

Received

Vendor-Specific FTP Training

9%

91%

Received

Percentage of Inventory

0%

100%

FTP

Page 28: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 28/29

Comparison Chart

6A UTP 6A FTP

Parameter TIA-568-C.1 Compliant Compliant

Data Rate 10 Gb/s 10Gb/s

Max Distance 100 meters 100 metersCable Size .285 in O.D. .290 in O.D.

 ANEXT Testing Not Required* Not Required*

Shared PathwayStd. Bundling/Layering Std. Bundling

Experience

84%

Worldwide

16%

Worldwide

Page 29: Nathan Benton

7/27/2019 Nathan Benton

http://slidepdf.com/reader/full/nathan-benton 29/29

Thank you 