name : broadway plaza location : downtown rochester, minnesota building size : 29 stories

34

Upload: caesar

Post on 06-Jan-2016

22 views

Category:

Documents


1 download

DESCRIPTION

Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories Primary Occupancy : Apartment Building Mixed Occupancy : Business/Retail (Floors 1-3). Management Goal / Thesis Goal: Home Away from Home. Lighting Depth Apartment Lobby Pool Skyway - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories
Page 2: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Name: Broadway Plaza

Location: Downtown Rochester, Minnesota

Building Size: 29 Stories

Primary Occupancy: Apartment Building

Mixed Occupancy: Business/Retail (Floors 1-3)

Management Goal / Thesis Goal:

Home Away from Home

Page 3: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Lighting Depth Apartment Lobby

Pool

Skyway

Electrical Depth and Construction Management Breadth Distribution System Redesign and Analysis

Short Circuit Analysis

Daylighting, Mechanical, and Construction Management Breadth Daylighting Study

HAP Analysis of Pool Loads

Dimming Cost and Energy Savings

SkyCalc Preliminary Analysis

 

Exterior Façade

Function Room

Conference Room

Conference Room Comparison Study

Page 4: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Lighting Depth: Spaces Not Being Presented

Function Room

Exterior Facade

Conference Room

Skyway

Page 5: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Location: 1st Floor

Function: Main entrance/Focal point Casual waiting tasks

Lighting Redesign: Apartment Lobby

Page 6: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Schematic Design Concept

Design Goals Providing a warm & inviting ambience

Creating focal points

Guiding visitors

Design Criteria Luminances of Room Surfaces

System Control and Flexibility

Horizontal Illuminance

10fc ~ General Entrance

30fc ~ Lounge Work Plane

50fc ~ Receptionist Desk

Vertical Illuminance

10fc ~ Receptionist

5fc ~ General Areas

Schematic Design Sketches

Page 7: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Solution: Entry Lighting Plan

FC1Fluorescent Cove

SC2Linear

Sconce

FP2Indirect-Direct Linear Pendant

UC1Tasklight

C1Fluorescent Cyc Light

WW2Linear Wall Wash

FD1CF Downlight

Page 8: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Solution: Lounge Lighting Plan

SP2Adjustable Spotlight

FP3Decorative Bowl Pendant

FC1FluorescentCove

L1FloorLamp

Page 9: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

# TypeFC1 Low-profile cove Cove 1 F54T5 DIM-ELEC. 13 796

FP2Linear Indirect-Direct Pendant

Pendant 2 F28T5 DIM-ELEC. 2 124

WW2 Perimeter wall wash Recessed 1 F32T8 ELECTRONIC 4 140UC1 Tasklight Surface 2 F13T5 ELECTRONIC 2 56SP2 Spotlight Recessed 1 20MR16/SP NA 4 80

FP3 Decorative bowl pendant Pendant 4 CF42W DIM-ELEC. 4 608

SC2 Linear sconce Wall 1 35MR11 NA 2 70L1 Floor lamp Floor 1 100A NA 4 400

C1 Cyc light Floor1 of

each

28T5 (red) 28T5 (green) 28T5 (blue) 28T5 (white)

Integrated Digital (Dimmable)

2 256

FD1 CF downlight Recessed 1 CF32W DIM-ELEC. 3 105Power ConsumptionPower Density

QuantityBallast/

TransformerLuminaire

DesignationDescription Mounting

Lamp

ASHRAE 90.1 Power Allowance: 1.8W/sq.ft. 2635

1.42 W/sq.ft.

Watts

Solution Summary

Energy Savings 21% below ASHRAE 90.1 11% below existing design

Page 10: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Lounge Renderings

IESNA: 30 fc Recommendation

Design Average: 40 fc

Page 11: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Entry Renderings

Page 12: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Fire Wall Model Study

Wall SectionReplication

# Type

C1 Cyc light Floor1 of each

28T5 (red) 28T5 (green) 28T5 (blue) 28T5 (white)

Integrated Digital (Dimmable)

Luminaire Designation

Description MountingLamp Ballast/

Transformer

Page 13: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Location: Northeast Corner of 3rd Floor

Function: Private Pool and Spa Area

Lighting Redesign: Pool

Page 14: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Schematic Design Concept

Design Goals Relaxed, private, controllable atmosphere created

Safety hazards minimized

Reflected glare minimized

Maintenance simplified

Design Criteria Daylighting Integration and Control

Uniformity of Light Distribution

•Coefficient of Variation ~ 0.3 or less

Horizontal Illuminance

30 fc ~ Pool Surface (Recreational swimming)

20 fc ~ 3 ft above the deck

Schematic Design Sketches

Page 15: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Solution: Pool Lighting Plan

FP4

Linear Indirect Lensed Pendant

FD5CF LensedDownlight C3,C4

Fiber optic Color-changing Floodlight, 10° tilt

Page 16: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Control System Details

Control System 5 Zones, a-e

Radio frequency control,

no wiring necessary

Zone changes possible

4 Preset Scenes

Integrated Photocell

Page 17: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

# TypeFP4 Indirect lensed pendant Pendant 1 F54T5 DIM-ELEC. 40 2440FD5 CF lensed downlight Recessed 1 CF32W DIM-ELEC. 8 484

C3Color-changing underwater flood lens

In-pool 1 Fiber Optic NA (MH ballast in

base unit)3

C4Color-changing underwater flood lens

In-pool 1 Fiber Optic NA (MH ballast in

base unit)2

C5Side light fiber optic cable

In-pool 1 Fiber Optic NA (MH ballast in

base unit)1 (96ft)

Power ConsumptionPower DensityUnderwater ConsumptionPower Density

Ballast/ Transformer

Underwater Luminaires

510

ASHRAE 90.1 Power Allowance: 1.1W/sq.ft. Underwater Power Allowance: 1.0W/sq.ft.

LampWattsQuantity

29241.0 W/sq.ft.

5100.97 W/sq.ft.

Luminaire Designation

Description Mounting

Solution Summary

Energy Savings 10% below ASHRAE 90.1 10% below existing design

Page 18: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Pool Rendering

IESNA: 30 fc Recommendation

Design Average: 31 fc

Pool

Page 19: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Pool Renderings

In-pool lighting only

Page 20: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

208V vs. 480V & 208V Distribution System Analysis

Purpose Analysis of alternative power distribution system based on first cost and efficiency

In conjunction with the Construction Management Breadth

Existing System (2) transformers, 2500 kVA-480V Multifunction floors, 1000 kVA-208V Residential

Redesigned System (1) 3750 kVA-208V Transformer

Analysis Method Reconfiguration and resizing of electrical equipment and system paths

Relocation of equipment (not included)

Cost analysis

Page 21: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

208V Single-Line Diagram

Page 22: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Utilization Voltages

Transformer Cost

Panel/Wiring Costs, etc.

Location Factor

Time Adjustment

Total Cost

208V Only $61,490.00 $622,973.60 1.02 0.975 $680,699.05480V & 208V $68,820.00 $431,389.11 1.02 0.975 $497,457.96

Total Cost Comparisons

RS Means 2003 Electrical Cost Data (materials & labor)

Location Factor: Rochester, Minnesota

Time Adjustment: 2002 Design

Conclusions Efficiency, Maintenance, and safety paralleled

First-cost basis ~ Maintain existing power distribution, 480V & 208V

Distribution System Cost Analysis

37% Increase for Redesign

Page 23: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Existing Condition

Daylighting Analysis

Ebv = Mbv/2 = (E1/2kv * ρb)/2

E1/2kv

Conclusion Decrease glass area decrease load

Minimal light loss

Goals Increase skywell efficiency

Decrease glass area

Allow dimming

Page 24: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Finalized Redesign

Glazing Description Trans. U-ValueShading

CoefficientSHGC

Insulating Triple Glazing Glass with Krypton Gas Fill,

1 1/4" Overall Depth63% 0.13 0.55 0.48

Well ~ 40’ X 6’ Splay ~47’ X 14’

Page 25: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Hap AnalysisExisting Design Redesign

Existing: 8.6 Tons Redesign: 7.4 Tons

Savings: 1.2 Tons or 86% of original

Energy Savings

No equipment resizing

Page 26: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Pool Dimming

Yearly Savings: $164.17

Dimming vs. Non-Dimming Equipment

Cost Difference Time of Payback

$400 2.5 years

Skyway Dimming

Yearly Savings: $246.35

Dimming vs. Non-Dimming Equipment

Cost Difference Time of Payback

$1820 7.4 years

With (11pm-5am) Dimming Considered 5.3 years

Daylighting Analysis

Alternative Option

Direct switching

Payback~0.5 years

Page 27: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Lighting Depth

Creates a “home away from home” welcoming atmosphere Provides flexibility and easy control for users Satisfies all goals and design criteria set forth

Electrical Depth and CM Breadth

Alternative power distribution system viable Selection of existing system based on first cost

Daylighting, Mechanical, and CM Breadth

Mechanical energy savings incurred Electrical energy consumption decreased

Conclusions

Page 28: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Individuals and CompaniesMr. Edward Wunderley, Mr. Donald Rimer, and Mr. Jack Grzybek of Burt HillMr. Michael Manley of Royal Management & DevelopmentMr. Joseph Crick of Oakwood Broadway PlazaMr. Andrew Sedlak  

Faculty Personal Dr. Richard Mistrick My fiancé, Todd Dr. Martin Moeck My parents, Donald and JaniceProfessor Kevin Parfitt Lori, AJ, and Aaron Jonathan Dougherty All of my fellow AE’sProfessor Paul Bowers 

THANK YOU

Page 29: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories
Page 30: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Lighting Depth: Spaces Not Being Presented

Function Room

Exterior Facade

Conference Room

Skyway

Page 31: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Daylighting Analysis

Pool

Continuous dimming over pool

Skyway Continuous dimming along corridor

Study DateDecember 21

June 21 May 13 to August 12

Dates Represented November 13 to February 12February 13 to May 12 August 13 to November 12

March 21

Rochester, MN weather data 3 Sky Conditions (5) 2-hour intervals per day

AGI 32 Software Study

Page 32: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

HAP AnalysisMethodology

Proper U-value calculation of surfaces

Lighting Load: 1.0 W/sq.ft.

Occupancy ~ 10 people

Evaporation load of pool (2003 ASHRAE HVAC Applications)

wp = 0.1A(pw - pa)Fa = 2.499 lb/h

Btuh = wp * 45Btu/lb = 112.5 Btuh (latent load)

Where:

pa = saturation pressure at room air dew point

pw = saturation vapor pressure taken at surface water temperature

Fa = 0.65, Condominium Pool Water Temperature = 80 F

Dry Bulb Air Temperature = 78 F % Relative Humidity = 55

Page 33: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

208V Single-Line Diagram

Page 34: Name : Broadway Plaza Location : Downtown Rochester, Minnesota Building Size : 29 Stories

Utilization Voltages

Transformer Cost

Panel/Wiring Costs, etc.

Location Factor

Time Adjustment

Total Cost

208V Only $61,490.00 $622,973.60 1.02 0.975 $680,699.05480V & 208V $68,820.00 $431,389.11 1.02 0.975 $497,457.96

Total Cost Comparisons

RS Means 2003 Electrical Cost Data (materials & labor)

Location Factor: Rochester, Minnesota

Time Adjustment: 2002 Design

Conclusions Efficiency, Maintenance, and Safety paralleled

First-cost basis ~ Maintain existing power distribution, 480V & 208V

Distribution System Cost AnalysisComponent

Redesign Cost

Existing Cost

Conductors $99,614 $76,611Ground Wires $6,934 $4,989Conduit $83,889 $69,747Circuit Breakers $66,243 $61,042Panels & Switchboards

$140,618 $98,550

Automatic Transfer Switches

$39,186 $25,860

Bus Duct Risers $182,240 $59,190Dry-Type Transformers

$4,250 $35,400

Total: $622,974 $431,389

Transformer Size (kVA)

Amperes Cost Totals

208V Only 3750 10409 $61,490.00 $61,490.00480V 2500 3007 $43,035.00208V 1000 2776 $25,785.00

$68,820.00

Utility Transformer Resizing

37% Increase for Redesign